Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹38.9 LAccepted-AOC | L1 | Accepted-AOC BEING LOWEST | |
| 2 | L2₹44.0 L+₹3.2 L (7.79%)Rejected-Finance | L2 | Rejected-Finance BEING NOT LOWEST | |
| 3 | L3₹47.0 L+₹6.2 L (15.3%)Rejected-Finance RZ 212F D BLOCK RAJ NAGAR PART II PALAM COLONY NEW DELHI 110077 | SOUTH WEST | DELHI | 110077 | L3 | Rejected-Finance BEING NOT LOWEST | |
| 4 | L4₹47.2 L+₹6.4 L (15.7%)Rejected-Finance WZ 1000 NANGAL RAYA PANKHA ROAD SOUTH WEST DELHI DELHI 110046 | DELHI | SOUTH WEST DELHI | DELHI | 110046 | L4 | Rejected-Finance BEING NOT LOWEST | |
| 5 | L5₹47.7 L+₹6.9 L (17.0%)Rejected-Finance | L5 | Rejected-Finance BEING NOT LOWEST |
Tender Value
₹49.8 L
EMD Value
₹1 L
Closing Date
30 Aug 2022, 6:00 pmClosed
ARJUN PATRO,IDSE
GE U ELECTRIC SUPPLY,DELHI CANTT
REPAIR AND MAINTENANCE OF OLD UNSERVICEABLE LT XLPE CABLE , 11 KV HT XLPE UNDERGROUND CABLE, LT STEEL TUBULAR POLES, POLE BOX ASSEMBLY AND CONNECTED ITEMS AT 4 NO PF, STATION ROAD, MAUDE ROAD, MALL ROAD, POLO ROAD, CHURCH ROAD, CASSEL ROAD, TIG
2022_MES_531631_1
GE ELECT/D-28/2022-2023
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE U ELECTRIC SUPPLY
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE U ELECTRIC SUPPLY
₹1 L
Yes
6 Oct 2022
23 Jun 2022
1 Sept 2022
23 Jun 2022
30 Aug 2022
11 Aug 2022
Amount
Excavation in trenches not exc. 1.5 m wide and not exc 1.5 mtr deep in soft loose soil for laying / taking up/ taking down of cables and getting out and levelling of bottom suface to required level all as specified and directed by Engineer- in- Charge.
Returning filling in,. Including spreading, levelling,. Watering and well ramming soil in layers not exceeding 25 cm thick all as specified and directed.
Removing excavated material (ie soil) from site to a distance n. exc 50 mtrs away and depositing where directed at a level n. exc. 1.5 mtr above the starting point all as specified and directed by Engineer-in-Charge.
Material and labour for river washed and screened, dry sand for filling in trenches below and around underground cables for cushioning of cables etc, complete all as specified.
S&F sub class B bricks having minimum compressive strength 75 Kg/ Sqcm laid in trenches for cable protection etc complete all as directed by Engineer-in-Charge.
All as per srl item No 5 here-in-before but using old bricks obtained under srl item No 1 here in before.
Supplying and laying un-reinforced precast concrete cable cover, class HV, type 1, flat size 300mmx 180mm x 40mm for cable protection
All as per srl item No 5 here-in-before but using old cable cover obtained under srl item No 1 here in before.
Supply, laying jointing , testing and connecting in replacement of LT XLPE PVC insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, IS 7098 marked, suitable for LT 1100 Volt system, laid in trenches fixed to pole, including jointing & testing complete all as specified and directed of following sizes:- Note :- Excavation, earth work ,cable protection , sand fillings , cable joint shall be measured and paid separately under respective items of schedule.
16 Sqmm 4 core
25 Sqmm 4 core
35 Sq mm 3.5 core
50 Sq mm 3.5 core.
70 Sqmm 3.5 core
95 Sqmm 3.5 core
120 Sqmm 3.5 core
185 Sqmm 3.5 core
240 Sqmm 3.5 core
300 Sqmm 3.5 core
630 Sqmm single core
Supplying, laying, jointing testing and connecting in replacement XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, 11 KV grade, IS 7098 marked, suitable for HT 11 KV(E) system, laid in trenches / ducts / encased in GI pipe / fixed to pole, including jointing & testing complete all as specified and directed of following sizes
95 sqmm 3 core.
120 sqmm 3 core.
185 sqmm 3 core
240 sqmm 3 core
300 sqmm 3 core
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 160 mm dia suitable for 0.6 mpa working pressure complete all as directed by Engr-in-charge.
Boring of hole under road/pavement/hard standing or any other situation by manual means and suitable for passing of GI pipe 100 to 150 mm bore and making good both ends all specified and directed
S&F in replacement GI Pipe (light grade) with necessary accessories/ fittings for cable protections/pole for crossing of culverts/nallah of following bore sizes
Taking out faulty underground 1100 Volt LT cable of different sizes by excavation and removing bricks of any size and relaying in the same trenches or re routing after rectification of fault or replacing faulty portion of cable with new cable and removing of surplus soil and using new bricks as required. Note: (a) 1100 Volt LT cable & joints shall be measured and paid for seperately under respective items of schedule. (b) Retrieved old serviceable bricks will be laid in trenches for cable protection. If extra bricks and sand required at site shall be measured and paid separately under respective items of BOQs. (c) Excavation and earth work will be measured and paid for seperately under respective items of schedule.
Taking out faulty underground 11000 Volt HT cable of different sizes by excavation and removing PCC cover of any size and relaying in the same trenches or re routing after rectification of fault or replacing faulty portion of cable with new cable and removing of surplus soil and using new bricks as required. Note: (a) 11000 Volt HT cable & joints shall be measured and paid for seperately under respective items of schedule. (b) Retrieved old serviceable PCC cable cover will be laid in trenches for cable protection. If extra bricks and sand required at site shall be measured and paid separately under respective items of BOQs. (c) Excavation and earth work will be measured and paid for seperately under respective items of schedule.
Supply, fixing and testing straight through joint heat shrinkable type with jointing kit suitable for cable PVC/XLPE insulated armoured heavy duty aluminium conductor 1100 Volts grade complete all as directed for the following sizes :-
16-50 Sqmm x 3.5 core/ 4 core
70-150 Sqmm x 3.5 core
185 -240 Sqmm x 3.5 core
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following size :-
95 Sqmm 3 core.
120 Sqmm to 185 Sqmm, 3 core.
240 Sqmm to 300 Sqmm 3 core
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following size :-
95 Sqmm 3 core.
120 Sqmm to 185 Sqmm, 3 core.
240 Sqmm to 300 Sqmm 3 core
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following size :-
95 Sqmm 3 core.
120 Sqmm to 185 Sqmm, 3 core.
240 Sqmm to 300 Sqmm 3 core
Supplying, laying, jointing testing and connecting in replacement HT cable, 11000 volts (E) grade, with Aluminum conductor of size 1000 Sqmm, single core, XLPE insulated, PVC sheathed, screened, Armoured with GI strip(Earthed), screened by a layer of extruded semi conducting cross linkable compound, copper tape, cross laid up with prefiller complete all as specified and directed.
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 1 core XLPE armoured aluminium conductor cable 1000 Sqmm
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 1 core XLPE armoured aluminium conductor cable 1000 Sqmm
Taking down unservicable RCC/ steel tubular poles of any type and supply & installing steel tubular swaged poles type 410 SP-31 (9 mtr long) of approx wt.147 kg conforming to IS 2713 (Part-II) including excavation, earth work, PCC foundation, base plate,PCC coping,GI pipe for cable protection etc. and GI bracket for fitting mounting, complete all as per manufacturer's instructions and as specified and as directed by E-in-charge. NOTE:- The unit rate in this item is deemed to be included the cost of exacavation and earth work in any type of soil,PCC foundation 1:4:8 type D-2 , PCC coping 1:2:4 type B-1 as in steel tubular pole and GI bracket made of GI pipe medium grade 40 mm bore, 1.5 mtr long for fixing of street light fitings . The steel pole shall be painted by bituminious paint total length inside and up to planting depth outside and remaining portion of pole painted with two coat of aluminium paint over a coat of red oxide complete all as specified and directed.
Earthing in replacement complete with galvanized steel earth plate electrode of size 60cmx60cmx6 mm thick, buried directly in ground (earth pit not less than 2.10 m below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level, connected to galvanized iron strip 25 x4 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel as shown in electrical plate No 3 of SSR Part I, connected to earth test point and the equipment on the other nuts and washers of galvanised ironside complete all as specified, including testing and commissioning complete all as directed. Note : (a) The unit rates quoted against this item shall be deemed to include the cost of excavation and earth work in any type of soil, common salt & charcoal dust in alternate layers, PCC 1:3:6 as in pit, precast RCC 1:2:4 type B-1 with necessary reinforcement as in cover & frame for pit, funnel, watering pipe 20 mm bore GI pipe light grade, protection pipe 40 mm bore GI pipe medium grade etc. (b) The quoted rates shall also deemed to include the cost of earth test point and earth strip/GI lead wire and protection pipe upto 7.5 meter beyond the earth plates electrode.
S&F in replacement KIOSK box wheather proof including made out of one piece mounted SMC base and door pole mounted hinged door size 333x233x120mm out side and 300x200x105mm inside dimensions comprising of aluminium bus bar 4 strips for 3 phase and neutral 63 Amps including embossing/painting of danger notice of size not less than 10cm x 7.5cm with letters, figures and conventional skull and bones in signal red colour on front face of KIOSK box body complete all as specified and directed.Incluiding MS clamp of size 25x3 mm with suitable size nut,bolts & washer.
M&L for re-painting of LT Panels/feeder pillars of approx size 2 to 4 Sqm with 2 coats of super enamal paint over a coat of red-oxide with sparygun including writing of feeder pillar numbers in appropriate size of letters as directed.
All as per item No 26 here in before but of approx size upto 1.90 Sqm
M&L for re-painting of LT Steel tubular poles of any sizes with apply of 2 coats of aluminium paint including rubbing with wire brush/emery paper & writing pole Nos in appropriate size of letters including making yellow and black strips upto height of 1.5 mtr above from ground level complete all as specified and directed.
Supplying and fixing in replacement of LED street light fitting fitting 70 Watt complete all as specified and directed.
Supplying and fixing in replacement LED street light fitting fitting 45 Watt complete all as specified and directed.
Taking down unservicable RCC/ steel tubular poles of any type and supply & installing steel tubular swan neck pole type 410 SP-31 (9 mtr long) complete with mild steel base plate, finial taper plug, bolts, nuts and screws including two coats of aluminium painting over a coat of primer for exposed surfaces and two coats of bituminous black paint over a coat of primer to the surfaces in contact with concrete inclusing two runs of PVC insulated 1100V multi-stranded copper wire of size 2.5 Sqmm from the junction box to the fitting complete all as specified and directed. Note :- The unit rate in this item is deemed to be included the cost oif exacavation and earth work in any type of soil,PCC foundation 1:4:8 type D-2 , PCC coping 1:2:4 type B-1 as in steel tubular pole and GI bracket made of GI pipe medium grade 40 mm bore, 1.5 mtr long for fixing of street light fitings . The steel pole shall be painted by bituminious paint total lenth inside and up to planting depth outside
Supply and fix in replacement air break switch gang operated tripple pole mechanically operated mechanism, switch air break gang operated mounted on 15 Nos insulator and steel frame with operating rod of 25 mm bore GI Pipe and locking arrangements worked from ground level for current rating 400 Amps, HT 11 KV grade including drop out fuses and necessary silver coper coating jumpers and making all electrical connections complete.
M&L in replacement of earthing complete with galvanized steel earth plate electrode of size 60cmx60cmx6 mm thick, buried directly in ground (earth pit not less than 2.25 m below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level, connected to galvanized earth lead wire 4.0mm dia by means of bolts ,nuts,check nuts and washers of galvanised iron or steel all as shown in electrical plate No 3 of SSR Part I, connected to earth test point and the equipment on the other side complete all as specified, including testing and commissioning complete all as directed. Note : (a) The unit rates quoted against this item shall be deemed to include the cost of excavation and earth work in any type of soil, common salt & charcoal dust in alternate layers, PCC 1:3:6 as in pit, precast RCC 1:2:4 type B-1 with necessary reinforcement as in cover & frame for pit, funnel, watering pipe 20 mm bore GI pipe light grade, protection pipe 40 mm bore GI pipe light grade etc. (b) The quoted rates shall also deemed to include the cost of earth test point and earth strip/GI earthing and protection pipe upto 7.5 meter beyond the earth plates electrode.
M & L for 2 coat of aluminium painting over a coat of red oxide to steel surfaces of HT 4/6 pole sturcture (Angle Iron/MS channel /MS clamp etc) including preparation of old surface complete all as specified.
Material & Labour for replacement of jumper/bus bar made of ACSR conductor of existing size on HT Four/Six pole structure having 2/3 incoming/outoing feeder including bus bar with PVC sleeve , lugs , nut bolts and washers complete all as directed.
All as per Serial item No 35 here-in-before but 4/6 incoming/outoing feeder complete all as specified and as directed
M & L for cutting and removing grass, vegetation bushes etc from surrounding 4 pole/6 pole HT structure , outside area of HT installation and removing all rubbish to a distance not exceeding 50 m as directed.
Material and labour for sprading of stone aggregate of nominal size not more than 25mm under 4/6 pole HT structure /surounding area of outdoor RMU manually without damaging any equipments, cable or parts , spreading & levelling of finished gravel uniformaly in layers n. ecc. 15 cm thick watered and rammed to true surface all as specified and directed
Suplying and laying in replacement in sub station 3.3 to 11 KV electrical insulation mat ISI marked complete all as directed by Engr-in-charge
Supplying and fixing in replacement male contact/moving contact for gang operated air break device 11 KV complete all as directed at site by Engr-in-charge.
Supplying and fixing in replacement female contact /fix contact jaw for gang operated air break device 11 KV complete all as directed at site by Engr-in-charge.
Supplying and fixing in replacement tinned copper flexible jumper 200 Amp/400 Amp for gang operated air break device 11 KV complete all as directed at site by Engr-in-charge.
Supplying and fixing in replacement MS jumper carrier for gang operated air break device 11 KV complete all as directed at site by Engr-in-charge.
Supplying and fixing in replacement back connector plate for gang operated air break device 11 KV complete all as directed at site by Engr-in-charge.
Supplying and fixing in replacement porcelain post insulator for gang operated air break device 11 KV complete all as directed at site by Engr-in-charge.
Supply installation & commissioning in replacement of 24V, 40A Float Cum Boost Battery Charger unit including battery bank comprising 02 Nos of 12 Volts, 00 AH sealed maintenance free batteries. The CCCV battery charger consisting of copper wound, air cooled transformer, 01 Set single phase full wave bridge rectifier consisting of diodes and SCRs, liberally rated mounted on heat sink and complete with resistor/condenser network for surge supperssion . During auto float mode automatic changeover shall take place from float mode to boost mode and vice versa, 01 Set of solid state constant potential controller to stabilize the DC output voltage of the float cum boost charger, 01 No electronic controller , DC digital ammeter , DC digital voltmeter, Potentiometer , DC, MCB for reverse battery protection . The charger should have alarm annunciation with visual and audible alarm with manual reset facility for fuse fail alarm. Float cum boost battery charger and DC distribution board shall be housed in powder coated sheet steel cubicle with panels of 1.6mm thickness , louvers for ventilation , gland plate will be provided for cable entry from bottom . The battery charger shall be divided into two compartments. The upper compartment shall house the battery charger & DCDB with all necessary controls. The lower compartment shall be suitable for housing the batteries. Tech specification shall be as under:- (a) Input working voltage-180 -270 Volts (b) Nominal Input Voltage - 230 V , AC , 50 Hz,1 (c) On load input power factor - > 0.8 (d) On load unit watt efficiencies-> 80% (e) No load losses of complete charge-< 10% (f) Ripple contents on the load (RMS)= 1% to 5% (g) Over load - 110% for 30 minutes and will give visual indication for over load condition. (h) Boost charging - 2.4 V/Cell . (j) Float charging -2.15 V/Cell (k) Float cum boost charging-Automatically changes from one state to another state as per battery condition and will give the visual indication for either float or boost based on charging mode. (l) Reverse polarity -No damage will caused . A visual indication for reverse polarity will appear with an audio alarm. (m) Short circuit-MCB protecton provided.
S&F in replacement pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers,nut size 150 mm height 150mm dia, 11000 volts grade complete all as specified and directed.
S&F in replacement Lightening arrestors expulsion type with all fittings, transmission class, discharge capacity 10 kilo Amps suitable for 11000 volts complete as specified and directed.
Dismantling and removing of PCC 4 Pole/6 Pole structure from site using hydra machine and making good to the existing surfaces complete all as specifed and directed by Engr-in-Charge
Note : contractor should procure and provide 50 % of the material as listed above within 15 days of the placing of work order and shall be verified by the Eng-in-charge
DS CONSTRUCTION
MV Engineers And Contractors
mayur enterprises
Rajindera Enterprises
Vijay Electricals
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .