Tender Value
Refer Docs
EMD Value
₹6,000
Closing Date
30 Sept 2023, 2:00 pmClosed
SE EUDC-X
33/11 KV S/S PURNIYA ALIGANJ LUCKNOW
Increasing Capacity of 250 KVA to 400 KVA LT Substation Shivpuram, Triveni Nagar and Earthing of Distribution T/Fs in the area of Puraniya and Ahibaranpur Sub Division Under the jurisdiction of EUDD-Daliganj, LESA, Trans Gomti, Lucknow against Sancti
2023_MVVNL_843328_1
28/EUDC-X/2023-24
Open Tender
Electrical Works
Item Wise
60 days
EUDD-Daliganj, LESA
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,180
EE EDD BKT LESA LUCKNOW
₹6,000
4 Oct 2023
26 Sept 2023
30 Sept 2023
26 Sept 2023
30 Sept 2023
26 Sept 2023
Amount
Loading, carriage & unloading of following materials from centre store Daliganj to work site and its stacking. Distance approx (0-50) kms.
250/400 KVA T/F
LT PVC Cable 1x400/3.5x 240/1x 70SQMM
ACSR Rabit/Dog /Racoon/weasel/ conductor
ABC( 3x120/95/70/25/16) Sqmm.
Repairing of T/F plinth of size 2x2x1.2 meters with help of 1st class bricks and massonary in the ratio 1:4 cement & sand coarse, filling the structure completely as per norms with RCC top 1:2:2 cement, sand coarse, stone grit with MS bar and MS channel for resting T/F. All material shall be arranged by the contractor.
Wiremess fencing of 11/0.4 KV S/S shall be made of rectangular of size as per site requirement not exceeding 3 meter fabrication 45x45x5 mm angle the frame is also have 1 no. Horizontal runner of MS flat 40x5 welded in middle to support of wire mess. Rectangular welded type wire mess of size 50x25 made of 12 S.W.G. wire mess shall be welded all along the periphery of the frame as well as on horizontal runner to give extra strength of welding to wire mess welded on the frame. Diagonal bracing of all the frame panel will be welded with MS flat of size 25x3mm to support as per RESPO specification & direction of E/I.
Construction of masonry type Distribution Pillar box with first class brick ballast cement, coarse sand, local sand, brick ballast and MS Round bar of 10 mm dia including supply and mounting of 02 nos. Straight MS Angle 50x50x6x750 mm- 2 nos., Henely type tailless fuse units 500 Amps. 650 Volts one no. for incoming and other for outgoing, Copper bus bar 4 nos. 1000x50x6 mm with locking arrangement made of 18 SWG BP Sheet.
Erection & commissioning of (3x120/95/70/25/16 Sq.mm) Aerial Bunched Conductor.
Laying and sagging of 3 phase 3 wire 11 KV line on ACSR weasel/rabbit/Raccoon/Dog conductor as per RESPO specification and direction of E/I.
Laying of LT PVC Cable 1x400/3.5x240 SQMM as RESPO specification & direction of E/I.
Earthing of T/F Pipe type with 60 fit deep borring and providing GI Pipe 1.5" dia (60 fit GI Pipe) and GI strip 25x5 mmx6 meter long attached with clamps, L piece, nut & bolts and GI Pipe Cap. All material shall be supplied by the contractor.
Safe Installation of 250/400 KVA T/F on double pole by providing and fixing of all accessories along with making HT/LT connection and its commissioning.
Dismantling of 250 KVA T/F on exsiting plinth along with dragging, loading cartage and unloading to work site J.E dump store/Central store.
Suppy and fixing
ALU LUG 400 KVA
CLAMP FOR CHANEL
COPPER L- PIECE
POWER CONTROL AND SWITCHGEARS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .