Facilities Management Division, Bangalore
HINDUSTAN AERONAUTICS LIMITED Facilities Management Division, Bangalore
Providing External Power Supply to proposed Reverting hanger by providing additional Transformer at raw material substation at Aerospace Division HAL BC
7011
FM/NE-P/Advt./01/24-25 Dt:05.04.2024
Works
Electrical Planning and Contract Section-E and M Dept-FMD-Bangalore
₹1,180
₹71,200
13 May 2024
13 Apr 2024
13 Apr 2024
13 May 2024
Name of the Individual / Firm / Company: * Mandatory
Type of ownership
Details of Constitution or Legal Status such as certificate of incorporation, shops and establishments, etc.,
Address for correspondence:
Bank(s) details: [Copy of the cheque leaf to be uploaded]
Related Document to be Uploaded to eProcurement Portal (Note Cancelled cheque leaf to be uploaded)
PAN No.:
Average annual financial turn over during the last 3 years, ending 31st March of the previous financial year [ should not be less than 30% of Amount put to tender]
TURN OVER IN Rs:
Please Enter Turn over in Rupees for all the 3 years
Details of Registered Contractor
ESI No.:
GST Detail:
Please Enter GST Details
Related Document to be uploaded in ePortal
Contact details
Please Enter Contact person Name
Please Enter Mobile No
Valid Electrical contractor licence of appropriate voltage issued by any state Govt. under clause 45 of Indian Electricity Rules 1956 and as amended from time to time or to declare engage an electrical contractor who has the above mentioned licence and requisite experience.
Latest Bankers Solvency Certificate from Nationalized/ scheduled Bank issued within a period 12 months from the final date of submission of tender.
Please Enter Details to 'Name of the Bank' , 'Date of Issue','Value in C89``Rs. in Lakhs
Experience of having successfully completed similar works during last 7 years ending last day of month previous to the one in which applications are invited. [Latest work experience certificate may be uploaded] (i) THREE similar completed works each costing not less than the amount equal to 40% of the estimated amount put to tender. (ii) TWO similar completed works each costing not less than the amount equal to 50% of the estimated amount put to tender. (iii) ONE similar completed work costing not less than the amount equal to 80% of the estimated amount put to tender.
Type of Work: [Incase of private works the same shall be supported with TDS certificate]
Type of Work: [Incase of private works the same shall be supported with TDS certificate]
Please Enter Details for Work No II
work done
Type of Work: [Incase of private works the same shall be supported with TDS certificate]
Please Enter Details for Work No III
Details of person holding the power of Attorney :
Related Document to be Uploaded to eProcurement Portal
Please Enter Details for Person holding Power of Attorney
DECLARATION I
Please Accept the Declaration I
DECLARATION II
Please Accept the Declaration II
The payment terms shall be governed as per the terms indicated in special conditions of contract.
Basic Rate to be quoted for each item. Subject work is called on works contract basis and prevailing GST of 18% has been added in the BOQ on overall total. Any revision on this GST rate is to HAL account.
Sucessful offer that is L-1 (Lowest offer) will be determined including GST.
Amount towards GST will be paid along with RAR payment against invoice.
The tenderers are requested to abide by the rules of prevailing GST act.
This BOQ specification has to be read in conjunction with technical specifications and tender drawings. Any ambiguty in these have to be brought to the knowledge of contract section before submission of tender to avoid future claims/dispute.
Specification of item
1000 KVA, 11KV/415V Transfomer at Raw substation.
An external hand operated 'OFF' load tap changer with handle having a position indicating plate and locking device.
Explosive Vent/Pressure release valve(PRV)
Air releasing valve.
Double float buccholtz relay with an alarm and trip contacts.
De-hydrating breather with silica gel and oil seal etc.
Diagram and rating plate.
Earthing terminals.
Lifting hook
Drain valve
Filter valve.
Radiator with top and bottom stop valves and drain and air releasing plugs.
Conservator tank with Magnetic oil level indicator.
Dial type thermometer with MRP resetting devices with alarm and trip contacts.
Weatherproof marshalling box with connectors and control wiring cable gland including winding temperature indicator.
First fill of mineral oil.
Bars stud type neutral brought out through a separate bushing for earthing.
Bi-directional wheels with locking facility to arrest movements.
1 No. cable end box on HT side suitable for 1R of 3CX95 Sqmm 11KV XLPE insulated Aluminium armoured cable with Heat shrinkable type indoor cable end joints.
1 No. end box on LT side suitable to connect 1600A, 415V TPN Aluminium overhead sandwich bus trunking to LT Panel.
LT Panel at Substation (Extension of Existing LT Panel)
Incomer
1No - 1600A, 415V gr. 50KA, 4P MDO Type ACB
Lot - 1600A TP + 800A N, 415V, short circuit rated 50KA for 1sec, Aluminium bus bars with busbar insulators, heat shrinkable PVC sleeves etc.
1No- Multi function meter (MFM/MDM)suitable for 3ph, 4 wire, 240V(L-N), 5A, CL-1,RS 485 Port Digital MFM/MDM of power logic PM2230 of Schneider or any equivalent make meeting technical specification of above MFM complete in all respect.
1 Set of - 1600/5A current transformers of suitable class and VA burden for metering.
1Set of - 1600/5A or 1A current transformers of class 1 and 15VA burden for APFC realy.
1No- 13A 415V gr TP 100KA MPCB of for tapping power for metering and control circuit
1Set - RYB indicating lamps of LED module with 6A SP MCB.
1Set- 6A, MCB for the protection of measuring instruments.
Outgoings:
1 No - 1250A 415V gr. 50KA TP+NL MDO type ACB
1 No - 1000A 415V gr. 50KA TP+NL MDO type ACB
1 No - 800A 415V gr. 50KA TP+NL MDO type ACB
2Nos - 630A 415V gr. 50KA TP+NL MCCB
1 No - 400A 415V gr. 50KA TP+NL MCCB
1 No - 250A 415V gr. 50KA TP+NL MCCB
2 Nos - 125A 415V gr. 50KA TP+NL MCCB
Supply and laying in already excavated trench / masonary duct/ encasing in pipe/ fixing on wall using necessary M.S clamps testing & commissioning of 3C x 95sqmm 11KV XLPE insulated earthed aluminium conductor armoured HT U.G cable as specified in the technical specifications to the tender document and as directed by Engineer-in-charge. Note:- Excavation, concrete cutting and reconcreting will be measured separately.
Supply & laying in the already excavated cable trench/fixing on wall/duct wall with necessary M.S clamps / encasing in pipes etc., testing & commissioning of 3.5Cx300 Sqmm XLPE insulated Aluminium conductor 1100V gr. Armoured U.G cables complete with all necessary consumables as directed and as per technical specification. (LT panel to Capacitor Panel). Note:- Excavation, concrete cutting and reconcreting will be measured separately.
Supply, laying and connecting of 16C X 2.5 Sqmm size copper conductor XLPE insulated 1100V grade Armoured control cables including glands and end terminations using suitable copper lugs with suitable marking ferrules complete as directed by the EIC. Note:- Excavation, Concrete cutting and reconcreting will be measured separately. (HT panels to Tranformer)
Supply & providing of 3C x 95sqmm Heat shrinkable type indoor cable end joints for the existing 11KV armoured cable using suitable jointing kits of approved make with all required accessories complete in all respects, including connecting to the 11KV circuit switchgears/breakers/Transformer as directed by the Engineer-in-charge.
Supply and connecting indoor type cable end joints for 3.5Cx300 sqmm LT cable of 1.1KV gr., Aluminium conductor XLPE insulated armoured LT UG cables by employing necessary glands, terminals, bolts & nuts etc., complete in all respects.
1600A Bus Trunking (Outdoor)
Supply, erection, testing and commissioning of factory build IP-65/IP-66 rated with canopy for outdoor 1600A, 3 phase and neutral system with 100% neutral busbar 415V, 50Hz outdoor sandwich insulated Aluminium Bus Trunking fabricated out of Aluminum (High Conductivity) conductors having a rated single phase RMS short time current withstanding capacity as specified in technical specifications, including necessary clearance between Phase to Phase and Phase to Neutral/Earth, necessary creepages busbar insulation with class F grade uniformly applied to withstand the relevant di-electric properties, having good structural strength, Electrical characteristics etc., as per IS/IEC standards, with required bus duct fittings & accessories like horizontal and vertical bends, elbows, offset sections, reducers, busbar section joints, expansion joints, making necessary wall openings, making good the same by sealing the opening, replastering, suitable outdoor compatible wall bracket at the opening to avoid rain water leakage, re-painting of the re-made wall portion to match with existing finish etc., complete as per site requirement including providing internal continuous earthing using Aluminum strips of 50% of phase/neutral cross section area etc., complete and as per good Engineering practice. 1.5mm thick CRCA with powder coating with IK10/1.6mm Electro galvanised/ Hot dipped GI Sheet steel/ 2mm thick Aluminium enclosure powder coated to shade RAL 7032 or as per OEM standard.
Supply, connecting, testing and commissiong of 1600A rated Bi-metallic copper flexible connector for 3phase and neutral supply(4nos in each set) between transformer LT side bus bar and overhead sandwitch busbar trunking with required harwares including suitable outdoor type adopter box at transformer LT side for interconnection complete in all respect and as directed by OIC/EIC.
Supply, connecting, testing and commissiong of 1600A rated Aluminium flexible connector for 3phase and neutral supply(4nos in each set) between transformer LT Panel incomer bus bar and overhead sandwitch busbar trunking with required harwares including suitable Indoor type adopter box at transformer LT panel side for interconnection complete in all respect and as directed by OIC/EIC.
300 KVAR Automatic power factor correction panels
Incoming
1No - 800A 415V gr. 50KA, TPN ACB, ACB shall be Manually drawout(MDO) type. Air Circuit breaker shall be of approved make suitable for 415V 3 Ph & N supply with microprocessor based tripping device comprising of overload, short circuit and instantaneous ground fault protection including suitable range inbuilt CT's and separate LED indications for overload, short circuit and ground fault along with release and also micro switches for service, isolated and locking positions for the breaker, door interlock, secondary isolating contacts, auxiliary contacts as required including ON/OFF indications, trip push button, trip indication, front operating handle and other connected accessories complete in all respects. ACB should be rated for Icu=Ics=Icw for 50KA 1sec.
1 Lot-800A TP + 400A neutral Aluminium busbars with busbar insulators, heat shrinkable PVC sleeves etc.complete.
1 Set-800/5A current transformers of suitable class and VA burden for metering.
1 set Digital VAF meter
1no 16A 415V gr TP 50KA MPCB of for tapping power for metering and control circuit
1no suitable rating TP SPD
1Set RYB indicating lamps of LED module with 6A SP MCB.
1Set- 6A 415v gr TPN MCB for the protection of measuring instruments.
1Set - 3 Phase 12 channel Intelligent reactive power management controller (power factor correction relay), programmable for controlling thyristor switching module, suitable capacity SMPS, required control wiring, including necessary interconnections among CTs, thyristor switching modules etc., as per standards.
Outgoing
Suitable fans for ventilation
4Nos. - 50KVAR 415 volts filter unit comprising of not less than 66.2KVAr 525V 50Hz, super heavy duty MPP capacitor bank including 440volts grade 7% detuned aluminium reactor controlled by suitable capacity Thyristor switching module(SCR-SCR Type) for each bank separatley.
2Nos. - 30KVAR 415 volts filter unit comprising of not less than 40KVAr 525V 50Hz, super heavy duty MPP capacitor bank including 440volts grade 7% detuned aluminium reactor controlled by suitable capacity Thyristor switching module(SCR-SCR Type) for each bank separatley.
1No. - 20KVAR 415 volts filter unit comprising of not less than 26.5KVAr 525V 50Hz, super heavy duty MPP capacitor bank including 440volts grade 7% detuned aluminium reactor controlled by suitable capacity Thyristor switching module(SCR-SCR Type) for each bank separatley.
1No. - 10KVAR 415 volts filter unit comprising of not less than 13.2KVAr 525V 50Hz, super heavy duty MPP capacitor bank including 440volts grade 7% detuned aluminium reactor controlled by suitable capacity Thyristor switching module(SCR-SCR Type) for each bank separatley.
2Nos - 5KVAR 415 volts filter unit comprising of not less than 6.6KVAr 525V 50Hz, super heavy duty MPP capacitor bank including 440volts grade 7% detuned aluminium reactor controlled by suitable capacity Thyristor switching module(SCR-SCR Type) for each bank separatley.
6Nos of 125A, 36KA 415V Gr.TP TM based MCCB (for 50KVAR & 30 KVAR filter unit)
1No of 63A, 36KA 415V Gr.TP TM based MCCB (for 20KVAR filter unit)
3Nos of 32A, 36KA 415V Gr.TP TM based MCCB (for 10KVAR filter unit & 5KVAR filter unit)
Transformer Plinth
Transformer Plinth
Providing 150mm thick 1:4:8 cement concrete bed using 40mm graded aggregate including curing, etc., complete as directed by the Engineer-in-charge.(Required for transformer foundation bed & BBT foundation only)
Construction of size stone masonary with 1:8 cement mortar including curing etc., as directed by Engineer In Charge.
Rendering 10mm thick 1:6 cement plaster on fair faces of the above stone masonry including curing as directed by Engineer In Charge.
Providing 150mm thick 1:2:4 cement concrete using 20mm graded aggregate including curing etc., complete as directed by the Engineer-in-charge.(For BBT support foundation & coping for transformer plinth only)
Earthing
Supply, providing and Fixing Cast Iron Pipe earth station confirming to IS 3043 complete with 2750mm long, 100 mm Inner Dia(ID),13mm thickness CI Pipe, with 2 part clamp made out of G I flat 50 x 6 mm continously welded around the pipe using cast iron welding electrodes as per drawing. The cost also incudes excavation for earth pit, providing & laying homogenous mixture of charcoal lumps, salt & sand all around the pipe as per specification, supplying and fixing of RCC Collar of size 450 mm dia, 450 mm height and 50 mm thick over Cement concrete base of minimum size 150mm width & 100mm thick all around below collar shall be provided using 1:2:6 CC after necessary excavation, refilling of soil, consolidating, ramming, leveling of soil etc., supplying & fixing the label board(MS Plate of size 300mmx200mmX2mm) welding to the elctrode complete as per specification, std drawing, instructions of EIC.
Supply & providing earth stations using 600x600x3.15mm thick copper plate electrode complete at 2.5 mtr. below the ground level with 20mm dia class B G.I pipe for watering, G.I funnel etc. & Cement concrete base of minimum size 750x750x100mm thick shall be provided using 1:2:6 CC after necessary excavation, refilling of soil, consolidating, ramming, leveling of soil etc. and providing cement concrete chamber of inside dimension 300x300x300mm with a wall thickness of 120mm using 1:2:6 CC above the base concrete including providing 50mm thick RCC cover including required salt & charcoal, 2runs of 50x6 mm(300mm) copper strip from plate electrode upto top of the chamber etc. as per technical specification enclosed with the tender documents & as per IS 3043 complete in all respects[For Transformer neutral earthing].
G.I Strip
Supply, fixing & connecting the 50X6mm(300sqmm) size G.I strip on wall / clamping to the existing duct wall / fixing on steel structures/ laying 2 ft. below the ground level with necessary excavation, concrete cutting & re-concreting, refilling, consolidation & levelling of soil after laying for interconnection between the earth pits and LT panels earthing as directed by Engineer-in-charge. Note:- Excavation, concrete cutting & re-concreting will be measured separately.
Supply, fixing & connecting the 40X6mm(240 sqmm) size Copper strip on wall / clamping to the existing duct wall / laying in cable tray/ laying 2 ft. below the ground level with necessary excavation, concrete cutting & re-concreting, refilling, consolidation & levelling of soil after laying for interconnection between the earth pits and transformer neutral as directed by Engineer-in-charge. Note:- Excavation, concrete cutting & re-concreting will be measured separately.
Excavation in all types of soil for Cable trench/cable duct refilling, consolidating of soil after laying the cable including ramming and levelling to smooth finish as per the Technical specifications enclosed and as directed by the Engineer-in-charge. Note: Removing & shifting the excess digging soil/debris for making cable duct from the work site and deposit the same outside the HAL premises including loading, transportation etc., and as directed by EIC/OIC. as per the Technical specifications enclosed and as directed by the Engineer-in-charge.
Concrete cutting/Chipping the existing 1:2:4 heavy duty cement concrete road/floor using power/ hydraulic hammer including removing debris from the work site and deposit the same outside the HAL premises including loading, transportation etc., and as directed by EIC/OIC.
Re-concreting the cut portion with 1:2:4 cement concrete by employing 20mm graded aggregate granite of 150mm thick to smooth finish including curing, complete in all respects and as directed.
Disconnecting, Dismantling & shifting the APFC panel as-is-basis without any damage and Re-fixing & commssioning the same in substation as shown by Engineer-in-charge/Plant Maintenance department of Aerospace Division (Refer Drawing). The scope also includes disconnecting the existing cables from panel and reconnecting after shifting and erection of APFC panel, complete in all respects and as directed by the engineer-in-charge.
Dismantling, shifting and re-fixing in the same subtation of one no. Existing 300KVAR APFC panel comprising of incoming ACB and outgoings of 10No's of SDFU's with capacitor bank.
Disconnecting & removing of Existing 2Rx3.5cx300sqmm LT Al.Arm cables and re-routing and connecting to APFC panel
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
raw.json
RAW_JSON
Technical_Bid_EC2926.pdf
TENDER_DOCUMENT • 1.17 MB
Tender_dwg_1.pdf
TENDER_DOCUMENT • 0.28 MB
PQ_FreeView_EC_2926.pdf
TENDER_DOCUMENT • 0.21 MB
Tender_dwg_2.pdf
TENDER_DOCUMENT • 0.23 MB
Tender_Notice_EC2926_.pdf
TENDER_DOCUMENT • 0.13 MB
PB_Freeview_EC2926.pdf
TENDER_DOCUMENT • 0.34 MB
Amendment_No_1.pdf
TENDER_DOCUMENT • 0.04 MB
Undertaking_Letter_EC2926.pdf
TENDER_DOCUMENT • 0.02 MB
ECS_Format.pdf
TENDER_DOCUMENT • 0.01 MB
PQ_EC2926.xlsm
TENDER_DOCUMENT • 0.03 MB
Check_list.pdf
TENDER_DOCUMENT • 0.03 MB
Price_Bid_EC2926.xlsm
TENDER_DOCUMENT • 0.05 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .