Loading…
Loading…
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹10.6 L
EMD Value
₹13,000
Closing Date
6 Nov 2026, 11:00 am
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
SE ETC Jhansi
132KV Substation Hansari, Lalitpur Road, Jhansi - 284135
Supply, Installation, Data Integration, RTU-Gateway Port Configuration on IEC-104 Protocol and upgradation, Restoring Relay ICD-Cid Files, IP Addresses of All Required Data of Integration of SCADA System Of Existing SCADA System of 132 KV SS Mehrauni
2026_UPTCL_1198285_1
ETS-19/ETCJ/2026-27
Open Tender
Electrical Works
Fixed-rate
60 days
Mehrauni under ETD Jhansi
As per PQR of tender documents
2 documents required · 2 mandatory
₹590
SE ETC jhansi
₹13,000
17 Oct 2026
17 Oct 2026
6 Nov 2026
17 Oct 2026
6 Nov 2026
17 Oct 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, Installation, Data integration, RTU/Gateway Configuration and Upgradation, Restoring relay ICD/CID files, IP addresses of all Required data of integration of SCADA system of existing for existing SCADA system of 132kv Substaion Mehrauni. Work also includes Port configuration on IEC-104 protocol for Data transmission to UPSLDC lucknow and SLDC Modipuram(back-up). | - | - | 101 | - |
| 2 | Bay Integration/configuration in the existing SCADA of 132kV Transformer's BCPUs relay setting, database point configuration as per the exiting database, Buffered/Un-buffered Report, Control Block updation as per the BCPUs files.
1. 132/33 KV Transformer Bays- 02 Nos. | 1 | Job | 101 | ₹101 |
| 3 | Configuration of RTU Checking and Configuration of ICD./CID Files. Configuration as per the existing respective 132 KV & 33 KV Feeders as per The schematics and field signals. Configuration Datasets, Report Control Block as per below Feeders-
1. 132 KV Bays - 3 Nos.
2. 33 KV Bays - 8 Nos. | 1 | Job | 101 | ₹101 |
| 4 | Checking and troubleshooting of communication architecture of fiber Optic ring system and making it operational for all 132kv/33kv feeders. Fixing splicing of fiber optics patch cord of damaged fiber where required. | 1 | Job | 100 | ₹100 |
| 5 | Gateway Configuration and testing validation work of the 132KV Bays to send data to SLDC Lucknow & Modipuram over IEC- 61805-104 Protocol. | 1 | Job | 101 | ₹101 |
| 6 | Gateway Configuration and testing validation work of the 33KV Bays to send data to SLDC Lucknow & Modipuram over IEC- 61805-104 Protocol. | 1 | Job | 102 | ₹102 |
| 7 | Supply and Installation GPS Time Synchronization Server with Display to make exisiting RTU/Relays/SCADA Synchronization. | 1 | Job | 103 | ₹103 |
| 8 | SCADA HMI repair & Restoration work of all feeders real Time data at local SCADA system as previously running on the SCADA.Also rectifying the issues related to IEC61850 variables and Buffered/Un-buffered report control blocks to make System healthy. | 1 | Job | 104 | ₹104 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.97 MB
SBD.pdf
Tender Documents • 0.95 MB
BOQ_2264165.xls
BOQ • 0.24 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .