Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.7 LAccepted-AOC 38 30 92 SAI NAGAR MARRIPALEM VISAKHAPATNAM 530 018 | VISAKHAPATANAM | ANDHRA PRADESH | 530018 | L1 | Accepted-AOC QUOTED RATES ARE REASONABLE AND ACCEPTED | |
| 2 | L2₹17.5 L+₹17,680.40 (1.02%)Rejected-Finance 15 EMERSON ROAD DANAPUR CANTT PATNA 801101 | PATNA | PATNA | BIHAR | 801101 | L2 | Rejected-Finance OTHER THAN LOWEST |
| Sl No | Description | Qty | Unit | M/S SAROJ KUMAR SINGH L2 | Anjali Constructions L1 |
|---|---|---|---|---|---|
| 1.00 | Excavation in trenches n. exc 1.5 m wide for foundations of PCC / Steel Pole , laying cables/ pipes etc. not exceeding 1.5 m deep and getting out in SOFT/LOOSE soil complete, all as specified. | 305 | Cubic Metre | 290 ₹88,450 | 220 ₹67,100 Lowest |
| 2.00 | Excavation in trenches n exc 1.5 m wide for foundations of PCC / Steel Pole , laying cables/ pipes etc. exc 1.5 m but not exceeding 3.0 m deep and getting out in SOFT/LOOSE soil complete, all as specified. | 0.32 | Cubic Metre | 270 ₹86.4 | 250 ₹80 Lowest |
| 3.00 | Returning filling in including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick complete, all as specified. | 150 | Cubic Metre | 145 ₹21,750 | 120 ₹18,000 Lowest |
| 4.00 | Removal of excavated surplus spoil to a distance n. exc. 50m and depositing where directed at level not exceeding 1.5 m above the starting point complete all as specified. | 150 | Cubic Metre | 60 ₹9,000 Lowest | 80 ₹12,000 |
| 5.00 | Cutting the existing road straight by manual, depth and width not less than 1 metre below ground level for passing of underground cable and filling back with excavated soil upto 75% road portion and 25% shall be made with cement concrete 1:2:4 using 20mm graded aggregate stone complete all as specified. | 24 | Running Metre | 220 ₹5,280 Lowest | 300 ₹7,200 |
| 5.01NOTES APPLICABLE TO SERIAL ITEM 1 TO 4: (a) Excavation work shall be carried out manually only. (b) LT/HT cable, water supply/ sewage/telephone lines, if any, get damaged during excavation & earthwork, demolition of PCC shall be repaired by the contractor immediately as per existing specifications to the entire satisfaction of Engineer-in-Charge. | |||||
| 6.00 | Brick protection with pulverized fuel ash lime bricks laid flat across the route of underground cable all as specified. | 4.6 | Per 1000 Nos | 6,500 ₹29,900 | 6,000 ₹27,600 Lowest |
| 7.00 | Clean dry sand ( locally available) as cushioning for under ground cable 230 mm thick (one layer of 80 mm thickness before laying the cable and other layer of 150 mm thickness after laying the cable) complete all as specified.
NOTE:- Punned down thickness (over all 180 mm) shall be considered for measurement and payment. | 104 | Cubic Metre | 1,300 ₹1,35,200 | 1,000 ₹1,04,000 Lowest |
| 8.00 | PCC type D-2 (1:4:8), using 40 mm graded stone aggregates as in foundation of electric poles, struts, PCC block including necessary form work and fair finish to exposed surfaces without using extra cement etc. complete all as specified and directed | 0.32 | Cubic Metre | 5,000 ₹1,600 Lowest | 7,500 ₹2,400 |
| 9.00 | PCC type C-2 (1:3:6), using 40 mm graded stone aggregates as in as in foundation of electric pole, stay assembly and strut PCC block including necessary form work and fair finish to exposed surfaces without using extra cement etc. complete all as specified and directed | 1.98 | Cubic Metre | 5,000 ₹9,900 Lowest | 7,500 ₹14,850 |
Tender Value
₹16 L
EMD Value
₹32,000
Closing Date
14 Nov 2025, 6:00 pmClosed
GARRISON ENGINEER AIR FORCE BIHTA
Military Engineer Services AF stn Bihta
REPAIR / MAINT OF EXTERNAL ELECTRIFICATION, LT CABLE / PANEL AND CONNECTED WORKS IN TECH AND DOMESTIC AREA AT AF STN BIHTA
2025_MES_736841_1
GE/AF/BHT-45/2025-26
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Bihta
Refer NIT and Tender Documents
8 documents required · 8 mandatory
₹500
GE AF BIHTA
₹32,000
Yes
27 Dec 2025
25 Oct 2025
15 Nov 2025
25 Oct 2025
14 Nov 2025
8 Nov 2025
25 Oct 2025 - 7 Nov 2025
Amount
Excavation in trenches n. exc 1.5 m wide for foundations of PCC / Steel Pole , laying cables/ pipes etc. not exceeding 1.5 m deep and getting out in SOFT/LOOSE soil complete, all as specified.
Excavation in trenches n exc 1.5 m wide for foundations of PCC / Steel Pole , laying cables/ pipes etc. exc 1.5 m but not exceeding 3.0 m deep and getting out in SOFT/LOOSE soil complete, all as specified.
Returning filling in including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick complete, all as specified.
Removal of excavated surplus spoil to a distance n. exc. 50m and depositing where directed at level not exceeding 1.5 m above the starting point complete all as specified.
Cutting the existing road straight by manual, depth and width not less than 1 metre below ground level for passing of underground cable and filling back with excavated soil upto 75% road portion and 25% shall be made with cement concrete 1:2:4 using 20mm graded aggregate stone complete all as specified.
NOTES APPLICABLE TO SERIAL ITEM 1 TO 4: (a) Excavation work shall be carried out manually only. (b) LT/HT cable, water supply/ sewage/telephone lines, if any, get damaged during excavation & earthwork, demolition of PCC shall be repaired by the contractor immediately as per existing specifications to the entire satisfaction of Engineer-in-Charge.
Brick protection with pulverized fuel ash lime bricks laid flat across the route of underground cable all as specified.
Clean dry sand ( locally available) as cushioning for under ground cable 230 mm thick (one layer of 80 mm thickness before laying the cable and other layer of 150 mm thickness after laying the cable) complete all as specified. NOTE:- Punned down thickness (over all 180 mm) shall be considered for measurement and payment.
PCC type D-2 (1:4:8), using 40 mm graded stone aggregates as in foundation of electric poles, struts, PCC block including necessary form work and fair finish to exposed surfaces without using extra cement etc. complete all as specified and directed
PCC type C-2 (1:3:6), using 40 mm graded stone aggregates as in as in foundation of electric pole, stay assembly and strut PCC block including necessary form work and fair finish to exposed surfaces without using extra cement etc. complete all as specified and directed
PCC type B-1 (1:2:4), using 20 mm graded stone aggregates as in coping of poles etc. with slightly rounded or chamfered angles including necessary form work and fair finishing the exposed surface without using extra cement complete all as specified and directed
GI pipe light grade with all fittings fixed as termination postal ,fixed to poles/ walls/ under floors/ under road etc complete including taking down existing tube all as specified of following size: -
40 mm bore
50 mm bore
80 mm bore
Supply, laying, jointing & testing of LT XLPE insulated cable screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 1100 volt grade with aluminium conductor conforming to IS-7098 (Part-I -1988) laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing including takind down existing cable complete all as specified of sectional area: -
10 Sq.mm,4 core
16 Sq.mm,4core
50 Sq.mm,3.5 core
70 Sq.mm,3.5 core
95 Sq.mm,3.5 core
120 Sq.mm,3.5 core
185 Sq.mm,3.5 core
PVC insulated unsheathed / sheathed cable with standard aluminium conductor 1100 Volts grade flat twin core service cable of size 4 sqmm confirming to IS:694/1990 with latest amendement ISI including disconnecting / taking out existing unsv/damaged old service cable completed all as specified and directed.
PVC insulated unsheathed / sheathed cable with standard aluminium conductor 1100 Volts grade flat twin core service cable of size 6 sqmm confirming to IS:694/1990 with latest amendement ISI including disconnecting / taking out existing unsv/damaged old service cable completed all as specified and directed.
Aluminium lugs for LT 1100 volts line complete of following Sizes:-
16 to 25 Sqmm
35 to 50 Sqmm
70 to 95 Sqmm
120 to 150 Sqmm
185 to 240 Sqmm
MCCB with adjustable thermal magnetic release, ICS=ICU=100%, 4 Pole, 415 volts, AC, with over load and short circuit protection and rupturing capacity, IN REPLACEMENT, complete all as specified of following size,: -
63 Amp, 16 kA.
100 Amp, 16 kA.
160 Amp, 16 kA.
250 Amp, 16 kA.
315-400 Amp, 25 kA.
630 Amp, 36 kA.
MCB suitable for 415 volt AC supply, TPN with over load and short circuit protection and rupturing capacity 6 kA, 'C' curve type of rating 10-63 Amp, IN REPLACEMENT, complete all as specified.
Cable joining kit (straight through heat shrinkable) for 1100 V (Earthed) grade cable complete with jointing material and accessories suitable for XPLE armoured aluminium conductor cable including taking down unserviceable termination complete all as specified of following size: -
16-50 Sq. mm, 3.5 to 4 core
70-95 Sq. mm, 3.5 core
Aluminium conductor steel, reinforced (ACSR) of size 6/3.00mm Ferret or 2.59mm weasel in overhead lines fixed on insulators, binding with and including binding wire 14 SWG complete all as specified and directed by Engineer-in-Charge. (for payment purposes, the weight of binding wire shall not be considered). including taking down unserviceable conductor complete all as specified .
Continous GI earth wire / guard cradle 4mm dia including GI binding wire 1.63mm on LT poles complete all as specified and directed by Engineer-in-Charge.
LT line rigid PVC spacers spiral type , spacer rod dia 13 mm , spiral hole dia 5-6 mm and spiral length 250 mm of following :
Two lines and phase to phase distance 300 mm
Three lines and phase to phase distance 600 mm
Four lines and phase to phase distance 900 mm
Cross arms, bracing, stiffeners supports, clamps and back plates fabricated from structural steel sections such as channel, angle iron, flat iron etc including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size and painting the same with two coats of aluminium paint (under and finishing coat) over a coat of primer (red oxide) after preparation of steel surface complete, IN REPLACEMENT ,all as specified and directed by Engineer-in-Charge.
Pin type insulator, porcelain vitreous white, brown or green including one galvanised mild steel spindle, two GI washers, one GI nut 100mm high, 65 mm dia suitable for 1100 volts grade, IN REPLACEMENT, complete all as specified and directed by Engineer-in-charge.
Shackle type insulator , porcelain vitreous, white, brown or green insulator 100mm height and 115mm dia for 1100 V including galvanised mild steel straps, washer, insulators bolt and nuts etc, IN REPLACEMENT all as specified and directed by Engineer-in-Charge.
Restreching / Restringing, tightening and repair to overhead line ACSR conductor of any size on LT poles including necessary Aluminium binding wire connectors PVC sleeves for jumpers, fixing of insulators and prunning of tree complete all as specified and directed Note : (i) The distance between pole to pole in one span (contains 2/4/6 runs ) ie one span will be considered for payment purpose. (ii) No extra conductor will be measured for binding to insulator / Jumpering etc.
Attending , repair and rectification of external LT electric supply complaints upto 1100 Volt grade, over head/underground system alongwith necessary T&P , safety device as per site requirement for the following type of complaints complete all as specified and directed
Replacement of worn out jumpers, jointing and tightening with new ACSR conductor. Note : single phase/two wire of 3 phase /4 wire system will be considered as one job for payment purpose.
Disconnecting from over head conductor, cutting worm out portion of LT cable of any type and size, carry out repairs including taking out cable from underground loop line and rejoining the same to restore electric supply. Note : (i) LT jointing kits, cable protection pipe if required at site will be measured and paid separetly. (ii) Quoted rate is deemed to be inclusive of cutting and removing the pole coping and inserting the cable alongwith protection pipes,
Taking down old unsv Street light/flood light fittings in any position of any capacity for repair by replacement of unsv spares (SPD / Driver /MCB etc ) and re-fixing the same in existing location. Note :- Spares for repair of street light fitting will be measured and paid underrespective itmes
Note for itmes Nos 26.01 to 26.03 (a) The contractor has to provide sufficient resources for completion of day to day complaint 24 Hrs from the time of reporting any delay beyond above mentioned time limit without limitation of suffient cause , penalties will be recovered twice of the quoted rate for eachun-attended complaint. (b) The contractor will intimate MES authority well in advance if electric shutdown is required during rectification of complaints. (c) The quoted rate is deemed to be inclusive of transportationand other expanses require for the resource deployment at the complaint site around scattered military station at Bihta
Supplying , erecting and fixing steel tubular swaged poles with cast iron base plate of size 300mm X 300mm x 6mm final taper plug, bolts nuts & screws for type 410 SP-31 (9.0 mtr long ) including painting with two coats of aluminium paint over one coat of red oxide primer on all exposed surfaces and tarring with black bituminiouspaint to embedded portion in PCC and providing 3 Nos of 30 cm wide circular bands with black & yellow paint starting from plinth level at the gap of 30cm in between 2 band and numbering of poles, in yellow paint over black printedback ground at a height of 2m from bottom of pole with 5 cm large bold letters 2'' (inch) wide including taking down old unserviceable PCC poles of any type complete all as specified and directed. Note : Excavation , earth work , PCC in foundationand coping shall be measured and paid separately under relevent itme of this schedule
Cutting anxious green growth/ vegetation growth for cleaning out the area around transformer/ installations and four pole structure yards at ground level by cutting out roots, unwanted plant bushes and removal of the same by surface excavation not exceeding 15 cm deep complete.
Cutting and trimming trees branch any girth and any size touching to overhead lines and cleaning the distance 2.0 mtrs length both sids of OH line with a span of 50 mtrs (approx) each disposing the same clearing the site upto the satisfaction level and all as directed by Engr-in-charge. Note : All tools, plants and machinary equipment and manning required are quoted in the rates.
Hot press moulded SMC junction box / Terminal Box insulated and made out of environment friendly, recyclable, UV resistant , halogen & silicon free, polycarbonate with glass fiber reinforced of intenal size 300 x 200 x 1055 mm having protection IP-66/67 including MCB single pole 6-32 amp and all fixing acessories as required, IN REPLACEMENT, complete. MAKE: / GE POWER / RITTAL or equivalent make mentioned in Appendix 'B'.
Security light bracket made of 40 mm bore GI light grade pipe 1.5 metre long bend to shape including necessary welding to pole(s) or fixed with suitable size of flat iron clamps, nuts, bolts and washers etc. IN REPLACEMENT, complete all as specified
Service and testing of 630A-1250A Electrical/Manual Operating ACB's by deputing Auth chanel parter of OEM complete including replacement of defective parts and makingit serviceable and sumbitting the detailed report all as specified and directed.
ACB 4 pole , 415V , with Thermal Magnetic Release (Manual Fixed type ) of capacity 630 Amps
Earthing complete with galvanised steel earth plate electrode of size 600 x 600 x 6 mm buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including GI strip 32x6 mm as earthing lead by means of GI or steel bolts/nuts/washers, protected by 15 mm bore GI light grade pipe. Earth plate shall be surrounded by alternate layer of charcoal or coke and common salt 15 cm thick all around bottom and top. 20 mm bore GI light grade pipe for watering and including funnel, wire mesh, RCC cover, reinforced with 8 mm dia TMT bars @ 75 mm C/C both ways with mild steel handle 12 mm dia, using round bar, PGI funnel with wire mess & frame, PCC (1:2:4) type B-1 (using 20 mm graded crushed stone aggregate) as in earthing pit including necessary excavation & earth work, all as specified & shown in electrical plate No. 3 of MES Schedule Part – I. Note:- (i) PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for watering shall be provided in slanting manner. (ii) The unit rate includes earthing lead & protection pipe upto 7.5 metre from top of earth plate. (iii) Earth resstance shall be less than 3 ohm. In case the test results are not found less than 3 ohm, complete earthing shall be redone by the contractor without any extra cost to Govt.
Dismantling LT steel tubular poleof any height by taking out from PCC foundation complete and shifting to other location as directed including fixing the pole intrue vertical position including excavation and earth work , PCC 1:4:8 type D2 (using 40 mm graded stone aggregate) as base concrete and PCC 1:3:6 type C2 (using 20 mm graded stone aggregate)in both foundation and coping of poles all as specified in SSR part-I 2009 and applying two coat of aluminium paint of pole surface complete including demolishing of existing coping etc all as directed by engr-in-charge
Notes: Amount of credit for retrieved materials is mentioned in tender documents in pdf form which will be deducted while acceptance of tender offline.
M/S SAROJ KUMAR SINGH (BID ID -3479343)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.42 MB
BOQ_825037.xls
BOQ • 0.41 MB
Tender452526.pdf
Tender Documents • 0.95 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .