Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.3 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹36.5 L+₹31,684 (0.88%)Rejected-Finance WZ 576 577 NANGAL RAYA NEW DELHI 110046 | NEW DELHI | NEW DELHI | DELHI | 110046 | L2 | Rejected-Finance Other than lowest | |
| 3 | L3₹43.8 L+₹7.6 L (21.1%)Rejected-Finance G 86 DATA RAM SECTOR 18 ROHINI NEW DELHI DELHI 110085 | NORTH WEST DELHI | DELHI | 110085 | L3 | Rejected-Finance Other than lowest | |
| 4 | L4₹47.7 L+₹11.5 L (31.9%)Rejected-Finance | L4 | Rejected-Finance Other than lowest |
Tender Value
₹47.5 L
EMD Value
₹94,940
Closing Date
11 Aug 2021, 6:00 pmClosed
GE (N) DELHI CANTT-10
GE (N) DELHI CANTT-10
REPAIR MAINT OF EXTRNAL ELECTRIC SUPPLY SYSTEM LT DISTRIBUTION NETWORK CABLES SWITCHGEAR INCL STREET SECURITY LIGHTS WITH CONNECTED ITEMS WORKS REPAIRS MAINT OF INTERNAL ELECTRIFICATION WORK SERVICES INCL REPLACEMENT OF UNSV WIRING VARIOUS TYPE
2021_MES_459603_1
GE/NORTH-36/2021-22
Open Tender
Civil Works
Item Rate
180 days
GE (N) DELHI CANTT-10
As per NIT
8 documents required · 8 mandatory
₹500
Yes
GE (N) DELHI CANTT-10
₹94,940
Yes
9 Sept 2021
14 Jul 2021
13 Aug 2021
14 Jul 2021
11 Aug 2021
28 Jul 2021
Amount
Excavation in trenches not exc 1.5 Mtr wide and n.exc 1.5 mtr in depth, getting out for electric cable and other works complete in any type of soil complete. Complete all as specified and directed.
Removing surplus excavated soil to a distance n.exc 50 mtr and depositing where directed at a level n. exc 1.5 mtr above starting point Complete all as specified and directed.
Returning, filling in, soil obtained from excavation including spreading, levelling, watering and well ramming in layers n.exc 25cm thick complete. Complete all as specified and directed.
Supply and laying sub class 'B' bricks laid dry and flat across the length of cable for protection of cable complete. Complete all as specified and directed.
M & L for sand cushioning for protection of cable with screen wash river sand complete. Complete all as specified and directed.
Labour only for taking out and relaying/ re-routing old/existing PVC/XLPE armoured aluminium conductor cable after repair complete of following sizes (Note :- Excavation & earth work, sand cushioning, bricks protection & GI pipe where required shall be measured & paid seperately) :-
Upto size 25 sqmm 2/3.5/4 Core
Size 35 sqmm to 70 Sqmm 3.5 Core
Size 95 sqmm to 150 sqmm 3.5 core
Size 185 sqmm 3.5 core and above
Checking & locating of fault in underground HT/LT cable of any size by cable fault locator machine complete all as directed
Dismantling & taking out HT/LT burnt cable ends of any size from transformer/LT panel/LT feeder pillar box/trenches any type/size, for repair/making suitable for reconnection to cable, providing lugs to burnt end of cables, preparing fresh terminals and reconnection, fixing the removed portion of cable with transformer/in trenches/along pole/ panel/feeder pillar box, including excavation of loop & refilling complete using old bricks and sand returning filling the excavated soil complete. Complete all as specified and directed.
M&L (in replacement) for GI tubing light grade with all necessary fittings laid in trenches/under road crossing/fixed on pole/wall/under floor including suitable mild steel FI clamps of required size complete for following sizes :-
40 mm bore
50 mm bore
80 mm bore
Supply and laying in repair cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of following size (Note :- Excavation & earth work, sand cushioning, bricks protection & GI pipe where required shall be measured & paid seperately) :-
10 Sqmm 2 core
16 sqmm 2 core
16 Sqmm 4 core
25 Sqmm 3.5 core
35 Sqmm 3.5 core
50 sqmm 3.5 core
70 sqmm 3.5 core
95 sqmm 3.5 core
120 sqmm 3.5 core
185 sqmm 3.5 core
400 sqmm 3.5 core
M&L Making hole below the road by drilling machine or hand drill without damaging road for inserting pipe upto 80 mm dia complete all as specified and directed (Note: GI pipe shall be measured & paid separately)
Dismantling & taking out defective LT PVC/ XLPE cable from trenches including excavation and earth work, cutting and removing defective parts and supply and fixing straight through joint heat shrink kit complete including jointing material and making connection of LT cables for the following sizes :-
25 sqmm 3.5 core to 50 sqmm, 3.5 core
70 sqmm 3.5 core to 120 sqmm, 3.5 core
150 sqmm 3.5 core to 400 sqmm 3.5 core
S&F in repair of 1100 volt grade, heavy duty cable PVC insulated aluminium conductor, unarmoured, multistranded, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended complete all as directed
16 Sqmm, twin core, flat or circular
Checking all incoming & outgoing connections and Mechanism, cleaning, servicing, overhauling, testing it for proper tripping system complete of 11 KV VCB of Make Crompton Greaves/AREVA/Siemens, installed at sub-station bldg, inspecting, servicing and testing all the connections of control wiring availability of proper DC supply and AC supply, cleaning of contacts, & terminals, using the blower for dusting, servicing of gears, including replacement of faulty control fuses, faulty wiring & faulty indication lamp, checking & closing of tripping system, taking out relay (over current relay and earth fault relay) from the 11 KV VCB and calibrating the relay and proper setting of relay and refixing back in existing position & testing for proper tripping/functioning system complete all as specified & directed [Note : (i) Necessary certificate for calibration of relay with setting detail shall be submitted by the contractor. (ii) Spare parts will be measured and paid separately]
S&F charging handle rod suitable for existing 11 KV VCB 630 amps capacity of make Crompton Greaves/Areva/ABB/Siemens complete all as directed
S&F in repair Charging Motor assembly set in existing VCB panel of existing make incl all connections & fixing arrangement and testing complete all as directed
S&F in repair Spring charging gear assembly (big size) for VCB upto 630 Amp as per existing make of VCB complete all as directed
S&F in repair Spring charging gear assembly (small size) for VCB upto 630 Amp as per existing make of VCB complete all as directed
S&F in repair power pack unit suitable for 220 volts AC input & 110 volts DC output complete with 12 volts, 7 AH sealed lead acid batteries and suitable voltmeter etc suitable for operation of HT Panel complete all as specified and directed
S&F in repair Tripping coil assembly 24 V DC for VCB 11 KV as per existing make of VCB complete all as directed
S&F in repair Closing coil assembly 24 V DC for VCB 11 KV as per existing make complete all as directed
S&F in repair TNC switch (Trip Neutral Close), with 2 NO + 2 NC suitable LT/HT Panel any type/size as per existing complete all as directed
S&F in repair heater, 230 Volt, as per existing wattage suitable for 11 KV HT VCB panel including electric connection complete all as specified & directed (Make - As per sample)
Disconnection of all electric connection & taking out old/defective Current Transformer (CT) from 11 KV VCB panel and Supply, fixing, installation & testing of Current transformer, indoor, single phase resin cast CTs of 100-50/5+5 amps ratio, Class 5P-10 with suitable VA burden and accuracy suitable for protection & metering incl making suitable arrangement for fixing in existing VCB panel and connection incl disconnection & taking out old/faulty current transformers (CTs) from 11 KV VCB panel complete all as specified & directed
Disconnection of all electric connection and taking down defective/unsv 11 KV PT and Supply, fixing, installation & testing of Potential transformer (PT) 3 phase, dry and draw out type 11 KV/110 Volt, with suitable VA burden per phase, accuracy class 1.0 complete with HT & LT HRC fuses for primary & secondary in VCB complete all as specified & directed Note for item No. 14 to 25 :- (i) All the instruments and T&P required for the above jobs shall be arranged by the contractor at site and cost of the deemed to be included in the above rates. (ii) The all above checking, inspection, installation & testing work shall be performed by HT expert/ engineer.
M&L for on line Dehydration of HV/ EHV grade transformer oil including filteration using automatic centrifuging machine minimum three cycles to achieve dielectric strength 50 to 60 KV breaking capacity by absorbing and abolishing all sludge particles as per BS-66-1963 including topping up with new transformer oil as required complete all as directed Note - (i) Centrifuging Machine with all T&P & testing machine of oil required for dehydration shall be arranged by the contractor. (ii) Oil required for topping up the transformer will be measured & paid separately.
M&L (in replacement) of Silica Gel (Blue colour) size not more than 5mm in breather of transformer after cleaning of breather.
M&L (in replacement) of breather of transformer of any make/capacity upto 630 KVA with exising size
Supply & filling new transformer oil of having dielectric strenght 60 KV to top up level complete all as specified and directed
M&L for replacement of fibre gasket sheet 5 mm thick to prevent leakage from transformer 11/0.433 KV ratio, upto 630 KVA capacity complete
S&F in repair LT Porcelain bushing with brass stud screwed with brass nuts, bolts and cork washer for transformer of capacity upto 630 KVA complete
S&F in repair HT 11 KV porcelain bushing with brass stud screwed with brass nuts, bolts and cork washer for transformer of capacity upto 630 KVA complete
M&L for replacement of porcelain insulator with suitable rubber 'O' ring for HT side bushing of transformer upto 630 KVA complete
All as per item 33 above but for LT side bushing
M&L for painting of transformer of capacity upto 400 KVA, outside portion only with one coat with spray painting with synthetic enamel paint after preparation of surface neat and clean for painting including numbering SM/MES No. with white paint complete all as directed
M&L (in repair) cable jointing kit for 11 KV cable for end termination cold shrink type joint with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following size:-
Size 70 sqmm to 120 sqmm, Indoor type
Size 70 sqmm to 120 sqmm, outdoor type
M&L (in repair) cable jointing kit for 11 KV (Earthed) grade cable for straight through cold shrink type joint with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable complete all as specified & directed for size 70 sqmm to 120 sqmm
Supply & laying in trenches/through pipes/ducts or on poles XLPE armoured cable of following sizes with aluminum conductor, 11 KV `E’ complete all as specified & directed of follwing sizes (Note :-Excavation & earth work, sand cushioning, bricks protection & GI pipe where required shall be measured & paid seperately) :-
95 Sqmm 3 core
120 Sqmm 3 core
M&L for chequered plate 5/6mm thick of required size for cable duct cover as required at site incl cutting & welding including painting with two coats of synthetic enamel paint over a coat of red oxide primer complete all as directed
Supply, installation, testing & commissioning (in replacement) of Gang operated air break switch with drop out fuse unit complete with 12 insulator set, HT 11 KV triple pole, 200 amps current rating complete with drop out fibre glass tube fuse, mechanically operated mechanism from ground level consisting of operating rod of 25 mm bore medium grade GI pipe of suitable length with locking arrengment, flat iron clamp 50mm x 6mm including MS channel of suitable size and length for fixing GOD including bolts, nuts and washers incl jumper connection with copper flexible designed jumper complete all as specified and directed
Cutting/ pruning of tree branches along/around over head line at places within a radius of 2 mtr from fasted conductor and removing from site and stretching the ACSR conductor complete all as directed .
M&L for painting of steel tubular poles 9 mtr to 11 mtr length with applying two coats of aluminium paint including cross arms and clamps except embedded portion of pole in ground and concrete after removing old painted surfaces by scraping of poles complete and two coat for making colour band/strip 30 CM with synthetic enamel paint of approved/yellow & black colour up to 1.2 mtr from coping level including numbering of poles complete all as directed
M&L for painting of RCC poles 8.5 mtr to 11 mtr long with two coat of cement based paint and two coat of synthetic enamelled paint in yellow & black stip 30cm up to 1.5 mtr above the ground level including preparation of surfaces complete and painting of connected cross arms, clamps with aluminium paint all as specified and directed.
M&L for spray painting of old/existing LT/HT panel/feeder piller box any size/type with powder coated paint withsmoke grey paint in outer/inner side of complete panel after cleaning and preparing surface complete all as specified & directed
M&L for replacement of door/ MS sheet of old/ existing LT panel board any type/size with cutting, welding & bend to shape and spray painting with powder coated paint with smoke grey paint in outer/inner side over one coat of primer after complete all as directed
M&L for replacement of lock assembly with key of old/ existing LT panel board any type/size complete all as directed
M&L for repair/overhauling of old LT panel board of any size/type, cleaning with compressed air, tightening of all electric connections to bus bar & switchgears, replacement of wornout lugs, nut, bolts, proper connection to main earth lead, glands to be provided/replaced as required at cable entries, fixing of door front & back side with proper locking arrangement, repair to PCC foundation as required at site and spray painting with powder coated paint with smoke grey paint in outer/inner side of panel after cleaning andpreparing surface incl sign writing complete all as directed
Supply, installation and connecting to electrical system in repair, LT distribution switch board panel cubical type for out door use, double door, with rigid hinges, door handles locking arrangement back side openable, compartmentalized design, mounted on suitable PCC blocks, fabricated out of CRCA sheet 3mm thick, suitably spaced, totally enclosed in chamber for reception of 3 phase, 440 V, 50 HZ, AC supply including all connection with aluminum strips, internal wiring with suitable size (minimum 1.5 sqmm) of PVC copper conductor wire with lugs. Panel shall be effectively PVC gasketed and sealed, glands to be provided at cable entries, powder coated painting and sign writing for in/out going connections all as specified & directed and comprising of following as under :-
4 Nos bus bars of high conductivity aluminium alloy, 3 Nos for phase (R,Y,B) rating 300 amp rating and 1 No for neutral rating 150 amp, mounted on DMC support with heat shrink sleeve - 01 set.
MCCB 4 pole, 200 amp, 415 volts, 25 KA - 01 No ( Incoming)
MCCB 4 pole 160 amp, 415 volts, 25 KA - 01 Nos. (outgoing)
MCCB 4 pole 63 amp, 415 volts, 16 KA - 05 No. (outgoing)
MCB SPN 63 amp, 240 volts, 'C' series,10 KA - 01 Nos. (outgoing)
Voltmeter (0-500V) digital type -01 No
Ammeter (0-200 amps) digital type with CT's - 01 No
Indication lamp (R,Y,B), LED type - One set of three
(jGrouting of panel including PCC work
All as per above item but LT panel comprising of following as under:-
4 Nos bus bars of high conductivity aluminium alloy, 3 Nos for phase (R,Y,B) rating 300 amp rating and 1 No for neutral rating 150 amp, mounted on DMC support with heat shrink sleeve - 01 set.
MCCB 4 pole, 160 amp, 415 volts, 25 KA - 01 No ( Incoming)
MCCB 4 pole 63 amp, 415 volts, 16 KA - 04 No. (outgoing)
MCB SPN 63 amp, 240 volts, 'C' series,10 KA - 01 No. (outgoing)
Voltmeter (0-500V) digital type -01 No
Ammeter (0-200 amps) digital type with CT's - 01 No
Indication lamp (R,Y,B), LED type - One set of three
Grouting of panel including PCC work
Servicing & overhauling of Air Circuit Breaker (ACB) of any capacity by taking out from existing LT panel, cleaning all parts internally and externally, checking of the proper tension of the springs mechanical mechanism, tightening of connection of moving, fixing contact, floating contacts, servicing of motor & charging system incl replacement of faulty parts/spares and re-fixing it on its original position and testing complete all as directed (Note :- Spare parts will be measured and paid separately under respective item)
Supply only following item/spares for Air Circuit Breaker (ACB) :-
Closing release of air circuit breaker
Shunt release of air circuit breaker
Under voltage release with time relay
S&F in repair 3 pole Power Contactor, MNX type of rating 32/40 amp AC3, closing coil 220 volt with auxiliary block (1 NO + 1 NC ) including electric connection in existing panel complete
S&F (in replacement) Capacitor metalized poly propylene heavy duty (MPP-H) for 3 phase 440 volts & 50 Hz system for permissible non- linear load 15% and connection in existing APFC panel complete of following capacity
M&L (in replacement) danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white with letters, figures and conventional skull and bones in signal red colour and fixed with M.S clamps, bolts and nuts of approved size for LT/HT 20 x 15 cm size complete all as specified and directed
S&F (in replacement) following items in the existing panel / location and connection with using aluminum lugs incl making necessary alteration in panel/door as required for proper fixing & connection complete all as specified and directed :-
MCB 4 pole 63 amps, 10 KA breaking capacity, B'' Series, 415 Volt
MCB 4 pole 100 amps, 10 KA breaking capacity, B'' Series, 415 Volt
MCCB 3 pole 63 amps, 16 KA breaking capacity, 415 Volt
MCCB 3 Pole 100 amps, 16 KA breaking capacity, 415 Volt
MCCB 3 Pole 125 amps, 25 KA breaking capacity, 415 Volt
MCCB 3 Pole 200 amps, 35 KA breaking capacity, 415 Volt
MCCB 4 Pole 200 amps, 25 KA breaking capacity, 415 Volt
MCCB 4 Pole 250 amps, 35 KA breaking capacity, 415 Volt
Volt meter (0 to 500 volts) digital type, three phase of size 96mm x 96mm
Amp meter (0 to 300 amps) digital type, three phase of size 96mm x 96mm with suitable CTs
Indicator lamp, LED type
Multifunction Meter, digital type, three phase, size 80mm x 80mm, accuracy class 1.0 for monitoring of various electric parameters such as voltage, current, wattage, frequency, power factor etc.
Note :- for item No 55 (i) MCCB should be properly fited in existing compartment and operating handle of MCCB should be proper in opening existing cover/door of compartment of LT panel board.
S&F (in replacement) lightning arrester, metal oxide type (gap less) for out door use complete with all fittings and fixing arrangements, transmission class, discharge capacity 65 kilo amps, suitable for 11000 volts including brackets, clamps, nuts, bolts, washers and connecting to earth wire 4mm dia GI with manufacturers test certificate complete all as specified & directed
S&F steel tubular electric pole, swaged, type 410 SP-31 (9 metre long) complete with CI base plate, bolts, nuts & screws incl 06 Nos hole on top edge for holding of D-clamp & insulators complete all as specified including the following:-
Excavation in post hole not exceeding 1.5 Mtr wide & 2 Mtr deep for pole foundation & getting out in soft loose soil, returning, filling in the excavated soil after fixing the pole in foundation, ramming earth around in layers n.exc 25 cm thick and disposal of surplus soil to a distance n.exc 50 metres.
Providing PCC 1:4:8, type D2 (using 40 mm graded stone aggregate) in foundation 600mm x 600mm x 1500 mm (planting depth) for concrete encasing the pole upto GL
Providing PCC 1:3:6, type C2 (using 40 mm graded stone aggregate) for plinth block /Collar above GL, 300 mm high and 450 mm dia
Painting of pole externally with one coats of black bituminous paint (upto planting depth) and above plinth block/ concrete collar with two coats of aluminium paint over a coat of red oxide primer including preparation of surfaces including painting of 30 cm wide black bands/strip 3 Nos with synthetic enamel paint in alternate layers upto the height of 1.5 Mtr above coping level
Dismantling and taking out unsv / damaged PCC pole any size/type complete
Taking down defective/ damaged ACSR conductor of any size and supply, fixing and stringing ACSR (Not less than Weasel) conductor not less than weasel including provn of binding wire etc for LT distribution line and replacement of all wornout nut bolts and washers complete all as specified and directed.
Taking down defective/ damage GI earth wire and supply, fixing and stringing of galvanised steel wire 4 mm dia for continuous earthing complete all as specified and directed
S&F (in replacement) pin/ shackle insulator of 100 mm height, 65 mm dia for 1100 volt grade porcelain vitreous white brown or green including one galvanised mild steel spindle two galvanised iron washers and one galvanised iron nut all as specified and directed.
Dismantling & taking down defective stay asembly and S&F stay assembly compring of 7/10 SWG galvanised stay stranded wire of reqd length fixed to pole with and including flat iron clamp, bolts, nuts and washers, galvanised 14mm dia, 400mm long stay bow with 16mm dia 180 cms, long stay rod with threded ends, GI nut & washers GI stay plate 230 x 230 x 6mm thick plate 2 Nos thimble, MS clamp made out of 50 x 6mm flat iron loop insulator 90mm x 140mm dia, hole 25mm porcelain complete all as specified and shown in electrical plate No 1 of SSR Part I including cost of the following:-
Excavation in post holes in any type of soil, returning filling and well ramming including disposal of surplus soil to distance n.exc 50mtrs from starting points.
PCC (1:3:6) type C2, using 40mm graded stone aggregated as in foundation.
M&L for replacement of galvanised stay strand 7/2.5 with proper tightening all as specified and directed
M&L for galvanised stay bow of 14mm dia including threaded end with nut all as specified and directed
M&L in repair for cross arms, bracing, supports, clamps and back plate, fabricated from structural steel section including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size including painting with two coats of synthetic enamel paint over a coat of red oxide primer complete all as directed after dismantling and taking out damage/rusted cross arms, bracings, supports, clamps and back plates from existing poles / pole structures complete all as directed.
S&F (in replacement) bracket for street light made out of 40 mm bore GI pipe medium grade not less than 1.2 mtr length bent to shape fixed on pole/wall with and including 50x6mm FI clamps = 02 Nos with nut bolts, washers including painting of clamps with two coats of synthetic enamel paint over a coat of red oxide primer complete
M&L in repair for loop junction box, outdoor type, size 30cmx20cmX15cm, made out of engineering plastic one piece moulding type, bus bar rating 63 amps 4 strips aluminium with bus bar mounting colour R, Y, B, N on DMC unbreakable insulator with cable entry main supply from bottom side and pole light connection from back side, simens grey colout, shock proof, rust proof, fire retardant, having front opening and locking arrangement with MCB SP 10 amps - 01 No, box duly fixed on the pole with flat iron clamp of size 25 mmX3mm with nuts & bolts complete all as specified and directed (Note : Cost of incoming& outgoing cable lugs & glands of suitable size deemed to be included in the quoted rate)
M&L (in replacement) for LED street/security light fittings 60 watt, made up of of pressure die cast aluminium housing with toughned glass and individual high power LEDs with secondary optics, IP 66 protection, clamp type suitable for 32-50mm dia bracket pipe, to be mounted on existing/ new GI bracket and connecting the street light fitting using 1.5 Sqmm PVC insulated copper cable complete all as directed. (Note - New GI bracket with clamp shall be measured & paid seperately)
M&L for LED Flood Light luminaire, energy saving & enviornmental friendly, long life diecast aluminium, IP65, with high power LED as light source incl necessary fixing arrangement with clamps of suitable size and connection using 1.5 Sqmm PVC insulated copper cable complete all as directed for following wattage
M&L for replacment of double compression stainless steel gland for power cable incl electric connection complete with new lugs/thimble complete all as directed
Size 22.9 mm dia suitable for 16 sqmm 4 core LT cable
Size 28.9 mm dia suitable for 25 Sqmm 3.5/4 core LT cable
Size 32.1 mm dia suitable for 35 to 50 sqmm 3.5/4 core LT cable
Size 37.7 mm dia suitable for 70 sqmm 3.5/4 core LT cable
Size 41.7 mm dia suitable for 95 sqmm 3.5/4 core LT cable
Size 47.1 mm dia suitable for 120 sqmm 3.5/4 core LT cable
Size 51.4 mm dia suitable for 150 sqmm 3.5/4 core LT cable
Size 56.6 mm dia suitable for 185 sqmm 3.5/4 core LT cable
Repair of earth pit incl required exacavation, earth work and PCC work to make good damaged/disturbed surfaces of earth pit chamber & making new pit cover of RCC 1:2:4 type B-1 using 20mm graded stone aggregate reinforced and lifting handle on RCC cover with 8 mm MS bars at 150 mm centre to centre both ways incl supply & fixing of wire mesh and funnel including re-connection of earth wire/strip with panel/transformer using GI nut, bolts & washer complete all as specified & directed
M&L for earthing complete with galvanised steel earth plate electrode 600x600x6mm thick directly buried in ground (earth pit not less than 2.25 m deep below ground level) with top edge of earth plate not less than 1.5m below the ground level connected to GI strip 32 x 6mm by means of bolts nuts check nuts and washers of galvanised iron at 2 points & GI pipe 15 mm bore light grade for protection of earthing wire PCC chamber 1:3:6 (type C-1) using 20mm graded stone aggregate, watering pipe 20mm bore light grade, funnel with wire mesh, 50 mm thick cover of RCC 1:2:4 type B-1 using 20mm graded stone aggregate reinforced with 8 mm MS bars at 150 mm centre to centre both ways and charcoal dust and common salt all as shown in electrical plate No. 3 of MES SSR part-I and including excavation & earth work & connecting the earthing point/equipment and testing complete
All as per item No 72 above item but for 4 mm GI wire
Supply of HT electric Rubber Mat sheet of size 1m x 2 m x 25 mm thick, ISI marked
All as above but for LT 15 mm thick
Taking down defective street light fitting any wattage from pole and repair the same including replacement of defective/ faulty LED driver and re-fixing the same incl connection complete all as directed
Supply only bitumen HT tape impregnated size 25 mm width complete
S&F Galvanised iron nut, bolt & washer any size as required at site complete all as directed
M&L for fabrication of sign board made out of heavy duty MS square pipe 40 x 40 mm for legs, MS angle iron 40x40 x5 mm thick for frame and MS sheet 3 mm thick and legs of sign board embedded in PCC (1:2:4) in 20 mm graded aggregate upto 45 cm including painting with one coat of red oxide paint and two coat of synthetic enamelled paint complete all as directed
M&L for writing letters or figures (Block, Roman,italic or indian ) n exc. 30 cm hight complete all as directed
S&F in repair time switch, digital type having suitable rating street light timer panel incl connection complete all as directed
S&F in repair off load changeover switch with sheet metal enclosure 63 Amp, 4 Pole, 415 volt incl connection complete all as directed
S&F in repair switch disconnector fuse unit with sheet metal enclosure TPN 100 Amp, 415 volt including HRC fuses incl connection complete all as directed
S&F in repair of PVC line seperator 10mm dia suitable for five wire of overhead conductor complete all as specified & directed
Taking down carefully copper/aluminium point wiring (light/fan/socket or power) complete including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets etc including making good the disturbed surfaces to match with the existing complete
Taking down unserviceable main switches, DBs including MCBs, bus bars chambers etc from wall / existing main boards and removing from site complete
M&L for point wiring with single core FRLS, PVC insulated, unsheathed multi stranded copper conductor of size 1.5 sqmm alongwith 1.5 sqmm earth wire of multi strand copper conductor (with same specification) drawing through existing conduit pipe including replacement of sunk zinc coated pressed steel terminal box of 1.60mm thick with 3mm thick plastic laminated sheet top cover, brass screws, cup washers etc and making good to the disturbed surfaces to match the existing complete for the following :-
One light point controlled by one switch
One ceiling/exhaust fan point controlled by one switch
One socket outlet 5 Amps controlled by one switch on same board
One socket outlet 5 amps controlled by one switch on independent board
One bell point controlled by one bell push switch
All as per item No 87 above but wiring with 2.5sqmm copper wire and 1.5sqmm earth wire for socket out let 16 Amps on independent board
All as per item No 87 above but wiring with 4 sq mm PVC insulated multi-stranded copper conductor for industrial socket outlet 3 pin 16 / 20 Amps point and one single core 2.5 sq mm PVC insulated unsheathed copper cable as earth continuity conductor
M&L for point wiring concealed type with 1.5 Sq.mm nominal cross sectional area, single core, 1100 Volts grade, multi-stranded, PVC insulated, unsheathed FRLS copper conductor cable including continuous earth wire of size 1.5 Sqmm nominal cross sectional area, single core, 1100 Volts grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable connected to common earth and earth dolly with suitable copper lugs drawing into and including rigid non-metallic PVC surface conduit of 20mm dia or higher, medium grade complete with all PVC conduit accessories,GI metal flush box of 1.60 mm thick suitable for modular/conventional switches/sockets/fan regulators with cover plates (modular type/conventional type as reqd) blanking plates, brass screws, cup washers etc including all cutting / chases etc in walls and making good to the disturbed surfaces to match the existing complete all as specified and directed for the followings :-
One light point controlled by one switch
One ceiling/exhaust fan point controlled by one switch
One socket outlet 5 Amps controlled by one switch on same board
One socket outlet 5 amps controlled by one switch on independent board
One bell point controlled by one bell push switch
All as per serial item No 90 above but with 2.5 Sqmm nominal cross sectional area copper conductor cable for one 16 Amps socket outlet point on independent board with 1.5 Sqmm nominal cross sectional area copper conductor cable as continuous earth wire.
All as per item No.90 above but wiring with 4 sq mm PVC insulated multi-stranded copper conductor for industrial socket outlet 3 pin 16 / 20 Amps point and one single core 2.5 sq mm PVC insulated unsheathed copper cable as earth continuity conductor
M&L for point wiring surface type with 1.5 Sq.mm nominal cross sectional area, single core, 1100 Volts grade, multi-stranded, PVC insulated, unsheathed FRLS copper conductor cable including continuous earth wire of size 1.5 Sqmm nominal cross sectional area, single core, 1100 Volts grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable connected to common earth and earth dolly with suitable copper lugs drawing into and including rigid non-metallic PVC concealed conduit of 20mm dia or higher, medium grade complete with all PVC conduit accessories,GI metal flush box of 1.60mm thick suitable for modular/conventionalswitches/sockets/fan regulators with cover plates (modular type/conventional type as reqd) blanking plates, brass screws, cup washers etc including all cutting / chases etc in walls and making good to the disturbed surfaces to match the existing complete all as specified and directed for the following :-
One light point controlled by one switch
One ceiling/exhaust fan point controlled by one switch
One socket outlet 5 amps controlled by one switch on independent board
One socket outlet 5 Amps controlled by one switch on same board
All as per serial item No 93 above but with 2.5 Sqmm nominal cross sectional area copper conductor cable for one 16 Amps socket outlet point on independent board with 1.5 Sqmm nominal cross sectional area copper conductor cable as continuous earth wire.
S&F Switch piano flush type 5/6 Amps single pole one way 230 Volts complete
S&F Switch piano flush type 15/16 A single pole one way 230 Volts complete
S&F Socket Outlet 2 in 1, 3 pin 5 Amps flush type 230 Volt complete
S&F Socket Outlet 2 in 1, 3/6 pin 5 and 15 Amp flush type 230 Volts complete
S/F Bell push, flush type 5 Amps 230 Volts complete
S&F electronic fan step regulator fiush type 120 watt, 230 Volt complete
S&F ding dong bell, AC, 230 volts, single pole complete
S&F lamp holder, 230 volt AC, PVC / Polycarbonate type with back plate suitable for batten fitting including 9 watt LED bulb inverter type upto 4 Hrs back up 6500 K complete all as specified & directed
S&F ceiling rose, 6 Amps, 250 volts, AC with three terminals and PVC / Polycarbonate insulated body of 50 x 25mm size complete
S&F modular switch 6 Amps, one way, one module 240 volts complete
S&F modular socket, 3 pin 6 Amps,240 volts, 2 module complete
S&F modular switch 16 A, 1 module,240 volts complete
S&F modular socket 6/16 A, 5 pin, 2 module, 240 volts complete
S&F modular Bell push 6 Amps, one module 240 volts complete
S&F modular fan regulator, step type, 120 W, humfree, AC, 230 volts, 2 module complete
S&F sheet metal enclosure with Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 Amps 'C' curve, 240 Volt complete
M&L in repair for two single core (submain) PVC insulated cable with 4 sqmm nominal cross sectional area stranded copper conductor and one single core green PVC insulated 4 sqmm stranded copper conductor earth continuity cable drawn through non metallic rigid PVC conduit 20 mm dia concealed in wall including all conduit and fixing accessories including cutting chases & making disturbed surfaces complete
All as per above but with 6 sqmm and 6 sqmm as earth wire
S&F MCB DB, single pole and neutral with 200 Amps rated bus bar, 230 volts, glazed, double door type, IP-43, including connecting all connections of wire to MCBs with proper lugs & making good to the disturbed surface complete for the following no of way :-
S&F loadline distribution box 4 way, AC, TP & neutral metal enclosure, Glazed double dooor, 415 V, AC, IP-43, concealed type with suitable bus bar, neutral link, earth link suitable for MCCB 63/100 Amps as incomer and MCB SP as out going complete all as directed Note:- MCCB shall be measured and paid seperately
S&F MCB DP/SPN, 240 Volts, AC of breaking capacity 10 KA, 'C' curve and connections by using suitable copper lugs complete of following rating :-
S&F MCB SP, 240 Volts, AC, 6 to 32 amps, breaking capacity 10 KA, 'C' curve and connection by using suitable copper lugs complete
S&F MCCB 4 Pole, 415 volt, AC, fixed type, with breaking capacity 16 KA suitable for load line DB & connection complete of following rating :-
63 amps rating
100 amps rating
Supplying and laying in replacement or fixing or passing through pipe, 1100 volts grade PVC insulated aluminium stranded conductor cable served with inner sheathing of PVC tape and overall PVC sheathed in service connections one twin core cable flat or circuler for the following size of cables :-
S&F in repair of switch piano, flush type, 5/6 Amp, single pole, one way, 230 volts Complete all as specified and directed.
S&F in repair of socket outlet 2 in 1, 3 pin, 5/6 Amp, flush type, 230 volts Complete all as specified and directed.
S&F in repair of switch piano flush type 15/16 Amp, single pole, one way, 230 volts Complete all as specified and directed.
S&F in repair of socket outlet 2 in 1, 3/6 pin 5 and 15 Amp, flush type, 230 volts Complete all as specified and directed.
S&F in repair of Bell Push, flush type, 6 Amp, 230 Volts Complete all as specified and directed.
S&F in repair electronic fan step regulator fiush type 120 watt, 230 Volt Complete all as specified and directed.
S&F in repair of modular switch 10 amps single pole one module, 230 volts Complete all as specified and directed.
S&F in repair of universal moudlar socket ,10 Amps, 5 pin, 2 module, 230 volts Complete all as specified and directed.
S&F in repair of modular switch 16/20 amps single pole one module, 230 volts Complete all as specified and directed.
S&F in repair of modular socket 16/20 amps, 2 module, 230 volts Complete all as specified and directed.
S&F in repair of modular bell push with indicator 6 amps, one module Complete all as specified and directed.
S&F in repair of modular fan step regulator 120 watt 2 module , 230 volts Complete all as specified and directed.
S&F in repair of GI metal flush box 1.60 mm thick incl making good to disturbed surface to match with the existing complete all as specified for following sizes .
S&F in repair of 3mm thick plastic laminated sheet cover with brass screws , cup wahser and cutting of grooves for switchs,scoket and regulator etc complete all as directed for following sizes.
S&F in repair LED Bulkhead luminaire 10 watt of polycarbonate housing and enclosed with acrylic diffuser IP-65 protection incl connection complete all as specified & directed
S&F in repair LED Post top lantern luminaire with die cast aluminium spigot, lid cover and clear acrylic cover 40 watt, 5700 K with IP-65 protection incl connection complete
S&F in repair wall mounted LED batten with aluminium housing and initigrated electronic drive 18/20 watt fixture 4 feet provided for efficient heat dissipation with polycorbonate diffuser and integrated electronic driver and all accessories pre-wired including connecting up with twin core flat flexible copper conductor cable of suitable size complete all as directed
S&F in repair surface and wall mounted LED batten 10 watt 2 feet long extruded aluminium housing provided for efficient heat dessipation with polycarbonate diffusser and integrated electronic drive, pre-wired including connecting up with twin core flat flexible copper conductor cable of suitable size complete
S&F in repair wall mounting bracket decorative luminaire powder coated housing,SS finish fixture with opal glass diffuser suitable for GLS, B-22 lamp incl connection complete all as directed
S&F in repair of highly efficient recessed mounted round shape downlight 5 watt, 230 volts, clear white light, CCT 6000K with driver incl connection complete all as directed.
S&F in repair P-5, LED PLL Lamp, 18 watt, 230 volt for existing false ceiling G-11 base light fitting complete all as directed)
S&F in repair highly efficient round shape downlighter 25 watt, 240 volt, CCT 5700 K with driver suitable for ceiling cutout 225 mm dia incl connection complete all as directed
S&F (in replacement) LED landscape bollard light 10 watt, 230 volt, inverted pyramid tripod type with soft 360 degree distribution, IP-65 protection, incl necessary civil work for grouting & foundation work of suitable sizewith PCC work complete all as specified and directed
S&F in repair 5 W LED T5 TL fitting (1ft) attractive wall mounted type suitable for mirror fittings, all accessories pre wired including up with twin core flat flexible copper conductor cable of suitable size complete all as specified and as directed.
S&F in repair surface/ceiling mounted LED panel type of size 2ft x 2ft, 36W, 230V, 5700K complete with driver full window glarefree opal diffuser LED panel with CRCA powder coated white housing complete with all accessories required for connection and making good the disturbed ceiling complete
S&F in repair of LED linear surface/ suspended fittings, extruded aluminium body with opal polycarbonate diffuser, 38 watt, 4 ft long, CCT 6000 K incl connection complete
S&F in repair decorative gate light made up of high grade unbreakable polycarbonate material suitable for & alongwith 10 watt LED bulb with B22 base complete all as directed
S&F energy saving LED security light fitting of 45 watts with pressure die-cast aluminium IP 66 luminaire with high power LED as light source comprising with electronic driver and all accessories prewired incl connecting up with PVC insulated copper conductor cable 1.5 sqmm, 3 core for connections and incl suitable GI tube bracket for mounting of light fitting, bend to shape at required degree and fixed to wall by means of suitable flat iron clamps, nuts, bolts and washers etc complete all as specified and directed.
S&F in repair exhaust fan 300 mm sweep, 230V, AC, steel body with louver shutter etc complete and connection from ceiling rose to fan terminal incl cutting of hole at wall for required size and making good disturbed surface complete all as directed
S&F in repair wall mounting fan 400 mm sweep, adjustable, plastic blade grill for protection, pull cord control for speed and oscillation on-off, ABS body incl connection complete all as directed
S&F in repair PVC flexible twin twisted copper conductor cable multi strand of size 0.5 sqmm nominal cross section complete
S&F electronic energy meter, current rating 10-60 amps, 240 Volt, AC, single phase, 2 Wire, accuracy Class 1.0, with LCD display incl/ fitted with temper proof meter box, weather proof, transparent, made out of FR polycarbonate, dust proof, good mechanical strength conforming to IS: 14772/2000,IP-65, size not less than 260 mm x 190 mm x 120 mm incl connection and depositing old meter to MES store complete all as directed
S&F in repair energy meter box wall mounting type of size 1000x1000x250mm made out of 2 mm thick MS (CRCA) sheet having six compatment having door for each single phase electric meter, including cutting, welding & bend to required shape and painting complete with one coat red oxide paint & two coat of synthetic enamelled paint complete all as directed (Note: Electric Meter will be measured and paid separately)
S&F in repair temper proof meter box for three phase energy meter made out of FR polycarbonate, dust proof, good mechanical strength conforming to IS: 14772/2000, IP-65, size not less than 260 mm x 190 mm x 120 mm incl connection complete all as directed
M&L for dismantling of unsv C/Fan of any make/model/sweep, cutting and removing the old defective/burnt winding, cleaning the core of fan motor and rewinding the fan motor with super enamelled copper winding wire of same gauge with insulating material and varnishing the core assembly, drying the moisture content to get appropricate speed and re-assemble the same complete all as directed (Note :- The cost of copper winding wire is deemed to be included in the quoted rate)
All as per item No 153 above but for exhaust fan upto 300mm sweep size
All as per item No 153 above but for exhaust fan of 380/450mm sweep size
S&F in repair capacitor 2.5/3.15 MFD suitable for C/fan incl connection complete
M&L in repair ball bearing suitable for any type/size/make of fan Complete all as specified and directed.
S&F in repair factory made metallic louver shutter duly painted complete all as specified and as directed for following size of exhaust fan :
300 mm sweep
450 mm sweep
M&L in repair factory made metallic fan blades of existing pattern ,size and colour scheme for complete all as specified and as directed for following size of exhaust fan :-
300 mm sweep
450 mm sweep
S&F in repair factory made ceiling fan down rod made out of heavy duty MS conduit pipe of 15mm dia duly with powder coat painted hole at both ends for passing cable/nut and cut at one end for fixing of fan shaft including nut bolt complete all as specified for the following sizes :-
Taking down carefully electric geyser of any type and capacity by disconnecting electric and water supply connection, opening nut, bolt, washer and replacing the defective parts and reassembling after cleaning and replacing defective parts and re-installing the same in original position and making necessary electric and water supply connection and testing complete all as specified and directed. (Note: Spare items shall be measured and paid seperately as supply only under relevant items)
Supply only geyser inner water tank 35/50Ltrs capacity steel body as per sample ,duly tested complete all as specified and directed.
All as per item No 162 above item but 25 Ltrs capacity
Supply only heating element capacity 1.5 KW (Round/Triangular) ISI marked suitable for geyser (as per sample) complete.
All as per item No 164 above item but capacity 2 KW.
Supply only thermostat suitable for 50/35/25 ltrs capacity geysers
Supply only Heavy duty hot water connection, SS rope threaded type with brass unions at both ends, 45cm long 15mm bore complete.
Supply only indicator lamp, Red/Green suitable for geyser of any type/capacity (Make as per sample)
Supply only geyser base plate assembly of any capacity any model all as specified and directed complete (Make as per sample)
S&F in replacement of outer cover MS sheet/ABS body of geysers 25 to 50 Ltrs capacity complete
S&F in repair Plug top, 3 pin, 05 amps, 230 volt complete
S&F in repair Plug top, 3 pin, 15 amps, 230 volt complete
S&F in repair PVC insulated and sheathed flexible cable 3 core Multi-stranded copper conductor size 2.5 Sqmm 1100 volt grade after taking out old unserviceable one including electric connection complete all as specified and directed
Supply, installation and connecting to electrical system in repair, LT distribution switch board panel cubical type for out door use, double door, with rigid hinges, door handles locking arrangement back side openable, compartmentalized design, mounted on suitable PCC blocks, fabricated out of CRCA sheet 3mm thick, suitably spaced, totally enclosed in chamber for reception of 3 phase, 440 V, 50 HZ, AC supply including all connection with aluminum strips, internal wiring with suitable size (minimum 1.5 sqmm) of PVC copper conductor wire with lugs. Panel shall be effectively PVC gasketed and sealed, glands to be provided at cable entries, powder coated painting and sign writing for in/out going connections all as specified & directed and comprising of following as under :-
(4 Nos bus bars of high conductivity aluminium alloy, 3 Nos for phase (R,Y,B) rating 400 amp rating and 1 No for neutral rating 200 amp, mounted on DMC support with heat shrink sleeve - 01 set.
MCCB 4 pole, 250 amp, 415 volts, 25 KA - 01 No ( Incoming)
MCCB 4 pole 160 amp, 415 volts, 25 KA - 05 Nos. (outgoing)
MCCB 4 pole 125 amp, 415 volts, 16 KA - 01 No. (outgoing)
(Voltmeter (0-500V) digital type -01 No
Ammeter (0-200 amps) digital type with CT's - 01 No
Indication lamp (R,Y,B), LED type - One set of three
Grouting of panel including PCC work
Supply, installation and connecting to electrical system in repair, LT distribution switch board panel cubical type for out door use, double door, with rigid hinges, door handles locking arrangement back side openable, compartmentalized design, mounted on suitable PCC blocks, fabricated out of CRCA sheet 3mm thick, suitably spaced, totally enclosed in chamber for reception of 3 phase, 440 V, 50 HZ, AC supply including all connection with aluminum strips, internal wiring with suitable size (minimum 1.5 sqmm) of PVC copper conductor wire with lugs. Panel shall be effectively PVC gasketed and sealed, glands to be provided at cable entries, powder coated painting and sign writing for in/out going connections all as specified & directed and comprising of following as under :-
4 Nos bus bars of high conductivity aluminium alloy, 3 Nos for phase (R,Y,B) rating 300 amp rating and 1 No for neutral rating 150 amp, mounted on DMC support with heat shrink sleeve - 01 set.
MCCB 4 pole, 160 amp, 415 volts, 25 KA - 01 No ( Incoming)
MCCB 4 pole, 160 amp, 415 volts, 25 KA - 01 No ( Incoming)
MCCB 4 pole 63 amp, 415 volts, 16 KA - 03 Nos. (outgoing)
MCB TPN 63 amp, 240 volts, 'C' series,10 KA - 08 Nos. (outgoing)
Voltmeter (0-500V) digital type -01 No
Ammeter (0-200 amps) digital type with CT's - 01 No
Indication lamp (R,Y,B), LED type - One set of three
Grouting of panel including PCC work
S&F in repair fresh air ventilating Fan 230/250 mm sweep, 230V, AC, plastic body with louver shutter etc complete and connection from ceiling rose to fan terminal incl cutting of hole at wall of required size and making good disturbed surface complete
Sch of Credit- Total contract sum shall be calculated after deduction of Sch of Credit amount Credit amount - 186754.00
Shiv Enterprises
NEETU TRADERS (INDIA)
Surjit and Sons
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .