GE (AF) ADAMPUR
GE (AF) ADAMPUR
SPECIAL REPAIR / RENEWAL / REPLACEMENT OF TRANSFORMERS DECLARED BER AT 8 WG AT AF STN ADAMPUR
2026_MES_799422_1
GE(AF)/ADM/T-58 OF 2026-27
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Under GE (AF) ADAMPUR
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE (AF) ADAMPUR
₹74,600
Yes
19 Nov 2026
19 Nov 2026
14 Dec 2026
19 Nov 2026
11 Dec 2026
4 Dec 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Dismantling and deposing of old 50 to 200 KVA Transformer from site to E/M Store including transportation (distance- upto 5 KM), labour and crane charges complete all as specified and directed. | 6 | Each Job | - | - |
| 2 | Supply, install, testing and commissioning of transformer stepdown 200 KVA outdoor type Oil immersed, ONAN copper wound complete with all standard accessories, vector group DYN 11/0.415 suitable for continuous duty for operation on AC 3 phase, 50 HZ with off load Tap changer to vary secondary voltage ±7.5 % in steps of 2.5% including transformer oil upto appropriate level all as per IS : 1180-2014 with latest energy efficiency level-2 with the following fitting/acessories all as directed:-
[a] Conservator with oil filling hole, drain plug, oil level indicator. [b] Two nos earthing terminal. [c] Rating and diagram plate. [d] Air release plug. [e] Off load tap changer. [f] Silica gel breather. [g] Four nos Bi-directional rollers. [h] Drain cum filter valve . [j] Top filter valve. [k] Thermometer pocket. [l] Radiator with butterfly valves. [m] Explosion vent with single diaphragm. [n] HV cable box. [o] LV cable box. Note : - Necessary provision is required to entry box of transformer for LT cable 3.5 core, 120 to 185 Sqmm single run on LT side and 3 core 95/120 sqmm cable on HT side including fixing arrangement in transformer with terminal box etc. | 1 | Each | - | - |
| 3 | All same as per item No 2 here-in-before but indoor type | 2 | Each | - | - |
| 4 | Supply, install, testing and commissioning of transformer stepdown 100 KVA indoor type Oil immersed, ONAN copper wound complete with all standard accessories, vector group DYN 11/0.415 suitable for continuous duty for operation on AC 3 phase, 50 HZ with off load Tap changer to vary secondary voltage ±7.5 % in steps of 2.5% including transformer oil upto appropriate level all as per IS : 1180-2014 with latest energy efficiency level-2 with the following fitting/acessories all as directed:-
[a] Conservator with oil filling hole, drain plug, oil level indicator. [b] Two nos earthing terminal. [c] Rating and diagram plate. [d] Air release plug. [e] Off load tap changer. [f] Silica gel breather. [g] Four nos Bi-directional rollers. [h] Drain cum filter valve . [j] Top filter valve. [k] Thermometer pocket. [l] Radiator with butterfly valves. [m] Explosion vent with single diaphragm. [n] HV cable box. [o] LV cable box. Note : - Necessary provision is required to entry box of transformer for LT cable 3.5 core, 120 Sqmm single run on LT side and 3 core 95/120 sqmm cable on HT side including fixing arrangement in transformer with terminal box etc. | 1 | Each | - | - |
| 5 | Supply, install, testing and commissioning of transformer stepdown 63 KVA indoor type Oil immersed, ONAN copper wound complete with all standard accessories, vector group DYN 11/0.415 suitable for continuous duty for operation on AC 3 phase, 50 HZ with off load Tap changer to vary secondary voltage ±7.5 % in steps of 2.5% including transformer oil upto appropriate level all as per IS : 1180-2014 with latest energy efficiency level-2 with the following fitting/acessories all as directed:-
[a] Conservator with oil filling hole, drain plug, oil level indicator. [b] Two nos earthing terminal. [c] Rating and diagram plate. [d] Air release plug. [e] Off load tap changer. [f] Silica gel breather. [g] Four nos Bi-directional rollers. [h] Drain cum filter valve . [j] Top filter valve. [k] Thermometer pocket. [l] Radiator with butterfly valves. [m] Explosion vent with single diaphragm. [n] HV cable box. [o] LV cable box. Note :- Necessary provision is required to entry box of transformer for LT cable 3.5 core 70 to 95 Sqmm single run on LT side and 3 core 95/120 sqmm cable on HT side including fixing arrangement in transformer with terminal box etc. | 2 | Each | - | - |
| 6 | S&F cable jointing kit for 11 KV grade cable for indoor termination, heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 3x95 Sqmm. complete all as specified and directed. | 3 | Each | - | - |
| 7 | S&F cable jointing kit for 11 KV grade cable for indoor termination, heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 3x120 Sqmm complete all as specified and directed. | 3 | Each | - | - |
| 8 | S&F cable jointing kit for 11 KV grade cable for out door termination, heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 3x120 Sqmm. complete all as specified and directed. | 1 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.41 MB
BOQ_896919.xls
BOQ • 0.30 MB
tender58.pdf
Tender Documents • 0.95 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .