Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.7 LAccepted-AOC R O H NO 55 SEC D BHARAT NAGAR TALAB TILLO JAMMU 180002 | JAMMU | JAMMU AND KASHMIR | 180002 | L1 | Accepted-AOC L1 Bidder | |
| 2 | L2₹18.9 L+₹15,409.50 (0.82%)Rejected-Finance | L2 | Rejected-Finance Other than lowest | |
| 3 | L3₹21.8 L+₹3.1 L (16.4%)Rejected-Finance | L3 | Rejected-Finance Other than lowest | |
| 4 | L4₹22.9 L+₹4.1 L (22.0%)Rejected-Finance | L4 | Rejected-Finance Other than lowest |
Tender Value
₹25 L
EMD Value
₹50,000
Closing Date
23 Aug 2023, 6:00 pmClosed
GE(I) 873 EWS
Garrison Engineer (Indep) 873 Engineer Works Section PIN 913 873 C/O 56 APO
REPAIR AND MAINTENANCE OF EXTERNAL ELECTRIFICATION OF HT AND LT LINES INCL TRANSFORMER, SERVICING GOD/VCB/BATTERY BANK, STREET/SECURITY LIGHT AND OTHER CONNECTED WORKS AT RAMBAN AND BANIHAL UNDER GE (I) 873 EWS
2023_MES_610380_1
NIT-40 of 2023-2024
Open Tender
Civil Works
Item Rate
180 days
Bhaderwah
As per NIT
7 documents required · 7 mandatory
₹500
GE(I) 873 EWS
₹50,000
20 Oct 2023
24 Jul 2023
25 Aug 2023
24 Jul 2023
23 Aug 2023
8 Aug 2023
Amount
Excavating in trenches, not exceeding 1.5metre wide and not exceeding 1.5metre depth for foundation, etc., and getting out in any type of soil, complete all as specified and directed.
Excavating in trenches, not exceeding 1.5metre wide and exceeding 1.5metre depth but not exceeding 3.0metre depth for foundation, etc., and getting out in any type of soil, complete all as specified and directed.
Sand cushioning to underground cables using new dry river sand laid in trenches 8cm thick below the cable and 15cm thick above the cable after laying and stretching the cable complete, punned to 18cm, complete all as specified and directed Note : Punned thickness of 18cms shall be measured for payment.
Supply and laying brick covering with width equal to length of bricks as mechanical protection to underground cable using old size sub class 'B' bricks, laid flat size 230mm x 115mm x 75 mm with width of brick perpendicular to length of cable, all as specified and as directed.
Laying only serviceable bricks as mechanical protection to underground cable with width equal to length of bricks, width of brick perpendicular to length of cable, all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick any type of soil, complete all as specified and directed.
Removing excavated soils to a distance exceeding 50m but not exceeding 100m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
Cement concrete type D-2 1:48 (using 40mm graded crushed stone aggregate) as in foundation filling and mass concrete, complete all as specified and directed.
Cement concrete type C-2 1:3:6 (using 40mm graded crushed stone aggregate) as in foundation filling and mass concrete, complete all as specified and directed.
Cement concrete type B-1 1:2:4 (using 20mm graded crushed stone aggregate) as in coping of poles, complete all as specified and directed.
Steel Tubular swaged poles type 410 SP-55 (11.0 mtr long) conforming to IS : 2713 Part-I to III 1980, complete with 6 mm thick mild steel base plate, finial taper plug, MS bolts, nuts, screws including painting upto 1.5metre above PCC coping in black and white strips 05 Nos of 30cms each starting from the bottom of the pole and two coats epoxy based paint aluminium grade finish to the remaining external surface over one coat of primer complete including taking down old unserviceable Pole all as specified and directed.
Steel Tubular swaged poles type 410 SP-31 (9.0 mtr long) conforming to IS : 2713 Part-I to III 1980, complete with 6 mm thick mild steel base plate, finial taper plug, MS bolts, nuts, screws including painting upto 1.5metre above PCC coping in black and white strips 05 Nos of 30cms each starting from the bottom of the pole and two coats epoxy based paint aluminium grade finish to the remaining external surface over one coat of primer complete including taking down old unserviceable Pole all as specified and directed.
XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor rating 11000 volts grade of size 95 Sqmm 3 core laid in trenches or passing through pipes/ducts or fixed to walls/poles including taking down old cable, complete all as specified and directed.
XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade ISI marked cross sectional area 16 Sqmm 2 core on wall including taking down old cable, complete all as specified and directed.
XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade ISI marked cross sectional area 16 Sqmm 4 core on wall including taking down old cable, complete all as specified and directed.
XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade ISI marked cross sectional area 35 Sqmm 3.5 core on wall including taking down old cable, complete all as specified and directed.
XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade ISI marked cross sectional area 50 Sqmm 3.5 core on wall including taking down old cable, complete all as specified and directed.
XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade ISI marked cross sectional area 70Sqmm 3.5 core on wall including taking down old cable, complete all as specified and directed.
XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade ISI marked cross sectional area 185Sqmm 3.5 core on wall including taking down old cable, complete all as specified and directed.
Switch Air break, gang operated (GOD) with 15 Nos insulators in replacement, outdoor type, Three Pole mechanically operated, suitable for vertical installation, Single break, provided with locking arrangements consisting of MS channel, HT Post type insulator copper alloy, high Pressure, Assembly operating rod 20 mm dia GI pipe medium grade for operating from 1.2 metre above Ground Level with locking arrangement complete confirming to IS-1318 of 1972 rated voltage 11 KV and for current rating 400 Amps including taking down old UNSV GOD complete all as specified and directed.
Pin type porcelain in replacement, vitreous white, brown or green insulator including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, 150mm height, 150mm dia for 11000 volt complete including taking down old unserviceable insulator complete all as specified and directed.
Pin type porcelain in replacement, vitreous white, brown or green insulator including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, 100mm height, 65mm dia for 1100 volt complete including taking down old unserviceable insulator complete all as specified and directed.
Disc type insulator, single series, porcelain, vitreous, white, brown or green including one galvanised mild steel spindle, two galvanised 145 mm height 255 mm dia for 11000 Volts grade including taking down old unserviceable insulator complete complete all as specified and directed.
Shackle type insulator porcelain vitreous white, brown or green including galvanised M.S. straps 31 x 5mm size, 75mm height, 90mm dia including galvanised mild steel straps, nut, bolts washers complete for 1100 volts grade insulator complete including taking up of old UNSV Shackle type complete all as specified and directed.
Aluminium conductor steel reinforced (ACSR) including binding to insulator with suitable size of binding wire and size of conductor Weasel (6/1 x 2.59 mm), Squirrel (6/1 x 2.11mm) or Ferret (6/1 x 3.00 mm) including taking down old ACSR conductor, complete all as specified and directed.
Stay Assembly using stay rod of 20mm dia complete accessories as shown in Electrical Plate No 1 of SSR 2009 Part-I such as loop type insulator, porcelain, vitreous white/ brown or green, large size with overall dimensions 90 x 140mm clearance of hole 16mm, stay wire of size 7/4mm etc., including taking down old, complete all as specified and directed. Note: Excavation and concrete shall be measured and paid separately.
Loop type insulator large size porcelain vitreous of size 90 x 140 mm clearence of hole 16mm complete, fixed in repair all as specified and directed.
Cross arm bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, drilling holes for bolts, in any shape or size as indicated or directed and also inclusive of two coats of aluminium paint over one coat of red oxide primer including dismantling / taking down old unserviceable structural steel all as specified and directed.
Restringing / Restretching / Tightening of old ACSR conductor of any size and make on HT / LT Poles by disconnecting and removing from insulators including providing necessary binding wire and jumpering after proper stringing all as directed.
Painting of steel tubular pole any type with cross arms with one coat of aluminium paint after preparation of surfaces of pole / cross arms by scrapping of old paint, cleaning of all rusted surface and painting upto 1.5metre above PCC coping in black and white strips 05 Nos of 30cms each starting from the bottom of the pole and two coats epoxy based paint aluminium grade finish to the remaining external surface of pole and cross arms structure over one coat of primer and marking of MES No complete all as specified and as directed.
Lightning arrestor expulsion type, consisting of multiple spark gaps in series with one or more non-linear resistor to limit voltage surge on AC power circuit to interrupt power flow current suitable for outdoor installation and exposed direct to sun with ambient temperature between (-) 10° C to (+) 50° C suitable for surge discharge capacity 65 KA, 11000 Volts grade conforming to IS-4350 complete with all fittings including taking down old unserviceable arrestor, complete all as specified and directed.
Cable jointing kit for 11 KV (earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50-95 Sqmm including taking down old UNSV joints complete all as specified and directed.
Cable jointing kit for 11 KV (earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120-185 Sqmm including taking down old UNSV joints complete all as specified and directed.
Cable jointing kit for 11 KV (earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50-95 Sqmm including taking down old UNSV joints complete all as specified and directed.
Cable jointing kit for 11 KV (earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120-185 Sqmm including taking down old UNSV joints complete all as specified and directed.
Cable jointing kit for 11 KV (earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120-185 Sqmm including taking down old UNSV joints complete all as specified and directed.
Straight through epoxy joint suitable for LT cable 3.5 core, 25 Sqmm to 95 Sqmm including taking down old unserviceable joints, complete all as specified and directed.
Cutting and trimming of trees and branches to clear the over head line in the arc of HT/LT over head line feeders and removal of the trimmed branches of trees complete all as specified and directed. Notes : (i) Any ACSR conductor damaged during the cuttings of trees / branches shall be repaired and jointed / fixed by the contractor, to the entire satisfaction of Engr-in-Charge, without any extra cost and nothing extra shall be admissible from the department on this account what-so-ever. (ii) The cutting / trimming of tree branches shall be done to at least 2.00 metre radius of OH line. (iii) The unit of measurement is 'SPAN' i.e. distance covered between two poles.
MCCB 400 Amps, breaking capacity 36 KA, FP, 415V (microprocessor release) fixed in replacement complete all as specified and directed.
MCCB 250 Amps, breaking capacity 36 KA, FP, 415V (microprocessor release) fixed in replacement complete all as specified and directed.
MCCB 200 Amps, breaking capacity 36 KA, FP, 415V (microprocessor release) fixed in replacement complete all as specified and directed.
MCCB 160 Amps, breaking capacity 36 KA, FP, 415V (adjustable thermal and magnetic release) fixed in replacement complete all as specified and directed.
MCCB 100 Amps, breaking capacity 16 KA, FP, 415V (adjustable thermal and magnetic release) fixed in replacement complete all as specified and directed.
MCCB 125 Amps, breaking capacity 16 KA, TP, 415V (adjustable thermal and magnetic release) fixed in replacement complete all as specified and directed.
MCCB 63 Amps, breaking capacity 16 KA, FP, 415V (adjustable thermal and magnetic release) fixed in replacement complete all as specified and directed.
Change Over Switch (Front Operated) 200 Amps, 415 Volts, FP fixed in existing LT panel fixed in replacement complete all as specified and directed.
Off Load Change Over Switch 100 Amps, 415 Volts, FP in sheet metal enclosure suitable fixed in replacement complete all as specified and directed.
Street Light fitting 60 Watts LED made up of pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover having top opening seperate driver compartment with IP66 protection and impact resistance of IK07 with 10KV built-in surge protection device including taking down old unserviceable Street Light Fitting any type complete, all as specified and as directed. Make : Havells 'Endura Pearl Neo' Cat Part No SL60WLED757PASYTOPC or equivalent in Wipro / Philips / Crompton NOTE: CA NO shall be marked on each fitting with permanent marker before fixing and properly bound register shall be maintained for defect liablity period.
Earthing complete with GI earth plate electrode of size 600mm x 600mm x 6mm thick buried directly to ground vertically to a depth not less than 2.25 Mtr below the ground level with top edge of earth plate not less than 1.65 Mtr below normal ground level connected to GI strip 32 x 6 mm size and earthing lead protected with 50 mm bore GI pipe, light grade, filling around with charcoal dust and salt including excavation, returning, filling of earth and disposal of surplus soil to a distance not exceeding 50 mtr and connected to GI strip by means of GI nuts, bolts and washers strip connected to earth plate including chamber PCC 1:3:6 type C-1 using 20mm graded crushed stone aggregate in concrete pit pre-cast RCC 40 mm thick reinforced with 6 mm dia round at 75 mm C/C both way with 12 mm dia mild steel plain bar lifting handle 2 Nos funnel with wire mesh 20 mm dia GI pipe light grade watering pipe and frame work complete all as shown in electrical plate No. 3 of SSR Part-I 2009 including testing on completion complete all as specified and as directed.
Galvanised Iron earthing strip 32 x 6 mm from earth test point to electrical equipment including taking down old unserviceable earthing strip complete all as specified and directed
Earthing complete with galvanized mild steel earth plate electrode size 600mm x 600mm x 6mm thick buried directly in ground (preferably in vertical position) earth pit not less than 2.25 meter below normal ground level with top edge of the earth plate not less 1.5 meter (BGL) connected to galvanized iron earth lead wire 4mm dia by means of bolts, nuts, check nut and washer of galvanized iron including PCC pit in RCC 1:2:4 type B-1, precast RCC cover with suitable handle, excavation and earth work in any type of soil, 20mm bore “medium grade” galvanized iron water tubing fixed with cast iron funnel and wire mesh and 15mm bore “light grade” galvanized iron protection pipe for earth lead wire upto 5m length, charcoal, common salt, complete all as shown in EP No 3 of SSR 2009 Part-I, connected to test point complete, all as specified and testing on completion.
Galvanised Iron earth wire 4 Sqmm from earth test point to electrical equipment including taking down old unserviceable earth wire complete all as specified and directed
Material and labour for disconnecting electrical connection removing the defective transformer, loading and transporting to workshop from site and vice-versa including disconnecting and rewinding of 11/0.433KV, 63 KVA to 315KVA, Three Phase, Four Wire, 50Hz vector group Dyn 11 transformer with paper insulated copper winding wire / strip as per original data on HV (delta connection) and LV (Star Connection) 7 tapping brought on HV side for tap charger to change + 2.5%, 5%, 7.5% by means of manually operated Off-Load tap changing gear complete rewinding of HV on three limbs providing insulation material like spares, wooden blocks, cotton tape etc. and re-conditioning three limbs complete opening, replacement of cock sheet packing, vent diaphragm replacement of LT terminal plate, breather, filling of new transformer oil for top up with existing oil after proper filtration upto level of 50 KV dielectric strength and testing of transformer at factory and site after connecting all electrical connection in full load all as directed.
Notes :- 1. Spares required will be measured and paid separately under appropriate item. 2. The Quoted Rate shall be deemed to include transportation, electrical connections, Testing & Commissioning. 3. Necessary test certificate from authorised workshop after repair shall be submitted by the contractor to the Engr-in-Charge.
Supply only following Items / Spares required for transformers :-
(a) HT coil of suitable gauge of paper insulated copper winding wire for any capacity of transformer
(b) LT coils of suitable guage of paper insulated copper winding wire for any capacity of transformer
(c) Gasket for Transformer
(d) LT Terminal Plate for outgoing connections
(f) HT Bush and Bush Rod for Outdoor Transformer complete
(g) LT Bush and Bush Rod complete
(h) Breather for Transformer of capacity 63 KVA to 315 KVA
Supply, filling and top up with new Transformer Oil of dielectric strength more than 50 KV at 2.5mm gap confirming to IS : 335-1993 complete all as specified and as directed. Make : APAR Oils / Savita
Dehydration of transformer oil by using filtration plant of suitable capacity and removing the moisture / dust till obtaining the oil dielectric strength 45 KV at 2.5mm gap and above for various transformer / voltage stabilizer of any size located at different substations, complete all as specified & directed.
Disconnecting electric supply from both ends of defective Voltage Stabilizer of capacity 300 KVA after disconnecting electric supply from both ends and transporting the same from Ramban/Banihal to Workshop at Jammu, opening top cover, taking out transformer oil, checking for faults and replacing the defective parts, checking / testing the stabilizer, refilling and topping up the transformer oil and transporting back to Patnitop/nathatop and refixing in original position, making connections complete all as specified and directed.
Disconnecting electric supply from both ends of defective Voltage Stabilizer of capacity 20 KVA to 63 KVA after disconnecting electric supply from both ends and transporting the same from Ramban/Banihal to Workshop at Jammu, opening top cover, taking out transformer oil, checking for faults and replacing the defective parts, checking / testing the stabilizer, refilling and topping up the transformer oil and transporting back to patnitop/nathatop respectively and refixing in original position, making connections complete all as specified and directed.
Disconnecting electric supply from both ends of defective Voltage Stabilizer of capacity 100 KVA after disconnecting electric supply from both ends and transporting the same from Ramban/Banihal to Workshop at Jammu, opening top cover, taking out transformer oil, checking for faults and replacing the defective parts, checking / testing the stabilizer, refilling and topping up the transformer oil and transporting back to Patnitop/nathatop and refixing in original position, making connections complete all as specified and directed.
Notes for item no.57 to 59 :- (i) Spares required will be measured and paid separately under appropriate item. (ii) The Quoted Rate shall be deemed to include transportation, electrical connections, Testing & Commissioning. (iii) Necessary test certificate from authorised workshop after repair shall be submitted by the contractor to the Engr-in-Charge.
Supply only following Items / Spares required for Stabilizers :-
(a) Reversible motor low speed instant Start / Stop High Torque having speed 960 RPM and of capacity 0.08HP.
(b) Servo Circuit Card.
(c) RC Network.
(d) Dimmer for 300/100 KVA Voltage Stabilizer.
(e) Dimmer for 63/30/20 KVA Voltage Stabilizer.
Synthetic Insulation Mat in replacement, chequered type as per ISI specification of size 2.0m x 1.0m x 12mm thick suitable for LT Panels, Transformers or DG Sets, complete all as directed.
Steel pipe galvanised light grade, 80 mm bore laid in trenches or under ground/floor or road of fixed with pole for protection of cable including GI clamps with bolts nuts and washers complete all as specified and directed.
Steel pipe galvanised light grade, 50 mm bore laid in trenches or under ground/floor or road of fixed with pole for protection of cable including GI clamps with bolts nuts and washers complete all as specified and directed.
Supply & fix in repair Bus bar panel size 0.8x0.4x0.4Mtr, KISOK, outdoor type, CRPI tested, LT 440 Volts, 50 Hz, 3 phase 4 wire supply, comprising of bus bas chamber with 4 Nos aluminium strip bus bars PVC insulated with colour coding af rating 200A, floor mounted factory fabricated weather and vermin proof protection class IP 54 made out of 1.4 thick MS sheet CRCA on angle iron 30x30x4mm frame with front opening doors, locking arrangement powder coated internally and externally, shall have channel base of appropriate size and mounted on PCC foundation of size as required or approved by manufactures in PCC 1:3:6 type C-1, using 20 mm graded crushed stone aggregate as directed including earth work complete all as specified.
M&L testing & commissioning in replacement of LT panel frame CPRI approved, indoor type, factory made fabricated to CRCA sheet of 3.15mm thickness, double door front/ rear opening and locking arrangement, floor mounted on platform of suitable size, aluminium bus bas chamber (enclosed) with two coat of synthetic enamel paint over a coat of red oxide primer mounted on PCC blocks, fixed with grouted bold, nuts and washer and making complete connection in all respects as directed by Engr-in-Charge comprising of following fitments;-
(A) Incoming (i) MCCB 400 Amps, breaking capacity 36 KA, FP, 415 Volts (adjustable thermal and magnetic release) – 01 No (B) Outgoing (i) MCCB 200 Amps, breaking capacity 36 KA, FP 415 Volts (adjustable thermal and magnetic release) – 02 Nos (ii) MCCB 160 Amps, breaking capacity 36 KA, FP 415 Volts (adjustable thermal and magnetic release) – 01 Nos (iii) MCCB 125 Amps, breaking capacity 25 KA, FP 415 Volts (adjustable thermal and magnetic release) – 02 Nos (iv) MCCB 100 Amps, breaking capacity 16 KA, FP 415 Volts (adjustable thermal and magnetic release) – 01 Nos
Make of Panel : DV Electromatics Private Limited / Simon Fabricators / Electricfield Co / Adhunik Switchgear / Universal Switchgear Make of MCCB : L&T / Legrand / Schneider / Havells Make of Voltmeter / Ammeter / Multifunction Meter : SECURE / L&T (RISHAB) / C&S ELECTRIC / MECO
Aluminium cable lugs (connectors) for fixing/tightening of electric cable 16-35 Sqmm alonwith nuts and bolts, complete all as specified and directed.
Aluminium cable lugs (connectors) for fixing/tightening of electric cable 50-95 Sqmm alonwith nuts and bolts, complete all as specified and directed.
Aluminium cable lugs (connectors) for fixing/tightening of electric cable 120-240 Sqmm alonwith nuts and bolts, complete all as specified and directed.
Excavating in post holes (or similar holes) each n exc 0.5 cu. m, getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm,in soft/loose soil
ERW or induction butt welded tubes confirming to IS 1161-1979 grade Yst-240 etc as in posts of nominal bore 80mm and outside dia 88.90 mm medium grade (4.05mm thickness) including special shaped washer etc. complete all as specified and directed.
Providing plain cement concrete 1:3:6, type C2, using 40 mm graded stone aggregate, as in foundation filling and mass concrete complete all as specified and directed.
Pre-painted galvatume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of an colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws complete all as specified and directed.
Roof trusses (framed), trussed, purlins, crane gantries, rails and fastenings and heavy bracket framing (Beam, tee, angle, channel or flat sections) including distance pieces, cleats etc.Fe 410-W (Gde- E- 250) quality- A complete all as specified and directed.
Rolled mild steel plates as in guesset plates, base pletes etc complete all as specified and directed.
Mild steel bolts purpose made, with hexangonal or square head one end and screwed the other, or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut, exc 30 cm but n.exc 50 cm long dia of n.exc 12, complete all as specified and directed.
Preparation of new steel surfaces and applying two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed.
MS nut, bolts and washers of size 65 mm to 80 mm long 16 mm dia, fixed in repairs, complete all as specified and directed.
Supply and fixing in replacement 11KV CTPT metering unit, outdoor type, air cooled, pole mounted, CT Ratio 5/5 Amp, Burden 10VA, class-0.5S, STC-3 KA/1 Sec and PT Ratio 11KV/110V, Burden 0.5VA, class-0.5S, insulation-12KV/28KV all as per IS 2705/1992 and IS 3156/1992 complete all as specified and directed.
1.5 Sqmm, 10 core PVC insulated, unsheathed FRLS copper cable for connection from CT/PT unit to Trivector meter including taking down old all as specified and directed.
Trivector meter three phase four wire TVM 110 Volt, PTR 11kv/110V, 5A class 0.5S for active and 1 s reactive with water proof box complete all as specified and directed.
Supply ,Install Testing & Commissioning of self supporting totally enclosed double door at front, LT feeder piller compartmentalised design, dust and varmin proof of size 1000 mm(Height) x 1000 mm(Length) x 450 mm(Width) suitable for 440 Volt 3 phase 4 wire system made out of 3.15 mm thick CRCA sheet and built upon regid frame work having front and rear hinged doors with neoprence rubber gasket including danger plate, earthing strip point and, ventilation louvers at the rear side, bottom detachable gland plate complete with suitable size of Zinc/Cromium plated and nuts, bolts ;and washers etc. The pannel shall be synthetic enamelled painted and the control circuit diagram shall be with colour code solid conductor copper 1.5 sqmm cable for easy identification including incomming/outgoing cable holes at the bottom, complete after taking down the old unserviceable one. The Panel shall be emmbeded with 75 x 6 mm MS Angle Iron frame and to be grouted with PCC foundation (1:3:6 ) type C2 upto a height of 50 cm from normal ground level complete all as specified and directed by Engr in charge and comprising of the following:-
Make of Panel : DV Electromatics Private Limited / Simon Fabricators / Electricfield Co / Adhunik Switchgear / Universal Switchgear Make of MCCB : L&T / Legrand / Schneider / Havells Make of Voltmeter / Ammeter / Multifunction Meter : SECURE / L&T (RISHAB) / C&S ELECTRIC / MECO
Supply & fixing LED lights 70 Watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with driver and lamp complete and all as specified and directed. Havells/Wipro/HPL/Syska
R C TRADERS
SWASTIK TRADERS
M/S Builders Indias
Bidder Name
SWASTIK TRADERS
M/S Chib Engineers
M/S Builders Indias
R C TRADERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .