Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.4 CrAccepted-AOC 04 L BLOCK MARKET SECTOR 11 NOIDA 201301 UP GAUTAM BUDHA NAGAR | GAUTAM BUDDHA NAGAR | UTTAR PRADESH | 201301 | ₹1.4 Cr | L1 | Accepted-AOC L1 BIDDER |
| 2 | L2₹1.4 Cr+₹2.2 L (1.53%)Rejected-Finance 13 29 3RD FLOOR EAST PATEL NAGAR NEW DELHI 110 008 | WEST | DELHI | 110008 | ₹1.4 Cr+₹2.2 L (1.53%) | L2 | Rejected-Finance OTHER THAN L1 |
| 3 | L3₹1.5 Cr+₹4.7 L (3.32%)Rejected-Finance | ₹1.5 Cr+₹4.7 L (3.32%) | L3 | Rejected-Finance OTHER THAN L1 |
| 4 | L4₹1.6 Cr+₹12.2 L (8.54%)Rejected-Finance CHANDAN NAGAR OPP IOCL PERTROL PUMP RAMPUR ROAD BAREILLY UP 243001 | BAREILLY | BAREILLY | UTTAR PRADESH | 243001 | ₹1.6 Cr+₹12.2 L (8.54%) | L4 | Rejected-Finance OTHER THAN L1 |
| 5 | L5₹1.7 Cr+₹29.2 L (20.4%)Rejected-Finance 195 MAHESH NAGAR AMBALA CANTT 133001 | AMBALA | HARYANA | 133001 | ₹1.7 Cr+₹29.2 L (20.4%) | L5 | Rejected-Finance OTHER THAN L1 |
Tender Value
₹2 Cr
EMD Value
₹2.8 L
Closing Date
5 Nov 2024, 6:00 pmClosed
Brig T Lalit Mohan CE
Headquarters Chief Engineer Bareilly Zone Military Engineer Services Sarvatra Bhawan Station Road Bareilly Cantt Bareilly 243001
REPLACEMENT OF 02 X 5 MVA TRANSFORMERS AT SHIVAJI LINE AND BHAGAT LINES MRS UNDER GE UTILITY MEERUT CANTT
2024_MES_677151_2
CEBZ/MRT/T-31 OF 2024-25
Open Tender
Civil Works
Item Rate
90 days
Meerut
As per NIT
8 documents required · 8 mandatory
₹1,000
Yes
GE Utility
₹2.8 L
Yes
2 Jan 2025
22 Oct 2024
12 Nov 2024
22 Oct 2024
5 Nov 2024
29 Oct 2024
22 Oct 2024 - 25 Oct 2024
Amount
Supply and installation, testing & commissioning of copper wound, 33 KV Power Transformer, step down, outdoor type of capacity 5.0 MVA (5000KVA ), 33 KV/11 KV, 3 phase, 50cycles AC with On Load Tap Changing arrangements with remote control panel operation on 33 KV sides to vary secondary voltage from +5% to (-) 15% in steps of 1.25% (17 steps) , impedance 7.35% at normal/common tap No 5 including suitable marshalling box and HV terminals 3 Nos outdoor bare bushings and LV terminals connectors to connect the transformer with HT XLPE Power cable of size 300 sqmm x3 core with copper conductor and LV additional Neutral with one no solid porcelain type out door bushings on the transformer lid for earthing purpose complete in all respects with standard accessories and fittings conforming to IS-2026 primary side delta and secondary side star. The salient features of the transformer shall be as below :-
(a) (i) Transformer shall be Dyn11 vector group oil immersed naturally cooled, doubled wound electrolytic copper winding core type, Radiator cooled MS tank complete with first fill of transformer oil as per IS -335 with ONAN cooling system. The temperature of oil and winding shall not rise 50/55 degree C above ambient temperature. Transformer shall be painted with two coats of synthetic enamel paint . (ii) Rating and diagram plate (iii) Earthing terminals - 2 Nos. (iv) Lifting lugs (v) Thermometer pocket. (vi) Air release hole with plug. (vii) Oil filling hole with plug on & incl. conservator with drain valve and plug. (viii) Plain type oil indicator on one side of conservator with minimum and maximum oil level marking. (ix) Dehydrating breather - 01 No (x) Oil conservator with drain valve and plug. (xi) Sampling valves, top and bottom. (xii) Under base with flat treaded bi-directional rollers.
(xiii) Drain cum bottom filter valve with plug. (xiv) Top filter valve with plug. (xv) Explosion vent with diaphragm and equalizer pipe (pressure release device). (xvi) Jacking lugs and hauling holes. (xvii) Inspection cover. (xviii) Detachable radiators with shut off valves between radiators and tanks. (xix) Radiator with air release hole and plug. Oil drain hole with plug and lifting eye all as per manufacturer's standards. (xx) 150mm dia oil temperature indicator stem type. (xxi) Double float Bucholtz relay with two sets of contacts and isolating valves. (xxii) 150mm dia winding temperature indicator with maximum indicating pointer and resetting device. (xxiii) 100mm dia magnetic oil level gauge with low level alarm. (xxiv) Terminal arrangements
NOTE :- (a) Transformer shall be inspected by inspecting officers nominated by Accepting Officer at manufacturers factory and all test pertaining to IS: 2026 shall be carried out predispatch complete all as directed. (b) Site testing :Insulation resistance ,oil temperature alarm trip, Winding temperature alarm and trip, Bucholtz relay alarm and trip, Low oil level alarm, testing of annunciation systems by auxiliary relay triping of transformer, Polarity marking and phase sequence, Ratio test, dielectric strength and filtration if required should be carried out. (c) Control cables/Bus -duct shall not measured and paid separately. (d) Addl/Altr required for foundation and civil works as per manufacture's recommendation is included in quoted rates. (e) If any work required to succecceful complition of work but not mentioned in BOQ will have to be done by bidder without any extra cost to the department.
(f) Necessary addn / altn required in existing earthing strip for connection to new power transformer included within the overall quoted rates. (g) Necessary arrangement for dismantling of existing 5 MVA Power transformer and shifting it to MES store Yard as directed by Engineer-in-charge is included within the overall quoted rates.
Leo Air and Power Solution pvt Ltd. (BID ID -3158011)
ELECSA INFRATECH PVT. LTD (BID ID -3158165)
BHARAT ELECTRICAL TRADERS (BID ID -3157903)
Raman Electric Trading Co (BID ID -3157681)
Sant Construction Co. (BID ID -3157773)
B D Raizada Projects Pvt Ltd (BID ID -3157841)
R D Bansal (BID ID -3157902)
LUMOS INFRA PVT LTD (BID ID -3157851)
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .