| 1 | L1₹26.4 LAccepted-AOC DOOR NO IV 400 NEAR RAMANTHALI GHSS RAMANTHALI PO KANNUR 670308 | KANNUR | KERALA | 670308 | L1 | Accepted-AOC Being L1Bidder | |
| 2 | L2₹29.8 L+₹3.4 L (12.8%)Rejected-AOC | L2 | Rejected-AOC Being not L1Bidder | |
| 3 | L3₹35.0 L+₹8.6 L (32.5%)Rejected-AOC FLAT NO S 4 DOOR NO 10 4 107 17 SRINIVASA TOWERS SRI RAMNAGAR GAJUWAKA VISAKHAPATNAM 530 026 | VISAKHAPATANAM | ANDHRA PRADESH | 530026 | L3 | Rejected-AOC Being not L1Bidder |
Tender Value
₹18 L
EMD Value
₹36,000
Closing Date
15 Oct 2021, 6:00 pmClosed
GE DSSC
GE DSSC WELLINGTON BARRACKS-POST, WELLINGTON, THE NILGIRIS, TAMIL NADU,PIN-643231
MAINT AND REPAIRS TO LT CONTROL PANEL BOARDS, LT FEEDER/JUNCTION/BUSBAR BOXES INCLUDING ALLIED WORKS UNDER GE DSSC WELLINGTON
2021_MES_470307_2
8183/E8
Open Tender
Civil Works
Item Rate
240 days
WELLINGTON
PLEASE REFER TENDER DOCUMENTS AND NIT
8 documents required · 8 mandatory
₹500
GE DSSC WELLINGTON
₹36,000
Yes
1 Nov 2021
27 Sept 2021
19 Oct 2021
27 Sept 2021
15 Oct 2021
1 Oct 2021
Amount
Supply, install, testing & commissioning of LT control panel board "out-door type" of size 1500 mm (height) x 1200 mm (breadth) x 500 mm (depth) (minimum dimensions), factory fabricated CPRI approved (type-tested) with suitable neoprene rubber gasket to make it completely dust and vermin proof & degree of protection not less than IP-55 & general construction confirming to IS-13947, double door, front & back openable. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation and high grade aluminum bus-bar wrapped with coloured PVC tape /sleeves of rating in conformity to the Incoming ACB/MCCB rating. The panel board shall be fabricated out of 3.15 mm thick (for outer portions) & 2.00 mm thick (for inner portions) CRCA sheet duly pre-treated & powder coated, supporting angle iron frame & MC channel base suitable for 3 Phase, 4 wire system 415 /440 volts grade including complete internal wiring with not less than 2.5 Sqmm copper wire including cable glands of suitable sizes with suitable PCC (1:3:6) type C-2 foundation , necessary earthwork (if any) incl taking down old unsv LT panel of any size/type complete all as specified & as directed with & including the following accessories :
(Signal Sec Panel) (i) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Aluminium 500 Amps rated, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry /exit shall be provided in the bottom for both incoming and out-going cables with the help of glands matching the existing LT cable sizes. INCOMING : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit and adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 250 to 320 A - 01 Nos. Make : L & T, Cat No : CM98403OOQOOG or techno-commercially equivalent of Legrand /Siemens.
OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit and adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 200 to 250 Amps - 02 (01W+1S) Nos. Make : L & T, Cat No : CM90642OOPO or techno-commercially equivalent of Legrand /Siemens. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit and adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 80 to 100 A - 01 No. Make : L & T, Cat No : CM91712OOKOOG or techno-commercially equivalent of Legrand /Siemens. (c) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 63 to 80 A - 02 Nos. Make : L & T, Cat No : CM91712OOJOOG or techno-commercially equivalent of Legrand /Siemens. (d) Time switch 415 Volts, 3 Phase of 20 Amps rating with Contactor complete . Make : L&T, Cat No (AUTS02DIG00- timer, CS94190-contactor) or techno-commercially eqvt of Legrand /Siemens. (e) MCB SPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T/Legrand /Siemens. (f) MCB TPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T /Legrand /Siemens.
Description as per item 1 here in before but of size 1200 mm (height) x 1000 mm (breadth) x 500 mm (depth) (minimum dimensions) with & including the following accessories: (Ashoka Panel) (i) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Aluminium 600 Amps rated, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry /exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes. INCOMING : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 320 to 400 A - 01 Nos. Make : L & T, Cat No : CM98403OOROOG or techno-commercially equivalent of Legrand /Siemens (b) Onload changeover switch, open-execution modular construction type, confirming to IS/IEC 60947-3, rated current 400 Amps, 415 Volts, 4 Pole, AC 23A - 01 No. Make : L & T, Cat No : CO44000OOOO or techno-commercially equivalent in ABB/ Siemens.
OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 160 to 200 Amps - 01 No. Make : L & T, Cat No : CM90642OONO or techno-commercially equivalent of Legrand /Siemens. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 200 to 250 A - 02 (1W+1S) Nos. Make : L & T, Cat No : CM90642OOPO or techno-commercially equivalent of Legrand /Siemens. (c) MCB SPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T/Legrand /Siemens. (d) MCB TPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T /Legrand /Siemens.
Description as per item No 1 here in before but with & including the following accessories : (Akbar & Indra Panel) (i) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Aluminium 600 Amps rated, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry/exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes. INCOMING : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 320 to 400 A - 01 Nos. Make : L & T, Cat No : CM98403OOROOG or techno-commercially equivalent of Legrand /Siemens.
OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 200 to 250 Amps - 02 (01W+1S) Nos. Make : L & T, Cat No : CM90642OOPO or techno-commercially equivalent of Legrand /Siemens. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 125 to 160 A - 01 No. Make : L & T, Cat No : CM90642OOMO or techno-commercially equivalent of Legrand /Siemens. (c) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 80 to 100 A - 02 Nos. Make : L & T, Cat No : CM91712OOKOOG or techno-commercially equivalent of Legrand /Siemens. (d) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 63 to 80 A - 01 No Make : L & T, Cat No : CM91712OOJOOG or techno-commercially equivalent of Legrand /Siemens. (e) Time switch 415 Volts, 3 Phase of 20 Amps rating with Contactor complete . Make : L&T, Cat No (AUTS02DIG00- timer, CS94190-contactor) or techno-commercially eqvt of Legrand /Siemens. (f) MCB SPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T/Legrand /Siemens. (g) MCB TPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T /Legrand /Siemens.
Description all as per item No 1 here in before but with & including the following accessories : (Near Production dept Panel) (i) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Aluminium 600 Amps rated, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry /exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes. INCOMING : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 320 to 400 A - 01 Nos. Make : L & T, Cat No : CM98403OOROOG or techno-commercially equivalent of Legrand /Siemens. (b) Onload changeover switch, open-execution modular construction type, confirming to IS/IEC 60947-3, rated current 400 Amps, 415 Volts, 4 Pole, AC 23A - 01 No. Make : L & T, Cat No : CO44000OOOO or techno-commercially equivalent in ABB/ Siemens.
OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 160 to 200 Amps - 03 (02W+1S) Nos. Make : L & T, Cat No : CM90642OONO or techno-commercially equivalent of Legrand /Siemens. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 80 to 100 A - 01 No Make : L & T, Cat No : CM91712OOKOOG or techno-commercially equivalent of Legrand /Siemens. (c) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 63 to 80 A - 01 No Make : L & T, Cat No : CM91712OOJOOG or techno-commercially equivalent of Legrand /Siemens. (d) MCB SPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T/Legrand /Siemens. (e) MCB TPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T /Legrand /Siemens.
Description all as per item No 1 here in before but with & including the following accessories : (Manekshaw Panel near ITRC) (i) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Aluminium 400 Amps rated, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry /exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes. INCOMING : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 200 to 250 A - 01 Nos. Make : L & T, Cat No : CM92109OOP1OG or techno-commercially equivalent of Legrand /Siemens.
OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 125 to 160 A - 03 Nos (2W+1S). Make : L & T, Cat No : CM90642OOMO or techno-commercially equivalent of Legrand /Siemens. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 80 to 100 A - 03 Nos . Make : L & T, Cat No : CM91712OOKOOG or techno-commercially equivalent of Legrand /Siemens. (c) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 63 to 80 A - 02 No Make : L & T, Cat No : CM91712OOJOOG or techno-commercially equivalent of Legrand /Siemens. (d) MCB SPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T/Legrand /Siemens. (e) MCB TPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T /Legrand /Siemens.
Description as per item 1 here in before but of size 1200 mm (height) x 1000 mm (breadth) x 500 mm (depth) (minimum dimensions) with & including the following accessories:- (Officer Mess kitchen Panel) (i) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Aluminium 400 Amps rated, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry /exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes. INCOMING : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 160 to 200 A - 01 Nos. Make : L & T, Cat No : CM92109OON1OG or techno-commercially equivalent of Legrand /Siemens.
OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 80 to 100 A - 02 Nos (1W+1S). Make : L & T, Cat No : CM91712OOKOOG or techno-commercially equivalent of Legrand /Siemens. (b) MCB SPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 02 No. Make : L&T/Legrand /Siemens. (c) MCB TPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 02 No. Make : L&T /Legrand /Siemens. (d) M&L for re-fixing of Variable frequency drive (VFD) alongwith speed control knob of rating 7.5KW of V1000 model of Make: YASKAWA - 01 No (e) M&L for re-fixing of Variable frequency drive (VFD) alongwith speed control knob of rating 11KW of V1000 model of Make: YASKAWA - 01 No
Description all as per item 1 here in before with & including the following accessories:- (Circle Qtr 1 Panel) (i) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Aluminium 400 Amps rated, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry /exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes. INCOMING : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 200 to 250 A - 01 Nos. Make : L & T, Cat No : CM92109OOP1OG or techno-commercially equivalent of Legrand /Siemens.
OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 200 to 250 Amps - 02 Nos. (1W+1S) Make : L & T, Cat No : CM90642OOPO or techno-commercially equivalent of Legrand /Siemens. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 125 to 160 A - 01 No Make : L & T, Cat No : CM90642OOMO or techno-commercially equivalent of Legrand /Siemens. (c) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 63 to 80 A - 03 Nos. Make : L & T, Cat No : CM91712OOJOOG or techno-commercially equivalent of Legrand /Siemens. (d) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 50 to 63 A - 01 No. Make : L & T, Cat No : CM91712OOHOOG or techno-commercially equivalent of Legrand /Siemens. (e) MCB SPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 02 Nos. Make : L&T/Legrand /Siemens. (f) MCB TPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T /Legrand /Siemens.
Description as per item 1 here in before with & including the following accessories : (Circle Substation Panel) (i) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Aluminium 800 Amps rated, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry /exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes. INCOMING : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 500 to 630 A - 01 No Make : L & T, Cat No : CM94106OOT1OG or techno-commercially equivalent of Legrand /Siemens.
OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 320 to 400 Amps - 02 Nos. (1W+1S) Make : L & T, Cat No : CM94105OOR1OG or techno-commercially equivalent of Legrand /Siemens. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 80 to 100 Amps - 01 Nos. Make : L & T, Cat No : CM91712OOKOOG or techno-commercially equivalent of Legrand /Siemens. (c) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 63 to 80 Amps - 03 Nos Make : L & T, Cat No : CM91712OOJOOG or techno-commercially equivalent of Legrand /Siemens. (d) MCB SPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 02 Nos. Make : L&T/Legrand /Siemens. (e) MCB TPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T /Legrand /Siemens.
Supply, install, testing & commissioning of LT busbar junction box "out-door type" of size 750 mm (height) x 600 mm (breadth) x 300 mm (depth) (minimum dimensions), factory fabricated CPRI approved (type-tested) with suitable neoprene rubber gasket to make it completely dust & vermin proof & degree of protection not less than IP-55 & general construction confirming to IS-13947, double door, front & back openable. The box shall be provided with ventilation facility in the form of louvers for better heat dissipation & high grade aluminum bus-bar of rating 400A of length 600mm, min spacing of 80mm between the busbars & wrapped with coloured PVC tape /sleeves of rating in conformity to the Incoming cable rating. The panel board shall be fabricated out of 3.15 mm thick (for outer portions) & 2.00 mm thick (for inner portions) CRCA sheet duly pre-treated & powder coated, supporting angle iron frame & MC channel base suitable for 3 Phase, 4 wire system 415 /440 volts grade including I/C & O/G cable opening on bottom & at both sides including cable glands of suitable sizes with suitable PCC (1:3:6) type C-2 foundation , necessary earthwork (if any) incl taking down old unsv box of any size/type complete all as specified & as directed.
Notes for Item Nos 1 to 09:- (i) Design / drawing / BOM of the Panel Board showing the dimensions is to be obtained from the Manufacturer / Supplier & is to be got approved from the Engr-in-Charge & GE before placing final order to the manufacturer. (ii) Anything missed out in the technical specifications but technically required for efficient working is deemed to be included in the quoted rates.
M & L for repairs to feeder pillar box/LT panel etc, taking out old unserviceable and fixing of new hinges (if any) by welding/bolt nuts,addn/altn to MCCB enclosure cover with one incoming and No of out goings by grinding,cutting and painting all as shown and diretced, repairs to door lock by replacing unsv locks, extension of aluminium bus bars for incoming/outgoing MCCBs as per existing shapes and size, spray painting with two coats of approved grade & color synthetic enamel paint after scrapping incl preparation of old painted surfaces & fixing 02 nos (front & back) danger notice plate as per standard size complete all as specified and directed.
M & L for shifting the existing panel/Changeover boxes to a place directed by Engr-in-Charge incl making suitable fixing arrangement and isolating the existing cables properly incl making connections complete all as specified and directed. Note : The quoted rate is deemed to be inclusive of transportation and other misc charges like suitable size PCC platform /Plinth, earthwork, jointing materials etc.
Excavation in trenches n.exc 1.5m wide and n.exc 1.5m in depth for taking out/laying of UG Cables, GI Pipe etc. and getting out in hard dense soil complete all as specified and as directed.
Returning, filling in including spreading, levelling, watering and well ramming in layers n.exc 25cm thick complete all as specified and as directed.
Removing of excavated material to a distance n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point complete all as specified and as directed.
M & L for providing sand cushioning for protection of UG cable in trenches with coarse river sand of approved quality including filling, spreading and punning down to desired thickness complete all as specified and as directed. Note : Punned thickness shall be measured for payment.
Supply and laying sub class "B" bricks in trenches for protection of UG Cable with width equal to length of bricks, laid dry & flat complete all as specified & as directed.
M & L for GI pipe light grade with all running fittings (ISI Marked), laid in trenches, under road or fixing on wall/pole/crossing drain/nallah etc. of bore 100 mm complete all as specified and directed. Make : TATA/JINDAL/PRAKASH. Note : Wherever GI Protection pipes are to be placed/fitted above earths surface, cost of necessary clamping/fixing arrangements to the entire satisfaction of Engr-in-Charge is deemed to be included in the unit quoted rates.
M & L for cutting the existing hardstanding/PCC/WBM road at a depth of not less than 60 cm & 30 cm in width for passing of HT cables through GI pipes, returning filling in, complete incl finishing the surfaces by providing cement concrete type B1 (1:2:4) with 20 mm graded aggregate upto 20 cm, finishing to a uniform smooth surface complete all as specified and as directed.
Supply, laying, jointing & testing XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 240 Sqmm 3.5 core in trenches / through GI pipe / fixed along with pole structure etc with all fixing & connecting accessories incl taking down old cable complete all as specified & as directed. Make : HAVELLS/GLOSTER/POLYCAB.
Supply, laying, jointing & testing XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 Sqmm 4.0 core in trenches / through GI pipe / fixed along with pole structure etc with all fixing & connecting accessories incl taking down old cable complete all as specified & as directed. Make : HAVELLS/GLOSTER/POLYCAB.
Supply, laying, jointing & testing XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 Sqmm 3.5 core in trenches / through GI pipe / fixed along with pole structure etc with all fixing & connecting accessories incl taking down old cable complete all as specified & as directed. Make : HAVELLS/GLOSTER/POLYCAB.
M & L for earthing complete with galvanised steel plate electrode 600 x 600 x 6mm thick buried directly in ground (earth pit not less than 2.25mtrs deep below ground level) with top edge of plate not less than 1.5mtrs below normal ground level, connected to GI earth strip of size 32 x 6mm by means of bolts,nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 3 connected to earthing test point on completion with and including 40 mm bore medium grade GI protection pipe (7.5mtr long) for earth including PCC chamber pit with cover, watering pipe of 20mm dia medium grade with funnel, common salt, charcoal filling, including necessary excavation, earth work & taking down old earthing items in any type of soil complete all as specified. Make of GI pipe : TATA/JINDAL/PRAKASH.
Supply, install, commissioning & testing of ATS cum LT Control Panel "out-door type" of size 1200 mm (height) x 1200 mm (breadth) x 600 mm (depth) (minimum dimensions) factory fabricated CPRI approved (type-tested) with suitable neoprene rubber gasket to make it completely dust & vermin proof & degree of protection not less than IP-55 & general construction confirming to IS-13947, double door, front & back openable. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation & tinned copper bus-bar wrapped with coloured PVC tape/sleeves of rating in conformity to the Incoming ACB/MCCB rating. The panel board shall be fabricated out of 3.15 mm thick (for outer portions) & 2.0 mm thick (for inner portions) CRCA sheet duly pre-treated & powder coated, supporting angle iron frame & MC channel base suitable for 3 Ph, 4 wire system 415/440 volts grade incl complete internal/control wiring with appropriately sized/rated copper wires incl cable glands of suitable sizes incl suitable PCC (1:3:6) type C-2 foundation, necessary earthwork (if any) incl taking down old unsv Change-over/Panel complete all as specified & as directed with & incl the following accessories : BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Aluminium 200 A rated, duly insulated with 1100 V grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry/exit shall be provided in the bottom for both incoming & out-going cables with the help of glands, clamps etc. matching the existing LT cable sizes.
OUTGOINGS : (a) MCCB 4P (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting,suitable for isolation, having breaking capacity 25 KA & of rating 100 to 125 A - 01 Nos. Cat No : CM90642OOLO of Make L&T or techno-commercially equivalent of LEGRAND/SIEMENS. (b) MCB, TPN, 10KA, 415V, "C" curve, 63 A, ISI marked complete - 02Nos. (1W+1S) Make : L&T/SIEMENS/LEGRAND. (c) MCB, TPN, 10KA, 415V, "C" curve, 32 A, ISI marked complete - 02Nos. Make : L&T/SIEMENS/LEGRAND. (d) MCB, SPN, 10KA, 230V, "C" curve, 32 A, ISI marked complete - 03Nos (2W+1S). Make : L&T/SIEMENS/LEGRAND
NOTE: 1) Design / drawing / BOM of the Panel Board incl all accessories showing the dimensions is to be obtained from the Manufacturer / Supplier & is to be got approved from the Engr-In-Charge & GE before placing final order to the manufacturer.2) Anything missed out in the technical specifications but technically required for efficient working is deemed to be included in the quoted rates.3) The electrical connection of digital Multi Functional Meter in the ATS panel is to be done from load side so that monitoring of various parameters viz. Voltage, Current, KW, KVA, power factor, frequency etc. can be done for both SEB mains & DG mains.4) Necessary PCC foundation/plinth shall be as per the recommendations of OEM & cost of the same is deemed to be included in the quoted rates.5) Cost of taking down old unsv change-over switches/LT Panels is deemed to be included in the unit quoted rates.
Saket Enterprises
M.V.K.ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .