| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.3 LAccepted-AOC | ₹22.3 L Quoted ₹22.9 L | L1 | Accepted-AOC Accepted being lowest bidder |
| 2 | L2₹26.5 L+₹3.6 L (15.6%)Rejected-Finance | ₹26.5 L+₹3.6 L (15.6%) | L2 | Rejected-Finance Rejected being not lowest bidder |
| 3 | L3₹27.2 L+₹4.3 L (18.9%)Rejected-Finance | ₹27.2 L+₹4.3 L (18.9%) | L3 | Rejected-Finance Rejected being not lowest bidder |
| 4 | L4₹28.9 L+₹6.0 L (26.1%)Rejected-Finance 704 SILVER DEAL DAFFODIL WING 1 B T KAWADE ROAD PUNE 411 001 | PUNE | PUNE | MAHARASHTRA | 411001 | ₹28.9 L+₹6.0 L (26.1%) | L4 | Rejected-Finance Rejected being not lowest bidder |
| 5 | L5₹32.7 L+₹9.8 L (42.6%)Rejected-Finance | ₹32.7 L+₹9.8 L (42.6%) | L5 | Rejected-Finance Rejected being not lowest bidder |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
21 Oct 2021, 6:00 pmClosed
CWE KIRKEE
Headquarters CWE Kirkee, Military Engineer Services, Range Hills Road, Kirkee, Pune-411003
REPAIR/MAINT OF HT POLES GOD/DO UG CABLE AND ALLIED WORKS AT CME UNDER GE CME KIRKEE
2021_MES_478395_1
CWE/KKE/TOKEN-19 OF 2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
CME KIRKEE
AS PER TENER DOCUMENTS
5 documents required · 5 mandatory
₹500
Yes
GE CME KIRKEE
₹80,000
Yes
18 Nov 2021
28 Sept 2021
23 Oct 2021
28 Sept 2021
21 Oct 2021
16 Oct 2021
Amount
Dismantling of old unsv ACSR/AAC conductors of any type and size and setting aside for credit to contractor complete all as specified and directed.
Dismantling and removing and setting aside for credit to contractor PCC poles any type/size by breaking PCC foundation after disconnecting electrical connection incl site clearance complete all as specified and directed by Engr-in- Charge.
Dismantling and removing and setting aside for credit to contractor steel tubular pole any type/size by breaking PCC foundation after disconnecting electrical connection incl site clearance and depositing to AGE E/M store yard complete all as specified and directed by Engr-in- Charge.
Dismantling insulators any type any size complete all as speciified and as directed.
Dismantling cross-arms of M.S. channel or angle sections etc complete and setting aside for credit to contractor complete all as specified and directed.
Supply, install erect in true vertical position steel tubular swaged welded poles complete with MS base plate of 6mm thick of size 450mm x 450mm finial taper plug pole cap bolt nut and screwed, pole made out of ERW MS tubing confirming to IS 2713 Part(I & II) of 11.0 mtr long, type 410 SP-55 including drilling of holes of required size and nos for fixing of cross arms bracing support / taking out of cables etc with inbuilt junction box for 3 phase 4 wire AC supply and painting with one coat ofred oxide primer and two coat of aluminum paint for exposed surface and two coat of black bituminous paint for the portion embeded in concerete complete all as specified and as directed. (Note : Excavation, earth work & PCC shall be measured and paid separately).
M&L for cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers welding, bending cold or hot drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat and one finishing coat of paint all as directed by Engr-in-Charge.
Supply, laying, connecting and testing in repair XLPE insulated, screened, PVC bedded galvanised steel strip armoured electric power cable (heavy duty) with stranded aluminium conductor for 11000 volts working voltage cross sectional area 3 core, 95 sqmm.
Supply, laying and testing in repair 150 sqmm, 3 core XLPE insulated screended PVC bedded galvanised steel strip armoured electric power cable (heavy duty) with stranded aluminium conductor 11000 Volts (Earthed) grade, ISI marked confirming to IS-7098 Part II complete all as specified and directed.
Supply, laying and testing in reapir XLPE insulated screened PVC bedded, galvanised steel strip/ wire armoured, electric power cables (Heavy Duty) with stranded Aluminium conductor, 22000 V grade of size 3 core 300 Sqmm complete all as specified and directed.
Supply, laying and testing in repair XLPE insulatd screened PVC bedded, galvanised steel wire armoured, electric power cables(Heavy duty) with stranded aluminium conductor, 22000V grade of size 3 core 185 sqmm complete all as specified
Supply, laying and testing in repair cable XLPE insulated screened PVC bedded galvanised steel wire armoured, electric power cables(heavy duty) with stranded aluminium conductor, 22000V grade of size 3 core 150 sqmm complete all as specified and directed
S&F in repair cable jointing kit for 11 KV (earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and directed
S&F in repair cable jointing kit for 11 KV (earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and directed
S&F in repair cable jointing kit for 11 KV(earthed) grade cable for strainght through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and directed
S&F in repair cable jointing kit for 11 KV (earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 sqmm complete all as specified and directed
S&F in repair cable jointing kit for 11 KV (earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 sqmm complete all as specified and directed
S&F in repair cable jointing kit for 11 KV(earthed) grade cable for strainght through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 sqmm complete all as specified and directed
S&F in repair cable end termination, outdoor, heat shrinkable type joint complete with jointing material and accessories suitable for 22 KV, 3 core 120 to 185 sqmm, XLPE armoured aluminium conductor cable complete all as specified and directed.
S&F in repair cable end termination, indoor, heat shrinkable type joint complete with jointing material and accessories suitable for 22 KV, 3 core 120 to 185 sqmm, XLPE armoured aluminium conductor cable complete all as specified and directed
S&F in repair cable jointing kit, straight through, heat shrinkable type joint complete with jointing material and accessories suitable for 22KV, 3 core, 120 to 185 sqmm, XLPE armoured aluminium conductor cable complete all as specified and directed
S&F in repair cable end termination, outdoor, heat shrinkable type joint complete with jointing material and accessories suitable for 22 KV, 3 core, 300 Sqmm, XLPE armoured aluminium conductor cable complete all as specified and directed.
S&F in repair cable end termination, indoor, heat shrinkable type joint complete with jointing material and accessories suitable for 22 KV, 3 core, 300 Sqmm, XLPE armoured aluminium conductor cable complete all as specified and directed.
S&F in repair cable jointing kit, straight through, heat shrinkable type joint complete with jointing material and accessories suitable for 22 KV, 3 core, 300 Sqmm, XLPE armoured aluminium conductor cable complete all as specified and directed.
S&F PCC cable route indicators with suitable reinforcement of size 50 X 20 X 10 cm with letter inscribed on both sides as "MES HT CABLE" of specified font size not less than 60 mm as directed and mounted on PCC 40x 30x30 cm complete using PCC 1:2:4 B1 using 20mm graded stone aggregate and including painting using cement based paint to the satisfaction of Engr in charge. Note :- 1. Contractor is responsible to trace the route of HT cable with the help of cable testing Van and groute the route indicator alongwith the HT Cable route. 2. Each cable route indicator will be grouted at 100 RM distance.
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; n exc 10 sq m on plan for for laying of UG cable / pole/ Stays etc getting out including forming bottom surface to required level and gradient and getting out in following :-
(a) Soft /Loose Soil
(b) Hard/Dense soil
(c) Soft/Disintegrated rock
Returning filling in including spreading, levelling, watering and well ramming in layers n.exc. 25cm in soils complete all as specified and as directed.
Removing excavated material( soil) to a distance not exceeding 50mtr and depositing where directed at a level not exceeding 1.5mtr above the starting point complete all as specified and as directed.
M&L for clean dry river sand cushioning to under ground cable in trenches 8 cm in depth before laying the cable and 15 cm in depth after laying the cable including spreading levelling hand punning and consolidating complete all as specified and directed ( Note: Thickness after punning down shall be measured and paid)
Supply and laying unreinforced precast concrete cable cover, class HV, Type I flat of size 300mm x 180mm x40mmcomplete all as specified and as directed.
S&F in repair GI tubing light grade with all fittings for protection of cable laid in trenches or fixing to pole , wall with suitable size of FI clamp including necessary fitting complete of following sizes:-
a) 100 mm dia bore
b) 80 mm dia bore
S&F in repair pin type, porcelain, vitreous, white brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150mm height, 150mm dia for 11000 volts grade complete all as specified and as directed.
S&F in repair disc type, porcelain vitreous 145 mm high and 255 mm dia ball and socket type white, brown or green insulator single disc assembly for conductors working pressure 11 KV grade complete all as specified and as directed.
S&F in repair disc Type, Porcelain, vitreous, white, brown green insulator including galvanised mild steel straps, washers, insulator bolts, washers and nuts for 22 KV complete all as specified and directed.
S&F in repair pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, for 22KV grade complete all as specified and directed.
S&F in repair lightining arresters expulsion type complete with all fittings transmission class discharge capacity 65 Kilo Amp suitable for 11000 volts complete all as specified and as directed.
S&F in repair expulsion fuse unit single pole mounted on insulator & steel frame complete with fused barrel (drop out fuse) suitable for 11 KV for current rating upto 50 Amp complete all as specifed and directed.
S&F in repair gang operated air Brake switch triple pole mechanically operated mounted on insulator & steel frame with operating mechanisam worked from ground level suitable for 11 KV for current rating upto 200 Amp of approved make with and including operating rod, GI tubing 25mm dia medium grade single piece of suitable length and insulated handle complete all as specifed by Engineer-in-Charge. Note : AB switch shall consist of three insulators per phase and 9 isolators in all.
S&F in repair lightning arresters expulsion type complete with all fittings transmission class discharge capacity 10 Kilo Amp suitable for 22KV complete all as specified and directed.
S&F in repair HT 22 KV outdoor type dropout fuses double stack channel type complete with insulator of rating up to 200 Amps complete complete all as specified and as directed.
S&F in repair gang operated air brake switch triple pole mechanically operated mounted on insulator & steel frame with operating mechanisam worked from ground level suitable for 22 KV for current rating upto 400 Amp of approved make with and including operating rod, GI tubing 25mm dia medium grade single piece of suitable length and insulated handle complete all as specifed by Engineer-in-Charge. Note : AB switch shall consist of three insulators per phase and 9 isolators in all.
M&L for bituminous road cutting to a width of 60cm and depth 90cm for laying of HT cable and making good with PCC (1:3:6) type B1(using 20mm grade stone aggregate) complete all as specified and directed.
M & L for scrapping of old painted surfaces of electric pole covered by dust and other deposited materials by cleaning from steel tubular pole of length upto 11 metres including cross arms, bracing, clamps etc and painting with one coat of aluminium paint, retaining & repainting marking on pole & replacement of reflective band of width 4 cm RED-YELLOW-RED alternate coloured 3 numbers all as specified & directed by Engr-in-Charge.
M & L for scrapping existing deteriorated old aluminium paint by hard wire brush. Painting the existing 2 pole structure by aluminium paint including cross arms, support angles, clamps and any other structural part complete all as directed by Engr-in-Charge
M & L for scrapping existing deteriorated old aluminium paint by hard wire brush. Painting the existing 4 pole structure by aluminium paint including cross arms, support angles, clamps and any other structural part complete all as directed by Engr-in-Charge
M & L for scrapping existing deteriorated old aluminium paint by hard wire brush. Painting the existing 6 pole structure by aluminium paint including cross arms, support angles, clamps and any other structural part complete all as directed by Engr-in-Charge
M & L for fault detection in damaged HT/LT UG cable by using cable fault detector/locator vehicle mounted comprising of surge generator pulse, ECHO fault locator with high frequency distance calculator etc to accuracy of 2 meter for various location inside CME for UG cables of any size any type upto 22 KV incl excavation & Earthwork in any type of stratra to usually inspect/repair the damaged cable when and where required all as directed by Engr-in-Charge. Note : (i) Complaint will be notified to contractor on mobile phone at any time and contractor is responsible to rectify the fault within 4 hrs after notification, failing which Rs. 500/- per hrs shall be recovered from contractors dues. (ii) Rates included necessary earth work in any type of strata or road for opening the cable and prepare the cable ready to jointing work and making good to match with existing finishes.
M & L for Loose filling with aggregates of broken stone gauge 40 to 80 mm in HT substation yard complete including removal of any debris etc comlpiete all as specified and as directed
S & F in repair danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25 x 20 cm size. comlpiete all as specified and as directed
M & L for scrapping existing deteriorated old paint by hard wire brush, painting the existing HT bus bar panel by aluminium paint including handles minor parts complete and any other structural part complete all as directed by Engr-in-Charge
Dismantling and taking out old unsv earthing and material & labour for earthing using copper earth plate electrode of size 60cm X 60cm X 3.15mm thick burried directly in ground vertically at a depth not less than 2.25 mtr below normal ground level with top edge of earth plate at a depth not less than 1.5 mtr below normal ground level, earth plate surrounded from all sides by 15 cm thick and packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using copper strip of size 20X3 mm by means of bolts, nuts, check nuts and washers made of GI and protected by light grade 40 mm dia galvanised iron pipe and GI pipe light grade 20mm bore for watering, including funnel, wire mesh, CI pit cover and PCC chamber pit with PCC 1:2:4 type B-2 (including necessary excavation and earth work disposal of surplus soil to a distance not exceeding 50 mtr all as specified and shown on electrical plate No 3 of SSR Part-I 2009 including testing all as directed
Dismantling and taking down old unsv earthing and M&L for earthing complete with galvanized steel plate earth electrode 60cmx60cmx6mm thick surrounded by char coal and salt buried directly in ground vertically in pit of depth not less than 2.25 mtr below ground level with top edge of the earth plate at depth of not less then 1.5 mtr below ground level surrounded from all sides by char coal dust and common salt in alternate layers of 15 cm depth and earth plate electrode connected to galvanised earth lead wire of 4.0mm dia by means of GI nuts bolts, check nuts and washers and connected to earthling test point drawn through 15mm dia GI pipe for protection of GI earth lead wire including 20mm dia GI pipe for watering GI funnel , PCC 1:2:4 type B-2 (including necessary excavation and earth work disposal of surplus soil to a distance not exceeding 50 mtr with CI frame and RCC cover all as shown in electrical Plate No 3 on SSR Part-I including testing all as directed by Engr-In-Charge.
Dismantling and taking down old unsv earthing and M&L for earthing complete with galvanized steel plate earth electrode 60cmx60cmx6mm thick surrounded by char coal and salt buried directly in ground vertically in pit of depth not less than 2.25 mtr below ground level with top edge of the earth plate at depth of not less then 1.5 mtr below ground level surrounded from all sides by char coal dust and common salt in alternate layers of 15 cm depth and earth plate electrode connected to galvanised earth lead strip of size 25X4.0 mm by means of GI nuts bolts, check nuts and washers and connected to earthling test point drawn through 40 mm dia GI pipe for protection of GI pipe including 20mm dia GI pipe for watering GI funnel , PCC earth pit (1:3:6) type C-2 with CI frame and RCC cover all as shown in electrical Plate No 3 on SSR Part-I including testing all as directed by Engr-In-Charge.
M&L earth continuity conductor or main earthing lead of size 32x6mm galvanised iron strip fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc
S&F earth continuity conductor or main earthing lead of size 20x3 mm copper strip fixed to wall with S&F of porcelin /PVC insulator buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc complete all as directed by Engr-in-Charge
Cutting of tree branches of any girth along HT OH lines at a distance not less than 2 meter on either side of the pole cleaning of bushes and shrubes of any type along entire RM of pole. Cleaning /prunning should be carried out as and when directed during entire running period of contract or as when directed by E-I-C. A fine of one time quoted rate per running metre will be deducted if the over growth is found along the pole all as directed by Engr-in- Charge.
S&F in repair aluminium conductor, steel reinforced overhead conductors (all sizes) incl copper binding wire etc complete all directed by Engr-in-Charge
Cutting of tree branches/grass at sub station compound and removal of all the wasted materials at far distance from sub station, cleaning of ducts including leveling of undulated land complete all as specified and directed by Engr -in-Charge.
Demolition of cement concrete unreinforced of any description and in any position not otherwise specially provided for all as directed by Engr-in-Charge
M & L for PCC 1:4:8 type D2 using 40mm graded stone aggregate for foundation of poles complete all as specified and as directed.
M & L for PCC 1:3:6 type C2 using 40 mm graded stone aggregate for mass filling of poles etc complete all as specified & directed.
M&L for cement concrete as in coping including necessary form work type B1 (1:2:4) using 20mm graded stone aggregate all as directed by Engr-in-Charge
Stringing/Tension adjustment for the Sag of Overhead HT Line 3 wire including guard wire to the required tension complete all as directed by Engr-in-Charge for the following :-
a) Set of three conductor
b) Guard wire with Cradle
Supply and fix in replacement HV synthetic Insulating mat (ISI Marked) of size 2m x 1m x19mm complete all as specified and directed.
Supply, install, testing and commissioning in repair of factory made outdoor type sheet metal enclosure cable jointing box CPRI & MSEDCL approved of 3 way suitable for HT 25 KV grade 3 phase 3 wire system with 09 Nos epoxy insulators and 03 Nos copper bus bar and made out of 3.15mm powder coated CRCA sheet having gasketed front hinged split doors with bottom detachable gland plate for upto 3 cable entry/exit of size upto 300 sqmm with suitable size of cadmium plated and nuts, bolts and washers and incl weatherproof, bottom hole, outdoor triple key weather proof pad lockings. The panel shall be of powder coated colour red complete all as specified and directed
S & F self-fusing Ethylene Propylene Rubber(EPR) based high-insulating voltage tape of width not less than 2.54 mm (1 inch) and thickness not less than 0.75 mm of any length to protect HT/LT XLPE cable from moisture and current leakage complete all as specified and directed by Engr-in-Charge .
M & L for highly HT insulating opaque red coloured ANTI TRACK COMPOUND SPRAY 320 of MOSIL LUBICANTS that forms flexible chemical resistant coating to class H winding for electrical apparatus, in 500 ml spray bottles to protect HT equipments, bus bar, CTs, PTs from current leakage due to moisture complete all as specified and directed by Engr-in-Charge.
M&L for spraying chemical (roundup/glycel) on area to remove unwanted vegitation/grass at various locations as directed by Engr-in-Charge. Note: (i) Labour and equipments to spray chemical on required area are incl in quoted rates. (ii) Spray will be repeated quarterly or as per direction of Engr in Charge.
S & F in repair of unsv HT 11 KV bus bar insulator of HT panel complete as per direction of Engr-in-Charge.
S & F in repair of unsv HT 22 KV bus bar insulator of HT panel complete as per direction of Engr-in-Charge.
M & L for shifting heavy items / excavating / cleaning areas / clearing site by providing crane/hydra/JCB/tractor with trolley as required at site complete all as per direction of Engr-in-Charge.
S&F in repair glow sign board box type printed on poly carbonated sheet of size 200 x 100 x 25 cm having provision of 3 x LED tube light inside the box and 10 mtrs 3 core 1.5 sqmm circular PVC connecting wire with hanging arrangment as directed by engr -in charge. Note :- Background, font size & colour and material to be printed on board shall be as per direction of Engr-in-Charge.
S&F shock treatment chart duily printed with hindi & english, fitted with woden card board of size 100 CM x60CM with hanging arrangment for installations all as directed by Engr-in charge
S&F prevention from fire chart duily printed with hindi & english, fitted with woden card board of size 100 CM x60CM with hanging arrengment for installations all as directed by Engr-in charge
M&L for fixing MS sheet chequered,of size 4 mm thick laid over cable ducts as duct cover complete all as specified.
M&L in repair for stay assembly complete with all accessories, such as stay plate 300X300X6 mm, stay rod 215 cm long and 20 mm dia with nuts incl GI bow turn buckle, GI stay strand wire, stay clamp and loop insulator etc complete all as per electrical plate No 1 of SSR part 1 and as directed. Note: Excavation, PCC work will be measured and paid separately.
Taking down burnt out jumpers and M&L for new jumper connection not less than 1.5 Mtr long between bus bar system to GOD and GOD to DO fuse unit with jumper made of 11/22 KV aluminum conductor (11/22 KV) including clamps, crimple, PVC sleevless complete all as specifid and directed.
Dismantling post or strut embeded in concrete (wood/steel/RCC) any section embeded in concrete including taking out embeded portion and making good all as directed & specified
Dismantling fencing wire mesh of any description complete all as specified and directed.
S&F for hand rails, half round or others stock section or core for wooden hand rail straight portion, drilled and counter sunk for balusters running bars, for doors, balusters, nosing to steps including embedding in concrete and screwing etc, wind ties for roof including securing bolts, posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire etc, flat iron fillets (for securing wire mesh etc.,) including all necessary drilling, bolting or reveting etc., and similar work confirming to FE-290 Gde E-165 complete all as specified and directed.
M & L for mild steel screw bolts (machine made) with hexagonal or square heads at one head and screwed at the other, screwed end to be fitted with washers and one hexagonal or square nut, n exc 5cm long with dia of bolt upto 10mm complete all as specified and directed.
Supply only galvanised mild steel chain link fencing made out of 3 to 4 mm dia galvanised steel wire and of aperture 50mm x 50mm complete all as specified and directed. Note : Fixing shall be measured and paid separately.
Fixing only mild steel chainlink fencing including line wires, any mesh size and type to any type of standards, rails, straining bolts ,angles etc., including provision of binding wire complete all as specified and directed.
M & L for preparation of new steel surfaces of any description, over 10cm in width or girth not otherwise specified and applying two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer complete all as specified and directed.
Shardul Engineering
Mahindra Electric Stores
M/S - KRUPA ELECTRICALS
Star Electrical
SHREE VAIBHAV ELECTRICALS
Pritam Electro Mechanical Services
ONKAR ELECTRIC AND GENERAL STORE
M/S. Niksun Electro-Infra Private Limited
stage.html
html • 0.06 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .