Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
24 Aug 2023, 6:00 pmClosed
MAJOR AJIT CHOUDHARY
GE (AF) Kalaikunda PO Kalaikunda Air Field Dist Paschim Medinipore State West Bengal Pin 721303
REPAIR AND MAINTENANCE OF LT DISTRIBUTION SYSTEM WITH ALLIED WORKS IN CAMP-I, CAMP-II AND SV AREA AND SEWAGE LINE, MANHOLES, DRAINS ETC IN TECHNICAL AREA AT AF STATION KALAIKUNDA UNDER GE (AF) KALAIKUNDA
2023_MES_596352_2
C/8871/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
AF STN KALAIKUNDA
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE AF KALAIKUNDA
₹90,000
Yes
19 Sept 2023
27 Jul 2023
25 Aug 2023
27 Jul 2023
24 Aug 2023
10 Aug 2023
Amount
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in any kind of soil ,complete all as specified and directed Note : Manual excavation to be done. During excavation if any damage occured to existing cable any type/ water pipe line, it will be contractor responsibilty to get it repair and make functional by providing jointing kit etc without any extra cost. Contractor has to repair it within 24 hrs so that essential service can not be effected due to such damage.If contractor fails to repair it within 24 hrs penalty @ Rs 500/-per hour will be charged to contractor. In this GE decision will be final.
All as per item No 01.00 above here in before but depth exc 1.5 m wide and n exc 3.0 m complete all as specified and directed.
Returning filling in soft/loose soil, including, spreading levelling watering and well ramming in layers not exc. 25 cm complete all as specified and directed.
Removing surplus excavated material from site not exceeding 50 mtrs from starting point and depositing where directed at level not exceeding 1.5 mtr above the starting point all as specified and directed.
M&L providing sand cushioning with a layer of clean, dry, fine sand for protection of electric cable laid in trenches/ducts, punned down to desired thickness complete all as specified and directed. (Note: For payment purposes only punned down thickness of sand shall be measured )
M & L for laying old size sub class ‘B’ brick for PVC/ XLPE under ground cable protection in trench, layed in the manner that width of brick to be peperndicular to the axis of cable , over LT under ground cable
Laying only bricks for PVC/ XLPE under ground cable protection in trench, layed in the manner that width of brick to be peperndicular to the axis of cable , over LT under ground cable (retreived from taking out of old unsv cable) all as specified and directed.
Repairs / Maint of LT Panel board/ feeder pillar box of various sizes including disconnecting all incoming and outgoing connection after taking necessary shut down, cleaning the carbon/rust from bus-bar, re-thimbling with new lugs/thimble of existing size,replacing burnt DMC insulator or bus bar supports as per exsiting one, removing old burn out wiring and re-wiring with new cable of exsiting size, including replacement of un-serviceable parts and hard ware, replacement of all rusted nut bolts with new steel nut bolts and washer, wrapping of existing incoming and out going cables whose PVC insulation gets detoriated, cable to be wraped with insulation tape (minimum three layers over one another on detoriated portion) with colour code (Red, yellow blue for phase and black for neutral) complete all as specified & directed. Note :- (i) Cost of unsheathed multistranded copper conductor for internal wiring like connection of CTs and DMC insulators are deemed to be included in quoted rate. (ii) Suitable size of cable lugs to be provided by contractor for fixing /jointing the cable in bus bar etc. (iii) Cable gland if required shall be provided and included in cost of repair. (iv) Existing cable to be removed from MCCB/MCB and to be refixed after providing suitable size lugs. Cost of lugs included in cost of repair.
Supply and fixing in repair Indoor type insulated ring type low tension current transformers of ratio 200/5A accuracy class 1.0 for LT panel board, complete all as specified and directed by Engr-in-Charge including taking down unserviceable.
Supply and Fix in repairs,LED Indicator 16 mm with power consumption < 0.6W, LVGP & surge protection, 64/110 Volts AC/DC / 240 Volts AC, colour Red/Green/ Yellow/Amber/Blue/White, complete all as specified and directed. of Make - L&T / HPL / AE
Supply and fixing FRLS PVC insulated single core unsheathed multistrand copper conductor for voltage grade 1100 V of size 25 Sqmm single core including copper lugs complete all as specified and as directed.
Supply and fixing FRLS PVC insulated single core unsheathed multistrand copper conductor for voltage grade 1100 V of size 50 Sqmm single core including providing copper lugs complete all as specified and as directed.
Preparation of the old decorated existing external and internal steel surface of feeder pillar boxes/LT panels of any description, any size and in any position by thoroughly cleaning of dirt, fluxing material, other foreign matter and sand papering the surface to remove all scale and rust,wiped finally with mineral turpentine to remove oil, grease and including removal of disintegrated & deteriorated paint either by hand scrapping or by blow lamps, applying necessary filler coat and stopponf required and applying two coats of synthetic enameled paint over a coat of red oxide primer by using spray machine on old prepared surface and writing MES serial No with approved colour code complete all as specified and dircted by engr in charg Note (i) Painting to be done after carrying out all the welding work for replacement of hinges, door lock etc. (ii) Painting shall be done by spray gun. (Approximate minimum area : 40 sqm) (iii) Spray machine shall be of approved PSI
Preparation of the old decorated existing external and internal steel surface of feeder pillar boxes/LT panels of any description, any size and in any position by thoroughly cleaning of dirt, fluxing material, other foreign matter and sand papering the surface to remove all scale and rust,wiped finally with mineral turpentine to remove oil, grease and including removal of disintegrated & deteriorated paint either by hand scrapping or by blow lamps, applying necessary filler coat and stopponf required and applying two coats of synthetic enameled paint over a coat of red oxide primer by using spray machine on old prepared surface and writing MES serial No with approved colour code complete all as specified and as directed. complete all as specified and dircted by engr in charg Note (i) Painting to be done after carrying out all the welding work for replacement of hinges, door lock etc. (ii) Painting shall be done by spray gun. (Approximate minimum area : 30 sqm) (iii) Spray machine shall be of approved PSI
M&L for taking shut down including repairing of LT Panels (Indoor type) by providing connectors, copper lugs, nuts, bolts, etc of suitable sizes for incoming and outgoing UG cables including proper LT insulation tapes to cables which are deteriorated and cleaning the internal area of panel, cleaning the rusted parts by WD-40 and replacing the damaged spare parts like nuts, bolts , screws etc with new steel nut bolts washers including repairing of panel doors by welding broken hinges and repairing the door locks all as specified and directed by Engr-in-charge. Note : (i) LT panel in which repairing of internal wiring, not required and not covered under respective item here-in-before shall be measured under this item. (ii) Excavation required and cost of lugs is deem to be included in rate of the item. (iii) Contractor shall arrange the Welding machine on site for welding of detached Panel doors by providing MS hinges heavy duty and providing tower bolt for locking arrangement
M&L for taking shut down including repairing of feeder pillars out door type by providing connectors, copper lugs, nuts, bolts, etc of suitable sizes for incoming and outgoing UG cables including proper LT insulation tapes to cables which are deteriorated and cleaning the internal area of panel, cleaning the rusted parts by WD-40 and replacing the damaged spare parts like nuts, bolts , screws etc with new one including repairing of panel doors by welding broken hinges, providing new hinges where old hinge rusted and repairing the door locks / providing new locking arrangement including taking out incoming and out going cable burried in undergound cutting and providing new aluminium lugs and reconnected to bus bar/ MCCB`s/MCB`s all as specified and directed by Engr-in-charge. Note : (i) Feeder Pillar box in which repairing of internal wiring, welding of doors not required and not covered under respective item here-in-before above shall be measured under this item. (ii) Excavation required and cost of lugs is deem to be included in rate of the item. (iii) Contractor shall arrange the Welding machine on site for welding of detached Panel doors by providing MS hinges heavy duty and providing tower bolt for locking arrangement
M&L for Maintence and cleaning of surrounding area of sub stations, near LT panels, feeder pillars, transformer etc by cutting seasonal grass, bushes etc,including spreading of strong herbicides in order to stop the fast growth of grass/bushes around the feeder pillars and panels by employing skilled mazdoor including using own T&P as required to do the job and taking all precaution while men on working in sub station being dange zone all as specified and directed by Engr-in-charge. Note : As vegitation growth is very high in the Stn due to humid climate, area cleaning of installations can be repeated and to be done twice/thrice as per the requirement and directed by Eng in Charge.
Demolition of concrete of any description and in any position not otherwise specifically complete all as specified and directed.
Materials and Labour for plain cement concrete (1:3:6) Type C-2 using 40 mm graded aggregate in foundations, filling and mass concrete complete all as specified and directed.
Materials and Labour for plain cement concrete (1:2:4) type B0 using 12.5 mm graded aggregate in lintels up to 1.5m clear span, cills, steps; seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings up to 60 cm in height, copings, kneelers, apex stones, bed plates, kerbs, water troughs and the like including weathering, slightly rounded or chamfered angles throating, as directed including necessary from work complete all as specified and directed.
Supply and Fix in repairs,moulded case circuit breakers (MCCBs),conforming to IEC 60947-2& IEC 60947-2, AC 415V, 4 pole, with current rating 100 Amps and 25 KA breaking capacity Icu at 415V, AC, 50Hz, with adjustable Over Load setting: 0.8 - 1.0 x In and adjustable Short Circuit setting: 6-10 x In,complete all as specified and directed.
Supply and Fix in repairs,moulded case circuit breakers (MCCBs),conforming to IEC 60947-2& IEC 60947-2, AC 415V, 4 pole, with current rating 125 Amps and 25 KA breaking capacity Icu at 415V, AC, 50Hz, with adjustable Over Load setting: 0.8 - 1.0 x In and adjustable Short Circuit setting: 6-10 x In,complete all as specified and directed.
Supply and Fix in repairs,moulded case circuit breakers (MCCBs),conforming to IEC 60947-2& IEC 60947-2, AC 415V, 4 pole, with current rating 160 Amps and 25 KA breaking capacity Icu at 415V, AC, 50Hz, with adjustable Over Load setting: 0.8 - 1.0 x In and adjustable Short Circuit setting: 6-10 x In,complete all as specified and directed.
Supply and Fix in repairs,moulded case circuit breakers (MCCBs),conforming to IEC 60947-2& IEC 60947-2, AC 415V, 4 pole, with current rating 200 Amps and minimum 36 KA breaking capacity Icu at 415V, AC, 50Hz, with adjustable Over Load setting: 0.8 - 1.0 x In and adjustable Short Circuit setting: 6-10 x In, complete all as specified and directed.
Supply and Fix in repairs,moulded case circuit breakers (MCCBs),conforming to IEC 60947-2& IEC 60947-2, AC 415V, 4 pole, with current rating 250 Amps and 40 KA breaking capacity Icu at 415V, AC, 50Hz, with adjustable Over Load setting: 0.8 - 1.0 x In and adjustable Short Circuit setting: 6-10 x In, complete all as specified and directed.
Supply and Fix in repairs,moulded case circuit breakers (MCCBs),conforming to IEC 60947-2& IEC 60947-2, AC 415V, 4 pole, with current rating 400 Amps and Minimum 36 KA breaking capacity Icu at 415V, AC, 50Hz, with adjustable Over Load setting: 0.8 - 1.0 x In and adjustable Short Circuit setting: 6-10 x In, complete all as specified and directed.
Supply and Fix in repairs,moulded case circuit breakers (MCCBs),conforming to IEC 60947-2& IEC 60947-2, AC 415V, 4 pole, with current rating 630 Amps and 40 KA breaking capacity Icu at 415V, AC, 50Hz, with adjustable Over Load setting: 0.8 - 1.0 x In and adjustable Short Circuit setting: 6-10 x In, complete all as specified and directed.
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3½ core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 120 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc with and including disconnecting and taking out unserviceable, U/G cables,old serviceable bricks, GI pipes complete all as specified and as directed.
All as per Item No 29.00 here-in-before but size of cable 95 sqmm 3½ core, complete all as specified and as directed.
All as per Item No 29.00 here-in-before but size of cable 70 sqmm 3½ core, complete all as specified and as directed.
All as per Item No 29.00 here-in-before but size of cable 50 sqmm 3½ core, complete all as specified and as directed.
All as per Item No 29.00 here-in-before but size of cable 35 sqmm 4 core, complete all as specified and as directed.
All as per Item No 29.00 here-in-before but size of cable 25 sqmm 4 core, complete all as specified and as directed.
All as per Item No 29.00 here-in-before but size of cable 16 sqmm 4 core, complete all as specified and as directed.
All as per Item No 29.00 here-in-before but size of cable 10 sqmm 4 core, complete all as specified and as directed.
M&L for detecting of fault in 1100V (E) LT cable of any size , 3½ core laid in trenches/ducts with the help of electronic fault locating machine comprising of surge generator, echo fault locator with high frequency distance calculator etc and exposing the cable fault, removal of deteriorated portion of cable, treating the cable including making it ready for jointing work complete all as directed by Engineer-in-Charge. Note: - (i) The quoted rate shall deemed to include for the cost of earthwork excavation as required. (ii) Cable if replaced & cost of Jointing kit shall be measured & paid separately.
S& F SS enclosure for MCCB of rating 250 Amp In-built neutral Link for TPN system l IK08 and IP30 Protection having Louvers for better heat dissipation Suitable to accommodate upto 185 sq. mm. 3 1/2 core Aluminum armoured cable incl taking down unsv one and fixing serviceable/ new MCCB in enclosure and connectiing existing IC/OG cable with proper dimension lugs all as specified and directed. Note : New MCCB shall be measured and paid seperately.
S& F SS enclosure for MCCB 125 Amp In-built neutral Link for TPN system l IK08 and IP30 Protection having Louvers for better heat dissipation Suitable to accommodate upto 70 sq. mm. 3 1/2 core Aluminum armoured cable incl taking down unsv one and refixing serviceable/ new MCCB in enclosure and connectiing existing IC/OG cable by providing lugs of suitable dimension all as specified and directed. Note : New MCCB shall be measured and paid seperately.
Materials and Labour for Straight Through Joints, tubular sleeve type, for 1.1 KV Grade, underground cable including jointing kits and accessories complete for making joints, suitable for 3/3 ½ /4 core XLPE armoured, aluminium conductor cable, of size 6 sq. mm to 16 sq. mm, complete all as specified and directed. Make - Raychem/M-Seal/3M
Materials and Labour for Straight Through Joints, tubular sleeve type, for 1.1 KV Grade, underground cable including jointing kits and accessories complete for making joints, suitable for 3/3 ½ /4 core XLPE armoured, aluminium conductor cable, of size 25 sq. mm to 50 sq. mm, complete all as specified and directed. Make - Raychem/M-Seal/3M
Materials and Labour for Straight Through Joints, tubular sleeve type, for 1.1 KV Grade, underground cable including jointing kits and accessories complete for making joints, suitable for 3/3 ½ /4 core XLPE armoured, aluminium conductor cable, of size 70 sq. mm to 150 sq. mm, complete all as specified and directed. Make - Raychem/M-Seal/3M
Materials and Labour for Straight Through Joints, tubular sleeve type, for 1.1 KV Grade, underground cable including jointing kits and accessories complete for making joints, suitable for 3/3 ½ /4 core XLPE armoured, aluminium conductor cable, of size 150 sq. mm to 185 sq. mm, complete all as specified and directed. Make - Raychem/M-Seal/3M
Materials and Labour for Straight Through Joints, tubular sleeve type, for 1.1 KV Grade, underground cable including jointing kits and accessories complete for making joints, suitable for 3/3 ½ /4 core XLPE armoured, aluminium conductor cable, of size 240 sq. mm to 300 sq. mm, complete all as specified and directed. Make - Raychem/M-Seal/3M
Horizontal boring of holes, under road/ pavement / hard standing etc.,not exceeding 15 Metres in length, in any type of soil, suitable for passing through 40 to100 mm bore, galvanised steel tubing,and making good distrubed surfaces as per existing specification complete all as specified and directed.
Material and labour for 80 mm dia galvanized iron tube light grade for cable protection, supporting to poles, plinth protections, road crossing, trenches, footpath etc, including including all fitting clamps, nut, bolt and washers complete all as specified and directed.
Material and labour for 50 mm dia galvanized iron tube light grade for cable protection, supporting to poles, plinth protections, road crossing, trenches, footpath etc, including including all fitting clamps, nut, bolt and washers complete all as specified and directed.
Material and labour for 40 mm dia galvanized iron tube light grade for cable protection, supporting to poles, plinth protections, road crossing, trenches, footpath etc, including including all fitting clamps, nut, bolt and washers complete all as specified and directed.
S & F in repair rotary handle for operating MCCB direct ROM type complete all as specified and directed by Engr in Charge. make: L&T Cat No. CM98040OOOO or equivalent of make: Hager/Schneider/siemens
S & F in repair rotary handle for operating MCCB direct Extended ROM type including taking down complete all as specified and directed by Engr in Charge. make: L&T Cat No. CM98041OOOO or equivqlent of make: Hager/Schneider/siemens
M&L for fabricating door of feeder pillar box ,dust and vermin proof, cubical type LT panel fabricated from 3.15 mm thick CRCA sheet , with anticorrosive coating and finally epoxy polyester power coating with pure polyster Siemens grey structural RAL-7032 shade , protection class IP-54 by providing hinges complete all as specified and directed by Eng in Charge.
Demolition of reinforced concrete of any description and in any position not otherwise specifically provided for including reinforcement cut as required to facilliate demolition complete all as specified and directed.
Demolition of concrete of any description and in any position not otherwise specifically complete all as specified and directed.
Demolition of brick work or stone/boulder masonry, built in cement mortar including all quoins, arches, pillars, etc. complete all as specified and directed by Engineer in charge.
Dismantling of bricks (laid flat or on edge) kerbs, aprons etc. (each layer) laid, jointed and pointed in cement mortar complete all as specified & as directed.
Demolition and breaking up drain pipes (Salt glazed ware, AC or reinforced concrete) of internal dia 150 mm, set in cement mortar complete all as specified and as directed.
Taking down eaves gutters and rainwater pipes (any size or pattern), soil waste pipes (any size or pattern), including all fittings, heads, shoes, bends, swan-necks, etc., including cleaning or refixing or removal to Store (measured overall as fixed along the centre line over fittings and accessories) complete all as specified and as directed
Materials and Labour for plain cement concrete (1:3:6) Type C-2 using 40 mm graded aggregate in foundations, filling and mass concrete complete all as specified and directed.
M&L PCC 1:3:6 type C1 (with using 20mm graded shingle) as in bed of drain including forming channels complete all as specified & as directed
M & L for precast cement concrete M15 (Nominal Mix) using 20 mm nominal size graded crushed stone aggregate in landings, cover slabs (for man holes etc.) chullah hoods, chajjas, water troughs, mangers, shelves and similar articles with plain faces fair faces, including chamfers, weatherings, throating etc. and setting in cement mortar (1:4) complete with joints to match complete all as specified and as directed
M & L for chequered cement concrete tiles chemically treated , cast in rubber mould, glossy finish of approved colour, general purpose, double layer, size 25 cm X 25 cm X 22 mm thick, with mixture of white and grey cement in equal proportions and pigments, set, jointed and pointed in neat cement slurry in floor including laying over 20 mm thick bedding of cement mortar(1:4) all as specified and as directed.
Materials and Labour for plain cement concrete (1:2:4) type B0 using 12.5 mm graded aggregate in lintels up to 1.5m clear span, cills, steps; seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings up to 60 cm in height, copings, kneelers, apex stones, bed plates, kerbs, water troughs and the like including weathering, slightly rounded or chamfered angles throating, as directed including necessary from work complete all as specified and directed.
Supply and fix mild steel TMT bars 10 mm dia. and over, cut to length, bend to shape required including cranking, bending spirally for hopping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9 mm dia. or securing with clips complete all as specified and directed
Supply and fix mild steel TMT bars 6 to 8 mm dia., cut to length, bend to shape required including cranking, bending spirally for hopping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9 mm dia. or securing with clips complete all as specified and directed
M & L for concrete bed to glazed stoneware pipes of internal diameter 150 mm, class SP1, laid in trenches of depth more than 1.2 m in cement concrete M10(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate including forming cradles complete all as specified and as directed.
Cutting into existing manholes for connecting new drains of pipe of nominal size 150 mm, making good to pipe and rendering, cutting out existing benching for and forming branch channel (1/2 round or 3/4 section) in cement concrete M15(Nominal mix) using 20 mm nominal size graded crushed stone aggregate, smooth finished, and reforming benching as required complete all as specified and as directed.
Materials and Labour for brick work with Sub Class ‘B’ bricks straight or curved on plan exceeding 6M mean radius built in cement mortar (1:4), complete all as specified and directed.
All as per item No-67.00 above here in before but except bricks(brick obtained from demolition above here in before ) with and including removing mortar from and cleaning bricks, stacking for measurement including all extra handling and removal and disposing off rubbish as directed.
M&L for brick Subclass `B' (locally available best quality) laid on both side of drain using old size of brick bedded and jointed in cement mortar 1:6 and pointed in cement mortar 1:3 complete all as specified and as directed.
All as per item ser No 69.00 here-in-before but except bricks complete.
All as per item No- 69.00 here-in-before but brick laid on edge complete.
M & L for raking out joints/ pointing to brick work laid on flat in floors, surface channels, drain, roofs, etc including removing of rubbish, grass etc from the site to a distance exc, 250m but n. exc 500m and deposited where directed at a level not exc. 1.5m above the starting point, complete all as specified and as directed
M & L for raking out joints/ pointing to brick work in walls or to bricks on edge in floors, surface channels, drain, roofs, etc including removing of rubbish, grass etc from the site to a distance exc, 250m but n. exc 500m and deposited where directed at a level not exc. 1.5m above the starting point, complete all as specified and as directed.
M & L for flush pointing to brick laid flat in pavings in CM 1:4 complete all as specified and as directed.
M & L for flush pointing to brick on edge pavings in CM 1:4 complete all as specified and as directed.
Materials and Labour for rendering 5mm thick, cement plaster, in cement mortar (1:4) mixed with water proofing compound as per manufactures instructions over and including 10mm thick backing coat in cement mortar (1:4) on fair faces of brick work or concrete surface finished even and smooth without using extra cement in walls/spetic tank/manholes/soakage pits etc, complete all as specified and directed. Note: - (Water proofing compound will be measured and paid separately)
Supply only Liquid water proofing compound conforming to IS: 2645 - 1975 specification complete all as specified and as directed (Make : CICO No- 1/SIKA/ACCO PROOF).
Material and Labour for applying two coats of cement-based paint, white or tinted to new plastered surfaces on walls including priming with alkali resistant priming paint and including preparation of surfaces complete all as specified and directed.
Material, T&P and labour for cleaning of sewage line of dia/bore 100 mm in sewer line system using the cleaning devices as per rule 5 and protective gear and safety devices as per rule 4 of the Prohibition of Employment as Manual Scavengers and their Rehabilitation Rules, 2013 and removing blockage if any complete all as specified and as directed. Unit rate quoted shall deemed to be included of cleaning of shrubs, grass small roots etc. around the Manholes, Inspection chamber etc and along sewage lines wherever required or as directed and no extra payment shall be made on this account).
Material, T&P and labour for cleaning of sewage line of dia/bore 150 mm in sewer line system using the cleaning devices as per rule 5 and protective gear and safety devices as per rule 4 of the Prohibition of Employment as Manual Scavengers and their Rehabilitation Rules, 2013 and removing blockage if any complete all as specified and as directed. Unit rate quoted shall deemed to be included of cleaning of shrubs, grass small roots etc. around the Manholes, Inspection chamber etc and along sewage lines wherever required or as directed and no extra payment shall be made on this account).
Material, T&P and labour for cleaning/ desludging of septic tank/ soak well of capacity upto 200 users using the cleaning devices as per rule 5 and protective gear and safety devices as per rule 4 of the Prohibition of Employment as Manual Scavengers and their Rehabilitation Rules, 2013 and removing the sludge and solid contents in covered container outside MD land complete all as specified and as directed. Unit rate quoted shall deemed to be included of cleaning of shrubs, grass small roots etc. around the Manholes, Inspection chamber etc and along sewage lines wherever required or as directed and no extra payment shall be made on this account and .measurement shall be taken after allowing initial percolation of sludge water and only dried sludge shall be measured )
Material, T&P and labour for cleaning of blockage of wash basin, floor trap, nahani trap, gully trap (GT), kitchen, bath etc. (carrying sullage) in any length upto the first manhole by any means (using chemical or any mechanical device) & flushing with water complete all as specified and as directed.
Material, T&P and labour for cleaning of blockage of WC/Urinal (carrying soil waste) in any length upto the first manhole using the cleaning devices as per rule 5 and protective gear and safety devices as per rule 4 of the Prohibition of Employment as Manual Scavengers and their Rehabilitation Rules, 2013 and removing blockage if any complete all as specified and as directed.
M & L for 150 mm internal dia salt glazed stoneware pipes, class SP1 as per IS 651: 2007 laid in trenches and jointed with cement slurry and yarn complete all as specified and as directed.
S & F PVC-U, type B as per IS 13592: 2013 single socketed soil waste pipes in any length with rubber ring joints, 110 mm dia, laid in trenches complete all as specified and directed by Engineer- in- charge .
S & F PVC-U, type B as per IS 13592: 2013 single socketed soil waste pipes in any length with rubber ring joints, 110 mm dia, fixed to walls incuding mild steel clamp not more than 1metre C/C complete all as specified and directed by Engineer- in- charge .
S & F UPVC bends without inspection door (any angle), 110 mm dia conforming to IS 14735: 1999 complete all as specified and directed by Engineer- in- charge
S & F UPVC bends inspection door (any angle), 110 mm dia conforming to IS 14735: 1999 complete all as specified and directed by Engineer- in- charge
SUMAN CONSTRUCTION
M/S KANAN TRADERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .