SPECIAL REPAIR/REPLACEMENT OF BER DISTRIBUTION TRANSFORMERS ASSOCIATED WITH EXTERNAL ELECTRIC SUPPLY UNDER GE NAGROTA
2026_MES_782507_1
CWE/NGT-60/2026-27
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE NAGROTA
As per tender documents
8 documents required · 8 mandatory
₹1,000
GE NAGROTA
₹2.2 L
Yes
15 Sept 2026
3 Aug 2026
17 Sept 2026
3 Aug 2026
15 Sept 2026
7 Sept 2026
3 Aug 2026 - 17 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, Testing, Commissioning of Oil Cooled, Copper wound, Step down "BIS marked and BEE star labelled "transformer of capacity 500 KVA plinth mounted outdoor type with latest feature complete with standard fitted HT 11 KV 3 phase, LT 433 V 3, phase 4 wire,50 C/S oil immersed, naturally cooled externally cooling tube with delta connection on primary HT 11 KV side and star connection on secondary LT 433V with 7 position off circuit tap changer on HV side to be changed by means of hand operated off load changing gear (tapping range + 7.5% in steps of 2.5% each) with vector group Dyn-11, including first filling of new transformer oil of dilectric strength not less than 55 KV with all fitting and accessories such as LT box with cable gland, HT box with cable gland, Silica gel breather, Oil level indicator gauge, drain out valve (oil tank),exhaust vent, air release valve, temp gauge, cast iron wheel etc complying with Energy efficient level (EEL 2) (Two) as per IS 1180 (Part-1) 2014 with amendment 1,2,3 & 4 having total losses @ 50% load 1430W & total losses @ 100% load 4100W. Following items/ Accessories included in this rate complete all as specified and directed.
(i) Name, rating & diagram plate.
(ii) 7 positions Off circuit tap changing switch.
(iii) Earthing terminals.
(iv) Lifting lugs.
(v) Oil drain valve with plug.
(vi) Oil filter valve with plug.
(vii) Conservator with oil filling hole.
(viii) Thermometer pocket.
(ix) Air release plug
(x) Silica gel breather.
(xi) Removable inspection opening
(xii) Explosion vent
Note: The rate shall also include replacement of HT/LT Bus bar terminals of suitable size with clamps, nut bolts etc at site. | 1 | Each | - | - |
| 2 | All as per item srl No-01 here-in-before but transformer of capacity 400 KVA and total losses @ 50% load 1150W & total losses @ 100% load 3330W complete all as specified and directed. | 2 | Each | - | - |
| 3 | All as per item srl No-01 here-in-before but transformer of capacity 315 KVA and total losses @ 50% load 955W & total losses @ 100% load 2750W complete all as specified and directed. | 1 | Each | - | - |
| 4 | All as per item srl No-01 here-in-before but transformer of capacity 250 KVA and total losses @ 50% load 920W & total losses @ 100% load 2700W complete all as specified and directed. | 1 | Each | - | - |
| 5 | All as per item srl No-01 here-in-before but transformer of capacity 200 KVA and total losses @ 50% load 670W & total losses @ 100% load 2100W complete all as specified and directed. | 1 | Each | - | - |
| 6 | All as per item srl No-01 here-in-before but transformer of capacity 160 KVA and total losses @ 50% load 570W & total losses @ 100% load 1700W complete all as specified and directed. | 1 | Each | - | - |
| 7 | All as per item srl No-01 here-in-before but transformer of capacity 100 KVA and total losses @ 50% load 435W & total losses @ 100% load 1500W complete all as specified and directed. | 2 | Each | - | - |
| 9 | Replacement for earthing complete with galvanized steel earth plate electrode of size 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 meters below ground level) with top edge of earth plate not less than 1.5 meters below ground level surrounded on all sides by 150 mm thick charcoal and common salt starting from ground below earth plate upto 150mm above GI plate in alternate layers connected to galvanized earth strip 32 mm x 6 mm by means of nuts, bolts, thimbles, chuck nuts, washers of GI or steel, PCC (concrete chamber of size 300 mm x 300 mm x 300 mm inside dimension) shall be PCC 1:3:6 type C-1 (using 20mm graded crushed stone aggregate) with fair finish, internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4, funnel with wire mesh of 22 gauge, 80 mm thick PCC pit cover 320mm x 320mm of RCC 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) reinforced with XPM, JALLI pit all as shown in electrical plate No 3 of MES SSR Part-I (2009) as specified including provision of 40mm bore medium grade GI pipe for earth strip protection and 20 mm bore for watering complete, all excavation and earth work and connecting the earthing to an earthing test point /LT Panel/ Transformer as specified and testing on completion for desired result complete all as specified and directed.
Note: Manual digging only allowed for earthing. | 18 | Each Set | - | - |
| 10 | GI strip of size 32mm x 6mm for earth continuity conductor or main earthing lead fixed to wall burried in ground fixed alongwith poles complete all as specified and directed. | 40 | RM | - | - |
| 11 | Test point terminal block made of gun metal or phosphorus bronze size 75mm x 75mm x 25mm drilled and screwed including 3 Nos 8mm dia 25mm long hexagoanl head screw complete all as specified and directed. | 18 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.18 MB
BOQ_876674.xls
BOQ • 0.36 MB
TENDER60.pdf
Tender Documents • 0.57 MB
datecorr60.pdf
PDF • 0.11 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].