Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Fee/PreQual/Technical/Finance | Admitted-Fee/PreQual/Technical/Finance |
| 2 | Admitted-Fee/PreQual/Technical/Finance | Admitted-Fee/PreQual/Technical/Finance |
| 3 | Admitted-Fee/PreQual/Technical/Finance E 172 CHAURA MAIDAN 103 TUNNEL SHIMLA HIMACHAL PRADESH 171001 | SHIMLA | HIMACHAL PRADESH | 171001 | Admitted-Fee/PreQual/Technical/Finance |
| 4 | Admitted-Fee/PreQual/Technical/Finance DHARAMPUR | Admitted-Fee/PreQual/Technical/Finance |
| 5 | Admitted-Fee/PreQual/Technical/Finance | Admitted-Fee/PreQual/Technical/Finance |
Tender Value
₹10.0 L
EMD Value
₹20,000
Closing Date
17 Aug 2020, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer Electrical Division HPPWD Una
Executive Engineer Electrical Division HPPWD Una
Construction of District Welfare Office building at Hamirpur HP SH Providing EI there in .
2020_PWD_39365_1
PW-EDU-CB-TA-Tender-2019-20- 944-1000 Dt-21-07-202
Open Tender
Electrical Works
Item Rate
360 days
Hamirpur
Please refer tender document
6 documents required · 6 mandatory
₹350
EE Electrical
₹20,000
19 Aug 2020
29 Jul 2020
19 Aug 2020
29 Jul 2020
17 Aug 2020
29 Jul 2020
120 days
Amount
Wiring for light point / fan point / exhaust fan / call bell point with 1.5 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit with modular switch, modular plates, suitable G.I. box and earthing the light point with 1.5 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable as required.
Group C.
Wiring for twin control light point with 1.5 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit with 2-way, 5/6 amps. modular switch, modular plates, suitable G.I. box and earthing the light point with 1.5 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable as required.
Group C.
Wiring for circuit/sub-main with following size PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 1 No.HRFRLS/PVC insulated single core copper conductor cable of same size for earthing as required..Make:Phenolex/Polycab/Anchor/KEI or its equivalent as approoved by the engineer incharge.
2x1.5 Sq. mm.
2x4.0 Sq. mm.
2x10 Sq. mm.
Wiring for circuit / sub-main with 4x4 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 2 No.4 Sq.mm. (4X4+2X4)HRFRLS/PVC insulated single core copper conductor cable for earthing as required.Make:Phenolex/Polycab/Anchor/KEI or its equivalent as approoved by the engineer incharge.
Wiring for circuit / sub-main with 4x10 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 2 No.10 Sq.mm. (4x10+2x10) HRFRLS/PVC insulated single core copper conductor cable for earthing as required..Make:Phenolex/Polycab/Anchor/KEI or its equivalent as approoved by the engineer incharge.
Wiring for circuit / sub-main with 4x16 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 2 No.16 Sq.mm. (4x16+2x16) HRFRLS/PVC insulated single core copper conductor cable for earthing as required..Make:Phenolex/Polycab/Anchor/KEI or its equivalent as approoved by the engineer incharge.
Supplying and fixing following rating Modular switch /socket in the existing switch box / cover plate including connections etc. as required. Make:SSK/Anchor/L&T or its equivalent as approoved by the engineer incharge.
S.P. 5/ 6 Amps one way Modular switch.
5 pin, 5/ 6 Amps Modular socket outlet.
Supplying and fixing G.I. Modular box of (140mmx78mmx50mm) size with modular plate and cover in recess including providing and fixing 5 pin 5/6 amps modular socket outlet and 5/6 amps, modular switch, connections etc. as required.
Supplying and fixing G.I. Modular box of (140mmx78mmx50mm) size with modular plate and cover in recess including providing and fixing 6 pin 15/16 amps modular socket outlet and 15/16 amps, modular switch, connections etc. as required.
Supplying and fixing Ding-Dong / Electronic musical bell, suitable for D.C./A.C. single phase,230 volts complete as required:-
Supplying and drawing following size of PVC insulated, heat resistant, flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in existing surface / recessed, Steel/PVC conduit as required.
3x1.5 Sq. mm.
3x4.0 Sq. mm.
Wiring for circuit/sub-main with following size PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed PVC conduit along with 1 No. HRFRLS/PVC insulated single core copper conductor cable of same size for earthing as required.
2x1.5 Sq. mm.
Supplying and fixing of following sizes of PVC conduit along with the accessories in surface / recess including cutting the wall and making good the same in case of recessed conduit as required:-
25 mm. dia
50 mm. dia
Supplying and erection of wall mounted metal boards for switch gear mounting of suitable size, with permissible variation in size of plus minus 5mm, welded frame work made of M.S. angle iron (50 mm x 50 mm x 6 mm thick) with sufficient numbers of horizontal and vertical intermediate members (25mm x 6mm thick) flat iron including painting and bonding to the existing earth as required:-
Supplying and fixing 4 pole MCCB 20 Amp to 63Amp Ics = 100% icu, 25KA & @ 415 volts, 50 Hz with thermal magnet in release complete with connection ,testing and commissioning etc as required .Make:-L&T Cat. No. (CM91712OOCOOGC,M91712OOEOOG,CM91712OOHOOG),Schneider, ABB , or its equivalent as approved by Engineer-in -charge.
Supplying and fixing of 4 pole DU 125H/DU100D/DU125D/DNO MCCB Enclosure complete with connection testing and commissiong etcasrequired .Make:-L&T ( cat no-CM9O9960000), Legrand, ABB or its equivalent as approved by Engineer-in -charge.
Supplying and erection of 6 amps. to 32 amps. rating, 10 KA breaking capacity, 240 volts, 'C' curves, miniature circuit breaker of following poles in the existing MCB DB complete with connections etc. as required:-Make:L&T/ABB/schinder or its equivalent as approved by Engineer-in -charge .
Single pole. Cat-A.
Double pole. Cat-A.
Supplying and fixing following rating, double pole (single phase & neutral) 240 volts, residual current circuit breaker (RCCB), having a sensitivity current up to 300 miliampers in the existing MCB DB complete with connections, testing and commissioning etc. as required.Make:L&T/ABB/schinder or its equivalent as approved by Engineer-in -charge .
40 Amps. Cat-A.
Supplying and erection of 40/50/63 amps rating, 10 KA breaking capacity, 240 volts, 'C' curves, miniature circuit breaker of following poles in the existing MCB DB complete with connections etc. as required.Make:-L&T/ABB/schinder or its equivalent as approved by Engineer-in -charge .
Double pole. Cat-A.
Supplying and fixing following rating, double pole (single phase & neutral) 240 volts, residual current circuit breaker (RCCB), having a sensitivity current up to 300 miliampers in the existing MCB DB complete with connections, testing and commissioning etc. as required.Make:L&T/ABB/schinder or its equivalent as approved by Engineer-in -charge .
40 Amps. Cat-A.
25 Amps. Cat-A.
Supplying and fixing of SMDBs for power distribution board 4 way complince with latest standard IEC61 439 -2 DEKRA and ASTA certified rating upto 630 amp short time current with stand current 250 amp and 400 amp SMDB -36 KA ,630 amp SMDB-50 KA wth ingress protection -IP43 with INCOMING MCCB 3 pole 160 amp and outgoing MCCB 3 nos 63 and 1 no 20 amp MCCB, with metering box bottom cabling box ,Monting base , side cbling box ,corner box 4 no phase indicating lamp multi function meter ,with 3 nos CT coil of 200/5 amp complete as required with all leads and lift . Make :- L& T,schinder ,ABB or it equivalent asapproved by Engineer - in - charge .Dimension H 787 MM, W 670 MM,D 208.5 MM
Supplying and fixing of Segregated tripple pole and neutral 6 way, sheet steel MCB distribution board 415 Volt on surface /recess with provision to mount MCCB as incomer with provision of 100 amp insulated phase bus bar /neutral bar with shroud/s /earth bar sticking saddles cement spill protector /colour coded interconnected wire set /cable ties/blanking plate and circuit indentification labels .DP RCCB as subincomer and single pole MCB as out going.Powder painted including earthing etc as required.Make:-L&T (code-DBPGL006DD)/ABB/schinder or its equivalent as approved by Engineer-in -charge .
Supplying and fixing of following way, single pole and neutral sheet steel MCB distribution board, 240 volts, on surface / recess, complete with tinned copper bus- bar, wire-set, neutral link, earth bar, din-bar, detachable gland plate, blanking plate, cable, identification labels interconnections, phosphatized and powder painted, including earthing etc. as required:-Make:L&T/ABB/schinder or its equivalent as approvedby Engineer-in -charge .
Double door-4 way
Double door-8 way
Double door-12 way
Providing, laying and fixing of one No. aluminium conductor, PVC insulated and PVC sheathed, armoured/XLPE power cable, working voltage 1100 volts grade on surface etc. of the required size:-
Armoured cable 50 sq. mm (3.5 core)
Armoured cable 16 sq. mm (four core)
Providing and laying of one No. aluminium conductor, PVC insulated and PVC sheathed, armoured/XLPE power cable, working voltage 1100 volts grade direct in ground; to be laid 1 meter below the ground level including excavation sand cushioning, protective covering and refilling the trench etc. of the required size:-
Armoured cable 50 sq. mm (3.5 core)
Providing, Installation, testing and commissioning of ceiling fan with step type 2 module regulator, including wiring the down rods of standard length (up to 30 cm) with 16/0.20 mm twin twisted flexible, cotton braided, copper cable, including providing and fixing phenolic laminated sheet cover on the fan box and earthing etc. as required:- Make:Usha technix plus/Bajaj(more than three star) or its equivalent as approoved by the engineer in charge.
Ceiling Fan 1200 mm sweep, Category-A
Providing and installation of exhaust fan of following sizes in the existing opening, including making the hole to suit the size of the above fan, making good the damages, connections, testing and commissioning etc. as required:- Make:Usha technix plus/Bajaj or its equivalent as approoved by the engineer in charge.
Exhaust Fan, Light duty, (Domestic) 300 mm sweep
Supplying and fixing of bulk head fitting of all sizes and shapes, containing one No. thread type CFL lamp holder (s), complete with all accessories but excluding CFL lamp including making connections, testing etc. as required.
Bulk head fitting, CFL type (Category-A)
S/F Louver Shutter of aluminium body size 1'x1' on the existing exhaust fan suitable to be operated on start of exhaust fan as and when required as required complete.
Supplying and fixing surface square type LED 15 watt ,6000k ,with three year warranty and it should be compatible with specification e.i. Power Factor > .9,Harmonic Distortion<10% and efficiency>100 Lumens per watt,CRI> 80 suitable for input voltage: AC 220-240 V, 50/60Hz, complete with all accessories, connections, testing and commissioning etc.Make -Panasonic /Tisva/Philips or its equivalent as approved by Engineer-in-Charge
Supplying and fixing surface square Panel LED 12 watt ,6500k , with three year warranty and it should be compatible with specification e.i. Power Factor > .9,Harmonic Distortion<10% and efficiency>100 Lumens per watt, CRI > 80 suitable for input voltage: AC 220-240 V, 50/60Hz, complete with all accessories , connections, testing and commissioning etc.Make -Jaquar LIGHTING (Code-LNRO02S012SC SURFACE,SQ.)/PHILIPS/Tiswa/Panasonic or its equivalent as approved by Engineer-in-Charge
Supplying and fixing surface square type LED 18 watt ,6000k with three year warranty , and it should be compatible with specification e.i. Power Factor > .9,Harmonic Distortion<10% and efficiency>100 Lumens per watt, CRI> 80 suitable for input voltage: AC 220-240 V, 50/60Hz, complete with all accessories, connections, testing and commissioning etc.Make :-Jaquar(Mode-LNR0025018SC)/panasonic/Philips/Tiswa or its equivalent as approved by Engineer-in-Charge
Supplying and fixing surface/recess square type LED 24 watt ,6500k , with three year warranty and it should be compatible with specification e.i. Power Factor > .9,Harmonic Distortion<10% and efficiency>100 Lumens per watt, CRI> 80 suitable for input voltage: AC 220-240 V, 50/60Hz, complete with all accessories, connections, testing and commissioning etc.Make :-Jaquar(Mode-LNEP01S024XC)/panasonic /Philips/Tisva or its equivalent as approved by Engineer-in-Charge
Providing and fixing of surface mounted Luminaire LED 25 Watt batten ,having high Quality design aluminium extruded decorative end caps with three year warranty and it should be compatible with specification i.e. Power Factor >.9,Harmonic Distortion <10% and efficiency>100Lumens per watt ,CRI> 80 suitable for input voltage: AC 220-240 V, 50/60Hz, complete with all accessories, connections, testing and commissioning etc.as required .Make :-Philips(BN021LED25S6500PSU GRS1),Panasonic,Jaquar,Tisva or its equivalent as approved by Engineer-in-charge.
Supplying and fixing surface mounting 1'x4' size LED solution for recess/suspended application with the use of the latest LED technology 30 watts(3000 lumens)6500 K , with three year warranty and it should be compatible with specification i.e Power Factor > .95,Harmonic Distortion<10% and efficiency>100 Lumens per watt suitable for input voltage: AC 220-240 V, 50/60Hz, complete with all accessories, connections, testing and commissioning etc.as required Make :-Philips (Code :-SM270C LED30 S6500PSU WH) )/Tiswa/Jaquar or its equivalent as approved by Engineer-in-Charge.
Providing and fixing of LED Lamp B-22/E-27 base type of following wattage in the existing fitting,including connection ,testing and commsissioning etc as required.Make-Jaquar /philips /Panasonic or its equivalent as approved by Engineer-in-charge ..
Supplying and fixing Computer board comprising 3 nos 5 amp modular switches , metal box 2 module for jack box and metal box 200 mmx150 mmx75 mm for 5 amp switchs and 5amp sockets comprising sheet cover for each 2module metal box , one no computer jack (RJ-45)with shutter including connections etc as required .
Supplying and drawing Lan cable Cat -6 Finolex make, solid copper conductor 4 pair protected with PVC Sheathed in existing surface /recessed steel/PVC Conduit as required.Make Finolex ,D-link,Polycab or its equivalent as approved by Engineer-in-charge.
Supplying and fixing Lan switch (sheet steel body) D-Link DGS-1008 D 8 P0rt 10/100/1000 Giga an switch for getting blazing speed of Giga bit that delivers power performance and reliability i.e. increasing the speed of net work server in large in switching Protocol storing and farwarding as required.
Providing and fixing of lightning conductor finial, made of 25 mm dia. 300 mm long copper tube, having single prong at top, with 85 mm dia 3 mm thick copper base plate including holes etc. complete as required.
Earthing with copper earth plate 600 mmx600 mmx 3 mm thick, including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. ( but without charcoal or coke and salt ) complete as required.
Extra for using salt and charcoal for G.I. or copper plate earth electrode complete as required.
Providing and fixing 25mm x 5mm G.I. strip on surface or in recess for earth connections etc. as required.
Providing and fixing 25mm x 5mm copper strip in 40 mm dia. G.I. pipe from earth electrode etc. as required.
Supplying and fixing copper tape 20mmx3mm thick on parapet or surface of wall for lightning conductor as required ( for vertical run)
Supplying and fixing copper tape 20mmx3mm thick on parapet or surface of wall for lightning conductor as required ( for horizontal run)
Supplying and fixing of LED 60 Watt street light in Aluminium pressure die cast housing with toughened glass cover (IP 66 protection ) 5700 k, with three year warranty it should be compatible with specification e.i. Power Factor > .9, and efficiency>100 Lumens per watt, suitable for input voltage: AC 220-240 V, 50/60Hz, complete with all accessories, connections, testing and commissioning with three year warranty etc. as required.Make -PHILIPS (code:-BRP062LED68CWSLCS1PSU) /Wipro/K-Light or its equivalent as approved by Engineer-in-Charge.
Supplying and erection of street light bracket made of G.I. pipe 'A' class of suitable length and dia, the pipe bended to give an angle of 100 to 110 degree fitted with bolt & nuts at the top of existing pole or wall including painting the pipe with two coats of approved paint over priming coat complete in all respects as required:-
32 mm dia. G.I. pipe, heavy class
Providing and fixing of Rubber Mat 1x2 mtrs long 12mm thick in the front main panel etc as required at site
Supplying and fixing Shock treatment chart in main panel room on the existing wall etc as required and as approved by Engineer-in-charge.
Providing and commissioning of self supporting stool type ladder made out of aluminium section of size 66mmx31mmx3mm thick approximate with special steps of various sizes (i) 57mmx3mm thick approx. supported on 15 mm solid square rod. (ii) 63mm wide to 112mm wide at a required distance of 300mm apart on side and other supporting side having steps made out of 25 mm dia support approx. Aluminium fluited pipe at required distance of 300 mm apart complete with servicemen's plateform at the top and rubber shoes at four legs bottom end to make the ladder non slippery and durable. Required size 8 ft Height.
AJAY KUMAR GOVT CONTRACTOR
Shiv Shakati electric gen store
AKSHAY DOGRA
HAMIR ELECTRICAL
Krishan Pal
Vikas soni
Krishan Kumar
anil kumar govt. contractor
stage.html
html • 0.04 MB
finance_58130.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .