| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.0 LAccepted-Finance | L1 | Accepted-Finance technically qualified | |
| 2 | L2₹5.5 L+₹45,166 (8.98%)Accepted-Finance | L2 | Accepted-Finance technically qualified | |
| 3 | L3₹5.7 L+₹65,568 (13.0%)Accepted-Finance | L3 | Accepted-Finance technically qualified |
Tender Value
Refer Docs
EMD Value
₹10,500
Closing Date
25 Jun 2020, 2:00 pmClosed
Executive Engineer, EDD Leh
Office of the Executive Engineer, Electric Distribution Division Leh
Supply Installation Testing and Commissioning of 100KVA Substation along with laying of HT/LT line at Camp Office of Ladakh Police Headquarters Near NHPC Guest House Leh
2020_PDNRE_40_1
e-NIT NO 06 of 2020-21
Open Tender
Electrical Works
Turn-key
7 days
Leh
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
Payable To SE,Power Distribution Circle Ladakh
₹10,500
22 Jul 2020
13 Jun 2020
27 Jun 2020
15 Jun 2020
25 Jun 2020
17 Jun 2020
Amount
ST pole 09 Mtr. Long (410Mpa-SP-33, working load of 300KG) complete with pit excavation in hard soil, refilling the pit with soil and boulders as per REC Standard for sub-station
ST pole 08Mtr. Long (410Mpa-SP-15, with working load of 200Kg) complete with pit excavation in hard soil, refilling the pit with soil and boulders as per REC Standard
GI V- cross-arm (75 x 40x6mm) with GI Angle Pole Top Bracket (50x50x6 mm) including back clamps of 50X8 mm for fixing V-Cross arm and pole top bracket without making holes in the ST pole along with GI nuts & bolts as per REC standard for single pole structure.
11/0.433kV, 3-phase 100KVA Distribution Transformers with Bimetallic Terminal Connectors Energy Level- 2, (Aluminium wound upto 200kVA, Copper wound for 250kVA or higher kVA ratings) , and with LV Cable Box having detachable Aluminium Gland plate
Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
11kV Horn Gap Fuse Set 3 Phase 200A
120mm² (2Ckt) Cable for 100KVA, 1.1kV Grade, PVC Insulated Stranded Conductor FRLS type
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
GI Channel/Angle/Flat of sizes including clamps for sub-station (Refer REC Construction Standard F1)
Galvinized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. (Refer REC Construction standard F-10)
11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
LT Distribution Box for 100 DTR with TPN MCCB short circuit rating 16KA for incomer & 160A (100KVA) and suitable MCCB for outgoing Circuits with terminal extensions as per REC standard
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete (Sub-station pole)
Wedge Connectors / PG Clamps
Danger Plates with Clamps (HT/LT)
GI Barbed Wire for Anti Climbing (Sub-station pole)
3-Ø, 4-Wire Prodigy Meter with CT (AMR complaint)
Cement bottoming 1:2:4 mix as per REC standards .5cum/pole for 9 mtrs
Cement bottoming 1:2:4 mix as per REC standards 0.45 Cumic/pole for 8 Mtrs pole
Painting of Poles Red Oxide
Painting of Poles Aluminium Paint
Sundry items like aluminium lugs, Jumpers, binding Tape (for sub-station)
GI channel (75x40x6 mm) cross arms 4' including GI back clamps of 50X8 mm along with GI nuts & bolts as per REC standard.
0.03 ACSR Weasel Conductor including jumpering (single conductor length) in HT/LT line
LT Shackle insulator along with nuts & bolts as per REC standard.
Earthing of ST poles complete by GI Rod 20mm 2.5 mtr long through GI strip as per REC standards
M/S MUNEER HASSAN AKHON
ROYAL HAYAN CONSTRUCTION AND COMPANY
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .