Loading…
Loading…
Tender ID
Tender Value
₹4.3 L
EMD Value
₹8,660
Closing Date
24 Feb 2026, 1:00 pmClosed
Executive Engineer,JDA Division No.I
Executive Engineer,JDA Division No.1 Rail Head Complex, Jammu
Three Phase Power Supply through 25 KVA Servo Stabilizer to 02 Nos New 08 Passenger Lifts at South Block A2 Shopping Complex Bahu Plaza, Jammu 2nd Time
2026_HAUDD_302895_1
JDA/I/2025-26/e-NIT/88 Dated 11-02-2026
Open Tender
Electrical Works
Percentage
60 days
Jammu
As per NIT
3 documents required · 3 mandatory
₹500
Vice Chairman, JDA
₹8,660
27 Apr 2026
11 Feb 2026
24 Feb 2026
11 Feb 2026
24 Feb 2026
11 Feb 2026
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable In surface/ recessed steel conduit, with modular switch, moduler plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conducter single core cable etc. Group B (Make - Havells/Polycab/HPL/equivalent)
Wiring for circuit/submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor,single core cable in surface/recessed medium class PVBC conduit 2x 1.5 sq.mm +1x1.5 sr.mm earth wire (Make - Havells/Polycab/HPL/equivalent)
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC Insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit 2 X 2.5 sq.mm + 1 x 2.5 sq. mm earth wire (Make - Havells/Polycab/HPL/equivalent)
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/recessed medium class PVC conduit 2 x 4 sq.mm + 1x4 sq. mm earth wire (Make - Havells/Polycab/HPL/equivalent)
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/recessed medium class PVC conduit 2x6 sq.mm + 1x6 sq. mm earth wire
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC 6 Insulated copper conductor, single core cable in surface/recessed medium class PVC conduit 4 x 16 sq.mm + 2 x 6 sq. mm earth wire (Make - Havells/Polycab/HPL/equivalent)
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate 15/16 A switch (Make - Havells/Anchor/equivalent)
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate 6 pin 15/16 a socket outlet (Make - Havells/Anchor/equivalent)
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate 5/6 A switch (Make - Havells/Anchor/equivalent)
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate 3 pin 5/6 A socket outlet (Make - Havells/Anchor/equivalent)
SITC of GI Strip 25 x 3 mm (ISI Marked)
SITC of Chemical Earthingwith 14.2 mm Copper Earthing Pipe 3mtr length
Supplying and fixing following Modular base & cover plate on existing modular metal boxes 3 Module
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, 1 interconnections, powder painted includlng earthing 4 way (4 + 12), Double door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10KA, "C" curve, miniature circuit breaker suitable for inductive load of following poles In the existing MCB DB complete with connections, testing and commissioning Single pole (Make: Havells/equivalent)
Supplying and fixing 5A to 32 A rating, 240/415V, 10KA, "C" curve, miniature circuit breaker suitable for inductive load of following poles In the existing MCB DB complete with connections, testing and commissioning Triple pole and neutral (Make: Havells/equivalent)
Supplying and fixing following rating, double pole, 240 V, Isolator In the existing MCB DB complete with connections, testing and commissioning 63 A (Make: Havells/equivalent)
Supply & fixing bulk head with 9W LED Bulb
SITC of Exhaust Fans for new wash rooms 12" Size (Heavey Duty) (Make Havells / Bajaj / Crompton)
SITC of Copper Wound 1200mm Ceiling Fan with double ball beaming (Make Havells / Bajaj I Crompton)
SITC of LED Tube Light with batten type flttting 20Watts (Make - HPL / Havells I Crompton I Phillips/ Wipro)
SITC of 3-Phase 25KVA Copper Wound Servo Controller Automatic Voltage Regulator 3-Phase unit indoor type voltage Range:295-465 V or Specified by the customers. Output Voltages:400 V +/-1% (Can be set anywhere between 3801-415V) Output Voltage Regulation : +1% of set coltage over the specified input range from no laod ro full load ( Oil Cooled) Make Eletric field (Equalant)
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections modular plate (Make: Havells/equivalent)
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note: Vertical type MCB TPDB is normally used where 3 phase outlets 12 way (4 + 36), Double door
stage.html
html • 0.02 MB
cancelled_1.pdf
pdf • 0.13 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.65 MB
Bank_R.pdf
Other Document • 0.03 MB
BOQ_983055.xls
BOQ • 0.32 MB
Extension.pdf
PDF • 0.29 MB
Corrigendum.pdf
PDF • 0.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .