Elect. 400 K.V S.S Div Banda
Work of Installation of Cooling and Exhaust Fans for Radiator sections of 125 MVAR Bus Reactor Installed at 400 KV S.S Banda
2021_UPTCL_594482_1
T-22/E.400KVS/SDIV.(B)/2021-22
Open Tender
Electrical Works
Lump-sum
90 days
Elect. 400 K.V S.S Banda
Detail enclosed
2 documents required · 2 mandatory
₹236
Executive Engineer
₹4,000
18 Jun 2021
11 Jun 2021
18 Jun 2021
11 Jun 2021
18 Jun 2021
11 Jun 2021
11 Jun 2021 - 18 Jun 2021
Amount
Details of Work.
Fabrication of as per size of fan(w) x 2.70(L) x 2.45(h) mtr size, angle (angle size 65 mm x 65 mm) structure from iron net level (height from iron net level 1.35 mtr) for fixing of 3 no., 30 inch, 3 phase, 900 rpm, 910 watt, heavy duty Insductrial exhaust fan, ruggedly built suitable for outdoor use including cutting, welding & grinding of angle of angle structure for smooth finishing below 125 MVAR Bus Reactor Radiator bank (1 Bank contain 3 no. radiator) one no. angle structure has 6 no. leg for grouting of frame.
Fgrouting of 6 no. leg (grouting pit size, towards Top CC level to PCC level 0.45 mtr (h) x 0.3 mtr (round pit dia) of angle structure frame 1.25 or as per size of fan (w) x 2.70 (l) x 2.45 (h) mtr size (Angle size 65 mm) below 125 MVAR Bus Reactor bank with cement, coarse sand & stone ballast in 1:1.5:3 proportion for concreting & all associated work for completion of above work including all man, material and T&P
Providing & Fixing of 750 mm/ 30 inch Fan diameter, 3 phase, 900 rpm, 910 watt Heavy duty Industrial exhaust fan, ruggedly built suitable for outdoor use (Make- Crompton/ Havells/ Khetan) with guard net at its back side.
Providing & Fixing of 6 no., 4 phase, 16 Amp MCB for Heavy Duty Exhaust fans a7 also providing & grouting of cooling fan MCB cubical fan suitable with arrangement for fixing of 6 nos. MCB, 4 wire buses strip made up of copper (R,Y,B, N phases) for giving input supply to fan MCB, will be fitted 80 cm above ground level box size 750mm x 900 mm near the 125 MVAR Bus Reactor including glanding, Termination work, of cable at its both end with proper ferruling and finnally checking for smooth operation of the cooling fans under the guidance of supervision engineer.
Rates qouted by the bidders shall be without taxes. Taxes applicable if any to paid extra
SOMI ENTERPRISES AND SUPPLIERS
S N ENTERPRISES
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .