Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹10.1 CrAccepted-AOC VPO TEHSIL JAWALI DISTT KANGRA HP | KANGRA | HIMACHAL PRADESH | 175013 | ₹10.1 Cr Quoted ₹10.5 Cr | 1 | Accepted-AOC Due to L-1 |
| 2 | 2₹10.9 CrRejected-Finance | ₹10.9 Cr | 2 | Rejected-Finance due to L-2 |
| 3 | 3₹12.4 CrRejected-Finance | ₹12.4 Cr | 3 | Rejected-Finance due to L-3 |
| 4 | 4₹12.8 CrRejected-Finance VILL FAZALPUR BEHIND FOCAL POINT NEAR RANDHAWA MASADAN JALANDHAR | JALANDHAR | JALANDHAR | PUNJAB | ₹12.8 Cr | 4 | Rejected-Finance due to L-4 |
Tender Value
₹9.2 Cr
EMD Value
₹9.5 L
Closing Date
29 Dec 2021, 11:00 amClosed
Executive Engineer
Jal Shakti Division,Amb
Sub Head-Providing and laying of Rising main , Supply and Errection of Pumping machinery , Distribution System and C/O Civil work i.e. Pump Houses , collection Tank , Over Head tanks etc.
2021_HPIPH_54365_1
EE-JS-Divn Amb-CB-Tender LWSS Mata Chintpurni
Open Tender
Civil Works
365 days
Amb
Please refer Tender documents.
14 documents required · 14 mandatory
₹2,500
Executive Engineer JS Divn. Amb
₹9.5 L
Hamipur
22 Apr 2022
13 Dec 2021
29 Dec 2021
13 Dec 2021
29 Dec 2021
13 Dec 2021
13 Dec 2021 - 17 Dec 2021
20 Dec 2021
Amount
C/O Pump Houses,Toilet/Septic Tank, Collection Tank,OHSR 170000,90000,and 35000 ltr.Electrical installation
Excavation in foundation and trenches etc.(in pipes and pits) in all kinds of soils such as pick work, jumper work, blasting in soft/hard rock, chiselling/wedging out of rock/where blasting prohibited) saturated soil stacking the excavated soil as directed by the Engineer-in-charge as directed by the Engineer –in-charge in all leads and lifts.
Providing and laying cement concrete 1:6:12 (1Cement: 6 Sand:12 Graded stone aggregate 40mm nominal size) and curing complete excluding the cost of form work foundation and plinth in all leads and lifts
Providing and laying cement concrete work 1:2:4 (1Cement: 2 Sand:4 Graded stone aggregate 20mm nominal size) and curing complete excluding the cost of form work and reinforcement for reinforced concrete work in:-
a) Foundation,footing,bases of columns & the like & mass concrete etc.
b) Rectangular portion upto Ground level
Providing and laying cement concrete (M-10) 1: 3: 6 ( 1 cement : 3sand: 6 graded stone aggregate 40 mm nominal size) and curing complete excluding the cost of form work in foundation and plinth in all leads and lifts and as per the direction of the .Engineer-in-Chaarge.
(a) Brick work using common burnt clay building bricks (Ist class) in foundation and plinth in cement mortar 1:6 (1cement:6 sand) in all leads and lifts.
(b) Brick work using common burnt clay building bricks (Ist class) in super structure above plinth level upto floor two level in cement mortar 1:6 (1cement:6 sand) in all leads and lifts.
Brick work using common burnt clay building bricks (Ist class) in foundation and plinth above plinth level upto floor two level in cement mortar 1:4 (1cement:4 sand) in all leads and lifts.
Providing wood work in frames of doors, windows and other frames wrought framed and fixed in position with second class deodar wood in all leads and lifts.
Providing and fixing wood paneled glazed or paneled and glazed shutters for doors, windows and clear story 40mm thick windows including bright finished black enameled iron with necessary screws with second class deodar wood 40mm thick in all leads and lifts.
Prov. & fixing wire gauge shutters using galvanized MS wire gauge of IS gauge designation 85 G. with wire of dia. 0.56 mm for doors,windows & clerestrey windows including bright finished black enameled iron hinges with necessary screws.
Providing form work with steel plates 3.15mm thick welded with angle iron in frame 30x30x5mm, so as to give a fair finish including centring, shuttering , strutting and propping etc. with wooden battens and ballies height of propping and centering below supporting floor to ceiling not exceeding 4meters and removal of the same for insitu reinforced concrete and plain.
a)Flat surfaces such as soffits of suspended floors, roofs, landings and the like floors upto 200mm kin thickness.
b) Beams,cantilevers,girders & lintels, sides & soffits of beams, haunching, cantilevers, bressumers 1.00 mts. In depth in all heights from floor.
c) Edges of slabs and breaks in floors & walls under 20 cms. Wide.
d) Vertical surfaces such as wall (any thickness but not less than 0.1 mtr. Thickness) attached pillasters,buttresses,plinth & string courses etc. From top of foundation level up to all floor levels in all leads and lifts the entrire satifaction of the Engineer-in-Charge.
Providing and laying cement concrete work 1:2:4 (1Cement: 2 Sand:4 Graded stone aggregate 20mm nominal size) and curing complete excluding the cost of form work and reinforcement for reinforced concrete work in:-
a) Suspended floors, roofs, landings and shelves and their supports, balconies, beams ,griders bressumers and cantilevers upto all floor level.
Providing and laying cement concrete work 1:1.5:3 (1Cement: 1.50 Sand:3 Graded stone aggregate 20mm nominal size) and curing complete excluding the cost of form work and reinforcement for reinforced concrete work in:-
a) Lintels, beams ,griders bressumers and cantilevers upto all floor level.
b)Arches upto floor all level including all leads and lifts complete.
Cement concrets flooring 1:2:4 (1 cement :2 sand :4 graded stone aggregate 20mm nominal size) laid in one layer finished with a floating coat of neat cement (40mm thick) as per direction and to the entire satisfaciton of Engineer-in-charge upto all lead and lift.
20mm cement plaster in single coat of rough sides of bricks/concrete stone walls for interior plastering upto floor two level including arrises internal rounded angles chamber and rounded angles not exceeding 80mm in girth and finished even and smooth in cement mortar 1:6(1cement:6sand) within all leads and lifts.
20mm cement plaster in single coat of rough sides of bricks/concrete stone walls for interior plastering upto floor two level including arrises internal rounded angles chamber and rounded angles not exceeding 80mm in girth and finished even and smooth in cement mortar 1:4(1cement:4sand) within all leads and lifts.
Pointing on brick masonry in cement mortor 1:3 (! cement:3 sand)
6 mm cement plaster to ceiling in CM 1:4 (1Cement :4 Sand)
Providing plinth protection 50mm thick in cement concrete 1:3:6 (1cement:3sand:6 graded stone aggregate 20mm nominal size) including finishing of the top surface of concrete smooth in all leads and lifts.
Providing under layers for plinth protection of 75 mm thick( unconsolidated) bed dry brick / stone aggregated 40 mm nominal size will rammed & consolidated & grouted with fine sand including preparation of ground.
Providing Tor steel reinforcement for RCC work including bending,binding & placing in position complete upto floor two level.
Applying two coat of wood preservative on new wood based surface after and including preparing the surface by thoroughly cleaning dirt dust and other foreign matter.
Applying priming coat over new wood and wood based surface after and including preparing the surface by thoroughly cleaning oil dirt grease and other foreign matter sand papering and knotting ready mixed paint brushing wood primer pink in all leads and lifts.
Painting two coats(excluding priming coat) on new wood and wood based surface with ready mixed paint brushing the give and even shade including cleaning of all dirt dust and other foreign matter and sand papering and stopping with ready mixed paint other than white in all leads and lifts.
White washing with lime on undecorated walls surface (two coats) to give an even shade including thoroughly brooming the surface dirt dust mortar dirt and other foreign matter in all leads and lifts.
Finishing wall with water proofing cement paint of approved brand & manufacture & of required shade on undecorated wall surfaces (two coats) to give an even shade after thotoughly brushing the surface to remove all dirt & remains of loose powdered materials.
Providing and fixing M.S.fan clamp(Type-I of 16mm dial M.S. Bar bent to shape with hooked ends in RCC. Slab during laying including painting the exposed portion of loop all as per standard design complete.
Providing 40x3mm flat iron hold fast 40cm long including fixing to frame with 10mm dial meters bolts and nuts and wooden plug and embeding in cement mortar block 30x10x15cm (1:3:6(1cement:3sand:6 graded stone aggregate 20mm nominal size.
Providing and fixing following anodized aluminium fittings of anodized transparent and shade with necessary screw etc.complete
(a) Sliding door bolts 250x16mm.
(b-i) M.S. tower bolts (Barrel type) leads and lifts. 200x10mm.
(b-ii) M.S. tower bolts (Barrel type) leads and lifts. 150x10mm.
(b-iii) M.S. tower bolts (Barrel type) leads and lifts. 100x10mm.
(c-i) M.S. handles 125mm dia
(c-ii) M.S. handles 100mm dia
Providing and fixing of MS round bars (16 mm) in windows and ventilators.
Half brick masonry in common burnt clay building in cement mortor 1:4 (1Cement:4 Sand)
Stone/Boulder filling under floors/behind retaining walls.
Providing and Fixing of Gantry system 5 MT.Capacity complete in all respect and as per the direction of the Engineer - in- Charge.
Providing and fixing pressed steel door frame manufactured from commercial MS sheets of 1.25 mm thickness including hinges jump lock jamb, bead if required angle thrshold of MS angle 50x25 mm or base ite of 1,25 mm presses MS welded or rigidly fixed together by mechanical means, adjustable lugs with split and tails to each jamb including steel butt hinges 2.5 mm thick with guards, lck strike plate and shock as specified and laying a coat of steel
P/F Toilet Sheet(Orrisa Pan) Cera /Hindustan Make
P/F Plastic Tank(500 ltr) Santex,Vectos,Plasto Make
P/F Flushing Cistern(5 ltr) Cera /Hindustan Make
Providing and fixing CI Man Hole cover with frame (Medium duty) 500mm internal dia weight of cover not less then 100Kg i/c carriage of material in all leads and lifts.
Providing and fixing sand cast/Cast iron spun spigot & socket soil, waste and vent. Pipe 100mm dia i/c cowl with in all leads and lifts.
Collection tanks, OHSR Tank,
Providing and laying cement concrete M 30 not less then 1:1.5:3 (1 Cement :1.5 and:3 stone aggregate 20mm nominal size) and curing complete excluding the cost of form work & reinforcement for reinforced concrete work in Wall (any thickness, but not less than 0.10 m thickness) attached pilasters, buttresses, plinth & string course etc. from top of foundation level upto floor two level with in all leads and lifts and as per the direction of the Engineer - in- Charge.
a) In foundation and plinth including carriage of material in all leads and lifts.
b)Wall (any thickness but not less than 0.10m thickness) attached pillars, pilasters, buttresses, plinth and string courses etc. from top of foundation level up to all floor level including carriage of material in all leads and lifts.
Providing form work of ordinary timber plankings, so as to give rough finish including centring, shuttering, strutting and propping etc. with wooden battans and ballies height of propping and centring below supporting floor to ceiling not exceeding 4m and removal of the same for insitu reinforced concrete and plain In Arches upto any span in all leads and lifts and as per the direction of the Engineer-in-Charge.
a)Arches exceeding 6 mtr. In span within all leads and lifts.
Providing and fixing 200mm wide CI Rungs with chequarred/ Ribbed non slip surfaces i/c fixing in M/hole with 200X100X100mm cement conc. 1:3:6 (1 cement:3 Sand:6 Stone aggregate 40mm nominal size) in all leads and lifts the satisfation of the Engineer-in Charge.
Providing , Laying and jointing inlet, outlet and over flow pipe of suitable dia including carriage of material in all leads and lifts.
Providing , Laying and jointing GMS pipe scour 125mm dia (Medium class) including carriage of material in all leads and lifts.
Providing & fixing 100 mm dia CI Sluice valve RG/Kirloskar/LP/leader/Kirloskar/Suchdeva/any other approved make(with hand wheel) as per IS : 780-1984 class-I upto 300 mm dia.(i/c brass spindle & as per 2906-1984 class-II for dia.> 300 mm) complete with bolts nuts,rubber insertion etc.,(the tail piece if required shall be measured & paid for separatly)
Providing and Fixing sand cast/cast iron spun spigot and socket soil waste and ventilating pipe 100mm dia including carriage of material in all leads and lifts.
Providing & fixing CI man hole cover having fram (Medium duty) 500mm internal dia Weight of cover not less than 58 Kg Including carriage of material within all leads & lifts.
Providing and laying cement concrete using M - 30 concrete mix with not less than 1:1.5:3 (1 cement:1.5 Sand:3 )graded stone aggregate20 mm nominal size) withminimum&Maximum contents 360Kg/m3 & 400Kg/M3 max water cement ratio 0.45asper IS3370 Part-I)2009 Curing complete excluding the cost ofcentring&shuttering in wall I/C attached Butterersses Floor to level.
a)Foundation,footing.bases of columns & the like & the mass concrete.
b)Wall (any thickness,but not less than 0.10 mtr.thickness) attached pilasters,buttresses,plinth & string courses etc. from top of foundation level upto floor two level
(i) floor four level to floor five level
c)Column,pillars,posts & struts upto floor two level
(ii) floor two level to floor three level
(iii) floor three level to floor four level
(iv) floor four level to floor five level
d)Lintels,beams girders bressumers & cantilevers upto floor two level
(ii) floor two level to floor three level
(iii) floor three level to floor four level
e) Arches upto floor two level:
(ii) floor two level to floor three level
(iii) floor three level to floor four level
f)Suspended floors,roofs,landings.etc. upto floor two level
(i) floor two level to floor three level
Providing form work with steel plates 3.15mm thick welded with angle iron in frame 30x30x5mm, so as to give a fair finish including centring, shuttering , strutting and propping etc. with wooden battens and ballies height of propping and centering below supporting floor two level.
(i) Foundation,footing,bases of columns etc.and mass concrete.
(ii) Flat surface such as soffits of suspended floors,roofs,landing and the like
(iii) Vertical surfaces such as walls (any thickness) partitions and the like i/c attached pillasres buttresses, plinth & string courses and the like.
(a) Upto 4.00 mtrs.
For Vertical surfaces of tank
(iv) Columns,pillars.posts & struts.
(b) Beyond 4.00 mtrs.
(v) Beams, cantilever, girders & lintels.
Sides & soffits of beams,beam haunchings, catilevers, bressumers & lintels not exceeding 1.00 mtr.depth in all ht.from floor.
(vi) Providing form work of ordinary timber plankings, so as to give a rough finish including centring, shuttering , strutting and propping etc. with wooden battens and ballies height of propping and centering below supporting floor to ceiling not exceeding 4.00 mtrs.height.
Beyond 4.00 mtr.height.
Providing Tor steel reinforcement for RCC work including bending,binding & placing in position complete upto floor two level.
Providing in RCC work smooth finishing of the exposed surface with cement mortor 1:3 (1cement :3 Sand) complete in all respect within all leads & lifts.
Finishing wall with water proofing cement paint of approved brand & maunfacture and of required shade on undecorated wall surfaces (two coats) to give an even shade after throughly brushing the surface to remove all dirt & remains of loose powedered material etc.
Providing & fixing 500 mm dia.CI man hole cover with frame and the weight of frame & cover should not be less than 100 kg complete in all respect within all leads & lifts.
P/Laying GMS/MS Pipes conforming to relevants BIS codes of below mentioned diameters fully jointed with MS Flanges of Table - 5 as per IS :6392 - 1971 excluding the cost of excavation in trenches complete in all respect within all leads & lifts.
100mm dia (Medium class)
Steel work welded in built up sections,trusses & framed work i/c cutting, hoisting,fixing in position & applying a priming coat of red paint.In grating,framed guard bars,ladders,railing,brackets & similar works.
P/Laying GMS Pipes conforming to IS 1239 - 1979 (Part-1) screwed & socketed joints (Light grade) excluding the cost of excavation in trenches
Providing & fixing CI sluice valve RG/Kirloskar/LP/leader/Kirloskar/Suchdeva/any other approved make(with hand wheel) as per IS:780 - 1984 Class-I upto 300 mm dia i/c brass spindle & as per 2906 - 1984 Class II for diameters more than 300 mm complete with bolts,nuts,rubber insertion etc,(The tail pieces if required shade etc.
100 mm dia
Providing & fixing bends of required degrees made from parent tubes conforming to relevant codes fully flanged with MS Flange of Table - 5 conforming to IS: 6392 - 1971 complete in all respect within all leads & lifts.
100 mm dia
Constructing chamber for sluice valve, with CI surface box 100 mm top dia.,160 mm bottom dia.&180 mm deep (inside) with chained lid RCC top 1: 2: 4 mix (1 cement :2 Sand :4 graded stone aggregate 20 mm nominal size ) 100 mm thick foundation conc.1:5:10 mix (1cement : 5 sand : 10 graded stone aggregate 40 mm nominal size) & inside plastering with cement mortor 1:3 (1 Cement : 3 Sand ) finished with a floating coat of neat cment i/c curing complete. 600 x 600 x 750 mm inside size With 150mm th.walls of RCC 1:2:4 (1cement : 2 sand :4 graded stone aggregate 20 mm nominal size) complete with form work & reinforcement with 6 mm bars at not exceeding 150 mm centres both ways.
P/Fixing of below items required for OHSR complete.
a) MS Sheet locking arrangement for Manhole Cover
b) Lightening Conductor
c) Water measurement gauge
d) Vent Pipe i/c CI cowl complete
e) Flanged bell mouth a/w puddle collars
f) Expansion joints
Rising Mains
Providing, laying, jointing and testing in trenches of Galvanized MSERW flanged pipes conforming to IS/ISO 3183-2007 Grade L-290 or X42 as per dimensions weight and test pressure mentioned below in a random length of 4 m-6m. The pipes end shall be bevelled suitable for butt welding. The M.S. flanges are to be provided 1% of total joints as per table below conforming to IS 6392-1971 ( Latest upto date amendments ) and welding of flanges with pipes as per IS: 816-1965 with electrode as per IS: 814-1967 including required Nos. and size of M.S nuts and bolts as per IS: 1369-1967 and compressed asbestos fibre jointing geskets sheet not less than 3 mm thick as per IS; 2712-1965. The welding of flanges to be done on both faces in three layers(Two inner & one outer) to make the joints leak proof and to the entire satisfaction of the Engineer - in -charge. The laying of pipes should be conformed to IS: 5822-1994 ( Earth work in trenches, M.S. flanges and butt welded joint to be mensured and paid sepretely) The pipe shall have Zinc coating as per IS 4736 in factory latest with up to date ammendements.Pipe shall be coated from both side (Inside) or outer side with the required thickness of zinc coating as per two coats mains above.
200mm dia GMSERW IS 3183-2007(L290 or X42) Wall Thickness 7.90
200mm dia GMSERW IS 3183-2007(L290 or X42) Wall Thickness 7.10
200mm dia GMSERW IS 3183-2007(L290 or X42) Wall Thickness 6.40
200mm dia GMSERW IS 3183-2007(L290 or X42) Wall Thickness 5.60
200mm dia GMSERW IS 3183-2007(L290 or X42) Wall Thickness 5.10
200mm dia GMSERW IS 3183-2007(L290 or X42) Wall Thickness 4.80
Providing,Laying, jointing and testing in trenches ( to level or grade) GI pipe of following dia (H/M class) conforming to IS:1239-1990(Part-I)(Latest upto date ammendments of grade and wall thickness as specified below, suitable to with stand required hydraulic test pressure in randum length 4m-6m with plain ends and jointed with MS Flanges conforming to IS:6392-1971(latest upto date amendment) and welding of flanges as per 816-1969 with electrodes as per IS 814-1991 including required number and size of MS nuts and bolts as per IS 1369-1967 and compressed asbestos fibre jointing gaskets sheet not less than 3.00mm in thickness asper IS:2712-1998 & butt welded joints. The welding of flanges to be done on both faces in two layers on outer face & one layer on inner face to make the joints leak proof and to the entire satisfaction of the Engineer-in-Charge. the laying of pipes conform to IS 5822-1994 and as per CPHEEO manual and will include all operation such as cutting, welding and jointing including flushing, cleaning and hydraulic testing complete in all respects to the entire satisfaction of Engineer-in-Charge including entire carrage of material upto all lead and lifts.(Earth work in trenches,welding of flanges/butt welding will be measured and paid for seperately)
125mmdia GMS (H) as per IS:1239-1990(Part-I)
Providing & welding of MS flanges at suitable point, confirming to following tables as per IS- 6392-1971 (latest with upto ammendment ) with plain end GMS/MSERW pipe in requsite number of layers on both faces to make the joint leak proof ( The cost of Providing and Laying of GMS/GMSERW pipe to be measured & paid for seperately) The welding of flanges should Conform to IS: 816-1965 with electrode as per IS: 814-1967 including required Nos. and size of M.S nuts and bolts as per IS: 1369-1967 including cost of gasket sheet nuts & bolts. The thickness of geskets sheet not less than 3 mm thick as per IS; 2712-1965. the work shall be done to the entire satisfaction of the Engineer - in -charge with in all leads and lifts.
125mm dia GMS (H) as per IS:1239-1990(Part-I)Table 5
200mm dia GMSERW IS 3183-2007(L290 or X42) Table 38
200mm dia GMSERW IS 3183-2007(L290 or X42) Table 34
200mm dia GMSERW IS 3183-2007(L290 or X42) Table 28
200mm dia GMSERW IS 3183-2007(L290 or X42) Table 23
200mm dia GMSERW IS 3183-2007(L290 or X42) Table 17
200mm dia GMSERW IS 3183-2007(L290 or X42) Table 11
200mm dia GMSERW IS 3183-2007(L290 or X42) Table 5
Providing circumferencial butt welded joints by electrical arc welding to following diameter GMD/GMSERW pipe conforming IS/ISO 3183-2007 of Grade L320 or X46 having following wall thicknees, welded in requisite number og weld runs so as achieve the minimum effective throat thicknees of weld conforming to IS 816-1969 specification,by using welding eletrodes of 2.5mm to 6.30mm of Advani Oerlikon (Adore)-CITOJET/ESAB make,conforming to IS 814-1991, at site of complete in all pipes,welding of pipes to be done in three layers to make the joints leak proof and to achieve the minimum effective throat thickness of weld conforming to IS- 816-1969 specifications, by using welding electrodes of 2.5 mm to 6.3 mm of Advani oerlikon (Adore)-CITOJET/ESAB make, conforming to IS 814-1991, at site of work complete in all respects and including manual/mechnical handing of pipes in all leads and lifts to the entire satisfaction of Engineer- in- charge..
125mm dia GMS (H) as per IS:1239-1990(Part-I)
200mm dia GMSERW IS 3183-2007(L290 or X42)
Providing double flanged cast steel RG/Kirloskar/LP/leader/Kirloskar/Suchdeva/any other approved make Non Return Valve, follwing class of Leader/ Kirloskar make capable of with standing following normal seat pressure conforming to BS:1868/API-600 or latest ammendments. complete in all respect with in all leads & lifts.
200mm dia (Class ASA-600)
200mm dia (Class ASA-300)
Distribution Systems
Laying, jointing and testing in trenches GMS pipes ( light grade) including cost of bends complete as per IS :1239-1979, Part-I, of follwing diameters in trenches complete in all respect as per direction of Engineer-in-Charge. (Earth work in trenches to be measured and paid for separately) including entire carriage of material in all leads and lifts as per the directoon of the Engineer-in-charge.
65mm Dia (Light Class)
80mm Dia (Light Class)
100mm Dia (Light Class)
150mm Dia (Medium Class)
Dismentalling of of old GMS pipes in existing distribution system where changing is required of following including stacking of material at site in all leads and lifts and as per the direction of the Engineer-in-Charge.
20mm Dia (Light Class)
25mm Dia (Light Class)
32mm Dia (Light Class)
40mm Dia (Light Class)
50mm Dia (Light Class)
ReLaying, jointing and testing in trenches GMS pipes ( light grade) including cost of bends complete as per IS :1239-1979, Part-I, of follwing diameters in trenches complete in all respect as per direction of Engineer-in-Charge. (Earth work in trenches to be measured and paid for separately) including entire carriage of material in all leads and lifts as per the directoon of the Engineer-in-charge.
20mm Dia (Light Class)
25mm Dia (Light Class)
32mm Dia (Light Class)
40mm Dia (Light Class)
50mm Dia (Light Class)
Internal Electrical wiring for Pump House and Je qtr for WSS Nehri Narga and for Pump House WSS Salana Maslan
Wiring for light point / fan point / exhaust fan / call bell point with 1.5 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed PVC conduit and earthing the light point with 1.5 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable complete in all respect. "Group-C"
2X1.5 Sqmm
2X4Sqmm
Wiring for power plug with (2x4 Sq.mm) PVC insulated copper condoct single core cable in surface/recessed steel conduit along with 1 No.. 2.24mm dia bari copper wire for loop earthing as required i/c carriage of materials with all leads and lifts complete.
Wiring for circuit wiring with 2 x 1.5 Sq.mm PVC insulated copper conductor single core cable in surface/recessed steel conduit as required including carriage of material within all leads and lifts.
Wiring for sub-main wiring with the following size of copper conductor single core cable in surface/recessed steel conduit as required including carriage of materials upto all leads and lifts.
2x6 Sq.mm
Supplying and fixing metal box of 180mmx100mmx60mm deep (nominal size) on surface/recess with suitable size phenolic laminated sheet cover in the front including providing and fixing 3 pin 15/16 amps socket outlet and 15/16 amps, piano type switch, connections, ainting etc. as required..
Wiring for Three pin 5/6 amp. plug point with 15mm sq. PVC i/c copper condoctor cable i/c pdg. and fixing three pin 5/6 amp. Socket outlet on switch board ( in surface) recessed steel conduit wiring system and 5/6 amps. Tumble/iano type switch earthing the 3rd pin painting etc. as required (to be used only in no residential bldg. blance forward) crriage of materials with all leads and lifts complete.
Providing, Installation, testing and commissioning of ceiling fan with regulator, including wiring the down rods of standard length (up to 30 cm) with 16/0.20 mm twin twisted flexible, cotton braided, copper cable, including providing and fixing phenolic laminated sheet cover on the fan box and earthing etc. as required with in all leads & lifts complete. Ceiling Fan 1200 mm sweep, Category-A
Providing, Installation, testing and commissioning of prewired flourscent tube fitting 1x40 watt box type Cat A i.e. Bajaj make complete with balast starter and capacitor but excluding flourscent tube rod suitable to operate on 240volt single phase AC supply directly on surface with copper wiring as required complete as per direction of the Engineer-in-charge.
Supplying and fixing 40Amps to 63 Amps rating 240 Volts "L" series miniature circuit breaker of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required including carriage of material within all leads and lifts. Category- A, 63 Amps.
Supplying and fixing of following way single pole and neutral sheet steel MCB distribution board 240 volts on surface/recessed completed with tinned, copper busher neutral link, earth bar, detachable gland plate inter -connections, including painting, earthing etc. as required Bus bar 8 way.
Supplying and fixing 32 Amps rating 240 volts, L series miniature circuit breaker of following poles in the existing MCB, DB complete with connections testing and commissioning etc. as required Category "A", single pole.
Earthing with G.I earth pipe 4.5 mtr. long and 40mm dia, including accessories and providing masonry enclosure with copper plate having locking arrangement and watering pipe etc. ( but without charcoal or coke and salt ) complete as required i/c Carriage of Materials within all lead and lifts.
Extra for using salt and charcoal for pipe earth electrode at required i/c carriage of materials with in all leads and lifts.
Supplying and laying 6 SWG G.I. wire at 0.50 mtrs. Below G.L. for conductor earth eletrode i/c soldering as required complete as per direction of the Engineer-in-charge.
Supplying and fixing backellite brass batten/angle holder including connection as required complete as per direction of the Engineer-in-charge.
Supplying and fixing MVL light cast aluminium controlgear houseing complete with accessories 125 watts BPMV lamp deep drain aluminium houseing aclelic cover with toggle catches with best satisfaction of Engineer-in chrage i/c connection with 40mm dia G.I. pipe 1.5 mtr. Bend(1.00 and 0.5mtr.) i/c nut & screw grouted with cement in the existing MCB i/c Carriage of material with all leads and lifts.
Pgd. And Connection of bulk head fitting of all size and shape containing one No. GLS lamp holder steel wire guard and lock complete with all accessories excluding GLS lamp i/c connection etc. required bull head fitting as required complete as per direction of the Engineer-in-charge. Category-A
Pumping Machineries.
Submersible Pump set for LWSS Chintpurni Booster Stage Tubewell No.1
Supply and errection of submersible pumping set of reputed make such as KSB/Calama/BS/Oswal / worthigton/ LUBI/ GROUNDFOS/HINDUSTAN/SEERAX/SABAR/Johnston/Amrut conforming to latest relevent BIS . The pump should be fitted with free fine impellers of suitable alloys as per BIS ;5659-1978 with upto date amendments,suitable for raw / clear water having greased packed bearing and shell with wound stator on motor side and with shaft protection on pump side ensuring better liffe for shaft conforming to BIS specifications The pump shall be directly coupled to suber-sible squirrel cage electric induction motor of same make conforming to BIS ;9283-1979 with upto date amendments, totally dust and water proof for submersible pump, duly isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed,lubricated bearing and provided with stainless steel thrust bearing plate to withstand non vertical loads with minimum wear and tear.It should also be fitted with a device to make up expa-of water with heating of motor The pumpset should include water level guard i/c cable ,errection clamps, cable clips and suitable for opertion on data given below. Specifications offered a Pumps :- Specifications i) Make ii) Model iii) No. of stages iv) Manufacter's certificate to be attached Performance i) Discharge ii) Head iii) Efficiency of Pump a) Duty Head b) (+) 10% Duty Head. c) (-) 15% Duty Head d) Performance curve to be attached b) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speed v) Insulation
Discharge, (Q) 8.76 LPS
Total Head ( H ) 79.7 Mts.
SWL in Tubewell 40 mtr. bgl.
R.L. point of discharge 246.00 mtr
R.L. of Pump House = 173.00 mtr
Seasonal fluctuation + draught condition + bowl assembly.9 mtrs.
Drawdown in Tubewell 13.72 mtrs.
StaticHead =73.00 mtrs.
Static suction lift + tive
Rising main Column pipe
Length 490.00 mtrs Length 75.00 mtr
Dia 125 mm (H) Dia 125 mm (H)
Class GMS (H)
iv) Pumping hours 16hours
v) Alititude of installations above M.S.L 700mtr
vi) Characteristic of water
a) Temperature 25 Deg Cel.
b)Turbidity __________________JTU
c) Allkanity _________________mg/1Ca Co3
d) Size of solids _______________ mm
e) others
vii) Depth of T/well 125.50 mtr
viii) Dia of T/well assembly 300/200 mm
ix) Length of assembly pipe 125.50 mtr
x) Dia of housing pipe 300mm
xi) Length of housing pipe 70 mtr
OPERATING CONDITIONS
i) Type of current A.C Three phases.
ii) Frequency 50 Cycles/ Sec.
iii) Rated Voltage 415+/-15% Volts
iv) System of earthing Double Loop earthing as per BIS 3843-1987 latest
v) Speed of Revolution __________________ RPM 2900
MOTOR
i) Ref to BIS code BIS 9283-1979 with upto date amendments
ii) Type of enclousre of motr As per BIS :4691-1985 (latest)
iii) Mechnical out put in HP
iv) Class of insulation : Class B The motor should be able to withstand intial current of 2.50 times the rated current for two minutes without suffering damages of permanet deformations
i) Ref to BIS code BIS 5659-1978 with upto date amendments
ii) Driver Type Electric drivern
iii) Operating Range -15%to +10% of Total head at duty point
iv) Deliver size of Pump ;---------- (to be quoted by tenderer)
Providing ICTP Main Switch with HRC fuses of Havell/L&Tmake and having capacity 30%extra of the operational rating as per IS : 4064-1978 with upto date amendments.
Providing MS Sheet steel fabricated floor mounted switch board including angle iron post of suitable height and size ISA 40x40x6 mm duly painted with sheet of 16 gauge comprising and capable of mounting the following accessories with all internal connections.
MCB of L&T/Havells make of suitable capacity on incoming feeder with or without intial oil filling as the case may be with neutral linked under voltage releases as per IS ; 2516-1985 with upto date amendments.
ELCB of recommended make L&T/Havells as per IS ;2516-1985 with up to date ammendments, and of suitable range which should have control box , operating handle and trip / reset bush button on / off of indicators, reindicating off spring condition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal release with metallic tape CTS. It should also be fitted with earth fault for tripping of breaker on occurence of Earth fault.
The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage,reverse phasing,overloading and phase voltage difference as per IS; 3842 ( Latest Edition )
Bus bar chamber of L&T / Hevells make having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current one copper bar of half the rating of full length for neutral phase as per IS : 8084-1976 and IS: 11353-1985 read with BIS : 5578- 1985 with upto date ammendments Three phase indicator lamps complete with toggle switches for Bus Bar Chamber individual motors as per IS: 3452 (P-I&II) with upto date ammendments.
Capacitor of BHEL/GEC/ L&T make as per IS ; 2834-1968 with upto date amendments,to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevent ISI code ( of Seimens / Glocter/IEC make ) from bus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments . Rating of capacitor will be approved by HPSEB
Providing suitable oil immersed star delta starter of Kilburn/L&T/ Havells/IMP make as per IS : 8544-1979 with'upto date amendments for Squirrel cage / Slipring motor mounted on panel board with magnetic 'type overload release and dashpot, time lag, under voltage release with or without 'initial oil filling as the case may be with single phase prventor as per IS ;1248 ( P-5)1983 with up to date amendments.
Providing and fixing of double flange Cast Iron Sliuce valve of Leader / Kirloskar RG/Kirloskar/LP/leader/Kirloskar/Suchdeva/any other approved make for the Column pipe and capable of withstanding the normal seat pressure and as per IS 780-1984(Cast Iron) with latest ammendments
Providing and fixing of double flanged swing type cast iron Reflux valve of Kirloskar/Leader RG/Kirloskar/LP/leader/Kirloskar/Suchdeva/any other approved make having Bye pass arrangement on the rising main and capable of 'withstanding normal Seat Pressure as per IS:5312-1984 (P-I) (Cast Iron) with latest ammendmets PN 1.0 in R/main 125 mm dia.
Providing pressure gauge of Prega/Precision make complete with all accessories such as stop cock, Copper tubing as per IS: 3624-1987 with upto date ammendments..
Supply of PVC 3 core copper cable jointless, flat water proof cable as per BIS 694-1998 latest with upto date amendments, suitable for the pumpsets offered from MCCB to motor including all other electrical equipments/ accessories such as thimble, flexible pipe,solder, nuts and bolts, cable glands, clips etc, laid in pipes or trenches under floor . The type, size and make shall be subject to approval of HPSEB authorities.
lowering of GMS Column pipe assembly 125 mm dia(MG) including MS flanges of Table 17 as per IS : 6392-1971 with upto date amendments, rubber/asbestos gasket of min. 3mm thickness as per IS 2712-1979 and required numbers of nuts and bolts as per IS ;1364-1983 . The Column pipe shall be as per relevent IS Code The Column pipe should be extended upto 5 mtr. beyond the outer wall of the pump house in the direction of Rising main . The Column pipe should be properly jointed with the Rising main including all necessary accessories like increaser / reducer, flanges, bends etc, including supporting clamps (2Nos.) at the top of T/well assembly, and as per the direction of Engineer - in - Charge.
Providing and laying copper PVC insulated 3 core armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554 ( P-I ) 1988 or latest with upto date amendments of Seimen /Gloster/IEC/ICC/ EICO/National / Grandlay make including all othe accessories such as thimble, flexible pipes, solder nuts and bolts,cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable. Suppy side From meter of HPSEB to Bus Bar and Switch)
Installation of all items appearing as above as per the systematic drawing attached with the documents or as per the direction of Engineer - in- charge.
Providing and laying copper PVC insulated 3 core armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554 ( P-I ) 1988 or latest with upto date amendments of Seimen /Gloster/IEC/ICC/ EICO/National / Grandlay make including all othe accessories such as thimble, flexible pipes, solder nuts and bolts,cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable. Suppy side From meter of HPSEB to Bus Bar and Switch)
Providing and fixing double earthing with G.I. wire / plate of 600x600x6.3mm thick electrode complete with material such as thimble, nuts and bolts,charcoal,salt, 25x5mm copper strip as per IS 3043-1987 with upto date amendments for motors and other eletrical equipments and digging of pits etc. complete in all restect as per the dirction of the Engineer-in-Charge.
Centrifugal Pumping Machinery for LWSS Chintpurni
Providing horizontal spindle ,horizontal / radial split casing / end suction (back pull out arrangement). Single / double / multi stage centrifugal pump or combination of pumps in series / parallel of recommended make such as Mather and Platt /KSB/Beacon weir/Kirloskar / BE/ Jyoti/LUBI/GROUNDFOS/HINDUSTAN as per BIS IS 1520 1980 with upto date ammendments read with IS- 9137. 1978 or latest edition suitable for lifting water for under mentioned characteristic with Bronze impellers / priming funnels, casing ring and shaft sleeves of Bronze shaft of stainless steel with cast iron casing, coupled directly through a flexible coupling on a common cast iron/cast steel base plate (base plate to be framed from the manufacturers of the pumping unit only) to slipring/Squirrel cage screen protected drip proof induction motor/,motors of standard make such as Kirloskar /Bhel /Crompton/NGEF /GEC/ Seimens /jyoti/ LUBI/GROUNDFOS/HINDUSTAN and suitable for operation on 415 (+/-5%) volts. 50 Cycles/Sec., 3 phase AC electric supply. The power of electric motor/motors should be at least + 10% in excess of the maximum power required by the pump/pumps in the Operation range of (+10%) and (-15%) of the duty point head. The motor/motors as per IS 325 IS 1978 with upto date amendments read with IS 900 1972 it should include cost of Bearing. Nuts, Bolts and painting etc. and should meet the following requirements.
Coupling
Base Plate
Discharge (Q) 13.15LPS each pump.
Total Head (H) 638.40.00 mtrs.
a)LWL In collection tank 244.00 mtr
b)R.L. of shaft 243.20 mtrs.
c)R.L. of discharge Pt. 776.2 mtrs.
d)Suction lift. + tive
e)Discharge Head
f) Static Head 533.00 mtrs.
Rising main.
Length 15480 mtrs.
Diameter 200 MM
Class GMSERW/ GMS (H)/(M)
Pumping hours. 16hours.
Altitude of installations above M.S.L 700_mtrs.
Characteristic of Water
a)Temperature ________Deg.Col.
b)Turbidity ________ JTU
c)Alloanity _________ mg/1 ca Co3
d)Size of solids __________ mm
e) Others.
Providing ICTP Main Switch with HRC fuses of Kilburn/L&T / Havells/Siemens/Standard make and having capacity 30% extra of the operational rating as per IS-4064 : 1978 with upto date amendments, immediately after the Energy meter of the HPSEB.
Providing MS Sheet, steel fabricated floor mounted switch board i/c angle iron post of suitable height and size ISA 40x40x6mm duly painted with steel sheet of 16 Gauge comprising and capable of mounting the following acccessories with all internal connections.
OCB of Kilburn/ L&T/MEI /GEC make and of suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per IS: 2516-1985 with upto date amendments.
ELRCBCT OP of recommended make L&T/Havells as per IS ;2516-1985 with up to date ammendments, and of suitable range which should have control box , operating handle and trip / reset bush button on / off of indicators,reindicating off spring condition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal release with metallic tape CTS. It should also be fitted with earth fault for tripping of breaker on occurence of Earth fault.
The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage reverse phasing, overloading and phase voltage difference as per IS: 3842 (Latest Edition).
Power factor meter of AE/L&T make as per relevent IS Code with upto date ammendments.
Frequency meter of AE/L&T make as per relevent IS Code with uptodate ammendments. .
Bus bar chamber of L&T / Havells make having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current one copper bar of half the rating of full length for neutral phase as per IS : 8084-1976 and IS: 11353-1985 read with BIS : 5578- 1985 with upto date ammendments.
Three phase indicator lamps complete with toggle switches for individual motors as per IS: 3452 (P-I&II) with upto date ammendments.
Pdg Hour run meter of recommended make of suitable capacity as per IS:722 (latest edition)
Capacitor of Mechell/BHEL/GEC/ L&T make as per IS ; 2834-1968 with upto date amendments,to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevent ISI code ( of Seimens / Glocter/IEC make ) from bus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments .
Providing suitable ATS starter of L&T/Hevells/Kilburn make as per IS: 8544-1979 with upto date ammendments for squirrel cage/slip ring motor mounted on panel board with magnetic type overload release and dashpot, time lag, under voltage release with or without initial oil filling as the case mayu be with single phase preventor as per IS 1248 (P-V)-1983 with upto date ammendments.
Providing and fixing of double flanged cast iron sluice valve of kirloskar/Leader / Kartar/LP/Suchdeva/RG or any approved make for suction pipe and capable of withstanding the normal seat pressure as per IS 780-1984 with latest ammendments.
Providing and fiximg of double flanged Cast steel Sluice valve of Leader/Kirloskar RG/Suchdeva any other approved make of 150 mm dia for the delivery pipe of pump and capable of with standing the normal Seat Pressure as per BIS 1414 API 600 (Cast steel) as the case may be with latest ammendments.
Providing and fiximg of double flanged Cast steel double flanged reflux valve of Leader/Kirloskar RG/Suchdeva any other approved make of 100 mm dia class- ASA 300 for the delivery pipe of pump and capable of with standing the normal Seat Pressure as per BIS 1414 API 600 (Cast steel) with nuts and bolts and rubber insertion shee of 21kgf/cm2 complete in all respect..
Providing and fiximg of double flanged swing type Cast steel Reflux valve of Leader/Kirloskar RG/Suchdeva any other approved make 125mm dia having Bye pass arrangement on the rising main of the Pump and capable of with standing normal Seat Pressure as as per BIS: 1414 API-600 with upto date ammendments.
Providing 100 mm dia circular dial pressure gauge of Prega/Precision make complete with all accessories such as stop cock, Copper tubing as per IS: 3624-1987 with upto date ammendments.
Installation of all items appearing at S.No.as above as per the systematic drawing attached with the tender documents or as per the direction of Engineer-in Charge.The contarctor should ensure proper jointing of delivery pipe line of pump with the Rising main including all necessary accessories like increaser /reducer specials etc. as per site conditions and as per direction of the Engineer-in Charge.
Fixing of double flanged GMS piping work(layout to be approved by Engineer-in-Charge) for suction and delivery pipes suitable to pumps offered and common header as per the rising main respectively complete with all specials such as bends,Tees,Reducers Inceasers with companion flanges matching with the relevant specifications of the accessories as indicated in the Drawing i/c rubber/ asbestos gasket of 3 mm thickness as per IS : 2712-1979 and required number of Nuts and Bolts as per 1364-1983.-the pipes shall be as per relevent IS code and to withstand 1.5 times total head.
i) Suction Pipe 200 mm dia.
ii) Delivery Pipe 150 mm dia.
iii) Common Header 200mm dia. and will extend upto 5 metres from the outer wall of the pump house in the direction of Rising main of 100 mm dia to be joined.
Providing and laying 3 core copper PVC Insulated armoured power cable(One cable carrying all the three phases) of suitable size and capacity to motors and all other elelctrical equipments as per IS: 1554(P-I)1988 or latest with upto date amendments of Seimen/Gloster/IEC/ICC/EICO/National/Grandlay make including all other accessories such as thimble, flelxible pipes, solder, nuts & bolts, cable glands etc. laid in pipes or trenches under floor.
Providing and fixing double loop earthing with Copper wire/plate 600 mm x 600mm x3.15mm thick electrode complete with material such as thimble, Nuts & Bolts charcoal, salt as per IS:3043-1987 with upto date amenments GI plate & strip of suitable size for motors and other electrical equipments and digging ofpits etc. complete in all respect as per the direction of the Engineer-in-Charge.
Submersible Pump set for LWSS Chintpurni Booster Stage Tubewell No.2
Supply and errection of submersible pumping set of reputed make such as KSB/Calama/BS/Oswal / worthigton/ LUBI/ GROUNDFOS/HINDUSTAN/SEERAX/SABAR/Johnston/Amrut conforming to latest relevent BIS . The pump should be fitted with free fine impellers of suitable alloys as per BIS ;5659-1978 with upto date amendments,suitable for raw / clear water having greased packed bearing and shell with wound stator on motor side and with shaft protection on pump side ensuring better liffe for shaft conforming to BIS specifications The pump shall be directly coupled to suber-sible squirrel cage electric induction motor of same make conforming to BIS ;9283-1979 with upto date amendments, totally dust and water proof for submersible pump, duly isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed,lubricated bearing and provided with stainless steel thrust bearing plate to withstand non vertical loads with minimum wear and tear.It should also be fitted with a device to make up expa-of water with heating of motor The pumpset should include water level guard i/c cable ,errection clamps, cable clips and suitable for opertion on data given below.
Discharge, (Q) 8.76 LPS
Total Head ( H ) 80.38 Mts.
SWL in Tubewell 40.00 mtr. bgl.
R.L. point of discharge 246.00 mtr
Seasonal fluctuation + draught condition + bowl assembly.9 mtrs.
Drawdown in Raw water Tank 12.00 mtrs.
StaticHead = 73 mtrs.
Static suction lift + tive
Rising main Column pipe
Length 570 mtrs Length 2.00 mtr
Dia 125mm (H) Dia 125 mm (H)
Class GMS
iv) Pumping hours 16hours
v) Alititude of installations above M.S.L 700 mtr
vi) Characteristic of water
a) Temperature 25 Deg Cel.
b)Turbidity __________________JTU
c) Allkanity _________________mg/1Ca Co3
d) Size of solids _______________ mm
e) others
OPERATING CONDITIONS
i) Type of current A.C Three phases.
ii) Frequency 50 Cycles/ Sec.
iii) Rated Voltage 415+/-15% Volts
iv) System of earthing Double Loop earthing as per BIS 3843-1987 latest
v) Speed of Revolution __________________ RPM 2900
MOTOR
i) Ref to BIS code BIS 9283-1979 with upto date amendments
ii) Type of enclousre of motr As per BIS :4691-1985 (latest)
iii) Mechnical out put in HP
iv) Class of insulation : Class B The motor should be able to withstand intial current of 2.50 times the rated current for two minutes without suffering damages of permanet deformations
i) Ref to BIS code BIS 5659-1978 with upto date amendments
ii) Driver Type Electric drivern
iii) Operating Range -15%to +10% of Total head at duty point
iv) Deliver size of Pump ;---------- (to be quoted by tenderer)
Providing ICTP Main Switch with HRC fuses of Havell/L&Tmake and having capacity 30%extra of the operational rating as per IS : 4064-1978 with upto date amendments.
Providing MS Sheet steel fabricated floor mounted switch board including angle iron post of suitable height and size ISA 40x40x6 mm duly painted with sheet of 16 gauge comprising and capable of mounting the following accessories with all internal connections.
MCB of L&T/Havells make of suitable capacity on incoming feeder with or without intial oil filling as the case may be with neutral linked under voltage releases as per IS ; 2516-1985 with upto date amendments.
ELCB of recommended make L&T/Havells as per IS ;2516-1985 with up to date ammendments, and of suitable range which should have control box , operating handle and trip / reset bush button on / off of indicators, reindicating off spring condition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal release with metallic tape CTS. It should also be fitted with earth fault for tripping of breaker on occurence of Earth fault.
The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage,reverse phasing,overloading and phase voltage difference as per IS; 3842 ( Latest Edition )
Bus bar chamber of L&T / Hevells make having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current one copper bar of half the rating of full length for neutral phase as per IS : 8084-1976 and IS: 11353-1985 read with BIS : 5578- 1985 with upto date ammendments Three phase indicator lamps complete with toggle switches for Bus Bar Chamber individual motors as per IS: 3452 (P-I&II) with upto date ammendments.
Capacitor of BHEL/GEC/ L&T make as per IS ; 2834-1968 with upto date amendments,to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevent ISI code ( of Seimens / Glocter/IEC make ) from bus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments . Rating of capacitor will be approved by HPSEB Capacitor.
Providing suitable oil immersed DOL starter of Kilburn/L&T/ Havells/IMP make as per IS : 8544-1979 with'upto date amendments for Squirrel cage / Slipring motor mounted on panel board with magnetic 'type overload release and dashpot, time lag, under voltage release with or without 'initial oil filling as the case may be with single phase prventor as per IS ;1248 ( P-5)1983 with up to date amendments.
Providing and fixing of double flange Cast Iron Sliuce valve of Leader / Kirloskar /RG/Suchdeva/LP/any other approved make for the Column pipe and capable of withstanding the normal seat pressure and as per IS 780-1984(Cast Iron) with latest ammendments
Providing and fixing of double flanged swing type cast iron Reflux valve of Kirloskar/Leader /RG/Suchdeva/LP/any other approved make having Bye pass arrangement on the rising main and capable of 'withstanding normal Seat Pressure as per IS:5312-1984 (P-I) (Cast Iron) with latest ammendmets.
Providing pressure gauge of Prega/Precision make complete with all accessories such as stop cock, Copper tubing as per IS: 3624-1987 with upto date ammendments.
Supply of PVC 3 core copper cable jointless, flat water proof cable as per BIS 694-1998 latest with upto date amendments, suitable for the pumpsets offered from MCCB to motor including all other electrical equipments/ accessories such as thimble, flexible pipe,solder, nuts and bolts, cable glands, clips etc, laid in pipes or trenches under floor . The type, size and make shall be subject to approval of HPSEB authorities.
lowering of GMS Column pipe assembly 65 mm dia(MG) including MS flanges of Table 17 as per IS : 6392-1971 with upto date amendments, rubber/asbestos gasket of min. 3mm thickness as per IS 2712-1979 and required numbers of nuts and bolts as per IS ;1364-1983 . The Column pipe shall be as per relevent IS Code The Column pipe should be extended upto 5 mtr. beyond the outer wall of the pump house in the direction of Rising main . The Column pipe should be properly jointed with the Rising main including all necessary accessories like increaser / reducer, flanges, bends etc, including supporting clamps (2Nos.) at the top of T/well assembly, and as per the direction of Engineer - in - Charge.
Providing and laying copper PVC insulated 3 core armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554 (P-I ) 1988 or latest with upto date amendments of Seimen /Gloster/IEC/ICC/ EICO/National / Grandlay make including all othe accessories such as thimble, flexible pipes, solder nuts and bolts,cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable. Suppy side From meter of HPSEB to Bus Bar and Switch)
Installation of all items appearing at S.No as above as per the systematic drawing attached with the documents or as per the direction of Engineer - in- charge.
Providing and laying copper PVC insulated 3 core armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554 ( P-I ) 1988 or latest with upto date amendments of Seimen /Gloster/IEC/ICC/ EICO/National / Grandlay make including all othe accessories such as thimble, flexible pipes, solder nuts and bolts,cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable. Suppy side From meter of HPSEB to Bus Bar and Switch)
Providing and fixing double earthing with G.I. wire / plate of 600x600x6.3mm thick electrode complete with material such as thimble, nuts and bolts,charcoal,salt, 25x5mm copper strip as per IS 3043-1987 with upto date amendments for motors and other eletrical equipments and digging of pits etc. complete in all restect as per the dirction of the Engineer-in-Charge.
Submersible Pump set for LWSS Chintpurni Booster Stage Tubewell No.3
Supply and errection of submersible pumping set of reputed make such as KSB/Calama/BS/Oswal / worthigton/ LUBI/ GROUNDFOS/HINDUSTAN/SEERAX/SABAR/Johnston/Amrut conforming to latest relevent BIS . The pump should be fitted with free fine impellers of suitable alloys as per BIS ;5659-1978 with upto date amendments,suitable for raw / clear water having greased packed bearing and shell with wound stator on motor side and with shaft protection on pump side ensuring better liffe for shaft conforming to BIS specifications The pump shall be directly coupled to suber-sible squirrel cage electric induction motor of same make conforming to BIS ;9283-1979 with upto date amendments, totally dust and water proof for submersible pump, duly isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed,lubricated bearing and provided with stainless steel thrust bearing plate to withstand non vertical loads with minimum wear and tear.It should also be fitted with a device to make up expa-of water with heating of motor The pumpset should include water level guard i/c cable ,errection clamps, cable clips and suitable for opertion on data given below. Specifications offered a Pumps :- Specifications i) Make ii) Model iii) No. of stages iv) Manufacter's certificate to be attached Performance i) Discharge ii) Head iii) Efficiency of Pump a) Duty Head b) (+) 10% Duty Head. c) (-) 15% Duty Head d) Performance curve to be attached b) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speed v) Insulation
Discharge, (Q) 8.76 LPS
Total Head ( H ) 87.97 Mts.
SWL in Tubewell 40 mtr. bgl.
R.L. point of discharge 246.00 mtr
R.L. of Pump shaft = 168.00 mtr
Seasonal fluctuation + draught condition + bowl assembly.9 mtrs.
Drawdown in Tubewell 13.72 mtrs.
StaticHead = 78.00 mtrs.
Static suction lift + tive
Rising main Column pipe
Length 870.00 mtrs Length 75.00 mtr
Dia 125 mm (H) Dia 125 mm (H)
Class GMS (H)
iv) Pumping hours 16hours
v) Alititude of installations above M.S.L 700mtr
vi) Characteristic of water
a) Temperature 25 Deg Cel.
b)Turbidity __________________JTU
c) Allkanity _________________mg/1Ca Co3
d) Size of solids _______________ mm
e) others
vii) Depth of T/well 125.50 mtr
viii) Dia of T/well assembly 300/200 mm
ix) Length of assembly pipe 125.50 mtr
x) Dia of housing pipe 300mm
xi) Length of housing pipe 70 mtr
OPERATING CONDITIONS
i) Type of current A.C Three phases.
ii) Frequency 50 Cycles/ Sec.
iii) Rated Voltage 415+/-15% Volts
iv) System of earthing Double Loop earthing as per BIS 3843-1987 latest
v) Speed of Revolution __________________ RPM 2900
MOTOR
i) Ref to BIS code BIS 9283-1979 with upto date amendments
ii) Type of enclousre of motr As per BIS :4691-1985 (latest)
iii) Mechnical out put in HP
iv) Class of insulation : Class B The motor should be able to withstand intial current of 2.50 times the rated current for two minutes without suffering damages of permanet deformations
i) Ref to BIS code BIS 5659-1978 with upto date amendments
ii) Driver Type Electric drivern
iii) Operating Range -15%to +10% of Total head at duty point
iv) Deliver size of Pump ;---------- (to be quoted by tenderer)
Providing ICTP Main Switch with HRC fuses of Havell/L&Tmake and having capacity 30%extra of the operational rating as per IS : 4064-1978 with upto date amendments. I
Providing MS Sheet steel fabricated floor mounted switch board including angle iron post of suitable height and size ISA 40x40x6 mm duly painted with sheet of 16 gauge comprising and capable of mounting the following accessories with all internal connections.
MCB of L&T/Havells make of suitable capacity on incoming feeder with or without intial oil filling as the case may be with neutral linked under voltage releases as per IS ; 2516-1985 with upto date amendments. MCB (1) Make (ii) Type iii) Range iv) Capacity. 40 Amp
ELCB of recommended make L&T/Havells as per IS ;2516-1985 with up to date ammendments, and of suitable range which should have control box , operating handle and trip / reset bush button on / off of indicators, reindicating off spring condition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal release with metallic tape CTS. It should also be fitted with earth fault for tripping of breaker on occurence of Earth fault.
The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage,reverse phasing,overloading and phase voltage difference as per IS; 3842 ( Latest Edition )
Bus bar chamber of L&T / Hevells make having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current one copper bar of half the rating of full length for neutral phase as per IS : 8084-1976 and IS: 11353-1985 read with BIS : 5578- 1985 with upto date ammendments Three phase indicator lamps complete with toggle switches for Bus Bar Chamber individual motors as per IS: 3452 (P-I&II) with upto date ammendments.
Capacitor of BHEL/GEC/ L&T make as per IS ; 2834-1968 with upto date amendments,to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevent ISI code ( of Seimens / Glocter/IEC make ) from bus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments . Rating of capacitor will be approved by HPSEB
Providing suitable oil immersed star delta starter of Kilburn/L&T/ Havells/IMP make as per IS : 8544-1979 with'upto date amendments for Squirrel cage / Slipring motor mounted on panel board with magnetic 'type overload release and dashpot, time lag, under voltage release with or without 'initial oil filling as the case may be with single phase prventor as per IS ;1248 ( P-5)1983 with up to date amendments.
Providing and fixing of double flange Cast Iron Sliuce valve of Leader / Kirloskar /RG/suchdeva/LP or any other approved makk for the Column pipe and capable of withstanding the normal seat pressure and as per IS 780-1984(Cast Iron) with latest ammendments
Providing and fixing of double flanged swing type cast iron Reflux valve of Kirloskar/Leader RG/suchdeva/LP or any other approved makk having Bye pass arrangement on the rising main and capable of 'withstanding normal Seat Pressure as per IS:5312-1984 (P-I) (Cast Iron) with latest ammendmets
Providing pressure gauge of Prega/Precision make complete with all accessories such as stop cock, Copper tubing as per IS: 3624-1987 with upto date ammendments.
Supply of PVC 3 core copper cable jointless, flat water proof cable as per BIS 694-1998 latest with upto date amendments, suitable for the pumpsets offered from MCCB to motor including all other electrical equipments/ accessories such as thimble, flexible pipe,solder, nuts and bolts, cable glands, clips etc, laid in pipes or trenches under floor . The type, size and make shall be subject to approval of HPSEB authorities.
lowering of GMS Column pipe assembly 125 mm dia(MG) including MS flanges of Table 17 as per IS : 6392-1971 with upto date amendments, rubber/asbestos gasket of min. 3mm thickness as per IS 2712-1979 and required numbers of nuts and bolts as per IS ;1364-1983 . The Column pipe shall be as per relevent IS Code The Column pipe should be extended upto 5 mtr. beyond the outer wall of the pump house in the direction of Rising main . The Column pipe should be properly jointed with the Rising main including all necessary accessories like increaser / reducer, flanges, bends etc, including supporting clamps (2Nos.) at the top of T/well assembly, and as per the direction of Engineer - in - Charge.
Providing and laying copper PVC insulated 3 core armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554 ( P-I ) 1988 or latest with upto date amendments of Seimen /Gloster/IEC/ICC/ EICO/National / Grandlay make including all othe accessories such as thimble, flexible pipes, solder nuts and bolts,cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable. Suppy side From meter of HPSEB to Bus Bar and Switch)
Installation of all items appearing at S.No as above as per the systematic drawing attached with the documents or as per the direction of Engineer - in- charge.
Providing and laying copper PVC insulated 3 core armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554 ( P-I ) 1988 or latest with upto date amendments of Seimen /Gloster/IEC/ICC/ EICO/National / Grandlay make including all othe accessories such as thimble, flexible pipes, solder nuts and bolts,cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable. Suppy side From meter of HPSEB to Bus Bar and Switch)
Providing and fixing double earthing with G.I. wire / plate of 600x600x6.3mm thick electrode complete with material such as thimble, nuts and bolts,charcoal,salt, 25x5mm copper strip as per IS 3043-1987 with upto date amendments for motors and other eletrical equipments and digging of pits etc. complete in all restect as per the dirction of the Engineer-in-Charge.
Unipro Techno Infrastructure Pvt Ltd
HILL CONSTRUCTION AND ENGINEERING CO. SOLAN
R.G. INDUSTRIES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid