Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Rejected-Technical | Rejected-Technical requred paper is not submited |
| 4 | Rejected-Technical | Rejected-Technical Required papaer is not submit |
Tender Value
Refer Docs
EMD Value
₹4,000
Closing Date
5 Apr 2024, 4:00 pmClosed
SE
132 KV Hydil colony husainabad Jaunpur
work for repairing of 33KV VCB and control panel and miselaneious work area of EDD-III Jnp under jurisdiction of EE ETD-I Jaunpur
2024_PVVNV_920571_1
100/EDC-I(Jnp)/2023-24
Open Tender
Electrical Works
Lump-sum
180 days
work
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,180
SE EDC-I jaunpur
₹4,000
Yes
23 Apr 2024
28 Mar 2024
6 Apr 2024
28 Mar 2024
5 Apr 2024
28 Mar 2024
Repairing gear box with spring charging of 33 KV VCB operating machanism of different make .
Repairing and testing of 33/11 KV Transformer (3PF+01EF ) relay panel for alarm with triping by replaacing damaged components like transformers microprocessor Ics, chips, capacitor,diode resister A/D converters, display rectifier etc. if any required installed at various 33/11 KV Sub Station under EDC-1 jaunpur Works includes feruling and proper termination of connection in terminal blocks identifiying the proper continuity of protection cable from relay to CT decondary and checking of proper star point earthing of protction core.
Testing of 33 KV Breker Panel Brekers including testing of CTR Both by Primery Injection. Works includs cleaing and adjustment of relay contact and seting , cheking of closing and triping of brekers on remote / manual and protection trip commond CT by means of Primary Injection. Cheaking of actual triping time using VCB analiger and compresion with calculated time.
Testing of 33 KV Power Transfarmer pannel marshaling box and Brekers by Primery Injection. Testing of winding temprature Oil tempreature , Oil lable indicator, Buchholz Relay , surger Relay for alarm and tripig testing of relay. work includes cleaning and adjustment of Relay contacts and springs and cheaking of breaker's operation for remote/local closing tripiing and protection trip command genrated pb primery Injection. .
Testing of 11 KV Incoming /Outgoing Pannel including Testing of CTR by primary injection , testing of relays. Work includs cleaning of relay contacts and adjustment of spring . Cheaking operation and triping of VCB/OCB on remote/manual and protection trip command genrated through Primary injection. Cheaking of actual triping time using VCB analiger and compresion with calculated time.
Tesing of 33/11 KV 05 /08/10 MVA Power Transfarmer with its control pannel at various sub-stations under ETD-I JAUNPUR. Including following test: :- No Load/Ratio Test, Short Circuit tes, Magnetization current test, Magnatik Balance test, Insulation Test, Buchholz, OTI/WTI Circuite Test and allorm system, Earth resistance of Transformer Body , Neutral to Earth.
NARAYAN INFOTECH
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .