Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹58.2 LAccepted-AOC 1202 SAI PROVISO DHNISHT PLOT NO 72 73 SECTOR 20 KOPARKHAIRANE NAVI MUMBAI | THANE | MAHARASHTRA | 400601 | L1 | Accepted-AOC Being Lowest | |
| 2 | L2₹62.6 L+₹2.8 L (4.62%)Rejected-Finance 1 2 GR FLOOR VITHALKUNJ NO 3 V P ROAD ANDHERI WEST MUMBAI 400 058 | MUMBAI SUBURBAN | MAHARASHTRA | 400058 | L2 | Rejected-Finance Being other than lowest | |
| 3 | L3₹66.9 L+₹7.1 L (11.9%)Rejected-Finance B BLOCK 2 3 RAM BACHAN V B NAGAR PIPE ROAD KURLA W MUMBAI 400070 | MUMBAI SUBURBAN | MAHARASHTRA | 400070 | L3 | Rejected-Finance Being other than lowest | |
| 4 | L4₹67.1 L+₹7.3 L (12.2%)Rejected-Finance | L4 | Rejected-Finance Being other than lowest | |
| 5 | L5₹67.8 L+₹8.0 L (13.4%)Rejected-Finance | L5 | Rejected-Finance Being other than lowest |
Tender Value
Refer Docs
EMD Value
₹1.5 L
Closing Date
6 Jul 2023, 6:00 pmClosed
GE (NW) Navy Nagar, Colaba, Mumbai
GE NW NAVY NAGAR COLABA MUMBAI DR HOMI BHABHA ROAD NAVY NAGAR COLABA MUMBAI
REPAIR REPLACEMENT OF EXISTING FITTINGS AND FIXTURES WITH MODULAR FITTINGS IN CERTAIN SAILORS MARRIED ACCN IN RS COLABA AND REPAIR MAINTENANCE AND REPLACEMENT OF UNSERVICEABLE EARTHINGS AT EM INSTALLATIONS CLEANING AND REFIILING OF SAND IN CABLE DUCT
2023_MES_600094_1
8276/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE (NW) Navy Nagar, Colaba
Class C and category b(i)
8 documents required · 8 mandatory
₹1,000
GE NW NAVY NAGAR COLABA MUMBAI
₹1.5 L
Yes
24 Jul 2023
1 Jun 2023
7 Jul 2023
1 Jun 2023
6 Jul 2023
22 Jun 2023
1 Jun 2023 - 29 Jun 2023
Amount
Taking down carefully copper/ aluminium point wiring ie. light, fan, socket or power/points complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fittings etc. and making good disturbed surfaces of ceiling, walls, floors, etc.
Material and labour for point wiring complete with proper colour coding using, 1100 volts grade, 1.5 Sqmm, PVC insulated FRLS, unsheathed wire with multi stranded copper conductor confirming to IS-694, part-II, ISI marked and including PVC casing and capping not less than 25 mm size, ISI mark with all accessories on wall/ceiling/floor/roof etc, including 1.5 Sqmm, PVC insulated, FRLS, unsheathed, 1100 volts multistranded copper conductor green colour as continuous earth wire connected to common earth dolly all as specified and directed for the following :- NOTE : Circuit conductor from MCB DB to Switch boards should not be less than 2.5sqmm.
One light/Exhaust/Ceiling fan point controlled by one switch.
One 3 pin socket outlet, 5 Amps on the same board with other switches
One 3 pin socket outlet, 5 Amps, on the independent board
One bell point controlled by one push button
All as per item No 2.00 above but with 2.5 sqmm cable for one three pin 15 Amps socket out let controlled by one switch.
S & F in replacement with new modular switch piano, 1 module, single pole one way 6Amp.
S & F in replacement with new modular bell push switch, 1 module, single pole one way 6Amp.
S & F in replacement with new modular socket 2/5 pin, 2 module, 6A.
S & F in replacement with new Socket 6/16A, 6 pin, 2 module.
S & F in replacement with new modular switch piano, 1 module, single pole one way 16Amp.
S & F in replacement with new modular stepped type fan regulator, 2 module, single pole one way.
S & F in replacement with new lamp holder, Angle/Batten, PVC/Polycarbonate body with 7 W LED Lamp.
Taking out old wooden/PVC board and disconnecting all electric connection from switches, board and S & F modular PVC Gang box of 12 module for mounting of modular switches and sockets including blank plate for blank module all as directed.
All as per Item No 11.00 above but of modular PVC Gang box, 8 module.
All as per Item No 11.00 above but of modular PVC Gang box, 6 module.
All as per Item No 11.00 above but of modular PVC Gang box, 4 module.
All as per Item No 11.00 above but of modular PVC Gang box, 3 module.
All as per Item No 11.00 above but of modular PVC Gang box, 2 module.
All as per Item No 11.00 above but of modular PVC Gang box, 1 module.
S&F modular white cover plate with frame, 12 module.
S&F modular white cover plate with frame, 8 module.
S&F modular white cover plate with frame, 6 module.
S&F modular white cover plate with frame, 4 module.
S&F modular white cover plate with frame, 3 module.
S&F modular white cover plate with frame, 1 or 2 module.
Taking down unserviceable FTL and supply and fix Slim LED intigrated batten of 20Watt 4ft coolday light with powder coated CRCA decorative patti prewired complete with two Nos of PVC box of size 75x75x20mm for mounting light fittings including new ceiling rose with earth terminal connection, 3 terminal/ PVC/ polycarbonate, isolated body of size 60x20mm complete. Make of Light Fitting : Shakti Cat Part No - SZSLBMX020 or Wipro Cat Part No D532065 or BCLSB20WH of Bajaj
All as per Item No 24.00 above but Slim LED integrated batten of 10 Watt 2ft complete. Make of Light Fitting : Shakti Cat Part No - SZSLBMX010 or Wipro Cat Part No D531065 or BCLSB10WH of Bajaj
Taking out any type of bulkhead fitting/FTL and S&F 10 watt linear LED batten, 2 feet, aluminium extruded channel, powder coated with diffuser for glare free light, inbuilt motion sensor prewired with 25% dimmer illuminiuos in ideal time with all accessories including two nos of PVC box of size 75x75x20mm for mounting light fittings complete in common area and staircase. Cat ref SZSLAMX010-ISS of Make -Shakti or /Bajaj/Wipro/Philips.
S & F in replaement with new bell electric ding dong, AC, 230V single pole.
Supply and fixing of MCCB DB VTPN 4 way as per IEC 61439-3 Suitable for Flush /Surface mounting with 250 A Copper Busbar for each phase with 2 Neutral bar, 2 Earthbar and Cable ties for Cable management fully insulated busbar & shrouded Neutral bars improved Pan assembly for ease of installation prefitted masking sheet reversible metalic door for IP 43 & IP 54 DB's with provision for DPX³ 160 MCCB as incomer and SP/TP MCB's as outgoing complele all as specified and directed. Make : Legrand Cat ref : 507745 or equivalent in Siemens/Schneider/ABB
Supply and fixing of DPX³ 160, Thermal magnetic release , Ics=100% Icu MCCB 100A, 25kA, 4P. Make : Legrand Cat ref : 420055 or equivalent in Siemens/ Schneide /ABB
Supply and fix MCB SPN 63A, 10kA, 204V. Make : Legrand Cat ref : 408620 or equivalent in Siemens/ Schneide /ABB
M&L for LT FPB, weather proof, vermin proof, double door made out of 3.3mm thick CRCA sheet, CPRI approved, out-door type (IP-54) suitable for 3 phase, 4 wire, 415 volts, with Copper busbar strip of 600 amps capacity with necessary clamps, nuts, bolts and washers, internally prewired with all connecting accessories, floor mounted type made with angle iron legs 50x50x5 mm thick, powder coated painting incl foundation 60 cms above the ground level in PCC 1:3:6 type C2. all as specified & Directed consisting of following :-
Incomer : (a) DPX³ 250 MCCB with Electronic Sg (LSIg) Protection Unit, 250A, 36KA, 4P - 01 Nos. Make : Legrand Cat ref : 420539 or equivalent in Siemens/Schneider/ABB
Outgoings :
(b) DPX³ 160, Thermal magnetic release , Ics=100% Icu MCCB 100A, 25kA, 4P - 2 Nos. Make : Legrand Cat ref : 420055 or equivalent in Siemens/Schneider /ABB
(c) DPX³ 160, Thermal magnetic release , Ics=100% Icu MCCB 63A, 25kA, 4P - 6 Nos. Make : Legrand Cat ref : 420053 or equivalent in Siemens/Schneider /ABB
(d) Digital Ammeter Make-HPL/L&T/AE - 01 Nos
(e) Digital Voltmeter Make-HPL/L&T/AE - 01 Nos
(f) Phase indicator lamp R,Y & B - Set of 3
(g) Copper Bus bar 600 Amps rated of suitable size - Set
Notes : The panel board shall be fabricated from CPRI approved manufacturer and panel drawing shall be submitted by contractor for approval before placing the order.
Taking out existing unarranged UG cables/conduits from wall surfaces/chhajjas fixed with ms clamp after disconnecting from DBs/LT panels and keeping aside, making good for fixing of wall trunking complete all as specified.
Supply and fixing of DLP PVC trunking system with all connected fittings for fixing on wall ceiling surfaces (end, joint of lid, joint of body, interior angle, exterior angle, flat angle, derivation) confirming standard EN 50085-2-1 of under mentioned size and refixing/resaddeling of all dismantalled UG cables/submain inside the trunking and made connection as specified and directed :
PVC truncking 150X50MM
PVC truncking 80X50MM
Flexible cover 85MM width
Flexible cover 65MM width
Clip on partition
Base joint for tuncking
Joint for 85MM width cover
Joint for 65MM width cover
Flat angle for 150X50-DLP TRU
Flat angle for 80X50-DLP TRU
Internal angles adj 80-100 degree
External angles adj 60-120 degree
M & L for earthing complete with Galvanised steel earth plate eletrode 60cmx60cmx6mm thick buried directly in ground vertically to (earth pit not less than 2.25 meters deep below normal ground level) with top edge of plate not less than 1.5 meters below normal ground level, connecting to the Galvanised Iron Strip of size 32x6mm size, by means of Bolts, Nuts, Check Nuts and washer made of GI or Steel Earth connecting with test point, provision of Charcal and salt in alternate layers, watering pipe 20mm dia medium grade MS funnel with jali, PCC M-15 Type B-1 in pit with XPM not elss than 4Kg per Sqm and Earthpit with cover returning, filling, removing excavated material all as specified in electrical plate No 3 of SSR Part-I making good excavated surfaces such as hard standing refixing machine pressed precast concrete interlocking paver blocks removed during excavation on earthpit to match existing surfaces after taking out old/unserviceable one complete and testing on completion all as specified and directed by Engr-in-Charge
M & L for earthing with copper earth plate electrode 600mm x 600mm x 3 mm burried directly in ground earth pit not less than 2.25 mtr deep below normal ground level with top edge of the plate vertically to a depth not less than 1.5 mtr below ground level connected to the connecting copper strip 20 x 3 mm and including GI pipe 40 mm dia light grade for protection to the extend of 7.5 mtr as earthing lead by means of copper nuts, bolts as per connecting to equipment with provn charcol and salt complete all as per electric plate No 5 of SSR Part-1 including PCC chamber with RCC cover watering arrangement with GI pipe 20 mm dia medium grade and MS funnel, including excavation and earth work and returning, filling in including ramming and removal of surplus soil and testing on completion complete.
Material and labour for maintainance free environment friendly earth electrode set comprising of 17.2mm dia, 3 mtrs long rod of low carbon steel molecular copper bounded for a thickness of 250 micro OHMS, highly conductive ANSI/NSF STD-60 certified carbon bound backfill compound which shall set like concrete according to BS 7430 & IEEE 80 (each bag shall contain 50 lbs) after taking out old, U/S one complete all as directed by Engineer-in-Charge. Make- JEF Ecosafe or equivalent as approved by GE.
M & L for Galvanised iron strip 25 x 4mm burried in ground or fixed on walls/floor with suitable saddles and screws beyond 7.5mtr of earth lead connecting with test point after taking out old/unserviceable one complete all as specified and directed by Engineer-in-Charge.
M & L for copper strip 20 x 3mm burried in ground or fixed on walls/floor with suitable saddles and screws beyond 7.5mtr of earth lead connecting with test point after taking out old/unserviceable one complete all as specified and directed by Engineer-in-Charge.
Supply & fixing of single core PVC insulated and unsheathed cable with copper conductor in and including heavy duty PVC conduit fixed with screw on wall and using cable size 1x50 Sqmm 1100 Volt grade stranded copper conductor after taking out old, U/S earthing strip complete all as specified and as directed. Make of cable : Havells/Finolex/ L & T/Plaza/Anchor.
M & L Test point terminal block made of gunmetal /phosphorus bronze of size 75x75x25mm drilled and screwed including 3 Nos, 8mm dia 25mm long hex head screw fixed complete all as specified and as directed.
Supplying, filling, spreading, leveling in layers and well ramming dry river sand around cable in cable duct after cleaning of unwanted debris from cable ducts complete all as specified and directed.
Material & labour for MS chequered plate 5 mm thick size as per site requirement including cutting to required shape and appling two coats of synthetic enamel paint over a coat of red oxide primer and complete all as specified and directed by Engr-in-charge.
M&L for Cross arms, bracings, supports,clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint for climbing and light fitting post on steel tubular poles complete all as specified and as directed.
M&L for earth pit of PCC M-15 Type B-1 in pit with XPM not elss than 4Kg per Sqm MS funnel with jali, and Earthpit with cover and making good excavated surfaces such as hard standing refixing machine pressed precast concrete interlocking paver blocks removed during excavation on earthpit to mach existing surfaces after taking out old/unserviceable one complete and testing on completion all as specified and directed by Engr-in-Charge.
Supply & fix electrical Insulating mat confirming to IS15652/2006 (superceding IS: 5424-1969) B.I.S+CPRI+NTH+ERDA approved of C class of mats dielectric strength 65KV, sheet thickness not less than 3.0MM using at power houses including pasting of rubber mats with adhesive resin all as specified and directed by Engineer-in-Charge.
M&L for Dismantling of ACB and Supply, fix ,test and commissionning in existing panel ACB manual drawout type with microprocessor release 4Pole, 1600 Amps, MDO, 50KA suitable for 415V, 3phase, AC supply including necessary modification in panel with 2 mm thick CRCA sheet door and suitable size of Copper bus bar with PVC sleev and inculing dismantling of burnt ACB all specified and directed.
M&L for Dismantling of ACB and Supply, fix ,test and commissionning in existing panel ACB manual drawout type with microprocessor release 4Pole, 1250 Amps, MDO, 50KA suitable for 415V, 3phase, AC supply including necessary modification in panel with 2 mm thick CRCA sheet door and suitable size of Copper bus bar with PVC sleev and inculing dismantling of burnt ACB all specified and directed.
M&L for Dismantling of ACB and Supply, fix ,test and commissionning in existing panel ACB manual drawout type with microprocessor release 4Pole, 8050 Amps, MDO, 50KA suitable for 415V, 3phase, AC supply including necessary modification in panel with 2 mm thick CRCA sheet door and suitable size of Copper bus bar with PVC sleev and inculing dismantling of burnt ACB all specified and directed.
M&L for replacement of LT panel board at R-4 garden, factory made pedestal cubical double door outdoor type, CPRI approved, modular construction fabricated out of 3.15 mm thick MS sheet, epoxy powder coated to give superior finish, totally enclosed, dust and vermin proof with locking arrangement (compartment wise) front & back side opening system including air louvers at both side, rain shed 15 cm all around, overall size of each incoming & out going modules should not be less than ( 350mm x300mm x400mm ), platform mounted having minimun clearance of 450 mm above ground level suitable for 415 Volts 3 phase 4 wire system 50 Hz supply, having ETP grade copper busbar strip (three phase & neutral) duly tapped in colour coded FRP sleeves install on porcelain /epoxy insulator, floor mounted type based on angle iron frame and legs 50x50x5 mm thick, front and rear opening with double shutter and having locking arrangement with 50 mm lock make Navtal or Harrison with three keys and including grouting of panel with necessary PCC work complete all as specified. The scope of work including provision of housing the following accessories:-
Incoming: - (i) MCCB 630 Amp 4 pole 36 KA 415 V with microprocessor release having protection against over current, earth fault, short circuits and inbuilt battery and display system - 01 No. Make: Schneider, L&T or Legrand. (ii) On Load Changeover switch 630 Amp, 415V, 4 pole with open execution with front handle - 01 No. Make: Schneider, L&T or Havells. (iii) Digital type Voltmeter ( 0-500 Volts), 3 phase, 4 digit, high resolution, LED type with onsite programmability- 01 Nos. Make: Securemeters, Reshab or L&T. (iv) Digital type Ampermeter ( 0-300 Amps) three phase with copper wound CT coil assy of suitable ratio & size Class I accuracy, 0.5 VA burden & onsite programmability - 01 Nos. Make: Securemeters, Reshab or L&T. (v) Indicating lamp LED type with holder key flush mounted, Red, Yellow, blue with toggle switch - 1 set ( set of three) as in incoming phases. (vi) Tinned copper bus bar strips made of copper of size 50x10mm suitable length-04 Nos Outgoing: - (i) MCCB 400 Amp 4 pole 36 KA 415 V with thermal magnetic release, Ics=100% Icu. - 01 No. Make: Schneider, L&T or Legrand. (ii) MCCB 250 Amp 4 pole 36 KA 415 V with thermal magnetic release, Ics=100% Icu. - 01 No. Make: Schneider, L&T or Legrand. (iii) MCCB 200 Amp 4 pole 36 KA 415 V with thermal magnetic release, Ics=100% Icu. - 06 No.s Make: Schneider, L&T or Legrand. (iv) All outgoing MCCB shall be connected through spreader and copper busbar not less than 5 mm thick strip. Note: All existing cable connections will be disconnected from old Panel carefully and re-connected with new Panel by providing glands and thimble all as directed by Engineer-in-Charge.
All as per Item No 49 above but scope of work including provision of housing the following accessories:- Incoming: - (i) MCCB 630 Amp 4 pole 36 KA 415 V with microprocessor release having protection against over current, earth fault, short circuits and inbuilt battery and display system - 01 No. Make: Schneider, L&T or Legrand. (ii) On Load Changeover switch 630 Amp, 415V, 4 pole with open execution with front handle - 01 No. Make: Schneider, L&T or Havells. (iii) Digital type Voltmeter ( 0-500 Volts), 3 phase, 4 digit, high resolution, LED type with onsite programmability- 01 Nos. Make: Securemeters, Reshab or L&T. (iv) Digital type Ampermeter ( 0-300 Amps) three phase with copper wound CT coil assy of suitable ratio & size Class I accuracy, 0.5 VA burden & onsite programmability - 01 Nos. Make: Securemeters, Reshab or L&T. (v) Indicating lamp LED type with holder key flush mounted, Red, Yellow, blue with toggle switch - 1 set ( set of three) as in incoming phases. (vi) Tinned copper bus bar strips made of copper of size 50x10mm suitable length-04 Nos Outgoing: - (i) MCCB 250 Amp 4 pole 36 KA 415 V with thermal magnetic release, Ics=100% Icu. - 04 No. Make: Schneider, L&T or Legrand. (ii) MCCB 200 Amp 4 pole 36 KA 415 V with thermal magnetic release, Ics=100% Icu. - 04 No. Make: Schneider, L&T or Legrand. (iii) MCCB 100 Amp 4 pole 25 KA 415 V with thermal magnetic release, Ics=100% Icu. - 02 No.s Make: Schneider, L&T or Legrand. (iv) All outgoing MCCB shall be connected through spreader and copper busbar not less than 5 mm thick strip. Note: All existing cable connections will be disconnected from old Panel carefully and re-connected with new Panel by providing glands and thimble all as directed by Engineer-in-Charge.
Note for item No 49 & 50 :- The panel drawing shall be submitted by contractor for approval before placing the order
Supply and fixing MCCBs thermal magnetic release,lcs=100% lcu in existing FP/panel, connecting to bus-bar with all connecting accessories and modification in busbar (if Necessary), connection complete and testting after complition, all as specified and directed, of following capacities :- Make-Legrand/Schneider/L&T/Standard/Havells/C&S
MCCB 63/100 Amps,16 kA,FP, 50 Hz.
MCCB 160 Amps,25 kA,FP,50 Hz.
MCCB 200 Amps,25 kA,FP,50 Hz.
MCCB 250 Amps,25 kA,FP,50 Hz.
M & L for replacement of ON Load change over switch 4 Pole, 415 Volt, in sheet steel enclosure of capacity 200 Amps complete all as specified & directed. Make-L&T/Schneider/Havells
All as per Item No.52 above but of capacity 63 Amps 4 ploe.
Supply & fix in repairs indicating lamp holder with bulb LED (Red, Yellow, Blue, Green) type to indicate incoming supply suitable for 24 V DC/110 VAC/230Volts AC and all as specified and directed. Make:Teknic/ C&S /L&T/Kaycee
M&L for taking out existing Panel and shifting of LT panel of any size with all accessories and fixing it to other location as directed by Engr-in-Charge at site, connecting cable connection with connecting accessories, incl foundation in PCC 1:3:6 type C2 all as specified and directed.
Darpan Construction
Genius Construction Co.
NOEL ENGINEERS
OM SAI POWER SYSTEMS
SHREE JAGDISH FURNITURE CO.
S S ENTERPRISES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .