| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹124.0 CrAdmitted-Finance AWL CENTRE 1 8 MAHAL INDUSTRIES AREA MAHAKALI CAVES ROAD ANDHERI EAST MUMBAI 400 093 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400093 | ₹124.0 Cr | L1 | Admitted-Finance |
| 2 | L2₹124.8 CrAdmitted-Finance | ₹124.8 Cr | L2 | Admitted-Finance |
| 3 | L3₹131.0 CrAdmitted-Finance | ₹131.0 Cr | L3 | Admitted-Finance |
| 4 | L4₹132.5 CrAdmitted-Finance E 44 GROUND FLOOR SECTOR 36 GREATER NOIDA G B NAGAR UP | ₹132.5 Cr | L4 | Admitted-Finance |
| 5 | L5₹137.4 CrAdmitted-Finance | ₹137.4 Cr | L5 | Admitted-Finance |
| Sl No | Description | Qty | Unit | LISHA ENGINEERS PRIVATE LIMITED L4 | K S M BASHIR MOHAMMAD AND SONS L5 | VASCON ENGINEERS LTD L3 | GHV (India) PVT. Ltd. L1 | Quality Buildcon Private Limited L2 |
|---|---|---|---|---|---|---|---|---|
| 1.00Civil, Architectural and E&M Works | ||||||||
| 1.01 | Schedule - A: DSR WORKS 2023 | 1 | Nos | 0.14 ₹105.8 Cr | 0.02 ₹120.7 Cr | 0.09 ₹112.3 Cr | 0.2 ₹99.1 Cr | 0.18 ₹101.0 Cr |
| 1.02 | Schedule - B: NDSR ITEMS | 1 | Nos | 0.1 ₹6.1 Cr | 0.39 ₹4.2 Cr | 0.25 ₹5.1 Cr | 0.05 ₹6.5 Cr | 0.18 ₹5.6 Cr |
| 1.03 | Schedule - C: PEB Works | 1 | Nos | 0 ₹7.6 Cr | 0.39 ₹4.6 Cr | 0.43 ₹4.3 Cr | 0.09 ₹6.9 Cr | 0 ₹7.6 Cr |
| 1.04 | Schedule - D: NDSR PLUMBING ITEMS | 1 | Nos | 0.15 ₹95.2 L | 0.39 ₹50.5 L | 0.07 ₹76.9 L | 0.05 ₹78.6 L | 0.18 ₹67.8 L |
| 1.05 | Schedule - E (E & M Items): Electrical & Mechanical Works | 1 | Nos | 0.01 ₹12.0 Cr | 0.39 ₹7.4 Cr | 0.3 ₹8.5 Cr | 0.12 ₹10.7 Cr | 0.18 ₹9.9 Cr |
Updated dates
Tender Value
₹177.6 Cr
EMD Value
₹3.5 Cr
Closing Date
19 Mar 2026, 3:00 pmClosed
Managing Director
Uttar Pradesh Metro Rail Corporation, Administrative Building, Near Dr. Bhimrao Ambedkar Samajik Parivartan Sthal, Vipin Khand, Gomti Nagar, Lucknow 226010
Civil, PEB and E and M works for construction of depot cum workshop at Mall road for Agra Cantt to Kalindi Vihar Corridor-2 of Agra Metro.
2026_UPMRC_266535_1
AGCC-08
Open Tender
Civil Works
540 days
Agra
Please refer Tender documents.
4 documents required · 4 mandatory
₹23,600
Yes
UPMRCL (Agra Project)
₹3.5 Cr
Yes
Online
18 May 2026
13 Feb 2026
20 Mar 2026
13 Feb 2026
19 Mar 2026
9 Mar 2026
13 Feb 2026 - 23 Feb 2026
23 Feb 2026
Civil, Architectural and E&M Works
Schedule - A: DSR WORKS 2023
Schedule - B: NDSR ITEMS
Schedule - C: PEB Works
Schedule - D: NDSR PLUMBING ITEMS
Schedule - E (E & M Items): Electrical & Mechanical Works
Note: 1. In case of any discrepancy/dispute in respect of DSR items, the item description, unit and rates of standard DSR shall be applicable.
BOQ OF CIVIL, ARCHITECTURAL AND E&M WORKS AT AGRA MALL ROAD DEPOT
GRAND SUMMARY OF BILL OF QUANTITIES (ALL SCHEDULES)
Schedule - A: DSR WORKS 2023
Schedule - B: NDSR ITEMS
Schedule - C: PEB Works
Schedule - D: NDSR PLUMBING ITEMS
Schedule - E (E & M Items): Electrical & Mechanical Works
Total of Schedule A,B,C,D & E (S.No: 1 to 5)
BOQ OF ARCHITECTURE FINISHES AT AGRA DEPOT
SUMMARY SCHEDULE - A: DSR ITEMS
EARTHWORK
CONCRETE WORKS
REINFORCED CEMENT CONCRETE WORK
MASONRY WORKS (BRICK / BLOCK WORK)
STEEL WORKS
FLOORING WORKS
ROOFING & SUSPENDED CEILING WORKS
FINISHING WORKS
ROAD WORKS
ALUMINIUM WORKS
WATERPROOFING WORK
GRANITE STONE WORKS
PILING WORKS
SANITARY FIXTURES
WATER SUPPLY
SEWAGE AND DRAINAGE
RAIN WATER HARVESTING & TUBEWELLS
DEMOLISHING WORKS
CLADDING AND GLAZING WORK
ANY OTHER ITEMS UNDER DSR-2023
HORTICULTURE WORKS UNDER HORTICULTURE DSR - 2025
Total of schedule A (Including GST )
Total of schedule A (Excluding GST )
BOQ OF ARCHITECTURE FINISHES AT AGRA DEPOT
SCHEDULE - A: DSR ITEMS
BILL OF QUANTITY
EARTHWORK
Disposal of building rubbish / malba / similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping ground or as approved by Engineer-in-charge, beyond 50 m initial lead, for all leads including all lifts involved.
Supplying and filling in Plinth/any other structure with sand floors, including watering ramming, consolidating and dressing complete.
Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m :
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.
Extra for every additional lift of 1.5 m or part thereof in excavation / banking excavated or stacked materials.
Total of EARTHWORK
CONCRETE WORKS
Providing and laying Damp-proof course 40 mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 12.5 mm nominal size).
Total of Concrete Works
REINFORCED CEMENT CONCRETE WORK
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete.
Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 1.10 times of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement.
Total of Reinforced Cement Concrete Works
MASONRY WORKS (BRICK / BLOCK WORK)
Providing, hoisting and fixing above plinth level up to floor five level precast reinforced cement concrete work in string courses, bands, copings, bed plates, anchor blocks, plain window sills and the like, including the cost of required centering, shuttering but , excluding cost of reinforcement, with 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) : 3 graded stone aggregate 20 mm nominal size).
Total of Masonary (Brick / Block)
STEEL WORKS
Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes, channels, sheets, grating, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-incharge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.). (This item is for SS Railing of Straight, Curved /Spiral etc)
Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge.
Providing and fixing carbon steel galvanised ( minimum coating 5 micron) dash fastener of 10 mm dia double threaded 6.8 grade (yield strength 480 N/mm2), counter sunk head, comprising of 10 mm dia polyamide PA 6 grade sleeve, including drilling of hole in frame , concrete/ masonry, etc. as per direction of Engineer-in-charge.
Total of Steel Works
FLOORING WORKS
Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete.
(a) Providing at required spacing to form modular framework, pedestals made out of GI tube of thickness minimum 2 mm and 25 mm outer diameter, fully welded on to the G.I. Base plate of size 100mm x 100mm x 3mm at the bottom of the pedestal tube, G.I. pedestal head of size 75mmx75mmx3.5 mm welded with GI fully threaded stud 16mm outer diameter with two GI Check nuts screwed on the stud for level adjustment upto 50mm, locking and stabilizing the pedestal head in position at the required level. The pedestals shall be fixed to the subfloor (base) through base plate using epoxy based adhesive of approved make or the machine screw with rawl plug.
(b) Stringers system in all steel construction hot dipped galvanized of rectangular size 570x20x30x0.80mm thick having holes at both ends for securing the stringers on to the pedestal head using fully threaded screws ensuring maximum lateral stability in all directions, the grid formed by the pedestal and stringer assembly shall receive the floor panel, this system shall provide adequate solid, rigid support for access floor panel, the system shall provide a minimum clear uninterrupted clearance between the bottom of the floor for electrical conduits and wiring etc. all complete as per the architectural drawings, as specified and as directed by the Engineer-in-charge.
(c) Providing and fixing Access Floor panel of 600x600x32 mm medium grade Filled Steel anti static high pressure Lamination of 800H grade (FS800H). Access Floor panel shall be steel welded construction with an enclosed bottom pan with uniform pattern of 64 hemispherical cones. The top and bottom plates of Steel Gauges: top 0.6 mm and bottom 0.7 mm fused spot welded together (minimum 64 welds in each dome and 20 welds along each flange). The panel should be Corroresist epoxy coated for lifetime rust protection and cavity formed by the top and bottom plate is filled with Pyrogrip noncombustible Portland cementitious core mixed with lightweight foaming compound. The access floor shall be factory finished with Anti-static High Pressure laminate with Non Warp technology upto 1mm thickness for superior adhesion and Surface flatness within 0.75mm.The panel is to withstand a Concentrated Load of 363 kgs applied on area 25mm x 25mm without collapse in the centre of the panel which is placed on four steel blocks. The panel will withstand and Uniformly Distributed Load (UDL) minimum 1250 kg/sqm and an impact load of 50kg all complete as per the approved manufacturers specification and as per the direction of Engineer-in-charge. All specification must be printed on the side of the panel to ensure the quality of the product.
Total of Flooring Works
ROOFING & SUSPENDED CEILING WORKS
ceiling tiles of approved texture (Spintone / Cosmos/ hexa) in the grid, including cutting / making opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc., wherever required. Main 'T' runners to be suspended from ceiling using G.I. slotted cleats of size 25x35x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm G.I. adjustable rods with galvanised steel level clips of size 85x30x0.8 mm, spaced at 1200 mm centre to centre along main 'T', bottom exposed with 24 mm of all T-sections shall be pre-painted with polyster baked paint, for all heights, as per specifications, drawings and as directed by engineer-in-charge.
Note :- Only calcium silicate false ceiling area will be measured from wall to wall. No deduction shall be made for exposed frames/opening (cut outs) having area less than 0.30 sqm. The calcium silicate ceiling tiles shall have NRC value of 0.50 (Minimum), light reflection > 85%, non-combustible as per B.S. 476 part IV, 100% humidity resistance and also having thermal conductivity <0.043 w/m O KC.
centre, with 25 mm long dry wall screws @ 230 mm interval, including fixing of gymsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 ,mm at 230 mm c/c including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound, jointing tapes, finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specifications and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed all complete as per drawings, specification and direction of the Engineer-in-charge but excluding the cost of painting with:
Total of Suspended Ceiling Works
FINISHING WORKS
Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections.
Total of Finishing Works
ROAD WORKS
Supplying and filling in plinth with sand under floors/Paver blocks, including watering, ramming, consolidating and dressing complete.
Note:- Cement content considered in M-30 is @ 340 kg/cum. Excess/ less cement used as per design mix is payable/ recoverable separately.
Construction of dry lean cement concrete sub base over a prepared sub-grade with coarse and fine aggregate conforming to IS:383, the size of coarse aggregate not exceeding 25 mm, aggregate cement ratio not to exceed 15:1, aggregate gradation after blending to be as per specifications, cement content not to be less than 150 Kg/cum, optimum moisture content to be determined during trial length construction, concrete strength not to be less than 10 Mpa at 7 days, mixed in a batching plant, transported to site, for all leads & lifts, laid with a mechanical paver, compacting with 8-10 tonne vibratory roller, finishing and curing etc. complete as per direction of Engineerin- charge.
Construction of granular sub-base by providing close graded Material conforming to specifications, mixing in a mechanical mix plant at OMC, carriage of mixed material by tippers to work site, for all leads & lifts, spreading in uniform layers of specified thickness with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per specifications and directions of Engineer-in-Charge.
Providing, laying, spreading and compacting graded stone aggregate (size range 53 mm to 0.075 mm ) to wet mix macadam (WMM) specification including premixing the material with water at OMC in for all leads & lifts, laying in uniform layers with mechanical paverfinisher in sub- base / base course on well prepared surface and compacting with vibratory roller of 8 to 10 tonne capacity to achievethe desired density, complete as per specifications and directions of Engineer-in-Charge.
Total of Road Works
ALUMINIUM WORKS
(a) Structural analysis & design and preparation of shop drawings for pressure equalisation or rain screen principle as required, proper drainage of water to make it watertight including checking of all the structural and functional design.
(b) Providing, fabricating and supplying and fixing panels of aluminium composite panel cladding in pan shape in metalic colour of approved shades made out of 4mm thick aluminium composite panel material consisting of 3mm thick FR grade mineral core sandwiched between two Aluminium sheets (each 0.5mm thick). The aluminium composite panel cladding sheet shall be coil coated, with Kynar 500 based PVDF / Lumiflon based fluoropolymer resin coating of approved colour and shade on face # 1 and polymer (Service) coating on face # 2 as specified using stainless steel screws, nuts, bolts, washers, cleats, weather silicone sealant, backer rods etc.
(c) The fastening brackets of Aluminium alloy 6005 T5 / MS with Hot Dip Galvanised with serrations and serrated washers to arrest the wind load movement, fasteners, SS 316 Pins and anchor bolts of approved make in SS 316, Nylon separators to prevent bi-metallic contacts all complete required to perform as per specification and drawing The item includes cost of all material & labour component, the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working curtain wall with aluminium composite panel cladding, cleaning and protection of the curtain wall with aluminium composite panel cladding till the handing over of the building for occupation. Base frame work for ACP cladding is payable under the relevant aluminium items.
The Contractor shall provide curtain wall with aluminium composite panel cladding, having all the performance characteristics all complete , as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer-in-Charge. However, for the purpose of payment, only the actual area on the external face of the curtain wall with Aluminum Composite Panel Cladding (including width of groove) shall be measured in sqm. up to two decimal places.
Providing and fixing aluminium tubular handle bar 32 mm outer dia, 3.0mm thick & 2100 mm long with SS screws etc. complete as per direction of Engineer-in-Charge.
Providing and fixing aluminium round shape handle of outer dia 100 mm with SS screws etc. complete as per direction of Engineer-in-Charge. Powder coated minimum thickness 50 micron aluminium.
Providing and fixing sheet covering over expansion joints with iron screws as per design.
Total of Aluminium Works
WATERPROOFING WORK
(a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing slab including adjoining walls upto 300 mm height including cleaning the surface before treatment.compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC
(b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs.
(c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm of cement admixed with water proofing compound conforming to IS : 2645 and approved by Engineerin-charge.
(d) Finishing the surface with 20 mm thick jointless cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineerin-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep.
(e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test.“All above operations to be done in order and as directed and specified by the Engineer-in-Charge :
Total of Water Proofing Works
STONE WORKS
Providing and fixing stone slab with table rubbed, edges rounded and polished, of size 75x50 cm deep and 1.8 cm thick, fixed in urinal partitions by cutting a chase of appropriate width with chase cutter and embedding the stone in the chase with epoxy grout or with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 6 mm nominal size) as per direction of Engineer-in-charge and finished smooth.
Total of Stone Works
PILING WORKS
Note: Truck Mounted rotary/TMR/Tube well boring machine shall not be used.
Note: 1. Initial and Routine Load Test shall not be carried out by Dynamic method of testing. Note: 2. Testing agency shall submit the design of loading platform for the approval of Engineer-in-charge.
Total of PILING WORKS
SANITARY FIXTURES
Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS:13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required :
Total of Sanitary Fixture
WATER SUPPLY
Providing and fixing G.I. pipes complete with G.I. fittings and clamps, i/c cutting and making good the walls etc.
Internal work ‐ Exposed on wall
Providing and fixing G.I. pipes complete with G.I. Fittings including trenching and refilling etc.
External work
Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :
Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete :
Providing and fixing gun metal non‐ return valve of approved quality (screwed end) :
Providing and placing on terrace (at all floor levels) polyethylene water storage tank ISI : 12701 marked with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. (P‐11564)
Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms.
Providing and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS:8931.
Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 a) 15 mm nominal bore
Total of Water Supply
SEWAGE AND DRAINAGE
Constructing brick masonry circular manhole 1.22m internal dia at bottom and 0.56m dia at top in cement mortar 1:4 (1 cement :4 coarse sand) inside cement plaster 12mm thick with cement mortar 1:3 (1 cement :3 coarse sand) finished with a floating coat of neat cement foundation concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40mm nominal size) and making necessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) finished with a floating coat of neat cement, all complete as per standard design :
Constructing brick masonry circular manhole 1.52 m internal dia at bottom and 0.56 m dia at top in cement mortar 1:4 (1 cement : 4 coarse sand) inside cement plaster 12mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement, foundation concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40mm nominal size) and making necessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) finished with a floating coat of neat cement, all complete as per standard design :
Extra depth for circular type manhole 1.52 m internal dia (at bottom) beyond 2.30 m :
Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as per IS : 10910 on 12mm dia steel bar conforming to IS : 1786 having minimum cross section as 23 mmx25mm and over all minimum length 263 mm and width as 165mm with minimum 112 mm space between protruded legs having 2 mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufacture's permanent identification mark to be visible even after fixing, including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) complete as per design. (P‐11565)
Making connection of drain or sewer line with existing manhole including breaking into and making good the walls, floors with cement concrete 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) cement plastered on both sides with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement and making necessary channels for the drain etc. complete :
Constructing brick masonry road gully chamber 50x45x60 cm with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) including 500x450 mm pre‐cast R.C.C. horizontal grating with frame complete as per standard design :
Providing and laying Non Pressure NP‐3 class (Medium duty) R.C.C. pipes including collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement:2 fine sand) including testing of joints etc. complete.
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Total of Sewage and Drainage
RAIN WATER HARVESTING & TUBEWELLS
Development of tube well in accordance with IS : 2800 (part I) and IS: 11189, to establish maximum rate of usable water yield without sand content (beyond permissible limit), with required capacity air compressor, running the compressor for required time till well is fully developed, measuring yield of well by "V" notch method or any other approved method, measuring static level & draw down etc. by step draw down method, collecting water samples & getting tested in approved laboratory, i/c disinfection of tubewell, all complete, including hire & labour charges of air compressor, tools & accessories etc., all as per requirement and direction of Engineer‐in‐ charge. (P‐2152)
Providing and fixing suitable size threaded mild steel cap or spot welded plate to the top of bore well housing/ casing pipe, removable as per requirement, all complete for borewell of:
Providing and fixing M.S. clamp of required dia to the top of casing/ housing pipe of tubewell as per IS: 2800 (part I), including necessary bolts & nuts of required size complete.
200MM DIA (P‐2153)
Providing and fixing Bail plug/ Bottom plug of required dia to the bottom of pipe assembly of tubewell as per IS:2800 (part I).
Total of Rainwater Harvesting & Tubewells
DEMOLISHING WORKS
Total of Demolishing Works
CLADDING AND GLAZING WORK
Structural analysis & design and preparation of shop drawings for the specified design loads conforming to IS 875 part III (the system must passed the proof test at 1.5 times design wind pressure without any failure), including functional design of the aluminum sections for fixing glazing panels of various thicknesses, aluminium cleats, sleeves and splice plates etc. gaskets, screws, toggles, nuts, bolts, clamps etc., structural and weather silicone sealants, flashings, fire stop (barrier)-cum-smoke seals, microwave cured EPDM gaskets for water tightness, pressure equalisation & drainage and protection against fire hazard including:
Fabricating and supplying serrated M.S. hot dip galvanised / Aluminium alloy of 6005 T5 brackets of required sizes, sections and profiles etc. to accommodate 3 Dimentional movement for achieving perfect verticality and fixing structural glazing system rigidly to the RCC/ masonry/structural steel framework of building structure using stainless steel anchor fasteners/ bolts, nylon seperator to prevent bimetallic contacts with nuts and washers etc. of stainless steel grade 316, of the required capacity and in required numbers.
Providing and filling, two part pump filled, structural silicone sealant and one part weather silicone sealant compatible with the structural silicone sealant of required bite size in a clean and controlled factory / work shop environment, including double sided spacer tape, setting blocks and backer rod, all of approved grade, brand and manufacture, as per the approved sealant design, within and all around the perimeter for holding glass.
Providing and fixing in position flashings of solid aluminium sheet 1 mm thick and of sizes, shapes and profiles, as required as per the site conditions, to seal the gap between the building structure and all its interfaces with curtain glazing to make it watertight.
Making provision for drainage of moisture/ water that enters the curtain glazing system to make it watertight, by incorporating principles of pressure equalization, providing suitable gutter profiles at bottom (if required), making necessary holes of required sizes and of required numbers etc. complete. This item includes cost of all inputs of designing, labour for fabricating and installation of aluminium grid, installation of glazed units, T&P, scaffolding and other incidental charges including wastages etc., enabling temporary structures and services, cranes or cradles etc. as described above and as specified. The item includes the cost of getting all the structural and functional design including shop drawings checked by a structural designer, dully approved by Engineer-in-charge. The item also includes the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working structural glazing as specified, cleaning and protection till the handing over of the building for occupation. In the end, the Contractor shall provide a water tight structural glazing having all the performance characteristics etc. all complete as required, as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer- in-Charge.
Note:- 1. The cost of providing extruded aluminium frames, shadow boxes, extruded aluminium section capping for fixing in the grooves of the curtain glazing and vermin proof stainless steel wire mesh shall be paid for separately under relevant items under this subhead. However, for the purpose of payment, only the actual area of structural glazing (including width of grooves) on the external face shall be measured in sqm. up to two decimal places. Note:-2. The following performance test are to be conducted on structural glazing system if area of structural glazing exceeds 2500 Sqm from the certified laboratories accreditated by NABL(National Accreditation Board for Testing and Calibration Laboratories), Department of Science & Technologies, India. Cost of testing is payable separately. The NIT approving authority will decide the necessity of testing on the basis of cost of the work, cost of the test and importance of the work. Performance Testing of Structural glazing system Tests to be conducted in the NABL accredited lab or by any other accreditation body which operates in accordance with ISO / IEC 17011 and accredits labs as per ISO/ IEC 17025.
1. Performance Laboratory Test for Air Leakage Test (-50pa to - 300pa) & (+50pa to +300pa) as per ASTM E-283-04 testing method for a range of testing limit 1 to 200 mVhr
2. Static Water Penetration Test. (50pa to 1500p) As per ASTME- 331-09 testing method for a range up to 2000 ml.
3. Dynamic Water Penetration (50pa to 1500pa) as per AAMA 501.01- 05 testing method for a range upto 2000 ml
4. Structural Performance Deflection and deformation by static air pressure test (1.5 times design wind pressure without any failure) as per ASTME-330-10 testing method for a range upto 50 mm
5. Seismic Movement Test (upto 30 mm) as per AAMA 501.4- 09 testing method for Qualitative test, Tests to be conducted on site.
6. Onsite Test for Water Leakage for a pressure range 50 kpa to 240 kpa (35psi) upto 2000 ml
For payment, only the actual area of glass on face # 1 of the glass panels (excluding the areas of the grooves and weather silicone sealant) provided and fixed in position, shall be measured in sqm.
(i) Coloured tinted float glass 6mm thick substrate with reflective soft coating on face # 2, + 12mm Airgap + 6mm Heat Strengthened clear Glass of approved make having properties as visible Light transmittance (VLT) of 25 to 35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 degree K etc. The properties of performance glass shall be decided by technical sanctioning authority as per the site requirement.
Total of Cladding and Glazing Work
ANY OTHER ITEMS UNDER DSR-2023
(i) For any Other Works which are not covered in above DSR items & Horticulture works etc and covered under DSR - 2023
Total of any Other Works Under DSR - 2023
HORTICULTURE WORKS UNDER HORTICULTURE DSR - 2025
Horticulture Works Under Horticulture DSR - 2025
Total of Horticulture Works Under Horticulture DSR - 2025
Total Amount for DSR Works at Depot (including GST )
BOQ OF CIVIL AND STRUCTURE AT AGRA METRO
SUMMARY SCHEDULE - B: NDSR ITEMS
CONCRETE WORK
WOOD WORK
STEEL WORK
STONE WORK
FIRE DOORS
MISCELLANEOUS WORKS
GEOTECHNICAL WORKS
TOPOGRAPHICAL SURVEY WORKS
FINISHING WORK
FLOORING WORK
SUSPENDED CEILING WORK
GLASS WORK
PILING WORKS
Total Amount for Schdule B NDSR Items
BOQ OF CIVIL AND STRUCTURE AT AGRA METRO
SCHEDULE - B: NDSR ITEMS
BILL OF QUANTITY
CONCRETE WORK
Providing, casting and fixing precast concrete-M30 grade RCC panel of required size and thickness in boundary walls with shutter finish including form work in precasting, providing hooks for lifting, handling, transporting, hoisting, necessary temporary suports, centering and erection in position to correct lines, stitching with columns etc. complete.40% Payment shall be released on completion of casting of precast panel balance 60% shall be released after completion of the fixing of panel up to the satisfaction of the engineer. Note: Payment for the reinforcement, hooks and stitch concrete shall be made separately.
Providing,hoisting and fixing of Precast Reinforced Cement Concrete M30 Grade in tie beams, gutter, window, sills/lintels steps of staircase, covers of Drain,covers of Trenches of all types and cable trough, sump and manholes complete cast to profile and the thickness as per approved GFC wherever required as directed by the engineer.The rate includes cost of all labour, materials and equipment and performing all operations required for manufacture and transportation of pre-cast reinforced cement concrete items, hoisting and fixing them in position to correct lines and levels, pointing and finishing, cutting, bending, providing and fixing of lifting hooks, etc, complete.
Extra cost for change in grade from M25 to M30 for all types of concrete works at all levels
Extra cost for change in grade from M25 to M35 for all types of concrete works at all levels
Total of CONCRETE WORK
WOOD WORK
Providing & fixing Toilet Cubicle (of following standard dimension which includes 600mm - 750mm door size width) made of heat, bacteria, water, chemical, scratch, impact and anti bacterial resistant 12mm thick solid compact laminate panels tested in approved laboratory. Finish of the compact laminate should be Suede, Raw silk model includes doors, pilasters & intermtediate panels finished with approved texture/shade as per the detail drawings & as per IS 2046 (Indian Standard) and as per fire retardant BS- 476/97 standard.
This also includes providing and fixing in position necessary hardware made out of Stainless steel (Grade 304-L) as per manufacturer’s specifications & Architects instructions like (1) Door Knob, (2) Gravity Hinges, (3) Thumb turn lockset with Occupancy indicators, (4) Coat hooks with Door stopper (5) U- Channels, (6) Adjustable foot/pedestal, (7) Top rail (8) Rubber noise deafening tape, (9) Screws & wall Plugs. All screws will of 304-L Grade in stainless steel with satin finish. All pilasters are supported by stainless steel Bottom Cladding.
The base of the stainless steel bottom cladding will be anchored to the floor with a clearance height upto 150mm. The top fitting should consist of SS top rail which will get fixed with pilasters. SS wall fixing is used only on the wall which will hold the SS top rail. Cubical sizes may vary upto +/- 200mm
Toilet Cubicle with standard dimension (approximate sizes) 2000 to 2100mm Height x 1000 to 1200mm Width x upto 1600mm Depth which includes 600mm door size width,
Toilet Cubicle with standard dimension (approximate sizes) 2000 to 2100mm Height x 1200mm to 1600mm Width x 1600mm Depth which includes 600mm door size width,
Toilet Cubicle I-Shape (Front Partition) with standard dimension of (approximate sizes) 2000-2100mm Height x 1000mm Width which includes 600mm door size width.
Total of Wood Work
STEEL WORK
Motorise Rolling Shutters
Providing and fixing Motorized rolling shutter (heavy duty), curtain made of single skinned Galvalume stell laths as per IS6248 with natural finish, partial bright steel with one coat of grey epoxy primer by spray with 900mm grill in height at eye level, pressed Galvalume steel hood and motor cover with natural finish, wind lock-storm anchors, CE certified CRS compact gear P.R.C make in direct driver operator and three station push button with deadman control.
Technical Specification should be as follow: Rolling Curtain: Constructed from single skinned galvalume, bright steel laths and is retained by interlocking with each other. Surface: Galvalume with nature finish, Partial Bright Steel with one coat of grey epoxy primer by spray Material Thickness: 1.2mm for clear width > 3.5m & 0.9mm for clear width <= 3.5m as per IS 6248 laths, 8.0mm Curtain Weight: 15.5 kg/m2 approx Structure Shape: Curved, Honeycomb Support Brackets: Mild Steel with one coat of grey epoxy primer by spray Shaft: Shaft is manufactured from mild steel tube of suitable outside diameter and wall thickness to suit the shutter application and is unsprung Finish: One coat of grey epoxy primer by spray Side Guides: 2.0mm thick heavy duty TG Galvanised Steel Finish: One coat of grey epoxy primer by spray Wind lock-storm anchors: Included
Hood & Motor Cover: 0.9mm thick Pressed galvalume steel hood box complete with reinforced bracket as required to suit the shutter width. Finish: Natural Finish Bottom Profile: Bend-resistant Galvanised steel profile for additional strength. Finish: One coat of grey epoxy primer by spray Locking arrangement: Shoot Bolt Arrangement Seals: Optional on side guides & bottom Surface with protective paint: Optional CE Certified CRS Compact Gear P.R.C. Make Indirect Drive Operator Drive Unit: Indirect drive operator. System power supply wired with industrial plug Safety mechanism: Patented safety mechanism for chain failure with inbuilt limit switches Control Switch: Three station push button with deadman control Emergency manual operation: Emergency operation by means of chain Optional Accessory: Additional three station push button Cost is inclusive of all materials and labour complete (curtain, grill, hood, motor, motor cover, anchors, gears, push button, deadman control and any other if required).
Total of Steel Works
STONE WORK
Providing and fixing 18 mm thick Polished Granite Stone cladding work for wall lining over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand) and cement slurry @ 3.3 kg/sqm including pointing in white cement complete as per the requirement of the engineer-in-charge.
Granite treads: Providing and laying 30mm thick FLAMED Sadarhalli Grey Granite Stone flooring in treads and landings (including bull nosing, rounding the nose and making groove) of steps of approved colour, size and pattern,(sample of granite stone shall be approved by Engineer-in charge) over 20mm (average) thick base of cement mortar 1:4 (1cement:4coresand) laid and jointed with neat cement slurry mixed with pigment to match the shade of granite stone complete as per specifications and architectural drawings. Allow for cutting & finishing for handrails fixing as per design.
Extra for Red/Raw silk/Jet Black/Tan Brown/Kashmir Yellow/Ikon/ Brown/Multi Red/Blue Pearl granite or any other colour as directed by Engineer.
Granite Risers: Providing and laying 20mm thick mirror polished Granite Stone in Risers of steps of approved colour, size and pattern, (sample of granite stone) be approved by Engineer-in-charge) over 12 mm thick bed of cement mortar 1:4 (1cement:4coarse sand) and jointed with neat cement slurry mixed with pigment to match the shade of granite stone complete as per specifications and relevant drawings.
Extra for Red/Raw silk/Jet Black/Tan Brown/Kashmir Yellow/Ikon/ Brown/Multi Red/Blue Pearl granite or any other colour as directed by Engineer.
Extra for Flamed Finish on Granite Works
Total of Stone Works
FIRE DOORS
Fire check doors supply of approved make (120 Minutes) 2 hrs fire rated door alongwith frame fabricated and successfully tested at CBRI Roorkee in both direction satisfying two criteria (Stability and Integrity) confirming to BS:476 Part II, IS3614 Part II as per schedule of requirement
Providing and fixing Clear vision Panel of 200mm x 300mm complete in all respect - 120 minutes fire rated
Providing and fixing Heavy Duty Door Closer complete in all respect - 120 minutes fire rated
Providing and fixing Eurofile mortice lock-240 with double pin cylinder having master arrangement and SS handles complete in all respect - 120 minutes fire rated
Providing and fixing Concealed SS finish tower bolts (300mm) complete in all respect - 120 minutes fire rated
Providing and fixing Magnum or equivalent make SS 4 ball bearing hinges complete in all respect - 120 minutes fire rated
Providing and fixing SS handles Dorma or equivalent make of double leaf door complete in all respect - 120 minutes fire rated
Providing and fixing Dorma or equivalent make panic bar of double leaf door complete in all respect - 120 minutes fire rated
Installation charges of Fire door in all respect
Total of Fire Doors
MISCELLANEOUS WORKS
Supplying, pouring and packing non-shrink grout as per manufacturer's specifications under base plates of columns,grouting of anchor bolts or any other location specified by The Engineer etc complete as per approved drawings and specifications, including cost of packing plates.
Providing and fixing in position approved quality Closed cell Polyethylene foam joint filler boards (25 mm thick) at expansion joints of concrete structures, as per drawings and instructions complete including fixing with adhesives etc to complete the work in all respect as per instruction of engineer-incharge.
Providing and laying of Filter media 600mm thick as directed at the back of retaining walls and any other locations etc as per Technical Specifications
Providing and laying weep holes in retaining wall by using AC pipes of 100mm diameter including proper grade and joining complete, as per Technical Specifications
Providing and laying approved quality silicon sealant with shore hardness of 22, with a movement accommodation of minimum + 50% of joint width, and having a minimum tensile strength of 1.7 Mpa, suitable for expansion joints in floors and roofs of buildings.
Providing and fixing MS bolt of 16mm dia 425 mm long length and threading upto 75mm including using suitable fixing arrangment
Supplying and fixing of GI Sheet of 16 Gauge for terrace expansion joint including cutting, screwing, placing in position etc complete
Painting two coats(excluding priming coat) over new steel and other metal surfaces with enamel paint, brushing to give even shade including cleaning the surface of all dirt, dust and other foreign matter etc. complete, as per Technical Specifications
Polysulphide sealant
Providing and fixing in position PVC water stopper 225mm wide 8mm thick in UG tanks including labour charges for handling and positioning etc. as per specification and directions of engineer with all necessary fittings, anchors, laps and with all lead and lift.
Granular Filling below the Foundations, Rafts, Rails/tracks etc all complete as per drawings and specifications
Providing and laying HDPE pipe (PN 10) confirming to IS: 14333-2022 for drainage of effluent waste, butt jointed at ends including all fittings & testing of joints complete as per direction of Engineer-in-Charge.
150mm dia
200mm dia
300mm dia
Construction of 200/150 mm size Deep Tube Well with 7.5 HP submersible pump
b. Erection, Dismantling and shifting (from station to station) of Rig Machine
a. 200 MM dia MS ERW Housing pipe having wall thickness 6 MM
b. 150 MM dia MS ERW Blind pipe having wall thickness 5 MM
c. 150 MM dia MS ERW Slotted pipe
a. Transportation of Air Compressor
b. Erection of Air Compressor
c. Running of Air Compressor
Transplanting the marked trees of various species and girth to the place shown by Engineer/Engineer's representative with a lead of 2 km. With all tools, plants, man and machinery and necessary preparation such as preparation of earth ball of tree roots of desired depth and diameters. Dislodging, lifting, transportation and transplanting trees from original place to the new place including all arrangements T & P, labour etc. For successfully completing the work will include excavatiing pits of adequate size, arranging loose soil, mixing of manure, fertilizers, insecticides etc. to ensure survival of trees being transplanted. Maintenance of tree i.e. watering, manuring, soil, heaping, spray of insecticides for 6 months. All above operations shall be executed as per specifications
Note:- Stage wise payment for the work will be as follows : (i) 30% after tree transplanted. (6)40% after sprouting and establishment of trees. (iii) 30% after completion of maintenance period of 1 year.
TRAP DOOR - Hingeable & sliding trap door system manufactured according to EN13964 TAIM Quality standard comprising 2 pannels of size mentioned in drawings one unit made up of 0.6 GMS in RAL 9016 (Matt White colour) or as specified by Engineer, polyester powder coated finish and approx 95% humidity resistance, fire performance Class A2-S1, d0. Substructure consisting of roburst hinging technology with visible U 1091 G shaped or equivalent profiles which are mounted along the width of the panels. The U 1091G profiles or equivalent are fixed using L shaped primary carriers U 1040 or equivalent of 1.0mm thick GMS, which runs perpendicular to the U 1091 G profiles. This is suspended rigidly from the bare ceiling with M6 or equivalent threaded rods and fasteners. All components are made of galvanized steel.The rectangular panels can be swing down using spring loaded pins and hung from bolted sleeves provided on the sides. Once all the panels are swung down, they can be pushed to either side of the opening and stacked together in order to carry out any kind of maintenance.
Making of cutout (core cutting) in pre-costructed RCC / CC work of all grades for services required.
100mm dia 200 mm long
200mm dia, 150mm long
150mm dia, 150mm long
Filling sunken areas with broken brick bats of 25-75mm Nominal size cement mortar (1:4) including ramming to required consolidation complete at any level. (P-11807)
Providing and fixing (approved make) galvanized chicken wire mesh of size 75 x25 mm mesh (24 guage - 12 mm size) to be fixed on junction of concrete and masonary work and other location & firmly anchored to by means of galonized wire nails including the cost of cuttign to reqired sizes, materials, labour, tool & plants as approved by engineer-in- charge. Nothing shall be paid extra for this items.
Providing & Laying 3mm thickness Polyurethane Self levelling Glossy system on concrete surface. The scope includes but not limited Providing and applying Neroflor 4000 primer, Neroflor screed 2mm, Neroflor PU SL 1mm over a concrete surface prepared after proper grinding by equipment to remove loose particle, contamination and latiance to provide a sound gripping surface including the edge line marking as per requirement/drawing/technical specifications. The primer has to ensure the excellent penetration and sealing of concrete as per the relevant drawing and specifications and under the directions of engineer-in-charge. The rates include all materials, labour, tools, Tolant and equipment. Nothing shall be paid extra
for depot-01
for depot-02
Supplying and installation of Motorised sliding gate with Italian Make Automation System and fixed fence. The item includes Motorised Double Leaf Sliding gate and fixed fence made of mild steel with one coat of grey epoxy primer by spray, European electromechanical actuator- Sonic 1500C, three station push button, pair of photocells with anodised aluminium vertical mountings, flashing light, etc. as per relevant approved drawing/technical specifications all complete. Nothing shall be paid extra
Supplying and installation of Manual Double leaf Swing gate 6000X2600mm made of mild steel with one coat of grey epoxy primer by spray, etc. as per relevant approved drawing/technical specifications all complete. Nothing shall be paid extra.
Designing, fabricating, testing, installing and fixing in position Curtain Wall with Porcelain Tile Panel Cladding, with open grooves for linear as well as curvilinear portions of the building, for all heights and all levels etc. including:
(a) Structural analysis & design and preparation of shop drawings for pressure equalisation or rain screen principle as required, proper drainage of water to make it watertight including checking of all the structural and functional design.
(b) Providing, fabricating and supplying and fixing panels of Porcelain tile panel cladding in pan shape of approved shades made out of 3mm thick Porcelain Tile panel material using stanless steel screws, nuts, bolts, wahsers, cleats, weather silicone sealant, backer rods etc
(c) The fastening brackets of Aluminium alloy 6005 T5 / MS with Hot Dip Galvanised with serrations and serrated washers to arrest the wind load movement, fasteners, SS 316 Pins and anchor bolts of approved make in SS 316, Nylon separators to prevent bi-metallic contacts all complete required to perform as per specification and drawing The item includes cost of all material & labour component, the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working curtain wall with Porcelain Tile panel cladding, cleaning and protection of the curtain wall with porcelain tile panel cladding till the handing over of the building for occupation.
Base frame work for Porcelain Tile panel cladding is payable under the relevant aluminium items. The Contractor shall provide curtain wall with Porcelain Tile panel cladding, having all the performance characteristics all complete, as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer-in-Charge. However, for the purpose of payment, only the actual area on the external face of the curtain wall with Porcelain Tile Panel Cladding (including width of groove) shall be measured in sqm. up to two decimal places.
Providing and painting DECO PU paint of approved brand and shade over M.S Structure two or more coats to given an even shade, including one coat of primer, preparation of surface using automotive putty, thinner etc. surface duly emery papered to give a perfactely smooth and even prepared surface before painting etc. complete in all respect as per satisfaction of Engineer-in-charge. The rates includes all materials, Labour, tools, plants and equipment. Nothing shall be paid extra on this items.
Providing 2.0 m high tamporary barricade and arrangement for traffic diversion such as traffic signals during Construction at site, for day and night as per requirement and Drawings.During Contruction barricading and arrangement for traffic diversion has to be kept continuously and maintained properly till the completion of all the activities. The construction barricading will have diffrent width in diffrent portion of the alignment as directed by the engineer keeping in view the movement of traffic at the ground level and minimum inconvenience to and safety of public. The barricade should be as per the tender drawing (Assuming that the barricading will be done in a stretch of 100 m at four places simultaneously). Note : The payment schedule for item No. 5.10 shall be as follows: Note :- Payment Stages (i) 70% on installation (ii) 30% on removal/shift.
Total of MISCELLANEOUS WORKS
GEOTECHNICAL WORKS
Drilling 150mm dia boreholes in all types of soil including mobilisation of machinery, conducting all SPT,vane shear test , collection of undisturbed and disturbed samples, setting up machinery, shifting etc. Including all lab, field tests & report preparation(pile foundation recommendations including safe pile capacities , pile settlement calculations, etc incorporating all field and laboratory testing) as per IRC: 78/IS codes.
Conducting Plate Load Tests at 2.0 mtr to 3.0 mtr depth (foundation lvl) from NGL. Test should continued till 25mm settlement in normal circumstances and 50mm in special cases such dense gravel, gravel and sand mixture is obtained or failure of the soil whichever as per IS: 1888 or refusal whichever is earlier.
Total of Geotechnical Works
TOPOGRAPHICAL SURVEY WORKS
Topographical Survey of the Depot Area
Establishing GPS Control Points
Pegging, making and Fixing of land boundary pillars of concrete block of size 100*100*1200 mm with concrete mix of 1 cement:2 coarse sand: 4 agrregate
Submission of Quarterly Progress Reports of project using Drone based Photogrammetry or RGB Lidar and Geo-Tagged High-Resolution Videography as per instructions of the engineer in charge including 1. Videography and photos 2. Ortho Image with 3cm GSD 3. DSM 4. Point cloud (*.LAS format) of the entire stretch (excluding underground structures which are not accessible to drones in air) including the actual progress of the structures and features which can be taken as input to measure changes in dimension etc. (Payment shall be made per Hectare)
Total of Topographical Works
FINISHING WORK
Painting on wood-work/ Brick-work/ Concrete-work/Wall/ with Italian Polyurethane coating with one coat of Italian Polyurethane sealer and one coat Italian Polyurethane Insulator coating of required shades to give an even shade.
Total of Finishing Works
FLOORING WORK
Providing & Laying "Resin based Epoxy" flooring of 3mm thickness on concrete surface. The scope includes but not limited "Providing and applying a 200 micron thick primer two component (Epoxy Resin: 100 P.B.W. (ASTM - D-1544, 5478, 1652) and Epoxy Hardener: 100 P.B.W. (ASTM D-1544, 5478, 2073) non fillerised Epoxy material over a concrete surface prepared after proper grinding by equipment to remove loose particle, contamination and latiance to provide a sound gripping surface."The Epoxy primer has to ensure the excellent penetration and sealing of concrete as per the relevant drawing and specifications and under the directions of engineer-in-charge. The rates include all materials, tools, plant and equipment. Nothing shall be paid extra.
Total of Flooring Works
SUSPENDED CEILING WORK
Providing and installing suspended ceiling system at all levels with interlocking grid of size 1200x600mm ceiling module of size (1250x600) consisting of demountable infill units (size 1200x600x1.2mm) having 50mm gap at every 1200mm, gap covered with 82mm wide channel having flanges to hold ceiling panels. The panels and channels shall be made from 1.2mm thick GI sheet, punched and bent to shape. The panels shall have perforated area 30-40%. The ceiling shall be powder coated (PPC, 80 micron) on exposed and unexposed surface with approved colour. The grid system shall include hangers and runners of size 50x50x3mm thick hot dip galvanised steel, fixed on soffit of slab with the help of stainless steel expansion fasteners of size 10x75mm (Tam Anchor), The ceiling system to include panels, hanging system including the cost of providing opening and electrical fittings/fixtures, secondary supporting system for opening and below cable tray and duct, access to maintenance, all complete as per requirement of Engineer-in Charge.
Total of Suspended Ceiling Works
GLASS WORK
Providing and fixing toilet mirror in 6 mm thick clear float glass with bevelled and polished at edge and copper coating on rear side. Fixed on wall with 6mm thick plywood and kraft paper backing fixed to wooden cleats with 8mm dia 38mm long stainless steel stud complete.
Providing and fixing in position frameless glass partition walls made out of 12mm thick toughened clear glass held in position by wall connecting profile (with or without open able glass door made out
(i) Two Set of 350mm long pull handles of approved make
(ii) Two number corner locks US10 of approved make
(iii) Floor spring BTS-80 of approved make.
(iv) Lock keeper Plate stainless steel strip at the bottom of doors for doors exceeding 1100mm
With openable door
Glass Fiber Reinforced Concrete (GFRC)
Providing and fixing Glass reinforced concrete (G.R.C) Jali 40 mm thick in approved size, pattern, design, thickness of any colour and shade approved by Engineer-in-Charge. The G.R.C Jali should be fixed on / between RCC / Block work or structural steel work with dry fixing method with all appropriate steel fralueweds, stainless steel (SS-304) 'L' shaped clamps, dash fastners and pins including anchoring, lifting, scafolding, manlift etc complete as per architectural drawing and specification. The screen should be made from '53 gade' white portland cement, quartz, fine silica sand, alkali resistant glass fibre, super plasticizer, polymer and UV resistant synthetic resistant inorganic pigment. The material casting should take place in synthetic rubber / FRP Mould. The Rates includes all materials (G.R.C Jali, MS frame and any if required), labour, tools, manlift, plant, equipments, surface preparation and any if required to complete the
Providing and fixing 12mm thick toughened glass on wall with stainless steel fitting. The rates include all Materials, necessary accessories, labor,tools and plants. Nothing shall be paid extra for this item.
Design supply & installation of Spider Glazing system for canopy, designed to withstand the wind pressure. The System held with Spider Fittings of SS-316 Grade Steel of approved manufacturer with glass panel having 13.52 mm thick clear toughened glass held together with SS- 316 Grade Stainless steel Spider & bolt assembly. The glass panel assembly shall be connected to MS/SS frame by means of SS- 316 Grade stainless steel brackets & Anchor bolts, non staining weather sealants of approved make, bushes and separators to prevent bi- metallic contacts, all complete to perform as per specification and approved drawings. The complete system to be designed to accommodate thermal expansion & seismic movements etc. The joints between glass panels (6 to 8 mm) and gaps at the perimeter to be filled with non staining weather sealant, so as to make the entire system fully water proof & dust proof. The rate shall include all Design, Engineering and shop drawing including approval from structural designer, labour, T&P, scaffolding, other incidental charges including wastage, enabling temporary services all fitting fixers nut bolts, washer, Buffer plates, fastener, anchors, SS channel laminated glass etc. all complete. For the purpose of payment, actual plan area of Glazing including thickness of joints shall be measured.
Providing and installing of 6.2 m wide automatic glass door operator LS220B LP as per site requirement and instructions of Engineer In- charge.
Providing and installing of 3M 150mm band as per site requirement, digital priniting Green guard Latex 3M approved M/c on 3M-480 CV3 series vinyl & one layer of 3M clear luster over Lamination 8548 as per instructionsof Engineer In-charge.
Structural Glazing: Providing and installing glazing with specified fixing of anodized aluminium section & finish using 2 sheet of 6mm thick toughened glass with nominal gap silicon sealant joint. Glass shall be clear toughened and laminated with 1.52mm thick polyvinyl butyral layer. all complete as per relevant architectural drawings and specification with cut out & holes. The rates include all Materials, frame works (all types)necessary accessories, labor,tools and plants. Nothing shall be paid extra for this items.
Total of Glass Works
PILING WORKS
Providing and fixing permanent MS liner (of required thickness or as directed by Engineer incharge) including cost of liner and driving the same for all type of dia bored cast in situ piles whereever required as per approved construction drawings and directions of Engineer incharge all complete
Notes: (A) The scope of work in above item includes a) All incidentals labour, material and works required to execute and complete the job.
Total of PILING WORKS
Total Amount for Schdule B NDSR Items
BOQ OF PEB AT AGRA DEPOT
SUMMARY SCHEDULE - C: PEB WORKS (NDSR ITEMS)
STRUCTURAL STEEL WORKS
ROOFING WORKS
MISCELANEOUS WORKS
Total of schedule C1
BOQ OF PEB AT AGRA DEPOT
SUMMARY SCHEDULE - C: ARCHITECTURAL FINISHING WORKS (NDSR ITEMS)
BILL OF QUANTITY (Schedule C - PEB Works)
Structural Steel Works
Designing, providing, fabricating, painting, transporting, erecting and securing in position structural steel work for buildings and workshops complete as per specifications, approved shop drawings and/or instructions. Work under this item would generally cover all structural steel work in the Buildings, including but not being limited to, columns, stanchions, beams, rafters, purlins, runners for cladding, gantry girders, brackets, hangers/ suspenders, runner beams for under slung cranes, bracings, Rain water Gutters, canopy’s, platforms etc, along with attachment/provision for fixing E&M, OHE and S&T equipment’s in the building steel roof structures (but excluding roof sheeting & wall cladding) Work to include all intermediate stages of activities not defined herein, but otherwise implied for total completion of work. Cost to include but not be limited to, all materials including wastage, all consumables, fasteners of all types for both temporary and permanent stages of work, all temporary stays, labour, temporary works including staging, scaffolding, tools, plant and equipment, and, costs of all incidentals and necessary testing of material, workmanship etc including cost of painting complete as per drawings and specifications.
Measurement will be on overall plan area basis between outer most edges.
NOTE: Providing, fabricating and supplying Hot Dip Galvanized Holding Down Bolts including all assemblies and accessories that are required to be embedded in concrete work by other agencies are included in the rate quoted by the tenderer in item nos. 1.1.1 to 1.1.2. Bolts shall be of sufficient length to ensure that a minimum 40mm length of threaded portion is embedded in concrete. Threaded portion to be left projecting outside the concrete surface shall be as per requirement of supplier's design and approved drawings.
Cost of fabricated, assembled and supplied Bolts shall include all necessary expenses incurred, including costs of all washers, nuts, lock nuts and pins that may be required for securing the structural member with the embedded bolts.
Work of actual fastening of the structural components with the embedded bolts shall have to be carried out by the supplier of the steel structure. However the foundation bolts shall be installed in foundation by civil contractor for construction of depot.
Workshop, Inspection Bays Buildings including portals, purlins, runners for cladding, gantry girders, Runway beamss etc.
for depot -01 (Front of pit wheel lathe )
front of work shop store
Car Parking Shed and Watch Tower including columns, rafters/trusses, runners, ties, purlins etc as shown in drawings or as directed and approved
Design, Supply and Erection of Structural steel (conforming to IS:2062 Grade B) work using structural sections incl. anchor bolts fabricated /procured to the required profile and shape as called for, hoisted, installed in position incl. All cutting, welding (continuous welding wherever required and directed) grinding & all operations, necessary templates, adequate temporary supports, scaffolding, staging, etc. incl. all tests on material and fabrication as required. Item to include the cost of sand blasting wherever required, primer and painting as per the specifications for internal and external surfaces as per technical specifications. Every precaution to be taken against rusting of sections. (Payment shall be on overall plan area basis between outermost edges for item no. 1.2.1 and in case of item no. 1.2.2 and 1.2.3 it will be measured and paid on actual weight hasis in MT)
Inspection platforms in Workshop / Inspection bay / Interior Cleaning / Washing plant Building etc and any other locations indicated on drawings, consisting of plates, rolled sections, chequered plates, tubes etc.
Rail track supporting columns of approximate length of 1210 mm of HE240 complete with base and capping plate, holding down bolts etc complete.
Miscelaneous structures for stabling lines, including drivers platform / staicase / Ladders etc as per drawing.
Total of Structural Steel Works
Roofing
Providing and fixing single skin trapezoidal Profiled sheeting with 1000 mm effective covered width 28-35 mm crests @ 200-300 mm pitch manufactured out of 0.5 mm TCT (Total coated thickness) Hi- tensile Galvalume/Zincalume steel. Sheets shall have wide pans with 2-3 nos stiffeneing ribs for effective water shedding and special male/female ends with full return legs on side laps for purlin supports and anti-capillary flute in side lap. Sheets shall have hot- dipped metallic Zinc-Aluminum alloy coating (150 gms / sqm, Zinc 45%, Aluminum 55% ) . Coating mass total on both sides AZ-150 or equivalent as per AS 1397-1993. Minimum 550 Mpa yield strength with silicon modified polyester (SMP) coating, (minimum silicone content 30% -50% or super-polyester XRW quality paint coat of approved colour.
Coating shall be as per AS/NZS-2728-1997, Category-3. Total coating thickness of 35 microns, comprising of 20 microns exterior coat of SMP over super-polyester XRW on top surface and 5 micron polyester reverse on back surface over 5 micron primer coats on both surfaces including side and end laps.
The Sheets shall be fixed using polymer coated hot dip galvanized hex head self drilling fasteners as per AS 3566 class 3 on each crest of sheets for connection with purlins and polymer coated hot dipped stitching fasteners @ 300 mm c/c on all sides and end laps Measurement shall be based on per unit of finished / laid surface area. Item to include curved sheets also whereever required. Approved sealing tapes shall be used on side laps and end laps of sheets and closers to be provided at the last end of sheets. The Contractor shall give a minimum 10 year guarantee for sheets against deterioration, disintegration loss of lusture, variation in colour etc. and leakages across laps, fasteners etc. All types of steel sheets shall be load tested to safely carry 1.10 times the design wind loads and coating thickness to the satisfaction of the Engineer in-charge. Fasteners shall also be load tested. The Contractor is to submit design and shop drawing for approval on the sheet profile, design and details before installation. The item includes all necessary flashing, trims ridge caping accessories & fastner to ensure an altight, insulated building which is not only functionally complaint but also aesthetically pleasing with contemporary international look.
Roofs of buildings (pit wheel lathe for depot-01 )
Side cladding, gable end clading etc all complete
Providing and fixing of Double sheeting composite insulated panels manufactured in a continuous process plant with high speed oscillation sprayed foam in roof & wall with all necessary flashing, trims, ridge capings, accessories & fastner to ensure an altight, insulated building which is not only functionally compliant but also aesthetically pleasing with contemporary international look. the specification is as follows :-. Composite insulated panels having on top side trapezoidal Profiled 28-35 mm deep and 200-300 mm pitch with 1000 mm effective cover width. the profile having 3 secondary ribs in pan and an anticapillary flute at side overlap shall be made of 0.50 mm TCT (Total coated thickness) prepainted Hi-tensile Galvalume/Zincalume steel grade AZ 150/G - 300 having hot dipped metallic Zinc - Aluminum alloy coating (150 gms / sqm, Zinc 45%, Aluminum 55%). as per AS 1397-1993. having 300 Mpa yield strength with silicon modified polyester (SMP) coating, (minimum silicone content 30%-50% or super-polyester XRW Coating or equivalent as per AS/NZS-2728-1997, Category-3. Total coating thickness of 35 microns, comprising of 20 microns exterior coat of SMP over super-polyester XRW on top surface and 5 micron polyester reverse on back surface over 5 micron primer coats on both surfaces and a bottom liner tray made of 0.5 mm TCT prepainted high tensile galvalume / zincalume steel grade AZ 150/G -300 of similar specification as for the top sheet in approved colour including side and end laps. The Panels shall have 30 mm thick (min) insulation core of rigid polyurethane foam. The panels of coustomised length shall have a return leg tongue to ensure snug and air tight joinery at bottom. The overlap side shall have an isolation tape to prevent thermal bridge. Roof and wall panels shall be fixed using polymer coated hot dipped hex head self drilling fasteners as per AS 3566 class 3 or equivalent on crest of panels for connection with purlins and stiching fastner @ 300 mm c/c on all sides and end laps etc. Measurement shall be based on per unit of finished laid surface area. Sealant and gaskets whereever necessary to be provided to ensure contemporary asthetic look of international standard.
Roof of buildings
Providing, supplying, erecting and fixing in position 3mm thk Polycarbonate sheets of approved texture and colour for roof lighting. Sheets to be profiled to match metal sheets described in item No. 2.0 & 3.0 and should include cost of laying sheets in curvature where required. Cost to include jointing, sealing with Butuladhesives and takes as per manufacturers specifications and cover all costs of labour tools, plants, temporary works etc all complete.
Total of Roofing
Miscelaneous Works
Providing, fabricating and fixing rain water drainage GI pipe 150mm dia OD 3.65mm thick from gutter at roof level to local drain in proper line and level.
Designing, providing, fabricating, painting, transporting, and securing in position louvers with wide / narrow slats as per drawings and instructions, complete with metal framework in 3 mm thick steel sheets. Units shall be capable of being manually operated from floor level. Cost to include all necessary fillers, seals, flashings, rubber strip nosing to slats complete in al respects. Payment shall be based on area measured within the framework of louver units
Turbo Ventilators
Supplying , fixing vertical turbo-ventilators complete with base. Flashing. Waterproofing as required at site and as per specification.
600mm diameter
Total of Miscelaneous Works
Total Amount for PEB Works
BOQ OF NDSR PLUMBING ITEMS AT AGRA DEPOT
SUMMARY SCHEDULE - D: NDSR PLUMBING ITEMS
SOIL, WASTE AND RAIN WATER PIPES
WATER SUPPLY
SEWERAGE AND DRAINAGE
PUMPS AND CONTROL PANELS
EFFLUENT TREATMENT PLANT
SEWERAGE TREATMENT PLANT
TOTAL OF SCHEDULE - D (NON - DSR PLUMBING ITEMS)
SCHEDULE - D (NON - DSR PLUMBING ITEMS)
BOQ OF NDSR PLUMBING ITEMS AT AGRA DEPOT
SUMMARY SCHEDULE - D: NDSR PLUMBING ITEMS
SOIL, WASTE AND RAIN WATER PIPES
Providing and fixing SS grating with frame including fixing to the floor with cement mortar.
100 mm dia (P- 11798)
Providing and fixing P.V.C. WC connector (straight or bend type) with rubber lip ring including 110 mm dia PVC pipe of required length and proper connection to C.I. pipe complete as required. (P-11843)
Providing and fixing on wall face M.S. Pipe rain water pipes conforming to IS:1239/3589 including jointing with seal ring. Leaving 10mm gap for thermal expansion
200 mm dia (P-11843)
Providing and fixing in position 100x50 mm GI reducing elbow including fix to floor with cement mortar. (P-11844)
Total of Soil, Waste and Rain Water Pipes
WATER SUPPLY
Providing, fixing, jointing and testing in position the following heavy class G.I. pipes conforming to IS:1239 cut to required lengths including all necessary fittings and specials such as bends, tees, union, reducers, flanges & plugs etc. Threading, jointing and making proper connections. 100mm thick fine sand around the pipes. Including excavation in all kind of soil (excluding hard rock), for pipe running at minimum 1.0 m to 1.2 m depth, dewatering, refilling, watering, ramming & removing the surplus excavated material and making good the same complete as required.
100 mm dia (P-11844)
Providing protection to embedded G.I. pipes and fittings by applying pyp kote primer (@ 100 gm/sqm) thereafter wrapping 4mm thick pyp kote (AW 4mm) protection coating by thermo fusion process. Overlap shall be maintained at 15mm. The application process shall be strictly according to manufacturer's specification.
25 mm dia (P-11845)
32 mm dia (P-11845)
40 mm dia (P-11845)
50 mm dia (P-11845)
80 mm dia (P-11845)
100 mm dia (P-11846)
Providing and fixing M.S. puddle flanges fabricated out of 6 mm thick M.S. plate of size 300 x 300mm plus dia of pipe of 750mm long pipe pieces fixed to RCC wall of water tanks. Including painting with two coats of primer complete as required. The entire fitting shall be hot dipped galvanised.
50 mm dia (P-11846)
65 mm dia (P-11846)
80 mm dia. (P-11846)
100 mm dia (P-11846)
150 mm dia (P-11847)
200 mm dia (P-11847)
Total of Water Supply
SEWERAGE AND DRAINAGE
Providing and laying non-pressure NP3 class R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :
300 mm dia (P-11847)
Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C. top slab with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand : 8 graded stone aggregate 40mm nominal size), inside plastering 12mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) finished with a floating coat of neat cement complete as per standard design: Inside size 90x80 cm and 45 cm deep with SRFC performated cover and frame heavy duty HD-20
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 (P-1843)Inside size 120x90 cm and 90 cm deep with SRFC performated heavy duty HD-20
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 (P-1844)Inside size 120x90 cm and 90 cm deep with SRFC performated cover extra heavy duty EHD-35
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Providing and fixing uPVC agricultural pipes conforming to IS:4985 Class IV (10 kg/sqcm) including all fittings, e.g. couplings, tees, bends. reducers and screwed adoptors, solvent welded joint as per manufacturers' iecommendations. [for Effluent Line in Work Shop]
160mm OD (P-11848)
Excavating trenches of required width for pipes, cables, etc including excavation for sockets. and dressing of sides. ramming of bottoms, depth upto 1.5 m including getting out the excavated soil, and then reterring the soil as required, in layers not exceeciiria 20 an in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m :
Pipes, cables etc. exceeding 600 mm dia.
Total of Sewerage and Drainage
PUMPS AND CONTROL PANELS
Providing and fixing heavy duty PVC insulated copper armoured cables 1.1KVA grade including necessary support clamps at ceiling level and connection lugs complete in all respects.
Power cable 3 core 4 mm (P-11849)
Power cable 3 core 6 mm2 (P-11849)
Providing and fixing of cast iron double flanged butterfly valves (PN-25) complete with 2 nos. matching flanges,bolts, nuts, 3.0 mm thick compressed asbestos gasket.
50 mm dia
65 mm dia
80 mm dia p-11850
100 mm dia P-11850
150 mm dia P-2180
Providing and fixing of cast iron double flanged dual plate type check valves (PN-25) including 2 no.s. matching flanges, nuts. bolts. 3 0 mm thick compressed gasket complete.
65 mm dia
80 mm dia (P-2180)
100 mm dia
Providing & fixing of resilient rubber neoprene lined style arch vibration eliminators suitable for raw-water upto pressure 20 kg/cm2..
65 mm dia
80 mm dia (P-2180)
100 mm dia (P-2180)
Providing and fixing of CI Y type suction strainer with gunmetal or brass internal parts installed outside water tanks.
100 mm dia
150 mm dia
Total of Pumps and Control Panels
EFFLUENT TREATMENT PLANT
Designing, providing, installation, testing and commissioning of Metro Boggey Wash effluent treatment plant (ETP) including all electrical & mechanical equipments, piping, valve sleeves, control panels based on any technology like MBBR / FAB, recirculation pumps, wiring panel etc. complete in all respects, including all equipments and consumable materials of ETP but excluding all civil work of R.C.C. tanks for the following incoming and outgoing parameters. The rate shall be inclusive of operation and maintenance for twelve months including man power and consumable items complete. The design basis considered to size the treatment plant is as follows including as required in the specification etc.
Inlet Parameters
Flow : Effluent =75m3/ day for 20 hours operation
COD : 400-600 mg/l
BOD : 200-250 mg/l
TSS : 200-300 mg/l
Oil & Grease : 30-50 mg/l
Outlet Parameters
COD : < 50 mg/l
BOD : < 10mg/l
TSS : <20 mg/l
Oil & Grease : <10 mg/l
The proposal should include the following units in general. However the alternate proposals will also be considered, if found technically suitable.
A) Below Ground Civil Tanks for the ETP plant.
Bar Screen Chamber, oil and grease tank. (R.C.C.)
Equalization tank.(R.C.C.)
Sludge Drying beds of adequate capacity ,for sun drying of ETP plant sludge (Brick Work + R.C.C. + Sand & Pebbles media for the sludge drying beds).
All R.C.C. Civil Foundations works for the Electro-mechanical equipment.
B) Above Ground ETP plant :
Bar Screens (2 nos.) , MSEP , to be fixed in Bar Screen Chamber.
Coagulation, Flocculation & Primary Tube Settling Tank (In M.S. Epoxy construction) & PVC media. -1 no.
Chemical doing pumps , dosing tanks (LDPE/ FRP) & agitators as required for Chemicals Dosing. (for Coagulator & Flocculator)- 1 set
FAB/ MBBR Bio –Reactor tank (In M.S. Epoxy construction) complete with internal strainers + fittings & PP media for the bio-reactor -1 no.
Chemical doing pumps , dosing tanks (LDPE/ FRP) & agitators as required for Chemicals Dosing. (for Secondary Tube Settler)- 1 set
Effluent Feed Pumps (Submersible) – CI construction , 2 nos. (1 working + 1 standby)
Air Blowers, Twin Lobe Type. 2 nos. (1 working + 1 standby)
Air Grids in the Equalisation tank & MBBR tank (in UPVC) with air diffusers as required-1 lot.
Chlorine Contact Tank (In M.S. Epoxy construction) -1 no.
Chlorine Dosing pump & Dosing pump -1set.
Filter Feed Tank (In M.S. Epoxy construction) -1 no.
Filter Feed Pumps (Horizontal Centrifugal -monoblock) – CI construction , 2 nos. (1 working + 1 standby)
Dual Media Filter –MSEP Vessel -1 no.
Activated Carbon Filter –MSEP Vessel -1 no.
Treated Water Storage tank (in HDPE) -15 KL capacity -1 no.
By Pass Arrangement before treated water Sump and from other units as required.
Effluent Treated Water Recirculation pump -2 nos. (1 working + 1 stand-by) of 200 LPM at 30 Mtr.)
ETP interconnecting valves and piping : MS- c-class piping for Air & UPVC – Sch 40 for Effluent & water lines connections. -1 lot
Instrumentation for Tanks water level controlling , pumps dry level protections , pressure Gauges , 2 nos. electro-magnetic flow meters, 1 no. energy meter & 1 no. Air Rota-meter – 1 lot.
Electrical Distribution panel for all ETP plant drives, interconnecting cables (Armoured, Al /Cu conductors) + GI cable trays & GI earthing as required - 1 lot.
1 year ETP -Operation and Maintenance is included.
Total of Effluent Treatment Plant
SEWERAGE TREATMENT PLANT
Designing, providing, installation, testing and commissioning of Sewage treatment plant (STP) including all electrical & mechanical equipments, piping, valve sleeves, control panels based on any technology like MBBR / FAB / Biocask , recirculation pump, wiring panel etc. complete in all respects, including all equipments and consumable materials of STP but excluding all civil work of R.C.C. tanks for the following incoming and outgoing parameters. The rate shall be inclusive of operation and maintenance for twelve months including man power but excluding the consumable items complete. The design basis considered to size the treatment plant is as follows including as required in the specification etc.
Inlet Parameters
Flow : 10 m³/ day for 20 hours operation
COD : 400-600 mg/l
BOD : 200-400 mg/l
TSS : 200-300 mg/l
Oil & Grease : 30-50 mg/l
Outlet Parameters
COD : < 50 mg/l
BOD : < 10mg/l
TSS : <30 mg/L
Oil & Grease : <10 mg/l
The proposal should include the following units in general. However the alternate proposals will also be considered, if found technically suitable.
A) Below Ground Civil Tanks for the STP plant.
Bar Screen Chamber, oil and grease tank. (R.C.C.)
Equalization tank.(R.C.C.)
Sludge Drying beds of adequate capacity ,for sun drying of STP plant sludge (Brick Work + R.C.C. + Sand & Pebbles media for the sludge drying beds). Sludge Drying beds of adequate capacity , for sun drying of STP plant sludge (Brick Work + R.C.C. + Sand & Pebbles media for the sludge drying beds).
All R.C.C. Civil Foundations works for the Electro-mechanical equipment.
B) Above Ground STP plant
Bar Screens (2 nos.) , MSEP , to be fixed in Bar Screen Chamber.
FAB/ MBBR /Biocask Bio –Reactor tank (In M.S. Epoxy construction) complete with internal strainers + fittings & PP media for the bio-reactor -1 no.
Tube Settler tank (In M.S.Epoxy construction) with PVC-media for tube settler-1no.
Chemical doing pumps , dosing tanks (LDPE/ FRP) & agitators as required for Chemicals Dosing. (for Secondary Tube Settler)- 1 set
Sewage Feed Pumps (Submersible)-CI construction, 2 nos. (1 working + 1 standby)
Air Blowers, Twin Lobe Type. 2 nos. (1 working + 1 standby)
Air Grids in the Equalisation tank & MBBR tank (in UPVC / SS) with air diffusers as required-1 lot.
Chlorine Contact Tank (In M.S. Epoxy construction) -1 no.
Chlorine Dosing pump & Dosing pump -1set.
Filter Feed Tank (In M.S. Epoxy construction) -1 no.
Filter Feed Pumps (Horizontal Centrifugal -monoblock) – CI construction , 2 nos. (1 working + 1 standby)
Dual Media Filter –MSEP Vessel -1 no.
Activated Carbon Filter –MSEP Vessel -1 no.
Treated Water Storage tank (in HDPE) -2 KL capacity -1 no.
By Pass Arrangement before treated water Sump and from other units as required.
Sewage Treated Water Recirculation pump -2 nos. (1 working + 1 stand-by) of 50 LPM at 30 Mtr.)
STP interconnecting piping : MS- c-class piping for Air & UPVC – Sch 40 for Effluent & water lines connections. -1 lot
Instrumentation for Tanks water level controlling , pumps dry level protections , pressure Gauges , 2 nos. electro-magnetic flow meters, 1 no. energy meter & 1 no. Air Rota-meter – 1 lot.
Electrical Distribution panel for all STP plant drives, interconnecting cables (Armoured, Al /Cu conductors) +GI cable trays & GI earthing as required - 1 lot.
1 year STP -Operation and Maintenance is included.
Total of Sewage treatment Plant
Total Schedule D (NDSR PLUMBING Items)
Plumbing, Electrical, VAC, Fire fighting & Fire detection systems for Metro Depot of Corridor 2 at Agra
SCHEDULE - E (E&M ITEMS)
Sub Head
PART-I
TOTAL
PART-II
TOTAL
PART-III
TOTAL
PART-IV
TOTAL
PART-V
TOTAL
GRAND TOTAL without GST 18 %
Plumbing, Electrical, VAC, Fire fighting & Fire detection systems for Metro Depot of Corridor 2 at Agra
SCHEDULE E - E&M
BOQ Item No.
ELECTRICAL SYSTEM
The BOQ specified below include the latest relevent standards, specifications, drawing details and the contractor is required to go through them as referred in tender document while quoting the rates. All the samples/ material intended to be used in the works shall be subject to approval before use as the Employer's representative may opt.
The description as mentioned in BOQ, specifications, special conditions, GCC drawing and the conditions mentioned therein whichever is stringent shall be applicable, acceptable and complied with.
Sub-letting of work by the contractor shall only be permitted in accordance with Special Conditions of Contract.
The items indicating zero/RO quantity can also be operated and variation clause shall be applicable as stipulated in GCC/ SCC.
Bus Bar Sizing calculations shall be submitted for approval of Employer or his representative.
Contractor's shall quote resonably rates against each item of BOQ (both in word and figure)
Switch Boards/panels
Supply, installation, testing & commissioning of front operated front access cubical type indoor duty floor / wall / recess/ surface mounting, totally enclosed dust and vermin proof (minimum protection IP 54) panels with neoprene gaskets, fabricated from 2 mm thick CRCA sheets with powder coated finish (minimum thickness 50 micron) suitable for 415 volts 3 phase 4 wire 50 Hz system to withstand symmetrical fault level as specified as below at 415 V including interconnections, bonding to earth etc. and flush doors conforming to relevant IEC60439/IS (viz. IS 8623 etc.) standard including the earth leakage protection complete as per specification & drawings as required and as given below. All internal wiring in the panels shall be carried out using high temperature FR wires.
MAIN LT PANEL
Note: Contractor shall provide and integrate an earmarked terminal boards for SCADA signals as per specification & requirements.
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 3200 A suitable to with stand symmetrical fault level of 65 kA at 415 V. The neutral busbar is to be of same size as phases.
Two incomers & one Bus Coupler shall be interlocked electrically & mechanically so that only two out of three shall be switched on at a time.
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 3200 A suitable to with stand symmetrical fault level of 65 kA at 415 V. The neutral busbar is to be of same size as phases.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required.
MAIN EMERGENCY PANEL
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 1000 A suitable to with stand symmetrical fault level of 50 kA at 415 V. The neutral busbar is to be of same size as phases.
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 1000 A suitable to with stand symmetrical fault level of 50 kA at 415 V. The neutral busbar is to be of same size as phases.
Two Normal incomers & DG incomer shall be interlocked electrically & mechanically so that only one out of three shall be switched on at a time.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
NORMAL PANELS
WORKSHOP OFFICE MDB-N1
1 no. 630A, 415V, Ics=35 kA, TP MCCB’s with fixed neutral and with variable overcurrent and short circuit releases & each complete with
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 630 A suitable to with stand symmetrical fault level of 35 kA at 415 V. The neutral busbar is to be of same size as phases.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
WORKSHOP BAY MDB-N2
1 no. 630A, 415V, Ics=35 kA, TP MCCB’s with fixed neutral and with variable overcurrent and short circuit releases & each complete with
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 630 A suitable to with stand symmetrical fault level of 35 kA at 415 V. The neutral busbar is to be of same size as phases.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
INSPECTION BAY MDB-N3
1 no. 250A, 415V, Ics=35 kA, TP MCCB’s with fixed neutral and with variable overcurrent and short circuit releases & each complete with
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 250 A suitable to with stand symmetrical fault level of 35 kA at 415 V. The neutral busbar is to be of same size as phases.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
STABLING SHED MDB-N4
1 no. 160A, 415V, Ics=35 kA, TP MCCB’s with fixed neutral and with variable overcurrent and short circuit releases & each complete with
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 160A suitable to with stand symmetrical fault level of 35 kA at 415 V. The neutral busbar is to be of same size as phases.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
SUB-STATION MDB-N5
1 no. 160A, 415V, Ics=35kA, TPN MCCB with variable overcurrent and short circuit releases & each complete with
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 160A suitable to with stand symmetrical fault level of 35 kA at 415 V. The neutral busbar is to be 50% of phases.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
PIT WHEEL LATHE MDB-N6
1 no. 160A, 415V, Ics=35kA, TPN MCCB with variable overcurrent and short circuit releases & each complete with
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 160A suitable to with stand symmetrical fault level of 35 kA at 415 V. The neutral busbar is to be 50% of phases.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
WATER PUMP PANEL MDB
1 no. 125A, 415V, Ics=35kA, TPN MCCB with variable overcurrent and short circuit releases & each complete with
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 125A suitable to with stand symmetrical fault level of 35kA at 415 V. The neutral busbar is to be 50% of phases.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
EMERGENCY PANELS
WORKSHOP OFFICE MDB - E1
1 no. 630A, 415V, Ics=35kA, TPN MCCB with variable overcurrent and short circuit releases & each complete with
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 630A suitable to with stand symmetrical fault level of 35 kA at 415 V.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
WORSHOP BAY MDB - E2
1 no. 160A, 415V, Ics=35kA, TPN MCCB with variable overcurrent and short circuit releases & each complete with
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 160A suitable to with stand symmetrical fault level of 35 kA at 415 V. The neutral busbar is to be 50% of phases.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
INSPECTION BAY MDB-E3
1 no. 160A, 415V, Ics=35kA, TPN MCCB with variable overcurrent and short circuit releases & each complete with
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 160A suitable to with stand symmetrical fault level of 35 kA at 415 V. The neutral busbar is to be 50% of phases.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
STABLING SHED MDB-E4
1 no. 125A, 415V, Ics=35kA, TPN MCCB with variable overcurrent and short circuit releases & each complete with
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 125A suitable to with stand symmetrical fault level of 35 kA at 415 V. The neutral busbar is to be 50% of phases.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
SUB STATION MDB - E5
1 no. 125A, 415V, Ics=35kA, TPN MCCB with variable overcurrent and short circuit releases & each complete with
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 125A suitable to with stand symmetrical fault level of 35 kA at 415 V. The neutral busbar is to be 50% of phases.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
FIRE PUMP PANEL MDB
Supply, Installation, Testing & Commissioning of 2 position ATS 0f 250 amp rating with single solenoid operator, having 4P with overlapping neutral and In-phase monitor. The ATS should be UL-1008 listed or confirming to AC-33A duty as per IEC 60947 -6- etc as per drawing & specification
ON,OFF, TRIP (Each for both supply)
out going terminals for cable collection to be provided
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 250A suitable to with stand symmetrical fault level of 35 kA at 415 V. The neutral busbar is to be 50% of phases.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
STREET LIGHTING
100 amps TPN COPPER bus bars with heat shrinkable insulation sleeve (2 Sets)
The switchboard shall be complete with all inter connections, risers, internal wiring, labels etc. complete as required.
CAPACITOR PANEL
Direct cable from Main LT Panel with the following accessories
Outgoing feeders consisting of following accessories.
All MCCB’s shall be of 25 KA breaking capacity.
The switchboard shall be complete with all inter connections, risers, internal wiring, labels etc. complete as required
Addition/Deletion Items
Adjustment rates for addition/deletion of compartmentalised switchgear in above panels/board of following rating including the supply, fabrication, extension, modification of the enclosure or in a separate enclosure, earthing ,basbar, other sub-systems, accessories etc complete as required and as per specifications and as specified in of item 1.0 above
630/400A, 415V, Ics=50 kA, 4P, MCCB with variable over current and short circuit releases and 1-set of three phase indicating lamps (red, yellow, blue)
400/320A, 415V, Ics=35 kA, 4P, MCCB with variable over current and short circuit releases and 1-set of three phase indicating lamps (red, yellow, blue)
250/200A, 415V, Ics=35 kA, 4P, MCCB with variable over current and short circuit releases and 1-set of three phase indicating lamps (red, yellow, blue)
400/320A, 415V, Ics=25 kA, 4P, MCCB with variable over current and short circuit releases and 1-set of three phase indicating lamps (red, yellow, blue)
250/200A, 415V, Ics=25 kA, 4P, MCCB with variable over current and short circuit releases and 1-set of three phase indicating lamps (red, yellow, blue)
160/125 A ,415V, Ics=25 kA, TP, MCCB with variable over current and short circuit releases with heavy duty solid neutral link and 1-set of three phase indicating lamps
100/63 A, 415V, Ics=25 kA ,TP, MCCB with variable over current and short circuit releases with heavy duty solid neutral link and 1-set of three phase indicating lamps
Less than 63A to 40A, 415V, Ics=25 kA ,TP, MCCB with variable over current and short circuit releases with heavy duty solid neutral link and 1-set of three phase indicating lamps
Electrical Operating mechanism (Motorised mechanism) for all types of above MCCBs
5-32A FP MCB 10 kA
40-63A FP MCB 10 kA
5-32A TP MCB 10 kA
40-63A TP MCB 10 kA
5-32A DP MCB 10 kA
40-63A DP MCB 10 kA
5-32A SP MCB 10 kA
40-63A SP MCB 10 kA
16-32Amp DP RCCB, 30 mA
Multiple LED/neon type indications
Timer
Ammeter/Voltmeter (3.5 digit display)
TP Contractor - 40/32 Amp.
Aux. Contact 1 NO + 1NC for MCB
Supply & fixing of 200 Amp on load, four pole ATS as per relavent IEC standards with HRC fuses and indications as required, suitable for 415 V, 3 phase, 4 wire, supply with suitable MS enclosure.
Supply & fixing of 125 Amp on load, four pole Automatic Transfer Switch (ATS) as per relavent IEC standards with HRC fuses and indications as required, suitable for 415 V, 3 phase, 4 wire, supply with suitable MS enclosure.
75 HP, Star Delta starter comprising 3 Nos. TP contactor AC-3 duty Auto/Manual switch, Start Stop push button, bimetallic over current relays single phasing preventer and timer & with potential free contacts for remote monitoring and control.
50 HP, Star Delta starter comprising 3 Nos. TP contactor AC-3 duty Auto/Manual switch, Start Stop push button, bimetallic over current relays single phasing preventer and timer & with potential free contacts for remote monitoring and control.
10/7.5 HP, Star Delta starter comprising 3 Nos. TP contactor AC-3 duty Auto/Manual switch, Start Stop push button, bimetallic over current relays single phasing preventer and timer & with potential free contacts for remote monitoring and control.
Upto 5HP, DOL starter comprising 3 Nos. TP contactor AC-3 duty Auto/Manual switch, Start Stop push button, bimetallic over current relays single phasing preventer and timer & with potential free contacts for remote monitoring and control.
Miscellaneous Switchgear
Other accessories
Supply and fixing of the following safety equipments in Aux. Sub.Station/MDB room as per detailed descriptions given below and as per relevant IE rules & code of standard practice
Supply of Mandatory Tools and Spares as per clause no. 1.15 of Technical Specifications (Mandatory Tools, Mandotary Spares for Electrical, Mandotary Spares for compressor, Mandotary Spares for EOT Cranes etc.) Total Cost of These Spares and Tools has been assumed as 2% of original contract value and deemed included in the price quoted by the contractor.
TOTAL E.01 - MV SWITCHGEAR
Supply, installation, testing & commissioning of front operated front access cubical type indoor duty dead front wall / recess/ surface mounting, totally enclosed dust and vermin proof (minimum protection IP 54) panels with foamed-in neoprene gasketted hinged doors, fabricated from 2 mm thick CRCA sheet with powder coated finish suitable for 415 V, 3-phase, 4 wire, 50 Hz system including suitably rated insulated copper busbars, interconnections, neutral bar assembly, phase segregating barriers, LED indicating lamps for incoming feeders,15% spare space for future expansion, knockouts and gland plates for entry of cables and conduits, all internal wiring using high temperature FR wires, independant terminals for each phase, earthing terminals and including the cost of providing Master key lock on the door and pad locking facility on door as well as at incomer, bonding to earth etc. complete as per specification, drawings as required and as under:
Lighting distribution boards (LDB) Type-1
1 no. 32 amp DP 10 kA MCB with thermal magnetic protective releases incoming with 2 pole 40 amp HDHC tinned copper bus bar with coloured heat shrinkable PVC sleeves and 6 nos 6/10/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out goings.
Lighting distribution boards (LDB) Type-2
1 no. 63 amp DP 10 kA MCB with thermal magnetic protective releases incoming with 2 pole 63 amp HDHC tinned copper bus bar with coloured heat shrinkable PVC sleeves and 12 nos 6/10/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out goings.
Lighting distribution boards (LDB) Type-3
1-32 amp 4P 10 kA MCB with thermal magnetic protective releases incoming with 4 pole 40 amp HDHC tinned copper bus bar with coloured heat shrinkable PVC sleeves and 3 single phase banks each comprising of 1-32 amp DP 30 mA ELCBR/RCCB incoming and 4 nos 6/10/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.
Lighting distribution boards (LDB) Type-4
1-40 amp 4P 10 kA MCB with thermal magnetic protective releases incoming with 4 pole 40 amp HDHC tinned copper bus bar with coloured heat shrinkable PVC sleeves and 3 single phase banks each comprising of 1-40 amp DP 30 mA ELCB/RCCB incoming and 6 nos 6/10/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.
Lighting distribution boards (LDB) Type-5
1-40 amp 4P 10 kA MCB with thermal magnetic protective releases incoming with 4 pole 40 amp HDHC tinned copper bus bar with coloured heat shrinkable PVC sleeves and 3 single phase banks each comprising of 1-40 amp DP 30 mA ELCB/RCCB incoming and 8 nos 6/10/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.
Lighting distribution boards (LDB) Type-6
1-63 amp 4P 10 kA MCB with thermal magnetic protective releases incoming with 4 pole 63 amp HDHC tinned copper bus bar with coloured heat shrinkable PVC sleeves and 3 single phase banks each comprising of 1-63 amp DP 30 mA ELCB/RCCB incoming and 12 nos 6/10/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.
Power distribution boards (PDB) Type-1
1-100 amp TPN 15 kA MCCB with thermal magnetic protective releases incoming with 4 pole 63 amp HDHC tinned copper bus bar with coloured heat shrinkable PVC sleeves and 8 nos 40 amps TP 10 kA MCB and 7 nos 32 amps DP 10 kA MCB with thermal magnetic protective releases out goings.
Power distribution boards (PDB) Type-2
1-125 amp TPN 25 kA MCCB with thermal magnetic protective releases incoming with 4 pole 125 amp HDHC tinned copper bus bar with coloured heat shrinkable PVC sleeves and 8 nos 63 amps TP 10 kA MCB with thermal magnetic protective releases out goings.
Lighting distribution boards (LDB) Type-8
6 WAY TPN with Timer on 2-phases
1-40 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with
1 single phase bank comprising of 1-40 amp 30 mA DP ELCB incoming and 6 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out goings
2 single phase banks each comprising of 1-40 amp 30 mA DP ELCB incoming with 32 amp ON position latched contactor and 24 hours programe timer for operation of incoming and 6 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out goings
TOTAL E.02 - DISTRIBUTION BOARDS
The Cable and Cable Containment System specified herein, must confirm to technical Specifications, in addtion to the description given in respective items of BOQ, whether explicitly specified or not. In case of contradiction between specifications and description in BOQ, the most stringent of the condition will apply.
It may be noted that Contractor will be required to carry out cable sizing based on actual cable lengths, as per Working Drawings developed by him and after incorporating any changes in load requirements from the tendering stage. Optimisation must be carried out during cable sizing to reduce the cable requirement and size. Further, Contractor must obtain Engineer's approval on the Cable SIzing Calculation.
Cable Laying in cable trays, walls etc
Supply, laying, testing and commissioning of 1100 V grade, armoured, FRLSH, XLPE, aluminium(AL) / Copper (CU) conductor cables on existing trays/walls/columns/ indoor including the cost of supports with suitable clamps, saddles, hooks, bolts etc. & in ground/trenches including the cost of proper dressing of cables, markers providing identification tags, sand filling etc. (cost of excavation, sand & bricks, included here) earthing of glands armouring etc. complete as per specifications as required and as below.
Cable jointing and termination of cable as per item 1.1 -including cost of supplying and fixing, crimping lugs, double compression brass glands, insulation tape etc. complete as per specifications and as required.
Supply, laying testing and commissioning of 1.5 sqmm 1100 V grade, armoured, FRLS PVC insulated, FRLS PVC sheathed copper conductor cables on existing trays/walls/columns/ indoor/ trenches including the cost of supports with suitable clamps, saddles, hooks, bolts etc. and including the cost of proper dressing of cables and including the cost of providing identification tags etc. complete as per specifications, as required and as below.
Note : Termination of all control cables to be provided under the above item and as per schematic diagram including the cost of supplying and fixing crimping lugs, compression type brass glands, heavy duty ferrules, insulation tape etc. complete as per specifications and as required
Supply and laying of 4 pair Cat-5e cable complete as required in heavy guage GI conduit.
Cable Trays & Raceways
Supply, fabrication & installation of perforated hot dipped galvanised double bended cable trays from 2 mm thick GI sheets continuously connected including horizontal and vertical bends, reducers, tees, and other accessories and duly suspended from the ceiling with 12 mm dia vertical GI rods supported by 40mm x 40 mm x 5 mm GI angle etc. (or installed on wall supported on suitable brackets as required) complete as per specifications, as required and as below.
Note: Trays shall be supported adequately at minimum 1 m distance from the building structure / ceiling by means of painted / galvanized (as specified) MS structural members secured to the structure by dash fasteners or by grouting. This support should be capable of withstanding the weight equivalent of 3m length of the cables that can be laid in the trays. At turns the support has to be double and at both ends of the bend.
Cable Trays - For LT Cables
Cable Trays - For Systemwide Cable Trays
Note: Fllowing requirement shall be as per Systemwide contractors & therefore certain quantity have been assumed.
Supply and fixing of additional length of MS rod hangers duly painted with 2 coats of spray paint for supporting the Cable Trays, complete for extension of the supports as in above item. The rate shall be proportionately applicable to the length of rod actually required.
Note : GI suspenders and necessary anchor fasteners or any other fabricated G.I. item of any size as approved is included in this item and shall not be paid separately
Note : GI suspenders and necessary anchor fasteners or any other fabricated G.I. item of any size as approved is included in this item and shall not be paid separately
Supply, installation and testing of sheet steel raceways in floor, fabricated from 2.0 mm thick GI with minimum coating thickness 260 gm / sq. meter on both sides with removable cover plate complete with counter sunk cadmium plated brass screws, bends, tee-junctions, cross junction etc. rendered electrially continous as approved and of following sizes
Supply and fixing pregalvanized factory fabricated GI ladder type cable trays, with radial bends, supports of the following sizes as per specifications
Runners 20 x 75 x 20 x 2.5 mm
Rungs 20 x 30 x 20 x 2.5 mm 250 mm C/C
Suspenders 25 x 25 x 4 mm angle 1800 mm C/C
Runners 20 x 75 x 20 x 2.5 mm
Rungs 20 x 30 x 20 x 2.5 mm 250 mm C/C
Suspenders 25 x 25 x 4 mm angle 1800 mm C/C
Runners 20 x 75 x 20 x 2.5 mm
Rungs 20 x 30 x 20 x 2.5 mm 250 mm C/C
Suspenders 25 x 25 x 4 mm angle 1800 mm C/C
Providing 2 hour fire rating with PROMASEAL Bulkhead Sealer system as per IS1530:Part 4 and BS: 476 Part 20 to seal the opening required to passage of cable, cable trays, ducts, MS pipes etc. through walls/slabs – Comprising of one layers of 100mm thick, 120kg density rock wool panels tightly sealed and coated with 1 mm of PROMASEAL Bulkhead Sealer. The layers of coating is also extended to 50mm into the adjoining wall/slabs and 100mm on cables to achieve 2 hour fire rating as per BS: 476 part-20: 1987. All the Joints are filled with Promaseal An Acrylic Sealant.
TOTAL E.03 - MV CABLING
Whether explicitly stated in the schedules below or not, the following must be complied with:
Supplying all materials, storing, handling, fixing, laying wiring and testing for light, fan, exhaust fan and 6A Socket points etc starting from the point control box to the point by using 2.5 sq.mm 1100 volts grade FR stranded copper conductor in concealed GI Stove enamelled 16 gauge conduit including 2mm thick GI boxes, fan regulator boxes, together with wiring accessories such as 6A moulded flush mounted modular switches, sockets in boxes of suitable sizes including circuit wiring with 2 x 2.5 sq.mm 1100 volts grade FR PVC insulated stranded copper conductor along with one run of 2.5 sq.mm PVC insulated (green colour) stranded earth wire complete with earthing of fixtures, sockets and boxes. PVC bushes for conduits ends, chrome-plated brass screws, identification ferrules at either ends complete in all respects as per standard specifications.
Note: Lights, fans and 6 amps socket outlets may be wired on a common circuit, and circuit shall not have more than ten points of light, fans and 6 amps sockets or a load of 800 watts whichever is less.
Switch Controlled Primary Light Points
Point wiring for switch controlled primary light points with 3 x 2.5 sq mm (P+N+E) FR PVC insulated 660/1100 volt grade flexible stranded (50 strands of 0.25 mm dia) copper conductor wires in IS embossed 25mm dia GI recessed and/or surface conduiting system including cost of providing saddles/ hangers etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting and including the cost of supplying and fixing modular grid plate mounted flush mounted 240 volt 6 amp control switch of approved quality & colour housed in zinc chromate passivated GI boxes with moulded cover plate and including cost of circuit wiring (from DB to first switch in the sub circuit) complete as per specifications and as required.
DB/MCB Controlled Primary Light Points
Point wiring for DB/MCB controlled primary light points with 3 x 2.5 sq mm (P+N+E) FR PVC insulated 660/1100 volt grade flexible stranded (50 strands of 0.25 mm dia) copper conductor wires in IS embossed 25mm dia GI recessed and/or surface conduiting system including cost of providing saddles/ hanger etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting complete as per specifications Including cost of circuit wiring (From DB to first light point) complete as per specifications & as required (cost of MCB not included)
Point wiring for Four/three 400W highbay/250W high/medium bay light fixtures, DB controlled primary light points with 3 x 4.0 sq mm (P+N+E) FR PVC insulated 660/1100 volt grade flexible stranded (56 strands of 0.3 mm dia) copper conductor wires in IS embossed 32mm dia GI recessed and/or surface conduiting system including cost of providing saddles/ hanger etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting complete as per specifications Including cost of circuit wiring (From DB to first light point) complete as per specifications & as required (cost of MCB not included)
Secondary Light Points
Point wiring for Secondary light points with 3 x 2.5 sq mm (P+N+E) FR PVC insulated 660/1100 volt grade flexible stranded (50 strands of 0.25 mm dia) copper conductor wires in IS embossed 25mm dia GI recessed and/or surface conduiting system including cost of providing saddles/hanger etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting complete as per specifications and as required.
Secondary light points for Four/three 400W highbay/250W high/medium bay light fixtures with 3 x 4.0 sq mm (P+N+E) FR PVC insulated 660/1100 volt grade flexible stranded (56 strands of 0.3 mm dia) copper conductor wires in IS embossed 32mm dia MS recessed and/or surface conduiting system including cost of providing saddles/hanger etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting complete as per specifications and as required.
Ceiling Fan Points
Point wiring for ceiling fan points with 3 x 2.5 sq mm (P+N+E) FR PVC insulated 660/1100 volt grade flexible stranded (50 strands of 0.25 mm dia) copper conductor wires in IS embossed 25mm dia GI recessed and/or surface conduiting system including cost of providing saddles/hanger etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting and including the cost of supplying and fixing modular grid plate mounted flush mounted 240 volt 6 amp control switch and 240 volt 300 watt 5 Step electronic speed regulator of approved quality & colour housed in zinc chromate passivated GI boxes with moulded cover plate and with inter connections complete as per specifications and as required.
Exhaust Fan Points
Point wiring for exhaust fan points with 3 x 2.5 sq mm (P+N+E) FR PVC insulated 660/1100 volt grade flexible stranded (50 strands of 0.25 mm dia) copper conductor wires in IS embossed 25mm dia GI recessed and/or surface conduiting system including cost of providing saddles/hanger etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting and including the cost of supplying and fixing modular grid plate mounted flush mounted 240 volt 6 amp control switch and including cost of supplying and fixing 240 volt 6 amp socket outlet near exhaust fan of approved quality & colour housed in zinc chromate passivated GI boxes with moulded cover plate and with inter connections complete as per specifications and as required.
Air Circulator Fan
Point wiring for 16 amp socket outlets with 3 x 4 sq mm (P+N+E) FR PVC insulated 660/1100 volt grade flexible stranded (56 strands of 0.3 mm dia) copper conductor wires in IS embossed 25 mm dia GI recessed and/or surface conduiting system including cost of providing saddles/hangers etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting and including the cost of supplying and fixing of 1 No. 16A 3 pin socket outlet in 2mm thick GI enclosure controlled by one 16A SP MCB complete as required. (Outlet shall be installed at 1800mm AFFL & Controlling MCB shall be installed at 1000mm) (Cost of circuit wiring included in above item)
Wiring for Socket Outlets
Point wiring for 6 amp socket outlets with 3 x 2.5 sq mm (P+N+E) FR PVC insulated 660/1100 volt grade flexible stranded (50 strands of 0.25 mm dia) copper conductor wires in IS embossed 25 mm dia GI recessed and/or surface conduiting system including the cost of providing saddles/hangers etc as required and including the cost of cutting/making good chases in brick work and including the cost of supplying and fixing modular grid plate mounted 240 volt 6 amp 5 pin combined shuttered socket outlets alongwith 240 volt 6 amp control switch of approved quality and colour housed in zinc chromate passivated GI boxes with moulded cover plate and interconnections and including the cost of loop earthing with 2.5 sq mm FR PVC insulated 660/1100 volt grade stranded copper conductor wires complete as per specifications and as required.
Point wiring for 16 amp socket outlets (1 outlet wired on 1 circuit) with 3 x 4 sq mm (P+N+E) FR PVC insulated 660/1100 volt grade flexible stranded (56 strands of 0.3 mm dia) copper conductor wires in IS embossed 25 mm dia GI recessed and/or surface conduiting system including cost of providing saddles/hangers etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting and including the cost of supplying and fixing modular grid plate mounted 240 volt 16 amp 3 pin combined shuttered socket outlets alongwith 240 volt 16 amp control switch of approved quality and colour housed in zinc chromate passivated GI boxes with moulded cover plate with interconnections complete as per specifications and as required.(Cost of circuit wiring included in above item)
Point wiring of 16 amp socket outlets (2 outlets wired in 1 circuit) with 3 x 4 sq mm (P+N+E) FR PVC insulated 660/1100 volt grade flexible stranded (56 strands of 0.3 mm dia) copper conductor wires in IS embossed 25 mm dia GI recessed and/or surface conduiting system including the cost of providing saddles/hangers etc. as required and including the cost of cutting/making good chases in brick work and including the cost of supplying and fixing modular grid plate mounted 240 volt 16 amp 6 pin combined shuttered socket outlets alongwith 240 volt 16 amp control switch of approved quality and colour housed in zinc chromate passivated GI boxes with interconnections complete as per specifications and as required. (two switched socket outlets shall be connected to one circuit. Both the outlets shall be measured and counted as 1 units) Cost of circuit wiring included in above item.
Point wiring for 20 amp single phase socket outlets with 3 x 4 sq mm (P+N+E) FR PVC insulated 660/1100 volt grade flexible stranded (56 strands of 0.3 mm dia) copper conductor wires in IS embossed 25 mm dia GI recessed and/or surface conduiting system including the cost of providing saddles/hangers etc. as required and including the cost of cutting/ making good chases in brick work and including the cost of supplying and fixing 20 amp 10 kA "C" DP MCB and including 240 volt 3 pin 20 amp industrial metal clad socket outlet with interconnections in 16 SWG powder coated GI box and including the cost of 3 pin 240 volts plug top complete as per specifications and as required.
Point wiring for 32 amp single phase socket outlets with 3 x 6 sq mm (P+N+E) FR PVC insulated 660/1100 volt grade flexible stranded (84 strands of 0.3 mm dia) copper conductor wires in IS embossed 25 mm dia G.I. recessed and/or surface conduiting system including the cost of providing saddles/hangers etc. as required and including the cost of cutting/ making good chases in brick work and including the cost of supplying and fixing 32 amp 10 kA "C" DP MCB and including 240 volt 3 pin 32 amp industrial metal clad socket outlet with interconnections in 16 SWG powder coated MS box and including the cost of 3 pin 240 volts plug top complete as per specifications and as required.(Cost of circuit wiring included in above item)
Point wiring for 3 phase 20 amp socket outlets with 6 x 4.0 sq mm stranded copper conductor FR PVC insulated 1100 volt grade wires (3P+N+2E) 660/1100 volt grade flexible stranded (56 strands of 0.3 mm dia) copper conductor wires in IS embossed 50 mm dia GI recessed and/or surface conduiting system including the cost of providing saddles/hangers etc. as require and including the cost of cutting/ making good chases in brick work and including the cost of supplying and fixing industrial type 20 amp 10kA "C" 4P MCB and 415 volt 20 amp industrial metal clad socket outlet in 16 SWG powder coated GI box with interconnections and including the cost of 415 volts 20 amp 4P plug top complete as per specifications and as required.
Point wiring for 3 phase 32 amp socket outlets with 6 x 6.0 sq mm stranded copper conductor FR PVC insulated 1100 volt grade wires (3P+N+2E) 660/1100 volt grade flexible stranded (84 strands of 0.3 mm dia) copper conductor wires in IS embossed 50 mm dia GI recessed and/or surface conduiting system including the cost of providing saddles/hangers etc. as required and including the cost of cutting/ making good chases in brick work and including the cost of supplying and fixing industrial type 32 amp 10 kA "C" 4P MCB and 415 volt 32 amp industrial metal clad socket outlet in 16 SWG powder coated GI box with interconnections and including the cost of 415 volts 32 amp 4P plug top complete as per specifications and as required..
Point wiring for 3 phase 63 amp socket outlets with 6 x 10.0 sq mm stranded copper conductor FR PVC insulated 1100 volt grade wires (3P+N+2E) 660/1100 volt grade flexible stranded (84 strands of 0.3 mm dia) copper conductor wires in IS embossed 50 mm dia GI recessed and/or surface conduiting system including the cost of providing saddles/hangers etc. as required and including the cost of cutting/ making good chases in brick work and including the cost of supplying and fixing industrial type 63 amp 10 kA "C" 4P MCB and 415 volt 63 amp industrial metal clad socket outlet in 16 SWG powder coated GI box with interconnections and including the cost of 415 volts 63 amp 4P plug top complete as per specifications and as required..
Point wiring for weather proof 16 amp outlets with 3 x 4 sq mm (P+N+E) FR PVC insulated 660/1100 volt grade flexible stranded (56 strands of 0.3 mm dia) copper conductor wires in IS embossed 25 mm dia GI recessed and/or surface conduiting system including the cost of providing saddles/hangers etc. as required and including the cost of cutting/making good chases in brick work and including the cost of providing and fixing 2 pole 16 amp switch with 16 amp 240 volts socket outlet and plug top mounted and including a IP 56 rated surface/recessed box with the total unit having IP 56 ingress protection complete as required. (Cost of circuit wiring included in above item)
Point wiring for weatherproof 3 phase 32 amp socket outlets with 6 x 6.0 sq mm stranded copper conductor FR PVC insulated 1100 volt grade wires (3P+N+2E) 660/1100 volt grade flexible stranded (56 strands of 0.3 mm dia) copper conductor wires in IS embossed 50 mm dia GI recessed and/or surface conduiting system including the cost of providing saddles/hangers etc. as require and including the cost of cutting/ making good chases in brick work and including the cost of supplying and fixing 4 pole 32 amp switch with 32 amp 240 volts socket outlet and plug top mounted and including a IP 56 rated surface/recessed box with the total unit having IP 56 ingress protection complete as required.
Supply installation testing and commissioning of Occupancy sensor based movement detector with a build-in switch suitable for recessed mounting at a height of 3m with detection pattern of 6m X 8m. The sensor should have an operating voltage range of 230VAC +/10%; 50/60Hz and should be able to take upto 6A of electrical load and should be able to provide the switch off delay from 1 minute to 30 minutes range. The sensor should be in compliance with EN/IEC 60669-2-1, IEC (EN) 60669-2-1, IEC (EN) 61547, IEC (EN) 55015 and IEC (EN) 55022, class B.
Supply installation testing and commissioning of Occupancy based movement detector with a build-in switch suitable for surface mounting at a height of 3m with detection pattern of 6m X 8m. The sensor should have an operating voltage range of 230VAC +/10%; 50/60Hz and should be able to take upto 6A of electrical load and should be able to provide the switch off delay from 1 minute to 30 minutes range. The sensor should be in compliance with IEC 61547, IEC 61347-2-13, IEC (EN) 55015, Class B.
TOTAL E.04 CONDUIT WIRING
The Lighting System specified herein, must conform to the technical Specifications, in addtion to the description given in respective items of BOQ, whether explicitly specified or not. In case of contradiction between specifications and description in BOQ, the most stringent of the condition will prevail.
Supply, installation, testing & commissioning of light fittings including all accessories e.g. ballast, HPF condensors, lamps, holders, surface/recess mounting arrangement etc. including necessary supports, accessories and hardware as per specifications & as required at site and as below:
Compliences and approvals
RFI <30MHz --- CISPR15
RFI > 30MHz --- CISPR15
Harmonics --- EN 61000-3-2
Immunity --- EN 61547
Safety --- IEC 61347-2-13
Performance --- IEC 62384
Vibration & bump test --- IEC 60598
Quality standard --- ISO 9001
Environment standard --- ISO 14001
Approvals marks --- Safety marks
a) LEDs
Colour Rendering Index Ra: 80
Colour Temperature: 6500K/5700K/4000K
Life: In excess of 50,000 hours
Surge - 2.5kV for Indoor Luminaires /4kV for Outdoor Luminaires
Supply, installation, testing and commissioning of LED recessed mounted 2x2 luminaire with a system lumen output of 3600 lumens and a minimum system efficacy of 115 lm/W. The Luminaire shall be IP20 rated and shall have a life of 50k hours at L70. Luminaire should have CRCA housing with PS diffuser and backlit panel. Similar to Philips catalogue no. RC380B LED36S -4000 G4 L60 W60 PSU OD ( For office area)
Supply, installation, testing and commissioning of LED recessed mounted 1x4 luminaire with a system lumen output of 3200 lumens and a minimum system efficacy of 115 lm/W. The Luminaire shall be IP20 rated and shall have a life of 40k hours at L70 .Luminaire should have CRCA housing with Opal PMMA diffuser. Similar to Philips catalogue no. RC380B LED32S-4000 L120W30 PSU OD.(For office area)
Supply, installation, testing and commissioning of LED Downlighter with integrated driver and minimum system lumen output of 1300 lumens with a minimum system efficacy of 105 lm/W. The luminaire shall have a CRI greater than 80 with rated system lifetime of 50,000 hours at L70. The luminaire optics shall have a high efficiency diffuser with more than 85% transmittance. Height of luminaire shall not be more than 70 mm.Similar to Philips catalogue no. DN 393B LED 12S PSU WH and must confirm to Ingress Protection Classification of IP 20.(For Toilet)
Supply, installation, testing and commissioning of LED Downlighter with integrated driver and minimum system lumen output of 2200 lumens with a minimum system efficacy of 100 lm/W. The luminaire shall have a CRI greater than 80 with rated system lifetime of 50,000 hours at L70. The luminaire optics shall have a high efficiency diffuser with more than 85% transmittance. Height of luminaire shall not be more than 70 mm.Similar to Philips catalogue no. DN 395B LED 20S PSU WH and must confirm to Ingress Protection Classification of IP 20.(For corridor/passegess,reception,entrace lobby)
Supply, installation, testing and commissioning of LED surface mounted downlighter luminaire with a system lumen output of 1200 lumens and a minimum system efficacy of 100 lm/W. The Luminaire shall be IP20 rated and shall have a life of 30k hours at L70.Luminaire should have polycarbonate cover with diffused optics. Similar to Philips catalogue no. SM260C LED12S- 4000 PSU WH.(For Toilets)
Supply, installation, testing and commissioning of LED surface mounted downlighter luminaire with a system lumen output of 2000 lumens and a minimum system efficacy of 110 lm/W. The Luminaire shall be IP20 rated and shall have a life of 30k hours at L70.Luminaire should have polycarbonate cover with diffused optics. Similar to Philips catalogue no. SM261C LED20S- 4000 PSU WH.(For corridors/passeges,entrace lobby)
Supply, installation, testing and commissioning of 32W LED 1x4 suspended fixture, with a system lumen output of 3400 lumens with up/down lighting system. The luminaire shall have extruded aluminoium housing and light output is by means of high efficiency pmma diffuser. (Similar to Philips catalogue No.SP680P LED 34S 6500 PSU WH L120 S1 or equivalent as approved make) (For office area)
Supply, installation, testing and commissioning of surface mounted LED Batten, with a minimum system lumen output of 4000 lumens and a minimum system efficacy of 105 lumen/watt. The luminaire shall have a CRI of greater than 80 with rated system lifetime of 50,000 hours at L70 and IP protection as IP20. The luminaire is made of CRCA housing and shall have diffused optics.Similar to Philips catalogue no.BN308C LED40 NW or equivalant. (for non false ceiling equipment room)
Supply, installation, testing and commissioning of surface mounted LED Batten, with a minimum system lumen output of 2000 lumens and a minimum system efficacy of 105 lumen/watt. The luminaire shall have a CRI of greater than 80 with rated system lifetime of 40,000 hours at L70 and IP protection as IP20. The luminaire is made of CRCA housing and shall have diffused optics.Similar to Philips catalogue no.BN308C LED20 NW or equivalant. (for non false ceiling equipment room)
Supply of 20w LED PIT light with intgreal control gear made of Extruded aluminium housing comprising of White (WH) LEDs connected in series and parallel. Engg. Plastic end caps with polycarbonate cover.Driver: Constant current output driver, operating range 150 – 265V AC supply voltages.Rotatable mounting brackets provided for ease of installation with IP-67 & IK10 protection & LEDs are provided with secondary lens optics to get optimum optical performance and CCT of 5700k with a power factor PF > 0.95 to be provided & Should not less than 100 lumens. should have a ambient range from -10 Deg to 50 Deg C. should be provided for the control gear THD < 10% & having 5kV surge protection. The product should compliance for DRIVER Compliance to safety requirements Photo biological. Compliance IEC 62471 (Make:-, Bajaj CAT No. BITEAP 20W LED or equivalent). (For Inspection pit)
Supply, installation, testing and commissioning of Batten with 18W LED Tube (MASTER TLED) with a nominal system lumen output of 2100 lumens.The luminaire should have a color temperature of 6500K and CRI>80. The luminaire shall meet IP65 rating with THD < 10% and PF > 0.95. ((Similar to Philips catalogue No.TCW 450P 2 X TLED 18 W+18W MASTER TLED or equivalent as approved make). (For workshop & inspection bay platform area))
Supply, installation, testing and commissioning of surface mounted LED batten with a system lumen output of 4000 lumens and system efficacy of 100 lumens/Watt . The luminaire shall be IP65 rated (Similar to Philips catalogue No.WT201C LED40S-4000 PSU L120 or equivalent as approved make) (For workshop & inspection Bay area)
Supply, installation, testing and commissioning of surface mounted LED Bulkhead with a system lumen output of 700 lumens and a system efficacy of 105 lumen/watt. The luminaire shall be IP65 & IK08 rated and shall have a CRI of 70. The housing of luminaire is made of high pressure die cast aluminium with front cover made of polycarbonate diffuser.Similar to Philips catalogue no.WT140W LED7S NW PSU S1 PC and must conform to Ingress Protection Classification of IP 65.(For Shaft, Parapet wall)
Supply, Installation, testing and commissioning of LED highbay symmetric beam luminaire with housing made of die-cast aluminium of system wattage not more than 72W. The luminaire shall be with dedicated optics to provide precise light distribution of symmetric beam angle. The luminaire shall be designed to meet its specifications on performance & lifetime at a design ambient temperature of 45 deg C. A specially designed heat management system to ensure luminous efficacy >=102 lm/ W for the system and ensure lumen depreciation upto 30% over 50k burning hours. The luminaire is designed to meet IP 65 classification and is compliant with relevant immunity, safety and performance and EMI standards. The system lumens shall not be less than 7200 lumens with 5700K CCT. The CRI shall be > 70. The luminaire shall be able operate from 190 - 270V AC, 50Hz with > 0.9 PF & THD <=20%. The luminaire shall have an in-built surge protection upto 3kV. The LEDs shall be of SMD type (not COB type). The luminaire shall be supplied with suitable suspended / surface mounting kit. Similar to Philips: BY400V LED72S CW SY PSU S2 FG WH – Surface.
Revolving Search Light
Supply, installation, testing and commissioning of flexible LED strip with suitable no. of Electronic Driver with a system wattage of 5W per mtr. The luminaire shall be IP65 rated and shall have a CRI of 80. This shall be powered by a seperate, replaceable, constant voltage electronic driver, output short circuit protection and other safety tests. The housing of luminaire is made of flexible PCB, dual layers, 5000x10x2 mm.Similar to catalogue no.Bajaj LED Strip 5W per meter or equivalent as approved make.(For Facade Lighting)
Supply, installation, testing and commissioning of LED In Ground Uplighter with a system lumen output of 1000 lumens and a system efficacy of 90 lumen/watt. The luminaire shall be IP67 & IK10 rated and shall have a CRI of 70. The housing of luminaire is made of high pressure die cast aluminium with front cover made of toughened glass diffuser.Similar to catalogue no.BA WO 12W WW or equivalent as approved make.(For Facade Lighting)
Supply, installation, testing and commissioning of wall surface mounted (only at Jali locations) LED Linear light with a system lumen output of 1900 lumens and a system efficacy of >80 lumen/watt. The luminaire shall be IP65 & IK08 rated and shall have a CRI of 70. The housing of luminaire is made of high pressure die cast aluminium with front cover made of toughened glass diffuser.Similar to catalogue no.BA WW IN1 AS 24W WW or equivalent as approved make.(For Facade Lighting)
HIGH/MEDIUM / LOW BAY FIXTURES
Supply, Installation, Testing & commissioning of LED luminaire similar to form factor of Philips Maxoled range or equivalent as per approved make. Fixture should have a IP65 rated high pressure die cast aluminum housing using dedicated lens based optics providing beam angles of 2X30 or 2X10 degrees (based on the application height). The luminaire shall be capable of delivering a minimum nominal system lumen output of 24000 at a minimum nominal system efficacy of 110 lumen/Watt and a Color rendering index (CRI) > 80. The fixture shall be designed to ensure L70 @ 50,000 burning hours or higher. The driver shall have a power factor of at least 0.95 and a THD<10% at full load.The luminaire shall comply with requirements of CE ,CISPR 15Ed72 , IEC 61347-2-13, IEC 61547, IEC 62384. (Similar to Philips catalogue No. BY416P LED240S CW SK60 FG GR NI S5 or equivalent as approved) (For Workshop Lathe & Inspection bay )
Supply, Installation, Testing & commissioning of LED luminaire similar to form factor of Philips Durabay range or equivalent as per approved make. Fixture should have a IP65 rated high pressure die cast aluminum housing using dedicated lens based optics providing beam angles of 2X30 or 2X55 degrees (based on the application height). The luminaire shall be capable of delivering a minimum nominal system lumen output of 16000 at a minimum nominal system efficacy of 130 lumen/Watt and a Color rendering index (CRI) > 80. The fixture shall be designed to ensure L70 @ 50,000 burning hours or higher. The driver shall have a power factor of at least 0.95 and a THD<10% at full load.The luminaire shall comply with requirements of CE ,CISPR 15Ed72 , IEC 61347-2-13, IEC 61547, IEC 62384. (Similar to Philips catalogue No. BY325P LED160S CW PSU GR FG XTFCL V1 or equivalent as approved) (For Workshop Lathe & Inspection bay ) (Light fixture code-M)
Supply, Installation, Testing & commissioning of 80 W LED High Bay luminaire similar to Philips cat no. BY 325P LED 100S CW FG WB or equivalent as approved makes) Fixtures should have IP-65 rating
Supply, Installation, Testing & commissioning of 70 W LED Low Bay luminaire similar to Philips cat no. BY 150P LED 76S CW PSU HE SY120 FG GR or equivalent as approved makes) Fixtures should have IP-65 rating
Supply, installation, testing & commissioning of the following fans including fixing arrangement and with all accessories like down rods, 5 step electronic fan regulators, cover plates, cups as required for the following complete with necessary GI pipe required for hanging of the fans etc.
Ceilng fan1200 mm sweep with Electronic regulator complete with all accessories required.
Ceilng fan 1400 mm sweep with Electronic regulator complete with all accessories required.
600mm sweep Air Circulator Fans minimum of 1400 rpm, Air delivery minimum of 400 mtr cube/minute , 230 to 240 volts, 1 phase, 50 Hz complete with stand, ground, regulator, pedestal as required. Note: Air delivery shall be measured at 3.6 mtrs from fan.
Supply, installation, testing and commissioning of exhaust fan with fan guards on both sides, double ball bearings, class-E insulation, capacitor (pf 0.90 or better) complete with all other accessories as per IS 2312 and as required, of following sizes:
size 450/300mm dia, 1400 rpm
HVLS Fans
Supply, installation testing and commissioning of "High Volume Low Speed Fans Dia: 16ft, Voltage 420V, Phase: 3 phase" with all other necessary accessories including down rod of suitable length & strength as per specification.
TOTAL E.05 - INDOOR LIGHTING AND FANS
Supply, installation, testing and commissioning of the following lighting fixtures including fixing arrangement and with all accessories and lamps as required for
Supply, installation, testing and commissioning of surface mounted LED flood light with a system lumen output of 21500 lumens. The luminaire shall have a aluminium pressure die-cast housing and a minimum system efficacy of 102 lumen/watt. The luminaire shall have a CRI greater than 70 with rated system lifetime of 50,000 hours at L70. (Similar to catalogue No.BVP410 LED 215 CW HE NB FG S4 XTFCL or equivalent as per approved make) (For external area)
Supply, installation, testing and commissioning of surface mounted LED flood light with a system lumen output of 13500 lumens. The luminaire shall have a aluminium pressure die-cast housing and a minimum system efficacy of 112 lumen/watt. The luminaire shall have a CRI greater than 70 with rated system lifetime of 50,000 hours at L70. (Similar to catalogue No.BVP122 LED 135 CW HE NB FG XTFCL S4 or equivalent as per approved make) (For external area)
Supply of LED based Flood light, housing made up of pressure die cast aluminum Alloy with effective thermal management,sturdiness and embossed brand name/logo name of manufacturer. The fixture should have a minimum system efficacy of 100 lumen/Watt and a minimum system lumen output of 7000 lumens and maximum system wattage of 70 Watts.The fixture shall have a CRI of minimum 70. The fixture shall be designed for a system life of 50,000 hours @70% lumen maintenance. Ingress Protection of IP65 (lamp and gear Compartment) and Mechanical Impact Resistance Rating of IK >=05.The fixture driver should have an operating voltage range of 140-270 V, surge protection of >=3KV, PF >0.9 and THD<20%. ( CAT No. - BVP 120 LED 70 CW NB FG S3 XT or equivalent as per approved make) (For external area)
Supply, Installation, Testing and Commissioning of LED Post Top cum Street Light having Top Red Illuminated for Aesthetic & Night Lilly Appearance with a system lumen output of 3500 lumens and a minimum system efficacy of 100 lm/W, Along with 2.35M Standard Pole, The luminaire shall have a rated system lifetime of 50,000 burning hours at L70. System wattage 35W, The luminaire should have a color temperature of 5700K and CRI > 70.IK-08 The luminaire shall meet IP66 with THD < 10% and PF > 0.9. Operating Voltage 140-270VAC,The luminaire shall have closed diffused optics with polycarbonate diffuser board. The total power consumption should not exceed 27W (including driver). Similar to Make BGP400 LED35 L CW MR FG S1 or equivalent as per approved make. (For entrance area)
Supply, Installation, Testing and Commissioning of LED Bollard Light having relaxed warm white well-lit, with reduced glare having opal PC diffuser.Symmetrical light distribution.Low maintenance cost. PDC Heat sink on Top for better thermal management and Extruded aluminium body in grey powder coated. Constant current electronic driver provided with high voltage, open & short circuit protection IP65 & IK07. Similar to Make BGBOL 1000 9W LED WH - 1M FLUTE BOLLARD or equivalent as per approved make. (For entrance area)
Supply, installation, testing and commissions of External lights as per specifications and drawings complete with the following
Lighting Poles
Luminaires
HIGH MAST LIGHTING
Supply, installation, testing and commissioning of 30 M high mast system with its accessories. Mast shaft shall be of Bajaj/Philips/Keselec/Thorn, hot dip galvanised and suitable for wind velocity as per IS 875. It shall also include accessories for high mast including head frame, steel wire rope, trailing cable, double drum winch, Galvanised Lantern carriage arrangement suitable for 12 luminaires Symmetric/Asymmetric & its control gear boxes and lightning arrestor. The mast shall have an External powertool installed inside the base compartment for its operation and including following:
High Mast complete as required above
Supply, installation, testing and commissioning of 20 M high mast system with its accessories. Mast shaft shall be of Bajaj/Philips/Keselec/Thorn, hot dip galvanised and suitable for wind velocity as per IS 875. It shall also include accessories for high mast including head frame, steel wire rope, trailing cable, double drum winch, Galvanised Lantern carriage arrangement suitable for 12 luminaires Symmetric/Asymmetric & its control gear boxes and lightning arrestor. The mast shall have an External powertool installed inside the base compartment for its operation and including following:
High Mast complete as required above
Supply, installation, testing and commissioning of 12.5 M high mast system with its accessories. Mast shaft shall be of Bajaj/Philips/Keselec/Thorn, hot dip galvanised and suitable for wind velocity as per IS 875. It shall also include accessories for high mast including head frame, steel wire rope, trailing cable, double drum winch, Galvanised Lantern carriage arrangement suitable for 12 luminaires Symmetric/Asymmetric & its control gear boxes and lightning arrestor. The mast shall have an External powertool installed inside the base compartment for its operation and including following:
High Mast complete as required above
PIPES
Supply and installation of following heavy/medium grade GI pipes for cables crossing the rail tracks with all bendings complete as required
Supply, fixing and laying of HDPE pipes complete with joints including necessary excavation & back filling complete as required
Supply, fixing 150 mm RCC Hume pipes(Class NP-4) in road crossing and below paved areas complete as required including road cutting and making good the damages etc.
TOTAL E.06 - EXTERNAL LIGHTING
EARTHMAT
Note : Detailed Earth Mat BOQ has been provided by considering soil resistivity of 30 ohm-meter, Contractor have to check the value of soil resistivity before execution & in case of deviation in above said value, contractor shall subject to submit detail earth mat calculations for approval to client. After their final approval work shall subject to commenced.
Supply, laying, testing and commissioning of 25 mm dia MS rod for earth mat (at 700mm to 2000mm deep as per approved drawing and as directed) as per specifications including lap (of not less than 150mm) & cross weld joints and providing bitumin coat at every joint as required. Risers from earth mat to be brought out as per approved drawings and specifications. (Cost of risers not included in this item).
Supply, laying, testing and commissioning of 30 mm dia MS rod for earth mat (at 700mm to 1000mm deep as per approved drawing and as directed) as per specifications including lap (of not less than 150mm) & cross weld joints and providing bitumin coat at every joint as required. Risers from earth mat to be brought out as per approved drawings and specifications. (Cost of risers not included in this item).
Supply, laying, testing and commissioning of 25 mm dia MS rod, laying of vertical earth electrodes 3 m deep from earth mat including weld joints with earth mat as per approved drawings and specifications. The weld joints to be provided with bitumin coats.
Supply, laying, testing and commissioning of 30 mm dia MS rod, laying of vertical earth electrodes 3 m deep from earth mat including weld joints with earth mat as per approved drawings and specifications. The weld joints to be provided with bitumin coats.
Extra for bituminous coating and hessian tape wrap or polyetylene faced hessian complete for buried strips sizes mentioned above as per specifications and drawings as required
PLATE EARTHING
Providing and making plate earthing station including the cost of 600 mm x 600 mm x 6.3 mm G. I. plate electrode, 15 mm dia G.I.watering pipe, CI funnel with wiremesh charcoal/coke , salt, all earth work, masonry enclosure with frame,hinged cover plate having locking arrangement,Disconnecting links, complete as per IS 3043:1987 for earthing.
Providing and making plate earthing station with 600mm x 600 mm x 3.15 mm Cu plate electrode, 15 mm dia G.I.watering pipe, CI funnel with wiremesh charcoal/coke, salt, all earth work, masonry enclosure with frame,hinged cover plate having locking arrangement,Disconnecting links, complete as required as per IS3043-1987 for earthing.
EARTHING STRIPS & CABLES
Supply, Laying, Testing and commissioning of copper/GI Strips/wire for interconnecting the earthing stations ,panels,DBs etc. of the following sizes in built up trenches /surface/wall/ground complete with holes & fixing,jointing / terminating accessories as per specifications & drawing as required. (Quantity shall be paid as per the actual measurement as executed, however direct measurement shall not excced the quantity indicated in drawing approved .
Note-1: In case of non availability of any of the sizes mentioned above, next higher size available in market shall be provided at the same rate.
Note-2: No additional payment will be made for providing Main Earth Terminals (made out of GI/Cu strips from within the above sizes). The METs will required to be fixed on walls as required and will be required to be provided with 12/16/20mm holes for connections of individual equipments including of other contractors'.
Supply, Laying, Testing and commissioning of unarmoured, stranded copper conductor, FRLS grade green coloured cables of following sizes for earthing, including termination of the same by copper lugs at both ends. Note : Item have been considered for S&T clean earth requirement.
TOTAL E.07 - PROTECTIVE EARTHING
Providing and fixing Lightning Conductor Finials made of 25 mm dia 300 mm long GI tube having a single prong at the top with 85 mm dia 6 mm thick GI base plate, fixing accessories and clamping with down conductor as per specifications & drawing complete as required.
Supplying and laying of the GI horizontal & Vertical conductor of following sizes on surface/wall / parapet/ shaft complete with joints, bimetallic connectors, testing links & other fixing accessories and clamping/ connection with earth terminations as per specifications & drawing as required
25 x 3 mm thick GI tape
32 x 6 mm thick GI tape
25 x 6 mm thick GI tape
Supply and fixing testing joints made of 25 mm x 6 mm thick GI strip 125 mm long with 4 Nos. GI bolts, nuts, check nuts and spring washers complete as required.
Providing and laying of 40 mm dia minimum 3.5 meter long medium class GI pipe. CI funnel with 20 gauge GI wire mesh, masonry chamber 400 x 400 mm with concrete base. GI cover with frame, painted with bitumastic paint and packing with mixtures of charcoal and common salt around plate electrode including digging of pit and suck gilling. GI pipe electrode to be cut tapered at the bottom and provided with holes of 12 mm dia drilled no less than 75 mm from each other upto 2 meter length from bottom
Supply, installation, testing & commissioning of air craft warning lights complete with non flickering type lights similar to GEC model ZH 752 or WIPRO model no. WAN 20001 or equivalent including lamps, mounting bracket, earthing, painting complete with accessories to automatically switch off lights. (Note:Point wiring shall be done under other Item)
TOATL E.08 LIGHTNING PROTECTION
Supply installation, testing & commissioning of the following totally enclosed, dust and vermin proof Low impedance compact sandwich bus duct
Ingress protection IP 55
Indoor mounts
16 SWG sheet steel clad
EC Grade Aluminium bus bar
Operation at 415 Volt 3 phase 50 Hz system
Insulation voltage 1000 volts
Fault withstand 65 kA symmetrical for 1 second
The bus duct shall be complete with all required accessories like clamps, end covers, thrust pads, flexible connections etc. as required and including wall/ceiling mounting brackets/suspenders and including the cost of expansion joints complete as per specifications, as required and as below and suitable for operation at 415 volt 3 phase 50 Hz system.
Supply installation, testing & commissioning of copper flexible end termination/ flange joints as per sketch enclosed and suitable for bus duct connections from Top/ Bottom of switchgear panels/ equipments and of the following current ratings compatible with the bus ducts as per Item 1 above complete as required.
TOTAL E.09 - COMPACT SANDWICH TYPE BUS DUCT
Supply of 25KV AC OHE (Presence / Absence Indicator for Inspection Bay, Interior Cleaning). Make : SAMADHAN SYSTEM Kolkata , Model :SS 402 OR EQUIVALENT
Erection of 25KV AC OHE (Presence / Absence Indicator for Inspection Bay, Interior Cleaning)
Supply, testing and commisioning of 1100 Volt grade , 1.5 sq mm, 3 core FRLSH copper cable conductor(armoured)
Laying and fixing of conductor cables on existing cable trays/ wall with heavy GI clamps with base and provide the cable tags / cable / route marker at both end of cable. 1100 volt grade 1.5 sqmm, 3 core FRLSH copper cable conductor (armoured).
Supply and fixing of 50mm x2 mm MS angle with fasteners.
TOTAL- E.10 OHE ON OFF INDICATOR
Note : Conduiting has been assumed for Telephone/Data Points through out the Depot. Requirement shall be confirmed by S & T Contractor.
CONDUITING AND GI SLEEVES FOR TELEPHONE SYSTEM
Providing and fixing in position the following 16 gauge GI Conduit concealed or exposed as called for including all accessories i.e. bends, junction boxes, of approved make and design.
Providing and laying of following medium class GI pipe including all fixing accessories concealed or exposed as called for :
TOTAL E.11 - CONDUITING AND GI SLEAVES FOR TELEPHONE, LAN & PA SYSTEM
Supply, Installation, testing and commissioning of the access control system based on the following components including but not restricted to gold plated connecting leads, connectors, jumpers, nuts, screws, bolts, mounting plates, cover plates, back boxes etc and as required to make the system complete and operational in all respects complete as per specifications and as required
Recessed/Surface mounted Networkable multiprocessor controlled 2 reader controller capable of controlling multiple readers (IN/OUT) with inbuilt trouble-shooting indications on front panel, memory buffer, power supply and 3 hours battery back-up alongwith TCP/IP connectivity complete as per detailed specifications and as required
4 reader controller - 100 mm Read range Contactless smartcard readers as per tender specification suitable for mounting on metal surface/metal frames or wooden frames wall or as required based on site conditions including all accessories, complete as required
100Mm Read range Contactless smartcard readers as per tender specification suitable for mounting on metal surface/metal frames or wooden frames wall or as required based on site conditions including all accessories, complete as required
100Mm Read range Contactless smartcard readers with Keypad as per tender specification suitable for mounting on metal surface/metal frames or wooden frames wall or as required based on site conditions including all accessories, complete as required
Recessed/Surface mounted Electromagnetic Locks suitable for glass/ wood doors capable of withstanding a minimum force of 600 lbs complete as per specifications and as per models specified:
Recessed/Surface mounted Push to Exit button mounted on stainless steel plate complete as per specifications
Recessed/Surface mounted Emergency Glass Break Door Release Switch Unit for Manual Override of reader controlled fire exit doors complete as per specifications and as per models specified
Recessed/Surface mounted Panic Sounder for access controlled doors complete as per specifications and as per models specified
Blank faced Smart Cards complete as per specifications and as per models specified
Printing of Sticky Photo ID for the Proximity cards( Multi color variable data for both sides - front & back) complete as per requirements of the Client and as required
Neck Lanyards with printed logo/name and card case as per requiremens of the Client and as required
Supply, installation & commissioning of Access Management Software with networked multi-user option/client & server configuration complete as per specifications and as required and including cost of PC as required. Software to be interfaced with time and attendance management software and to be suitable to interface with the Client's existing access management system. (Please indicate nos of clients softwares being provided) (Minimum recommended configuration of PC to be included in the price is detailed below)
PC with Intel Pentium 4 3.0 Ghz or above, 120 Gb SATA 10000 rpm HDD, 512 Mb RAM, 128 Mb Graphics Card, 1.44" FDD, DVD-Dual Layer Writer, Keyboard, Mouse, 3-USB Ports, 2-Serial Ports, 1-Parallel Port, 1-10/100/1000 Mbps Network Card and 17" Flat Panel Monitor
Desk Jet Printer A3 size ( Model HP 1225C)
Supply, installation, testing and commissioning road barriers of 4 m width alongwith vehicle loop detectors and accessories mentioned in the tender specification.
Supply, installation, testing and commissioning of card operated road barriers of 2 m width alongwith vehicle loop detectors and accessories mentioned in the tender specification.
Supply, installation, testing and commissioning of Half height , tripod turnstile gate as per tender specification.
Supply , laying , testing and commissioning of the cables (all cables whichever will include in access control system) in prelaid GI conduits/cable trays/ducts etc (by electrical contractor) with all accessories including glanding and termination. Quoted price shall be considering cabling for each door including that from card reader, push button, between controllers, door strike and magnetic contact.
TOTAL E.12- ACCESS CONTROL SYSTEM
Design, Manufacture & Supply of Silent DG set (as per latest CPCB norms) (Radiator cooled - cooling system designed for 50°C ambient of following aggregate capacity / rating. Comprising of Diesel Engines coupled to alternator both mounted on common base frame suitable for 3- phase, 415 volts 50 Hz 1500 RPM, Standby power rated output with other standard accessories i.e. Fule tank (990 Litres) with necessary medium class M.S. fule piping (25 mm size) with necessary fittings from DG set to Fule Tank, automotive batteries with leads as per manufacturer recomendations. DG sets along with AMF Panels shall be sutible for auto starting & auto synchronising with auto load sharing and remort monitoring & control arrangement compatible with the existing electrical system as per particular specifications complete as required.
Suitable number of silencers per DG set along with the insulation / aluminium cladding for sound attenuations as per specifications.
Supply of suitable rubber mat in front and back of DG control panel ( AMF panel) isolation panel as per latest standards (is:15652:2006) ammended upto date.
Detailed Maintenance & Operation manuals to be supplied after 3 months of Date of vendor approval of DG sets complete as per specifications.
Power Cableing / Control wiring, its termination inside the DG set from atternator to the DG isolation panel if any will be on part of the DG set contractor ( no separate measurements will be made).
Power Cables from the DG isolation Panel to the DG power Panel ( in scope of E&M contractor) shall be supplied and laid by E&M contractor. Necessary interfacing for the same with E&M contractor shall be done by DG set contractor for evacuation of 100 % of output power . Nothing extra shall be payable for the same. However, control cabling from DG set and its load management cum synchronising Panel with DG Power panel shall be in the scope of DG set contractor.
Installation / Erection, Testing & Comissioning including integrated Testing with all systems for the DG sets along with all accessories for the following Capacity DG sets complete as per specifications as required.
Exhaust System
Supply, installation of following sizes of MS Piping for Exhaust system as per IS: 3589 and 1239 (part-I) including providing suitable bends, reducers etc.
Supply, installation, testing and commissioning of 75 mm thick Rockwool LRB mattress insulation (of 150 Kg/M³ density) over the exhaust pipes of following diameter including cladding with aluminium sheet of 24 SWG and covering from outside complete as required suitable for DG exhaust pipe temp upto 450°C etc.
Supply & fixing of miscellaneous structural support for horizontal / vertical exhaust pipe including fabrication, hardwares and painting as per requirement
Portable Oil Filling pump Electrical Type necessary to deliver the oil upto height of 10 mtrs.
Providing & fixing of pre fabricated 22SWG GI sheet ducting (120 gsm galvanisation) for hot air discharge / supply air intake complete including support , bends, flange etc. as required.
TOTAL E.13 - DG SET
Design, manufacture, supply, installation, testing and commissioning of Electric Overhead Travelling Cranes with Gantry rail and Downshop leads to be installed in the Workshop bay, Inspection bay and other maintenance buildings like Emergency Train Unit (ETU) building. The location of cranes in the various buildings is shown in drawings complete as per below (There shall be one Downshop lead of adequate capacity for 2 cranes)
TOTAL E.14 EOT CRANES
Supply, installation, testing and commissioning of plug-in type Intelligent adderasable analogue multi criteria detectors above false ceiling/True Ceiling/below false ceiling/false floor including the cost of base plate, 75 mm dia M.S. outlet box for fixing of the detector base, mounting accessories etc. complete as per specifications and as required.
Supply, installation, testing and commissioning of plug-in type addressable analogue multi critical detectors below false ceiling/false floor including the cost of base plate, 75 mm dia M.S. outlet box for fixing of the detector base, mounting accessories etc. complete as per specifications and as required.
Supply, installation, testing and commissioning of plug-in type rate of rise cum fixed temperature addressable analogue Heat detectors including the cost of base plate, 75 mm dia M.S. outlet box for fixing of the detector base, mounting accessories etc. complete as per specifications and as required.
Supply, installation, testing and commissioning of '6" Loop (750 Detectors, 400 Devices) (Fire Alarm Capability: 1 Loop x 99//125/150 detectors/ devices) wall recess mounting microprocessor based analogue addressable Fire Control Panel expandable by minimum 2 additional loops (Fire loop shall be closed type) with minimum 80 character LCD display, 4 access levels, 1000 events historical logging, flash E-PROM, 240 volts ac power supply, automatic battery charger, 24V SLA batteries suitable for operating the entire system including the talk back units and the hooters/strobes for a minimum of 4 hours in battery condition. The Panel shall have suitable power amplifiers for hooter/strobes. The Panel shall be capable of being Integrated with the BMS System and shall include cost of supply and installation of any additional modules or interfaces required for the same. The panel shall be complete of being Integrated with the BMS System and shall include cost of supply and installation of any additional modules or interfaces required for the same. The pannel shall be complete as per specifications and as required.
Supply, installation, testing and commissioning of Repeater panel including the cost of mounting accessories complete as per specifications and as required
Supply installation testing and commissioning of dust and vermin proof addressable analogue Manual Call Boxes to initiate audio visual alarm including the cost of mounting accessories complete as per specifications and as required.
Supply installation testing and commissioning of addressable analogue Talk Back jacks with face plates for Fireman's Handsets to initiate audio conversation with Main Fire Alarm Panel including the cost of mounting accessories complete as per specifications and as required.
Supply, installation, testing and commissioning of Wall/ Ceiling mounting hooter cum speaker with strobe/flasher for visual indication including the cost of mounting accessories complete as per specifications and as required.
Supply, installation, testing and commissioning of Control Modules including the cost of mounting accessories complete as per specifications and as required.
Supply, installation, testing and commissioning of Monitor Modules including the cost of mounting accessories complete as per specifications and as required.
Supply, installation, testing and commissioning of Fault Isolator Modules including the cost of mounting accessories complete as per specifications and complete as required.
Supply installation testing and commissioning of two way Talk Back handsets to initiate audio interface complete as required.
Supply, installation, testing and commissioning of wall or ceiling mounted 240 Volt AC illuminated double sided pictorial exit signs provided with appropriate direction arrow painted in green on white with an 11W CFL Lamp including the cost of in-built rechargeable batteries with charger suitable for 90 minute operation and including the cost of accessories for surface/ recessed or ceiling suspended mounting complete as required.
Supply, installation, testing and commissioning of Response Indicator Lamp assembly in a dust tight sheet steel enclosure as per detailed specifications including accessories for recess mounting as per approved sample as required.
Supplying, Laying, Termination, Testing &Commisioning of Fire Survival Cables (confirming to BS: 7629 and specifications for perfomance requirements of Fire Survival Cables) armoured, 1 twisted pair 1.5 sq.mm, screened / shielded copper conductor cable complying the CWZ category for looping of detection units along with necessary conduits and accessories etc. ( For loop Control )
Supplying, Laying, Termination, Testing &Commisioning of Fire Survival Cables (confirming to BS: 7629 and Section specifications for perfomance requirements of Fire Survival Cables) armoured, 1 pair 2.5 sq.mm, screened / shielded, Copper conductor cable complying the CWZ category along with necessary accessories. ( for power )
Supplying, installing, testing and commissioning of following sizes 16 guage GI conduits recessed/surface as required including clamps, hardwares etc required for conduiting arrangement complete as per specifications. (Quoted price shall include GI flexible conduits to connect from ceiling to false ceiling)
Supply, laying, testing and commissioning of 4 pair 2.5 sqmm screened copper armoured cable for outdoor use complete with providing sand cushioning brick protection etc.
Supply, laying, testing and commissioning of 4 pair 2.5 sqmm screened copper armoured cable in existing cable trays complete as required.
Supplying , laying , testing and commissioning of 6 core 2.5 sqmm copper armoured cable for outdoor use complete with providing sand cushioning and brick protection etc.
Supplying, laying, testing and commissioning of 50 core 1.5 sqmm copper conductor armoured cable for outdoor use complete with providing sand cushioning and brick protection etc.
PUBLIC ADDRESSING SYSTEM - FOR FIRE
Supply, installation, testing and commissioning of Wall/ Ceiling mounting 6 Watt Hooters cum speakers and Line Matching Transformer of minimum required db at 10 M distance as per NFPA guidelines including the cost of mounting accessories complete as per specifications and as required.
Supplying, installing, testing and commissioning of Public Address System complete as required and with the following:
Supplying, installing, testing and commissioning of 25mm 16 gage GI conduits recessed/surface as required including clamps, hardwares etc required for conduiting arrangement complete as per specifications. (Quoted price shall include GI flexible conduits to connect from ceiling to false ceiling)
TOTAL SUM OF F.01
Providing, laying, jointing and testing in trenches the following sizes of MS class `C' (heavy class) pipes conforming to IS:1239 with accessories like fittings including tees, elbows, reducers, flanges, rubber gaskets, GI nuts, bolts and washers and providing protection to embedded MS pipes and fittings by applying pyp kote primer (@ 100 gm/sqm) thereafter wrapping 4 mm thick pyp kote (AW 4 mm) protection coating by thermo fusion process. Overlap shall be maintained at 15 mm. The application process shall be strictly according to manufacturer’s specification, inclusing necessary excavation trenches and refilling as required. (For under ground works)
80 mm dia
100 mm dia
150 mm dia
Providing, laying, jointing, testing and commissioning of following sizes of pipes conforming to IS-1239 with all accessories like all fittings (standard MS fitting with welded joint shall be used on the pipes) including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer including supporting/fixing the pipe on floor / wall /ceiling with clamps, hangers (using anchor fastners) or angle iron support work in trenches as per specification. G.I. pipe sleeve of suitable higher size shall be provided wherever the pipes are crossing the walls/floors and sealing the sleeves with glass wool in between & fire sealent compound at either end all as per Project Manager’s / Consultants requirements including cutting holes and chases in brick and making good the same to original conditions complete in all respects. (For above ground works)
All hangers, clamps, brackets etc. shall be of galvanized iron unless specified otherwire and then supply of the same shall also be included for rates under this head. Including two coats of synthetic enamel paint of approved shade over a coat of primer. Prior to application of primer the surface should be cleaned for any dirt, rusts, rough substance etc. Including painting of legends both direction arrow as per the approval of the Project Manager.
Welding of any kind on the galvanized support / hanger shall not be permitted.
25 mm dia
32 mm dia
40 mm dia
50 mm dia
65 mm dia
80 mm dia
100 mm dia
150 mm dia
200 mm dia (6 mm thick)
250 mm dia (6 mm thick)
Providing & fixing stainless steel fire hydrant single landing valve with 80 mm NB flanged inlet, SS-304 spindle controlled 63 mm dia female instantaneous outlet type. SS coupling, blank cap, chain, twist release type lug & all accessories Conforming to IS standards. Including flanged tapping from wet rise complete as required.
Single Landing Valve (For Internal & External Hydrants)
Providing & fixing swinging type First Aid hose reel in red colour drum with 45 mts long and 25 mm dia heavy duty rubber water hose, 25 mm dia ball valve, terminating with SS coupling & nozzle of 6 mm outlet with shut off valve confirming to IS 8090 - 1976 complete with SS socket for tap-off, drum and brackets (including painting) for fixing on wall with anchor fastner, bolts & nuts conforming to IS:884-1969 complete as required. Note- Hose reel drum to be connected with main fire pipe through MS pipe.
Providing & fixing controlled RRL fire hose pipe (as per IS:636) of 63 mm dia and 15 meter length rated for brust pressure of 35.7 Kg/sqcm. Hose shall be complete with ISI marked S.S male & female coupling (IS:903) bound & riveted to hose pipe with copper rivets & 1.5 mm copper wire.
Providing and Fixing stainless steel 63 mm dia instantaneous pattern branch short pipe, 20 mm dia nozzle conforming to IS 903, suitable for inter connection to hose pipe coupling complete as required.
Constructing masonry chamber 90x90x120 cms inside with 75 class designation brick work in cement mortar 1:5 (1 cement : 5 fine sand) for valve with 560 mm dia. SFRC Manhole cover with frame (Heavy duty) and R.C.C. top slab 1:2:4 mix (1cement:2 coarse sand : 4 graded stone aggregate 20 mm nominal size) necessary excavation foundation concrete 1:5:10 mix (1 cement : 5 fine sand and 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1cement :3 coarse sand) 12 mm thick finished with a floating coat of neat cement complete as per standard design with FPS bricks.
Providing & fixing Gun Metal fire brigade connection consisting of 4 No. 63 mm dia instantaneous type male couplings with built-in check valves, 1 No., 150 mm dia flanged outlet complete with bolts, nuts and rubber insertions as required and as per IS standards
Providing & fixing Gun Metal fire brigade suction hose coupling (draw-out connection) with nut for female coupling as per IS standards complete with 100 mm dia GI suction pipe and 100 mm dia foot valve (to be connected to static tank). Provision of GI drop pipe and foot valve shall be made in all the fire water static storage tanks (2 No) (GI pipe to be paid separately through appropriate item while cost of foot valve to be included).
Providing & fixing Stainless steel cabinet (to enclose FB connection,draw off connection & for external hydrants) fabricated from 16 g sheet with full front glass door and locking arrangement duly painted with one coat of primer and two or more coats of synthetic enamel paint of approved make and shade and suitably mounted on a raised masonry platform as required (Approx 0.75m x 0.6m x 0.25m)
Providing and fixing single acting air valve with screwed inlet 20 mm dia.
Providing and fixing Gate Valves of the following sizes (conforming to BS: 5154 and Section E 30 of the M & W Specifications) having Bronze body conforming to BS 1400 with screwed ends suitable for pressure rating of 16 bars.
25mm dia
32mm dia
40 mm dia
Providing and fixing pre fabricated 4 mm thick glass door (with SS frame) of size 2.1 m x 0.9 m with center opening for fire hose cabinet suitabely marked on the outside with the letters "FIRE HOSE" including locking arrangement suitable to accommodate 1 no Hydrant landing valves, 1no fire hose reel, 2 nos.15m long 63mm dia hose pipe,1 no branch pipe, 1no. fire man's axe and 2 nos fire extiguishers. All SS work to be in Red P.O. colour over appropriate primer.
Supplying and fixing of surface type stainless steel Fire hose cabinet of Size 1800(H)x1200(W)x600(D) mm made of 12G SS thick with 6mm thick glazed glass double flap hinged doors including necessary locking arrangement suitable to accommodate 1 no. 63 mm dia Single headed landing valve, 1 no. first aid hosr reel with 25 mm dia,45 m long thermoplastic hose, 2 nos 63 mm dia synthetic hose pipe 15 m long,1 no.branch S.S. Pipe.
Supplying and fixing of hose cabinet fabricated from of size 900 mm x 600 mm x 450 mm made of 3 mm aluminium sheet with 6 mm thick glazed glass doors i/c necessary locking arrangement suitable to accommodate external hydrant with butter fly valve, 2 Nos.15 mtr. Long Hose pipe, 1 No. branch pipe, mounted on wall OR raised brick platform 600mm in height built in brick masonary in cement mortat 1:5, 12mm thick plaster on all sides and finished with existing/ proposed external finish & duly painted with Post office red externally and white internally with synthetic enamel paint completein all respect, for external hydrants, as required.
Providing and fixing dial type pressure gauge with isolation cock and pipe.
Dial diameter 100 mm caliberation 0-15 kg
Providing & fixing CI butterfly valve of pressure of pressure rating of PN 1.6 . Including rubber gasket, flanges, nuts, bolts, washers & painting complete as required.
50mm dia
65 mm dia
80 mm dia
100 mm dia
150 mm dia
200 mm dia
250 mm dia
Providing & fixing dual plate CI wafer type Double Plate check valve tested to a pressure of 16 Kg/sqcm. Including rubber gasket, flanges, union, nuts, bolts, washers & painting complete as required.
65 mm dia
80 mm dia
150 mm dia
Designing, providing and fixing Orifice plate made out of stainless steel plate (thickness as per specification) for 80/100/150 mm dia. pipe to reduce pressure upto 3.5 Kg/sqcm complete in all respects.
Providing and fixing standard firemans axe with heavy rubber handle.
Providing and laying non-pressure NP2 class (light duty) R.C.C pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc.complete.
250 mm dia. R.C.C pipe
Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all-round R.C.C pipes including bed concrete as per standard design.
250 mm dia. R.C.C pipe
Providing & fixing brass quartzoid sprinklers (UL approved) of 15 mm dia size, suitable for sustaining the pressure on the seat & water hammer effect. The type & temperature rating shall be as follows :
Spray recessed (adjustable) without rossette (ss) (68 deg.C) standard sprinkler (Pendant / Upright Type)
Supplying 15 mm size quartzoid bulb type sprinklers ,of rating 68 degree C. pendent / upright with required accessories. (spare)
Providing and fixing inspector's test assembly complete with test value, sight glass sectional drain valve union with corrosion resistant orifice all complete
Providing and fixing installation valve with turbine type automatic alarm to be connected with control valve drain and test valve as per manufacturer's design.
150 mm dia.
Providing and fixing electrically operated Flow indicating switches including 1.5mm thick gasket, nuts and bolts etc.
For 80mm to 150mm dia pipes
For 50mm dia pipes
For 25mm dia pipes
Supply, installation, testing and commissioning of electrically driven multistage, single outlet high pressure centrifugal type fire hydrant /sprinkler pump, suitable for automatic operation consisting of the following:
Common base plate for (a) and (b) from M.S. Channel for required size.
Supply, installation, testing and commissioning of Jockey pump (pressurisation pump) comprising of the following:
Common base plate for (a) and (b) from M.S. channel as required size.
For pump defined above & of duty as follows :
Flow : 180 LPM
Head : 70/88/90 MTRS
Providing, fixing, testing and commissioning of precharged air vessel (size 450 mm dia & 2000 mm height) for pressurization of hydrant / sprinkler system complete with adequate pressure switches (as per design/requirement) with valves to operate as per operating sequences including 25 mm dia drain valve, air release valve with stop cock on the top, 100 mm dia inlet with isolating valve duly painted from inside and outside complete as required.
Providing and fixing Cast Iron Double Flanged `Y' Type Stainers of the following sizes with nuts, bolts, gaskets etc.
200 mm dia
80 mm dia
Supply and installation of stainless steel expansion bellow
200mm dia
150mm dia
80mm dia
65mm dia
Providing and fixing carbon-di-oxide type fire extinguishers consisting of welded M.S. cylinderical body, squeeze lever discharge valve fitted with pressure indicating guage internal discharge tube 30 cms long high pressure discharge hose, discharge nozzle, suspension bracket conforming to IS:15683 finished externally with red enamel paint and fixed to wall with brackets complete with internal charge.
Capacity 4.5 Kg.
Providing and fixing mechanical foam type fire extingushers consisting of welded M.S. trolley mounted cylindrical body, squeeze lever discharge valve fitted with pressure discharge hose, discharge nozzle, trolley etc., ISI marked as per IS:13386 finished externally with red enamel paint.
Capacity 50 lit (D.G.Room)
Providing and fixing carbon-di-oxide fire extingushers trolley mounted with all accessories internal discharge tube,high pressure discharge hose,discharge nozzle, ISI marked as per IS:2878 finished externally with red enamel paint.
Capacity 22.5 kg.
Providing and fixing ABC Powder type fire extinguishers consisting of welded M.S. cylinderical body, squeeze lever discharge valve fitted with pressure indicating guage internal discharge tube 30 cms long high pressure discharge hose, discharge nozzle, suspension bracket conforming to IS:15683 finished externally with red enamel paint and fixed to wall with brackets complete with internal charge.
Capacity 6.0/5.0 Kg.
Providing and fixing fire extinguisher water type of capacity 9 litre with internal plastic lining and IS marked as per IS 940 with gun metal cap, CO2 cartridge and initial refill.
The rate shall include supply and fixing set of 4 fire buckets capacity 9liters fabricated from 24 gauge MS sheet brackets and stand for 4 buckets complete in all respects including filling of sand. These 4 buckets alongwith all accessories and stand etc shall constitute one set
TOTAL SUM OF F.02
GAS (NOVEC 1230)PANEL FLOODING SYSTEM FOR ELECTRICAL LT PANELS
Supply, fixing, testing and commissioning of Automatic linear pneumatic Tube Detection based Clean agent System for Electrical Panels ( Firetrace Tube Panel Protection System), consisting of the following components.
10 LB CAPACITY Clean agent system complete with all necessary gas ,fitting ,support ,and accessories,connected with valve.
2.5/5 LB CAPACITY Clean agent system complete with all necessary gas ,fitting ,support ,and accessories,connected with valve.
End of line adaptor
Pressure Switch
Flexible Polymer Detection Tube with all necessary fittings & supports.
Master Control Unit for connecting each system with electronic hooters and productivity input to Scada /Fire Alarm system including all necessaries +electrical wiring to make each entire system functional
Note: The items indicated above are notable items. The vendor to include all allied and implid items in required quantity at no extra cost.
TOTAL SUM OF F.03
TOTAL SUM OF F.01+F.02+F.03
VENTILATION & AIR CONDITIONING ( VAC) WORKS
Supply, Installation, testing and commissioning of Air Cooled Variable Refrigerant Volume/Variable Refrigerant Flow System suitable for R410A and 415 ± 10% , 50 Hz, AC supply. The unit shall consist of indoor units and external condensing units and other accessories as listed below complete in all respects. The unit shall be fully charged with gas and oil.
Outdoor Unit: Supply, installation, testing and commissioning of Modular type outdoor condensing units equipped with highly efficient scroll/hermetic type DC twin rotary compressors with invertor technology, special acryl precoated heat exchanger,low noise condenser fan with motor, auto check function for errors in display panel, auto address setting, as per specifications and capacities as mentioned below.
The units shall be complete with necessary mounting frames
Capacity shall be as under :
Indoor Units: Supply, installation, testing and commissioning of Ceiling mounted/Ceiling concealed type, FCU Metallic of Low/Medium/High static indoor units each complete with coil, pre-filter, corded remote controller etc. The units casing shall be of steel construction and 220 volt, 1 phase, 50 Hz, AC supply all as per specifications. CFM shall be selcted as per approved design.
The capacities shall be as follows:
Supply, installation, testing and commissioning of Centralized Remote controller with scheduler for operation of indoor units.
Supply, installation, testing and commissioning of Imported fittings Y-joints, distributor and headers for all Indoor units as per layout drawings.
Scheduled Timer: Supply, installation, testing and commissioning of Scheduled Timer.
VRF 4 WAY CASSETTE UNITS : Supply, installation, testing and commissioning of 4 -Way Cassette Type units each complete with coil, pre-filter,pump, corded remote controller etc. The units casing shall be of steel construction and 220 volt, 1 phase, 50 Hz, AC supply all as per specifications. CFM shall be
The capacities shall be as follows:
VRF Hi-WALL UNITS : Supply, Installation, Testing and Commisioning of indoor units complete with centrifugal blower, cooling coil (min 3/4 rows for ductable splits), air filter of efficiency 80% down to 20 microns-washable filter, & insulated drain pan all as per specifications. Each unit shall be supplied with Fire retardent Flexible connection at supply. The unit shall be supplied with min 2.0 Rmt FRLS Power cable & 3 Pin Top 6 Amp rating. Each Indoor units should have Cordless Remote Controller as a standard accessory.
The capacities shall be as follows:
Notes:
Refrigerant Piping: Supply,installation,testing and commissioning of Interconnecting refrigerant pipe work with (19mm/13mm thick) closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoor units as per specifications, all piping should be laid on Galvanised/Powder Coated tray supported by Galvanised M S Hangers & Clamps.
41.3 mm O.D. (Outer dia) (insulation : 19 mm)
34.9 mm O.D. (Outer dia) (insulation : 19 mm)
28.6 mm O.D. (Outer dia) (insulation : 19 mm)
22.2 mm O.D. (Outer dia) (insulation : 19 mm)
19.1 mm O.D. (Outer dia) (insulation : 13 mm)
15.9 mm O.D. (Outer dia) (insulation : 13 mm)
12.7 mm O.D. (Outer dia) (insulation : 13 mm)
9.5 mm O.D. (Outer dia) (insulation : 13 mm)
6.4 mm O.D. (Outer dia) (insulation : 13 mm)
Supply,installation,testing and commissioning of control cum transmission wiring of 2 core x 1.5 sqmm copper in suitable GI conduits between indoor and outdoor units.
Split Unit: Supplying, installation, commissioning and testing of Metallic body Air Cooled Split type wall mounted Air conditioners with evaporating unit comprising of cooling coil, blower with motor and condensing unit comprising hermetically sealed rotory compressor, condenser coil, propeller fan. Unit shall be with metallic body & complete with controls, interconnecting copper refrigerant piping with insulation, electrical cabling etc. (15m length included) between evaporative and condensing unit, refrigerant gas and oil. The unit shall be suitable for operating on 220 ± 6% volt 1, phase 50 cycle AC supply. The units shall be suitable for corded remote operation. The refrigerant piping & cabling shall run in PVC sleeve. Quoted price shall include cost of : Steel supporting structure for outdoor units suitable for wall mounting / floor mounting etc.Voltage stabiliser also to be provided with split AC.
Nominal capacity 1 TR
Nominal capacity 1.5 TR
Nominal capacity 2.0 TR
Providing, fixing and testing of copper refrigerant piping of appropriate sizes duly insulated with nitrile rubber insulation of 6mm/9mm thickness for all types of split AC units. The pipes plus nitrile rubber insulation are to be covered with PVC flexible conduits for protection.
12.7 mm/6.3 mm copper refrigerant pipe
15.6 mm/9.3 mm copper refrigerant pipe
Condensate Drain Piping:: Providing, fixing and testing GI Class B drain piping for condensate from unit to nearest suitable drain system as per site conditions as per instructed at site engineer complete with all required fittings and providing clean out plug at suitable location for the pipe when required complete with 6mm thick elastomeric nitrile rubber insulation over GI pipe:
32mm Dia.
25mm Dia.
TOTAL OF V.01
Supply, installation, testing and commissioning of following equipment.
Supply, installation, testing and commissioning of Propeller type fan complete with motor suitable for 220±6% volt, 1 phase, 50 Hz AC supply, mounting frames and louvers.
Size 610 mm dia - 900 RPM
Size 450 mm dia - 1400 RPM
Size 380 mm dia - 1400 RPM
Size 380 mm dia - 900 RPM
Size 300 mm dia - 900 RPM
Size 225 mm dia - 1400 RPM
Axial Flow Fans: Supply, Installation, Testing and Commissioning of axial flow fans for the following capacity. Fan shall be supplied with GI gravity louvers, bird screen and fan guard.
17000 CMH - 25 mm WG St Pr.
6800 CMH - 20 mm WG St Pr.
5440 CMH - 20 mm WG St Pr.
2500 CMH - 15 mm WG St Pr.
1200 CMH - 15 mm WG St Pr.
936 CMH - 15 mm WG St Pr.
Supplying, Installing, Testing and Commissioning of Tube Axial Flow fans with back draft gravity dampers, adjustable pitch blade, GSS/MS casing, cast aluminum alloy impeller complete with TEFC Sq. cage induction motor with class 'F' insulation , 1450 RPM, suitable for 415 volts +/- 10%, 50 Hz+/- 3%, three phase AC supply with support, mountings and flexible connection etc. & of following capacity.
13500 CFM (20 mm static pressure)
7000 CFM (20 mm static pressure)
INLINE FAN: Supply, installation, testing and commissioning of ceiling suspended Inline fans complete with Louvers,bird screen,speed regulator, rain guard, 5m length copper cable, earthing wire all compete as required of following capacities and shop drawing mentioned.
850CFM ,15mm St.Pr.
1700CFM ,15mm St.Pr.
Note:- All inline fans should be single phase supply with 3 speed regulators etc.
Supply , Installation testing & Commissioning of Air Curtain 1200mm width & door height 7 to 8Ft .Velocity 20-22 MPS
Supply, installation, testing and commissioning of synthetic fill pad type air washer at 500 FPM velocity across pads giving 90% adiabatic saturation efficiency, DIDW Class-I backward curved centrifugal fan with TEFC weather proof, High efficiency motor of IP:55 protection suitable for 415 +10% Volts, 3 phase, 50 cycles power supply, mounted on a common base , multi sleeve pulleys for fan and fan motor. The fan capacity shall be based on outlet velocity not exceeding 2000 FPM, complete with 8" thick celdek fill, 3mm thick FRP steel reinforced tank, water pump 2 Nos. (1+1), cover pipe, distribution pipe, distribution pan, filters at air inlet, water piping, make up water with ball valve, drain and overflow connection, all housed in double skin casing mounted on vibration isolators complete in all respects as per specifications.
8000 CFM with 50mm Static Pressure
18500 CFM with 50mm Static Pressure
Supplying, Installing, Testing and Commissioning of Wet Scrubber . complete with fan, double skin casing, FRP coated steel tank, DIDW centrifugal backward curved fan with V belt drive motor monoblock pumps complete with all fittings as per specification. Scrubber duct shall be in 18 G
Capacity 4500 CFM static pressure 65mm blower motor
Capacity 10500 CFM static pressure 65mm blower motor
TOTAL OF V.02
Supplying, fabricating, installing and testing of factory fabricated G.I. Sheet metal ducts with flanges complete with supports, vanes, dampers, links, levers and quadrants etc. as per specifications and drawings. The rates shall include all materials of the duct and labour for suspension and supporting arrangement for plenums, ducts, complete with fire retardant flexible connection as required and specifications.
0.63 MM (24 Gauge)
0.80 MM (22 Gauge)
1.00 MM (20 Gauge)
1.25 MM (18 Gauge)
Grilles and Dampers
Providing and fixing, testing and commissioning of G.I construction Duct Dampers for Controlling the Airflow in Ducts.
Providing, fixing, testing and commissioning of powder coated extruded aluminum sections grills
Exhaust air with dampers
Exhaust air without damper
Providing and fixing, testing and commissioning of powder coated extruded aluminium section grills with dampers for supply air terminal.
Providing and fixing, testing and commissioning of powder coated extruded aluminium section Linear grills supply/ Return air.
Providing, fixing, testing and commissioning of exhaust air/fresh air louvers of powder coated extruded aluminium construction with bird screen, minimum 80 mm deep.
Providing, fixing, testing and commissioning of duct/ wall mounted MS Fire dampers suitable with spring return type motor actuator for automatic damper operation and interlocking with Fire Alarm System Panel, 90 minute fire rating, CBRI approved as per specification.
Supplying, installation, testing & commissioning of external thermal insulation on ducts with closed cell cross linked Polythylene (XLPE) foam of density 33 Kg/m3 with 13 mm thick & thermal conductivity not exceeding 0-035 w/mk at an average temp of 40 oc. The material shall be rated as class 1 as per BS 476, part7. the smoke density as per AS-1530.3 shall not exceed 1. the material shall have fire approval fron CBRI, rorkee and no toxicity under flamming & non-flaming condition as per AITM 3.000 (1993). Adhesive used for setting the insulation shall be non-flamable vapour proof. all joints should be sealed with 3mm thick, 50mm wide PE tape & flange to be overlapped with 6" width of same material thickness. finally duct insulated should be strapped by 12mm plastic packing strip at every random meter & conforming to standard specification.
13mm thick closed cell cross linked polyethylene (XLPE) foam with factory laminated Al PE foil for supply air duct.
Supplying and fixing of accoustic lining of duct with fiber glass rigid board of density 48 kg/m3 sealed in fiberglass tissue paper and covered with 0.5mm perforated aluminium sheet & conforming to standard specification. 12mm thick fiber glass rigid board.
TOTAL OF V.03
NOTE-Roof Extractors/Turbo Ventilators shall be included in the scope of PEB Contractor.
TOTAL (V.01 +V.02+V.03)
COMPRESSED AIR SYSTEM
The BOQ specified below include the latest relevent standards, specifications, drawing details and the contractor is required to go through them as referred in tender document while quoting the rates. All the samples/ material intended to be used in the works shall be subject to approval before use as the Employer's representative may opt.
The description as mentioned in BOQ, specifications, special conditions, GCC drawing and the conditions mentioned therein whichever is stringent shall be applicable, acceptable and complied with.
Sub-letting of work by the contractor shall only be permitted in accordance with Special Conditions of Contract.
The items indicating zero quantity can also be operated and variation clause shall be applicable as stipulated in GCC / SCC.
Contractor's shall quote resonably rates against each item of BOQ (both in word and figure)
Supply, installation ,testing and commissioning of air compressor capacity 170 CFM at 10 bar with 30 KW Electrical motor 3 Phase 440 Volts complete with all accessories along with Electrical Control panel, necessary wiring , earthing,reservoir tank of 1500 litres capacity with apropriate inlet and outlet flanges designed for full rated capacity of 2 compressors etc. complete in all respects and as per specifications.
Providing MS pipes conforming to IS 1239 (Class C) complete with all fittings such as elbows, sockets, tees, unions, reducers, flanges,clamps and plugs etc with threading, jointing and making connections including cutting hole in wall/floor/slab and making good the same with cement concrete 1:2:4 complete in all respect as per specifications including painting pipe and fittings with two or more coat of synthetic enamel paint of approved quality as per pipe colour over a coat of red oxide primer outside with 1 coat of primer and 2 coats of enamel paint,complete.
100 mm dia nominal bore
80 mm dia nominal bore
65 mm dia nominal bore
25 mm dia nominal bore
20 mm dia nominal bore
15 mm dia nominal bore
Providing M.S. structural work, fabricated from standard sections eg. M.S. rods, angles channels including cutting to size, drilling holes, fixing fastener /insert plates in RCC structural members as directed by the Engineer-in-Charge including cutting and making good the walls and floors (for supports,clamps,M.S. ladders,gratings etc.)
Providing gunmetal ball valve with SS ball & teflon seats and seals inside spindle type tested to 500 psi, complete.
25 mm dia nominal bore
20 mm dia nominal bore
15 mm dia nominal bore
Wafer Type, Cast Steel, Non Return Valves, Suitable for ASA 150 flanges,.
Size 100 mm NB
Size 63 mm NB
Providing cast iron body PN 16, IS: 210 FG 220 and double flange simple operation type butterfly valve conforming to IS: 13095 with SS304 disc and shaft nitnile rubber replaceable seat of the following size complete with bolts, nuts, washers and rubber isertions as per specification.
100 mm dia
65 mm dia
Pressure Gauges, 150 mm Dial, complete with mounting nipple and isolation valve. Range 0 - 10 Kg/Cm Sq.
Auto Drain Assembly, with Solenoid Valve and Timer. Timer should be adjustable between 5 Mins to 120 Mins. Size 15 mm NB.
Providing Filter regulator 1/2" at every droplet after the ball valve suitable for 10 bar pressure.
TOTAL SUM OF M.02
Supplying, Installing, testing and commissioning of air compressor capacity 55 CFM at 10 baar with 11 KW Electrical motor 3 Phase 440 Volts complete with all accessories along with Electrical control panel, necessary wiring, earthing etc. complete in all respects as per specifications & as required nothing extra is payable
Providing and fixing MS pipes conforming to IS 1239 (Class C) complete with all fittings such as elbows, sockets, fees, unions, reducers, flanges,clamps and plugs etc with threading, jointing and making connections including cutting hole in wall/floor/slab and making good the same with cement concrete 1:2:4 complete in all respect as per specifications including painting pipe and fittings with two or more coat of synthetic enamel paint of approved quality as per pipe colour over a coat of red oxide primer outside with 1 coat of primer and 2 coats of enamel paint, complete.
50 mm dia nominal bore
15 mm dia nominal bore
Providing and fixing M.S. structural work, fabricate from standard sections eg. M.S. rods, angles channels including cutting to size, drilling holes, fixing fastenera/insert plates in RCC structural members as directed by the Engineer-in-Charge including cutting and making good the walls and floors (for supports, clamps, M.S. ladders, gratings etc.)
Providing and fixing gunmetal ball value with SS ball & teflon seats and seals inside spindle type tested to 500 psi, complete.
50 mm dia nominal bore
15 mm dia nominal bore
Pressure Gauges, 150 mm Dial, complete with mounting nipple and isolation valve. Range 0 - 10 Kg/Cm Sq.
Auto Drain Assembly, with Solenoid Valve and Timer. Timer should be adjustable between 5 Mins to 120 Mins. Size 15 mm NB.
Providing and fixing Filter regulator 1/2" at every droplet after the ball valve suitable for 10 bar pressure.
TOTAL SUM OF M.03
Supplying, Installing, testing and commissioning of air compressor capacity 21 CFM at 10 bar with 5.5 KW electrical motor 3 Phase 440 Volts complete with all accessories along with Electrical control panel, necessary wiring, earthing with Filter regulator and PU tube (10 meter) along with cleaning air gun etc. complete in all respects as per specifications & as required nothing extra is payable.
Providing and fixing MS pipes (Not more then 20 meter) conforming to IS 1239 (Class C) complete with all fittings such as elbows, sockets, fees, unions, reducers, flanges,clamps and plugs etc with threading, jointing and making connections including cutting hole in wall/floor/slab and making good the same with cement concrete 1:2:4 complete in all respect as per specifications including painting pipe and fittings with two or more coat of synthetic enamel paint of approved quality as per pipe colour over a coat of red oxide primer outside with 1 coat of primer and 2 coats of enamel paint, complete.
TOTAL SUM OF M.04
TOTAL OF M.02+M.03+M.04
Providing & fixing fully submersible sump pumps in S.S. for dewatering with 40 mm thick solid handling capacity suitable for operation on 415 ± 10% V pH 50 cycle A/C power supply & lifting arrangement.
Set of Two Pumps for Drainage (1W+1SB) p-2273
Capacity 180 LPM each
Head 8-10 Mts
Supply, installation, testing & commissioning of vertical inline multistage pumping set (Imported) with Stainless steel-316 body, Stainless steel-316 impeller, Stainless steel-304 casing, shall of Stainless steel-316 and C.I. base & head with mechanical seal, connected to a TEFC induction motor suitable for 415+1- 10% itaitS, 3 phase 50 cycles A.C. Supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating under foundations, 80x40 mm I section base plate boted to cement concrete foundations complete. Venaor to submit performance curves and technical catalogue of the proposed model for review and information.
Domestic Water Transfer Pumps to O.H. Tank at Water Supply Pump Room
Set of two Pumps ( 1Working +1Stand hy)
Capacity - 5.0 LPS
Head - 50 M (P-2179)
Irrigation Pumps at STP Pump Room
Set of two Pumps ( 1Working +1Stand by)
Capacity - 4.0 LPS
Head 40 M.
Domestic Water Transfer Pumps to Auto Coach Washing plant
Set of two Pumps ( 1Working +1Stand by)
Capacity - 7.0 LPS
Head - 40 M
Raw Water Transfer Pumps to Buildings from Pump Room
Set of two Pumps ( 1Working +1Stand by)
Capacity - 5.0 LPS
Head - 50 M
Providing and fixing horizontal monoblock pumping set with C.I. body and bronze impeller, shaft of SS-316 and M.S. base & head, mechanical seal, connected to a TEFC induction motor suitable for 400/440 volts, 3 phase 50 cycles A.C. supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads under foundations, 80x40 mm M.S. section base plate bolted to cement concrete foundations complete
Filter Feed Pumps at Water Supply Pump Room
Capacity - 5.0 lps
Head - 22 M.
Set of two Pumps ( 1Working +1Stand by)
Providing submersible pump-set as per specification with direct coupled motor rated for 3 phase, 50 cycle 415 ±10% volts. AC supply with the following cluty: (Provisional item)
Total head-100 mtr. Approx.)
Flow rate-12000 Lt/ hr (Approx)
TOTAL SUM OF P.01
Providing and fixing heavy duty PVC insulated copper armoured cables 1.1KVA grade including necessary support clamps at ceiling level and connection lugs complete in all respects.
Control cable for liquid level controller 2 core 1.5 mm2
Providing all materials and labour for supplying & fixing multi level indicator cum controller,and having the controller equipped with level monitoring systenm and phase monitoring system for automativ opeartions of various pumps & havingmulti level 4 nos. visual indications on panel with alarm system and timer including necessary cable and acknowledge facilities as per requirement and all complete as approved .providing repeater panel in control room for water level indivcations in various tanks.
Water tanks(UGT'S & OHT'S)
All above level Controllers / Indicators to be complete with sensors, switches, relays, all wiring from the sensors to the Control Unit, Control Units to Motor Control Centers of the various Pumps and to the various alarm and indicating devices.
Sensors Terminal Units would be in weather proof enclosures (minimmum IP-56).
TOTAL SUM OF P.02
Cotroller with low voltage relays, stainless steel probes and PVC shroud, wiring from tank top to probe of required length. ( No of probes as required for the function of each controller).
For Dewatering pump
To Start pump when sump is full and to stop when sump is at low level and both pumps are start when sump is overflow.
For Borewell
To Start pump when water in UG Tank at low level and close pump when water at high level in UG Tank.
For domestic water transfer to building
To cut off duty pump on low water level in the treated water tank (UGT) and higher water level in the OHT. To start pump at low water level in OHT.
For irrigation STP pump
To cut off duty pump on low water level in the treated water tank (UGT) and higher water level in the OHT. To start pump at low water level in OHT.
For domestic water transfer to auto coach
To cut off duty pump on low water level in the treated water tank (UGT) and higher water level in the OHT. To start pump at low water level in OHT.
For raw water transfer to building
To cut off duty pump on low water level in the raw water tank (UGT) and higher water level in the OHT. To start pump at low water level in OHT.
For filter feed pump.
To cut off duty pump on low water level in the raw water tank (UGT) and higher water level in the treated water tank (UGT).
TOTAL SUM OF P.03
TOTAL SUM OF P.01+ P.02+P.03
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.31 MB
Vol_04_Tech_Specs.pdf
Tender Documents • 3.44 MB
Vol_01_NIT_ITT_FOT.pdf
Tender Documents • 1.14 MB
Vol_03_Tech_ER.pdf
Tender Documents • 1.48 MB
Vol_02_GCC_SCC.pdf
Tender Documents • 1.02 MB
Vol_07_SHE.pdf
Other Document • 0.79 MB
Vol_08_Geotech_Report.pdf
Other Document • 3.76 MB
Vol06_Drawings.pdf
Other Document • 29.07 MB
Vol_05_BOQ.pdf
Other Document • 0.24 MB
BOQ_309718.xls
BOQ • 1.67 MB