Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹40.0 CrAccepted-AOC A 602 SARITA GARDEN CHS LTD OPPOSITE SBI BANK VAKOLA PIPELINE SANTACRUZ EAST MUMBAI 400055 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400055 | ₹40.0 Cr | L1 | Accepted-AOC L1 Accepted |
| 2 | L2₹43.8 CrRejected-Finance THIRD FLOOR AMIT CRYSTAL SENAPATI BAPAT ROAD PUNE 411 016 | PUNE | PUNE | MAHARASHTRA | 411016 | ₹43.8 Cr | L2 | Rejected-Finance L2 Rejected |
Tender Value
₹40.0 Cr
EMD Value
₹20.0 L
Closing Date
23 Aug 2024, 5:30 pmClosed
Executive Engineer, Central Mumbai Electrical Divi
Executive Engineer, Central Mumbai Electrical DivisionSawli Building P.W.D.Compound, Ganpat Jadhav Marg,Worli, Mumbai 400018
Estimate No H11002 of 2024 25 Providing Fire and Electrical Safety Measures as per National Safety Councils safety Audit Recommendations at J J Hospital campus buildings Byculla Mumbai
2024_PWDM_1067441_1
H11002/5/1st call/24-25/B2
Open Tender
Electrical Works
400 days
J J Hospital campus buildings
Please refer Tender documents.
6 documents required · 6 mandatory
₹3,540
₹20.0 L
the Chief Engineer, PWD Mumbai Region
17 Oct 2024
9 Aug 2024
26 Aug 2024
9 Aug 2024
23 Aug 2024
9 Aug 2024
14 Aug 2024
Amount
Supplying and erecting PVC trunking (PVC casing-n-capping) of size 25 mm with accessories on wall/ceiling as per specification No: WG-MA/CON.
Supplying and erecting HMS PVC conduit FRLS grade 25 mm dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No: WG- MA/CC.
Supplying and erecting mains with 2x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting mains with 1x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting mains with 2x1.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW
Supplying and erecting mains with 1x1.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW
Supplying and erecting mains with 2x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting mains with 1x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Point wiring for light/fan/bell in 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm (2+1E) FRLSH grade copper wire with flush type switch and required accessories as per specification No: WG-PW/SW
Point wiring for light/bell/exhaust fan in 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm (2+1E) FRLSH grade copper wire, modular type switch, earthing and required accessories as per specification No: WG- PW/SW.
Point wiring for independent plug in 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm (2+1E ) FRLSH grade copper wire, modular type switch, earthing and required accessories as per specification No: WG- PW/SW
Supplying and erecting single pole and neutral distribution board (SPNDB), with 2 ways for incoming and 6 ways (6 poles) for outgoing SP MCBs, with door, 1.2mm thickness surface / flush mounted, IP 43 Protection on iron / GI frame as per specification no. SW-SWR/MCBDB
Supplying & erecting inverter LED batten 20W tube light fitting with polycarbonate housing, heat sink, integrated HF electronic driver, Min. 2600 mAhLithium ion Battery with charging time of 8-10 Hours and backup time of Min. 3 hrs. with minimum 25% of initial Watts having luminous efficacy of 100 lumen/watt, CRI>80, CCT of 6500K and THD<=20% having useful life of minimum 25000 hrs. with overheating protection with 2 years warranty.
Supplying and erecting fresh air cum exhaust fan of light duty 250 V A.C. 50 cycles 300mm. 1400 RPM rust proof body & blades, wire mesh, duly erected, complete.
Supplying and erecting modular type switch 16A duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type 3 pin 6 / 16A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting PVC Surface modular switch box with double mounting plate for 3 module duly erected.
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 95 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting &terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 300 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL (main incoming cable to main fire panel).
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 4 sq.mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU(for booster Pump)
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 6 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying & laying (including excavation) reinforced cement concrete pipe of IS 458:2003 NP-2 class of 150 mm internal diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete.
Providing & erecting 3 Pole MCCB 415V, 400A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure /panel as per specification no. SW- SWR/MCCB. Note : For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB. Hence 18563 X 20%= 3712.60/-
Supplying and laying (including excavation of suitable width & depth up to 90 cm) 146 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, to required depth complete.
Providing & erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 150 mm width & 100 mm height comprising all required standard accessories.
Providing & erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 300 mm width & 100 mm height comprising all required standard accessories.
Providing & erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 400 mm width & 100 mm height comprising all required standard accessories.
Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results as per specification no. EA-EP (earthig schedule: 2 nos for each 2 nos main fire pump for hydrant and sprinkler , 2nos for each 2 nos jockey pump for sprinkler and hydrant , 1 nos for main fire panel and 1 nos for disel engine pump).= total 6 nos of earthing.
Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required. As per specification no EA-EP.(25x5) (1kg/m x 60 m=60 kg)
Supplying, installation, testing and commissioning of main fire pump(MFP / EP) suitable for water discharge of 2280 to 2850 LPM at 120 to 90 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 75kW or of suitable kW capacity for manual/automatic operation and consisting of following : (a) Horizontal type, single stage, centrifugal/split casing pump of cast iron body & bronze impeller with stainless steel shaft(SS410 grade), mechanical seal conforming to IS 1520. (b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF- MFP/SSC/EP
Supplying, installation, testing and commissioning of jockey fire pump (JP) suitable for water discharge of 180 to 240 LPM at 110 to 90 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 11 kW or of suitable kW capacity for manual/automatic operation and consisting of following : (a) Horizontal/vertical type, multi stage, centrifugal casing pump of cast iron body & bronze impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520. (b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/JP
Supplying, installation, testing and commissioning of booster fire pump [BP] suitable for water discharge of 900 LPM at 35 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 7.5 kW or of suitable kW capacity for manual/automatic operation and consisting of following : (a) Horizontal/vertical type, single/multi stage, centrifugal casing pump of cast iron body & bronze/CI impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520. (b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation on with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (d)Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/BP
Supplying, installation, testing and commissioning of main fire pump (MFP/DP) suitable for water discharge of 2280 to 2850 LPM at 120 to 90 m head driven by 110 HP or suitable HP capacity diesel engine at required working speed suitable for automatic operation and consisting of following : (a) Horizontal type, single stage, centrifugal casing pump of cast iron body & bronze impeller with stainless steel shaft(SS410 grade), mechanical seal conforming to IS 1520. (b) Water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12/24 volts DC electric starting equipment with battery of required AH capacity with necessary charger suitable to work on 230v, 50Hz AC supply, diesel tank of minimum 150ltr capacity with first filling of diesel up to 100% level with necessary piping with valves up to engine , exhaust pipe extended up to 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications etc. as required. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with engine assembly and accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/SSC/DP
For addition of booster pump for fire hydrant/sprinkler, add as follows in the basic cost of item no 13-5-1 towards necessary accessories, indicators etc. with necessary interlocking and updation of control logic.....for 5.5/ 7.5 kW centrifugal type booster pump 1no(5working) , add Rs…....
Supplying and erecting 100 mm dia Cast Iron end line strainer of Y-type flanged end pattern, PN16 pressure rating, SS screen, end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) for positive suction complete as per specification no. FF-VL/ELS ( 2 nos for jockey pump + 5 nos for booster pump=7 Nos.
Supplying and erecting 200 mm dia Cast Iron end line strainer of Y-type flanged end pattern, PN16 pressure rating, screen of SS end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) for positive suction complete as per specification no. FF- VL/ELS ( 1 nos main pump+1 nos for sprinkler pump+ 1 for disel pump= 3 Nos).
Supplying and erecting 100 mm dia. cast iron double flange sluice valve complete with PN16 pressure rating, as per specification no. FF-VL/SV
Supplying and erecting 200 mm dia. cast iron double flange sluice valve complete with PN16 pressure rating, as per specification no. FF-VL/SV
Supplying and erecting 50 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV
Supplying & erecting cast iron double flange butterfly valve of size 75/80 mm dia. complete as per specification no. FF-VL/BFV
Supplying & erecting cast iron double flange butterfly valve of size 100 mm dia. complete as per specification no. FF-VL/BFV
Supplying & erecting cast iron double flange butterfly valve of size 150 mm dia. complete as per specification no. FF-VL/BFV
Supplying & erecting cast iron double flange butterfly valve of size 200 mm dia. Complete as per specification no. FF-VL/BFV
Supplying and erecting cast iron double flange ball type NRV of size 75mm/80 mm dia complete as per specification no. FF- VL/NRV
Supplying and erecting cast iron double flange ball type NRV of size 100 mm dia complete as per specification no. FF-VL/NRV
Supplying and erecting cast iron double flange ball type NRV of size 150 mm dia complete as per specification no. FF-VL/NRV
Supplying and erecting cast iron double flange ball type NRV of size 200 mm dia complete as per specification no. FF-VL/NRV
Supplying & erecting gun metal gate valve of size 25 mm dia complete as per specification no. FF-VL/GV
Supplying and installing air vessel of 300 mm dia1.5m in height M.S. tank installed inside pump house / on terrace complete as per specification no. FF-FFA/ACT (1 nos for hydrant + 1 nos for sprinkler= 2 nos).
Supplying and erecting 20/25mm dia gun metal air release cock, with necessary G.I. coupling to be fitted on top of air vessel or on wet riser complete as per specification no.FF-FFA/ARV (7no. For Riser + Two for Air Vessel= 9 nos.
Supplying and erecting 100 mm dia. pressure gauge , 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve, erected with provided G.I. pipe, elbow etc.complete as per specification no. FF-FFA/PG
Supplying and erecting 12/15 mm dia pressure switch with provided isolation valve, G.I. nipple, elbow, etc complete as per specification no. FF-FFA/PS
Making trench in Hard murum/Tar road having 0.75 m depth and minimum 0.3m width as per IS for laying provided cables up to voltage level 1.1Kv cable complete as per specification No. CW-EXN-CTR
Making cement concrete foundation in 1:2:4 cement concrete with foundation bolts and nuts complete ( cost of wooden box is included) for pumps (1.2x 1.2 x0.8)= 1.15 x 5 = 5.76 cum for overhead tank foundation (1.8 x 1.8 x 0.3)=0.972 x 5=4.86 cum total (6.9+5.82)= 10.62 Cu-M. For Hydrant Line Pedastal of size 1.2 m X 0.6 m X 0.6 m = 0.432 cum per pedastal , total terrace overhead ring line length 720 m /pedastal support will be at 4 m each ,hence total qty would be - 720/4 = 180 Nos ,so 180 X 0.432 = 77.76 cum ( pump foundation 10.62 cum + Pedastal 77.76 cum = 88.38 cum total)
Supply, Instalation, testing of zinc aluminite fire water storage tank having capacity 50 KL having structreaboce ground which gives positive suction to fire Pumps. The tank shall include all civil work including site prepartion , excavation , PCC which can load of tank including of 100% water.( for booster pump as per NBC).
Supplying and erecting iron, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority ( separate Iron work calculation sheet attached).
Supplying and erecting stainless steel single outlet hydrant valve fitted with necessary accessories complete as per specification no. FF-VL/HV.
Supplying and installing wall mounting swinging hose reel drum fitted with 19 mm dia. 30m long high pressure polypropylene (Polyhose) along with necessary accessories complete as per specification no. FF-FFA/HV
Supplying fire fighting reinforced rubber lined (R.R.L.) hose pipe, 63mm dia, 15m in length, fitted with necessary accessories complete as per specification no. FF-FFA/RRL
Supplying & erecting stainless steel branch pipe 63 mm dia fitted with 20 mm dia detachable hexagonal nozzle complete as per specifications no. FF-FFA/NZ
Supplying and erecting brass orifice plate having 6 mm. thickness, 140 mm outer dia with required diameter of inner hole at every single outlet hydrant valve as per specification no. FF-FFA/OP (For Internal Hydrant).
Supplying and erecting M.S./CRCA cabinet for housing single hydrant valve of size ( 400 x 400 x 400)mm or hose pipe box of size ( 600 x 600 x 200)mm made from min. 1.5 mm thick CRCA sheet with angle iron work of min. of size (25 x 25 x 4) mm having front doors with viewing glass of size (200x150) mm and locking arrangement with necessary fixing material such as rubber bidding etc. duly painted in post box red colour( Code 538 of IS 5)
Carrying out core cutting of size 3" to 5" dia x 15" length in the C.C./rock/stone wall with the help of specialized core cutting machine in proper manner and finishing the site as original.
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 25 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 50 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 65 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 75/80 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 100 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 150 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 200 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying & erecting gun metal gate valve of size 20 mm dia complete as per specification no. FF-VL/GV
Supplying & erecting gun metal gate valve of size 25 mm dia complete as per specification no. FF-VL/GV
Supplying and installing corrugated SS flexible conduit of size 25mm dia for connecting sprinkler head with necessary fittings as per specifications having 1000mm long with UL/FM
Supplying, erecting, testing and commissioning of quartzoid bulb sprinkler, 15 mm (½") dia. NBCM Body chrome finished, 68º C fixed temperature rating with deflector disc of conventional construction complete as per specification no. FF-SPR.
Supplying, erecting, testing and commissioning of horizontal sidewall quartzoid bulb sprinkler, 15 mm (½") dia quartzoid bulb. NBCM Body chrome finished, 68º C fixed temperature rating with deflector disc of conventional construction complete as per specification no. FF-SPR/SS
Supplying and erecting fire resistant mortar (20 kg) with fire resistance class S90 as per National Electrical Code (NEC) SP30-2011 suitable to seal the openings of all kinds of cables, pipes and cable support system in steel, aluminium and plastic profiles ( except hollow core conductors). The residual openings shall be closed with filler, as per specification no FF-FRM. Note :- For estimating purpose consider 1 bag of 20kg to cover 300mm x 400mm area 150mm thick or 0.018 m3. ( Approx 780 rooms in Hospital, Each rooms having Fire sprinkler and other utility opening ,hence conidered one 20 kg bag per room. Total Set Required ( 300 X 400 X 150 = 1 room X 780 =780 Nos)
Supplying, installing, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the 8 loop capacity and capable of supporting upto 250 devices and detectors per loop, with on-board LCD display with min 16 lines of text, operating at 230 V 50 HZ - AC with inbuilt Battery Backup of a minimum 24 hours in normal condition and 30 min in alarm condition, suitable provision for network connectivity, interfacing with third party equipment via a MODBUS/ OPC/ L-ON interface etc. conforming to IS 15908:2021, IS 2189: 2008, EN 54 & VDS / FM/ UL 8
Supplying, installing, testing and commissioning of repeater panel with suitable battery backup of a minimum of 24 hours in normal condition and 30 min in alarm condition, 80 backlit alphanumeric LCD display with inbuilt buzzer to indicate fault/fire alarm, manual control keys for silence/mute and to reset the FACP from the repeater station. Panel size shall not more than 175 x 275 x 65 mm conforming to EN 54 or UL approved with 3 years equipment replacement warranty FF-AFAS/RP
Supplying, installing, testing and commissioning of addressable optical smoke detector, single/twin LED’s with 360 degree view, suitable for low voltage 15 to 32 V DC two wires supply, in-built locking mechanism to check the removal and pilferage of the detector, in built isolation mode, start up current 300µA and alarm condition current shall be maximum 6.5 mA, operating temperature 0°C to 50°C, humidity 0-95% RH, IP 41, conforming to IS 2189: 2008, 11360_1985_Reff2020 EN 54 or UL Approved with 3 years equipment replacement warranty FF-AFAS/SD
Supplying, installing, testing and commissioning of intelligent addressable thermal/heat detector with rate of rise cum fixed temperature thermistor complete with base as required, suitable for temperature variations from -20°C to 38°C for fixed-heat and rate-of-rise type detectors and 0°C to 66°C for high heat type detectors, in built isolation mode, suitable for offices/ceiling cable trenches/less ventilation area's etc. with 3 years equipment replacement warranty IS : 2175 - 1988 reaffirmed 2000, IS 15908:2021 standards FF-AFAS/SD.
Supplying, installing, testing and commissioning of addressable manual call points ( break glass type/pull station type), made of addressable break glass plastic square in shape surface/flush mounted with "Break Glass" massage embedded on the glass, complete erected with mounting base and required accessories conforming to EN 54 or UL listed with 3 years equipment replacement warranty FF-AFAS/MCP.
Supplying, installing, testing and commissioning of addressable fire control/relay module complete as required, with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 reed relays, EN 54 or UL Listed FF- AFAS/CRM
Supplying, installing, testing and commissioning of addressable fire monitor module complete as required. EN 54 or UL Listed with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 Reed relays FF-AFAS/MM
Supplying, installing, testing and commissioning of addressable fire isolator module complete as required. EN 54 /FM or UL Listed with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 Reed relays FF-AFAS/ISM
Supplying, installing, testing and commissioning of addressable horn cum strobe sound/ hooter, output frequency 500 to 1000 Hz with dB as per Chart given in IS 15908:2021, with flashing at 1 Hz over the strobe’s entire operating voltage range EN 54, conforming to IS 2189: 2008, IS 15908:2021 standards with 3 years equipment replacement warranty FF-AFAS/SSH.
Supplying, installing, testing and commissioning FR, XLPE armoured cable 2 core 1.5 sq.mm. copper conductor complete erected on wall/ ceiling complete as per specification no. CB-LT/CU
Supplying, installing, testing and commissioning FR, XLPE armoured cable 8 core 1.5 sq.mm. copper conductor complete erected on wall/ ceiling complete as per specification no. CB-LT/CU
Supplying, Installing, Testing & Commissioning of Microprocessor based system 6 zone controller complete with capacity upto 16 Zone designed as per tender specifications for Zone wise Announcement can connect upto 2 call station upto 255 messages to be stored with 12 input points for trigger points for EVAC compliment IFC 60489. Routers with 3 EMG inputs contacts and 6 volume contacts shall have a superviosry features dual tone controls for speech & music processor with relays for activating pre recorded fire alarm messages it shall be rack mountable.
Supplying, erecting, testing and commissioning 120 W amplifier suitable to operate on 230 Volts A.C. / 12 Volts D.C. supply complete as per specification no. FF- PA/AFR
Supplying, erecting, testing and commissioning 15 to 30 Watts sound column or ceiling mounted complete as per specification no. FF-PA/SOC
Supplying and fixing 42 U floor mount server rack (Dimension-DxWxH – 800x1000x2070 mm) as per specification No. WG-NAS/RAK
Supplying, erecting, testing and commissioning stand mounted/handheld type wired microphone having 2 mV/Pa sensitivity, impedance level limit 300 ohms and 50 - 16000 Hz suitable to operate in -10 deg C to +55 deg C with min. 7 metre shielded cable and 3 Pin Professional XLR Connector, stereo jack complete as per specification no. FF- PA/MIC
Supplying, erecting, testing and commissioning rust free microphone floor stand of chrome plating/powder coating or S.S. material , 500 mm to 1500 mm height and sturdy mechanism ensuring trouble free movement complete.
Supplying, erecting, testing and commissioning of 2 core shielded sound cable complete as per specification no. FF- PA/MCC
Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts routed in wall complete.
Supplying and erecting 4 kg clean agent gas Nitrogen pressurised controllable dicharge mechanism, pressure guage, Discharge hose and nozzle epoxy polyster powder coated as per IS 15683 ISI mark fire. extinguisheroperating temperature (-)20 to (+) 55 C kg capacity suitable for A,B,C class of FIRE complete.
Supplying and erecting DCP Type 25 kg capacity trolley Mounted with controllable dicharge mechanism, pressure guage, Discharge hose and nozzle epoxy polyster powder coated as per IS 15683 ISI mark fire extinguisheroperating temperature (-)20 to (+) 55 C kg capacity suitable for A,B,C class of FIRE complete.
Supplying and erecting of fire Exit & Eire Exinguishersignlge Indicating the floor- numtber in words &syslem(Fire Exiinguisher& Accessories ) (Non CSR Approved by S.E.Office ,mumbai vide T.S letter no- 108 Date- 13/01/2022 )
Supplying , Installation , Testing And Commissioning of Hinged Metal fire door 120 min fire rated un insulated single 50mm THK Honey Comb Infill single double RBT 143 x 57mm frame Straight with anchor fast erness frame 1.0 & shutter 0.9 mm powder coated to ral shade SFP SS Ball bearing 4" x 3" x 3"mm hionghed for steel doors ingersoll rand briton 121, NCE. SES Door closer size 3 with standard ARM , sprayed silver finish SFP SS sashlock with 70mm back set and 24 mmfor end , SS lever handle 22x 125 mm on rose , Euro profile cylinder 70 mm with both side key 29 SS strike plate Escutchenosschott pyran fire rated clear Glass 6mm thick 240 x 340 33 Hinged Metal Fire Door 120 min fire Rated(Non-Csr)
Supply installation testing and commissioning of Fire Curtains with Galvanized MS powder coated head top box of suitable size, Powder coated side guides (100mm x 50 mm) and bottom bars with Gravity fail safe DC motors one per roller for curtain up operation with standard battery back-up fixed into 76/88 mm steel rollers with FAB690PU fabric must be according to DIN EN 13501-1 and stainless steel reinforced glass fibre with fire-retardant aluminum pigmented polyurethane coating, with its control panel and all installation assemblies & accessories required to complete the installation. The operation shall be suitable for dedicated 230 volts UPS, 50 Hz AC supply. Complete system tested in accordance with EN 1634-1 and EN 12101-1 (foar minimum 120 minutes integrity & tested at 1000°C) with CE certificate from European Notified Body. Both test reports EN 1634-1 & EN 12101-1 must be according to the requirement of particular project, if single roller curtain is there then single roller certificates and double roller curtain is there than double roller certificates must be submitted accordingly. The fire curtain must be according to Classification of Fire Resistance Performance in Accordance with EN 13501-2: 2016. The manufacturer’s valid EN certification for oversized fire curtains according to EN 15269-11 covering the sizes of offered fire curtains as per BOQ, should be available. Each Fire Curtain shall have independent control Panel suitable for 230V AC supply, provision to integrate with Fire signal, and battery backup. The emergency retract switch shall be provided on both sides of curtain. The Fire curtain shall reset automatically when fire control panel is reset. Fabric and all components sourced from the original manufacturer who has valid type test certificate of the fire curtain and third-party quality surveillance audit as per above standards including oversize certification according to applicable EN standards. The scope also includes fabrication, supply and installation of closed MS sections corner supports for fixing side channels, design suitable for stability and integrity with two hours fire rating, wherever required for full height of Fire curtain, as per approved design, duly finished with powder coating of finish matching to side channels of fire curtains.All the required test / certificates must be less than 5 Years validity. No mirror certificates allowed Installation: The fire curtain has fixing options to suit all types of ceiling configurations and can be integrated into either a suspended or a solid ceiling. It remains hidden until required. Upon receiving a signal from the fire detection system or on loss of power with the gravity fail safe system, the curtain automatically unwinds to its operational position.
Supplying and erecting PVC trunking (PVC casing-n-capping) of size 25 mm with accessories on wall/ceiling as per specification No: WG-MA/CON.
Supplying and erecting mains with 3x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW
Supplying and erecting modular type switch 6A / 10A duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type 3 pin 6 / 16A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting PVC Surface modular switch box with double mounting plate for 3 module duly erected.
Carrying out core cutting of size 3" to 5" dia x 15" length in the C.C./rock/stone wall with the help of specialized core cutting machine in proper manner and finishing the site as original.
Supplying and erecting iron, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority ( separate Iron work calculation sheet attached).
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 4 sq.mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU(for booster Pump)
Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results as per specification no. EA-EP (earthig schedule: 2 nos for each 2 nos main fire pump for hydrant and sprinkler , 2nos for each 2 nos jockey pump for sprinkler and hydrant , 1 nos for main fire panel and 1 nos for disel engine pump).= total 6 nos of earthing.
Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required. As per specification no EA-EP.(25x5) (1kg/m x 40 m=0 kg)
Supplying, installation, testing and commissioning of booster fire pump [BP] suitable for water discharge of 900 LPM at 35 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 7.5 kW or of suitable kW capacity for manual/automatic operation and consisting of following : (a) Horizontal/vertical type, single/multi stage, centrifugal casing pump of cast iron body & bronze/CI impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520. (b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation on with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (d)Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/BP
For addition of booster pump for fire hydrant/sprinkler, add as follows in the basic cost of item no 13-5-1 towards necessary accessories, indicators etc. with necessary interlocking and updation of control logic.....for 5.5/ 7.5 kW centrifugal type booster pump 1no(1working) , add Rs…....
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 25 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 50 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 65 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 75/80 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 100 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 150 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting 100 mm dia Cast Iron end line strainer of Y-type flanged end pattern, PN16 pressure rating, SS screen, end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) for positive suction complete as per specification no. FF-VL/ELS
Supplying and erecting 100 mm dia. cast iron double flange sluice valve complete with PN16 pressure rating, as per specification no. FF-VL/SV
Supplying and erecting 50 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV
Supplying and erecting 75/80 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV
Supplying & erecting cast iron double flange butterfly valve of size 100 mm dia. complete as per specification no. FF-VL/BFV
Supplying & erecting cast iron double flange butterfly valve of size 150 mm dia. complete as per specification no. FF-VL/BFV
Supplying and erecting cast iron double flange ball type NRV of size 100 mm dia complete as per specification no. FF-VL/NRV
Supplying & erecting gun metal gate valve of size 25 mm dia complete as per specification no. FF-VL/GV
Supplying and erecting stainless steel single outlet hydrant valve fitted with necessary accessories complete as per specification no. FF-VL/HV.
Supplying and installing wall mounting swinging hose reel drum fitted with 19 mm dia. 30m long high pressure polypropylene (Polyhose) along with necessary accessories complete as per specification no. FF-FFA/HV
Supplying fire fighting reinforced rubber lined (R.R.L.) hose pipe, 63mm dia, 15m in length, fitted with necessary accessories complete as per specification no. FF-FFA/RRL
Supplying & erecting stainless steel branch pipe 63 mm dia fitted with 20 mm dia detachable hexagonal nozzle complete as per specifications no. FF-FFA/NZ
Supplying and erecting 20/25mm dia gun metal air release cock, with necessary G.I. coupling to be fitted on top of air vessel or on wet riser complete as per specification no. FF-FFA/ARV (7no. For Riser + Two for Air Vessel= 9 nos.
Supplying and erecting 100 mm dia. pressure gauge , 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve, erected with provided G.I. pipe, elbow etc. complete as per specification no. FF-FFA/PG
Supplying and erecting brass orifice plate having 6 mm. thickness, 140 mm outer dia with required diameter of inner hole at every single outlet hydrant valve as per specification no. FF-FFA/OP (For Internal Hydrant).
Supplying and erecting M.S./CRCA cabinet for housing Floor Hydrant valve, hose pipe, hose reel and branch pipe (size 1000 x 736 x 736 mm.) made from 16 SWG sheet and angle iron 25 x 25 x 4 mm. having front doors with viewing glass (8"x6") and locking arrangement with necessary fixing material such as rubber bidding etc. duly painted in post box red colour( Code 538 of IS 5) (BoX for Two set of Hose Pipe along with 1set of Branch Pipe).
Supplying, installing, testing and commissioning ofmicro processor based intelligent addressable main fire alarm panel, central processing unit with the 8 loop capacity and capable of supporting upto 250 devices and detectors per loop, with on-board LCD display with min 16 lines of text, operating at 230 V 50 HZ - AC with inbuilt Battery Backup of a minimum 24 hours in normal condition and 30 min in alarm condition, suitable provision for network connectivity, interfacing with third party equipment via a MODBUS/ OPC/ L-ON interface etc. conforming to IS 15908:2021, IS 2189: 2008, EN 54 & VDS / FM/ UL 864 (10th edition) with 3 years replacement warranty FF-AFAS/CP
Supplying, installing, testing and commissioning of repeater panel with suitable battery backup of a minimum of 24 hours in normal condition and 30 min in alarm condition, 80 backlit alphanumeric LCD display with inbuilt buzzer to indicate fault/fire alarm, manual control keys for silence/mute and to reset the FACP from the repeater station. Panel size shall not more than 175 x 275 x 65 mm conforming to EN 54 or UL approved with 3 years equipment replacement warranty FF-AFAS/RP
Supplying, installing, testing and commissioning of addressable optical smoke detector, single/twin LED’s with 360 degree view, suitable for low voltage 15 to 32 V DC two wires supply, in-built locking mechanism to check the removal and pilferage of the detector, in built isolation mode, start up current 300µA and alarm condition current shall be maximum 6.5 mA, operating temperature 0°C to 50°C, humidity 0-95% RH, IP 41, conforming to IS 2189: 2008, 11360_1985_Reff2020 EN 54 or UL Approved with 3 years equipment replacement warranty FF-AFAS/SD
Supplying, installing, testing and commissioning of intelligent addressable thermal/heat detector with rate of rise cum fixed temperature thermistor complete with base as required, suitable for temperature variations from -20°C to 38°C for fixed-heat and rate-of-rise type detectors and 0°C to 66°C for high heat type detectors, in built isolation mode, suitable for offices/ceiling cable trenches/less ventilation area's etc. with 3 years equipment replacement warranty IS : 2175 - 1988 reaffirmed 2000, IS 15908:2021 standards FF-AFAS/SD.
Supplying, installing, testing and commissioning of addressable manual call points ( break glass type/pull station type), made of addressable break glass plastic square in shape surface/flush mounted with "Break Glass" massage embedded on the glass, complete erected with mounting base and required accessories conforming to EN 54 or UL listed with 3 years equipment replacement warranty FF-AFAS/MCP.
Supplying, installing, testing and commissioning of addressable fire control/relay module complete as required, with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 reed relays, EN 54 or UL Listed FF- AFAS/CRM
Supplying, installing, testing and commissioning of addressable fire monitor module complete as required. EN 54 or UL Listed with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 Reed relays FF-AFAS/MM
Supplying, installing, testing and commissioning of addressable fire isolator module complete as required. EN 54 /FM or UL Listed with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 Reed relays FF-AFAS/ISM
Supplying, installing, testing and commissioning of addressable horn cum strobe sound/ hooter, output frequency 500 to 1000 Hz with dB as per Chart given in IS 15908:2021, with flashing at 1 Hz over the strobe’s entire operating voltage range EN 54, conforming to IS 2189: 2008, IS 15908:2021 standards with 3 years equipment replacement warranty FF-AFAS/SSH.
Supplying, installing, testing and commissioning FR, XLPE armoured cable 2 core 1.5 sq.mm. copper conductor complete erected on wall/ ceiling complete as per specification no. CB-LT/CU
Supplying, erecting, testing and commissioning 120 W amplifier suitable to operate on 230 Volts A.C. / 12 Volts D.C. supply complete as per specification no. FF- PA/AFR
Supplying, erecting, testing and commissioning 15 to 30 Watts sound column or ceiling mounted complete as per specification no. FF-PA/SOC
Supplying, erecting, testing and commissioning stand mounted/handheld type wired microphone having 2 mV/Pa sensitivity, impedance level limit 300 ohms and 50 - 16000 Hz suitable to operate in -10 deg C to +55 deg C with min. 7 metre shielded cable and 3 Pin Professional XLR Connector, stereo jack complete as per specification no. FF- PA/MIC
Supplying, erecting, testing and commissioning rust free microphone floor stand of chrome plating/powder coating or S.S. material , 500 mm to 1500 mm height and sturdy mechanism ensuring trouble free movement complete.
Supplying, erecting, testing and commissioning of 2 core shielded cable complete as per specification no. FF- PA/MCC
Supplying and installing corrugated SS flexible conduit of size 25mm dia for connecting sprinkler head with necessary fittings as per specifications having 1000mm long with UL/FM
Supplying, erecting, testing and commissioning of quartzoid bulb sprinkler, 15 mm (½") dia. NBCM Body chrome finished, 68º C fixed temperature rating with deflector disc of conventional construction complete as per specification no. FF-SPR.
Supplying, erecting, testing and commissioning of horizontal sidewall quartzoid bulb sprinkler, 15 mm (½") dia quartzoid bulb. NBCM Body chrome finished, 68º C fixed temperature rating with deflector disc of conventional construction complete as per specification no. FF-SPR/SS
Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts routed in
Supplying and erecting 4 kg clean agent gas Nitrogen pressurised controllable dicharge mechanism, pressure guage, Discharge hose and nozzle epoxy polyster powder coated as per IS 15683 ISI mark fire extinguisheroperating temperature (-)20 to (+) 55 C kg capacity suitable for A,B,C class of FIRE complete.
Supplying and erecting DCP Type 25 kg capacity trolley Mounted with controllable dicharge mechanism, pressure guage, Discharge hose and nozzle epoxy polyster powder coated as per IS 15683 ISI mark fire extinguisheroperating temperature (-)20 to (+) 55 C kg capacity suitable for A,B,C class of FIRE complete.
Supplying and erecting fire resistant mortar (20 kg) with fire resistance class S90 as per National Electrical Code (NEC) SP30-2011 suitable to seal the openings of all kinds of cables, pipes and cable support system in steel, aluminium and plastic profiles ( except hollow core conductors). The residual openings shall be closed with filler, as per specification no FF-FRM. Note :- For estimating purpose consider 1 bag of 20kg to cover 300mm x 400mm area 150mm thick or 0.018 m3. ( Total 108 rooms in Hospital, Each rooms having Fire sprinkler and other utility opening ,hence conidered one 20 kg bag per room. Total Set Required ( 300 X 400 X 150 = 1 room X 186 =38 Nos)
Making trench in Hard murum/Tar road having 0.75 m depth and minimum 0.3m width as per IS for laying provided cables up to voltage level 1.1Kv cable complete as per specification No. CW-EXN-CTR
Making cement concrete foundation in 1:2:4 cement concrete with foundation bolts and nuts complete ( cost of wooden box is included) for pumps for pump (1.2x 1.2 x0.8)= 1.15 x 6 = 6.9 cum for overhead tank (1.8 x 1.8 x 0.9)=2.91 x 2= 5.82 cum total (6.9+5.82)= 12.72 Cu-M
Supplying and erecting of fire Exit & Eire Exinguisher signlge Indicating the floor- numtber in words &syslem(Fire Exiinguisher & Accessories
Supply, Installation, testing of zinc aluminite fire water storage tank having capacity 20 KL having structreaboce ground which gives positive suction to fire Pumps. The tank shall include all civil work including site prepartion , excavation , PCC which can load of tank including of 100% water.( for booster pump as per NBC).
Supplying , Installation , Testing And Commissioning of Hinged Metal fire door 120 min fire rated un insulated single 50mm THK Honey Comb Infill single double RBT 143 x 57mm frame Straight with anchor fast erness frame 1.0 & shutter 0.9 mm powder coated to ral shade SFP SS Ball bearing 4" x 3" x 3"mm hionghed for steel doors ingersoll rand briton 121, NCE. SES Door closer size 3 with standard ARM , sprayed silver finish SFP SS sashlock with 70mm back set and 24 mmfor end , SS lever handle 22x 125 mm on rose , Euro profile cylinder 70 mm with both side key 29 SS strike plate Escutchenosschott pyran fire rated clear Glass 6mm thick 240 x 340 33 Hinged Metal Fire Door 120 min fire Rated
Supplying and erecting PVC trunking (PVC casing-n-capping) of size 25 mm with accessories on wall/ceiling as per specification No: WG-MA/CON.
Supplying and erecting HMS PVC conduit FRLS grade 25 mm dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No: WG- MA/CC.
Supplying and erecting mains with 2x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting mains with 1x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting mains with 2x1.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW
Supplying and erecting mains with 1x1.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW
Supplying and erecting mains with 2x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting mains with 1x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Point wiring for light/fan/bell in 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm (2+1E) FRLSH grade copper wire with flush type switch and required accessories as per specification No: WG-PW/SW
Point wiring for light/bell/exhaust fan in 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm (2+1E) FRLSH grade copper wire, modular type switch, earthing and required accessories as per specification No: WG- PW/SW.
Point wiring for independent plug in 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm (2+1E ) FRLSH grade copper wire, modular type switch, earthing and required accessories as per specification No: WG- PW/SW
Supplying and erecting single pole and neutral distribution board (SPNDB), with 2 ways for incoming and 6 ways (6 poles) for outgoing SP MCBs, with door, 1.2mm thickness surface / flush mounted, IP 43 Protection on iron / GI frame as per specification no. SW-SWR/MCBDB
Supplying & erecting inverter LED batten 20W tube light fitting with polycarbonate housing, heat sink, integrated HF electronic driver, Min. 2600 mAhLithium ion Battery with charging time of 8-10 Hours and backup time of Min. 3 hrs. with minimum 25% of initial Watts having luminous efficacy of 100 lumen/watt, CRI>80, CCT of 6500K and THD<=20% having useful life of minimum 25000 hrs. with overheating protection with 2 years warranty.
Supplying and erecting fresh air cum exhaust fan of light duty 250 V A.C. 50 cycles 300mm. 1400 RPM rust proof body & blades, wire mesh, duly erected, complete.
Supplying and erecting modular type switch 16A duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type 3 pin 6 / 16A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting PVC Surface modular switch box with double mounting plate for 3 module duly erected.
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 95 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting &terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 300 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL (main incoming cable to main fire panel).
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 4 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU(for booster Pump)
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 6 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying & laying (including excavation) reinforced cement concrete pipe of IS 458:2003 NP-2 class of 150 mm internal diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete.
Providing & erecting 3 Pole MCCB 415V, 400A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure /panel as per specification no. SW- SWR/MCCB. Note : For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB. Hence 18563 X 20%= 3712.60/-
Supplying and laying (including excavation of suitable width & depth up to 90 cm) 146 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, to required depth complete.
Providing & erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 150 mm width & 100 mm height comprising all required standard accessories.
Providing & erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 300 mm width & 100 mm height comprising all required standard accessories.
Providing & erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 400 mm width & 100 mm height comprising all required standard accessories.
Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results as per specification no. EA-EP (earthig schedule: 2 nos for each 2 nos main fire pump for hydrant and sprinkler , 2nos for each 2 nos jockey pump for sprinkler and hydrant , 1 nos for main fire panel and 1 nos for disel engine pump).= total 6 nos of earthing.
Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required. As per specification no EA-EP.(25x5) (1kg/m x 60 m=60 kg)
Supplying, installation, testing and commissioning of main fire pump(MFP / EP) suitable for water discharge of 2280 to 2850 LPM at 120 to 90 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 75kW or of suitable kW capacity for manual/automatic operation and consisting of following : (a) Horizontal type, single stage, centrifugal/split casing pump of cast iron body & bronze impeller with stainless steel shaft(SS410 grade), mechanical seal conforming to IS 1520. (b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF- MFP/SSC/EP
Supplying, installation, testing and commissioning of jockey fire pump (JP) suitable for water discharge of 180 to 240 LPM at 110 to 90 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 11 kW or of suitable kW capacity for manual/automatic operation and consisting of following : (a) Horizontal/vertical type, multi stage, centrifugal casing pump of cast iron body & bronze impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520. (b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/JP
Supplying, installation, testing and commissioning of booster fire pump [BP] suitable for water discharge of 900 LPM at 35 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 7.5 kW or of suitable kW capacity for manual/automatic operation and consisting of following : (a) Horizontal/vertical type, single/multi stage, centrifugal casing pump of cast iron body & bronze/CI impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520. (b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation on with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (d)Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/BP
Supplying, installation, testing and commissioning of main fire pump (MFP/DP) suitable for water discharge of 2280 to 2850 LPM at 120 to 90 m head driven by 110 HP or suitable HP capacity diesel engine at required working speed suitable for automatic operation and consisting of following : (a) Horizontal type, single stage, centrifugal casing pump of cast iron body & bronze impeller with stainless steel shaft(SS410 grade), mechanical seal conforming to IS 1520. (b) Water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12/24 volts DC electric starting equipment with battery of required AH capacity with necessary charger suitable to work on 230v, 50Hz AC supply, diesel tank of minimum 150ltr capacity with first filling of diesel up to 100% level with necessary piping with valves up to engine , exhaust pipe extended up to 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications etc. as required. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with engine assembly and accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/SSC/DP
For addition of booster pump for fire hydrant/sprinkler, add as follows in the basic cost of item no 13-5-1 towards necessary accessories, indicators etc. with necessary interlocking and updation of control logic..... for 5.5/ 7.5 kW centrifugal type booster pump 1no(1working) , add Rs…....
Supplying and erecting 100 mm dia Cast Iron end line strainer of Y-type flanged end pattern, PN16 pressure rating, SS screen, end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) for positive suction complete as per specification no. FF-VL/ELS ( 2 nos for jockey pump + 2 nos for booster pump=4 Nos.
Supplying and erecting 200 mm dia Cast Iron end line strainer of Y-type flanged end pattern, PN16 pressure rating, screen of SS end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) for positive suction complete as per specification no. FF- VL/ELS ( 1 nos main pump+1 nos for sprinkler pump+ 1 for disel pump= 3 Nos).
Supplying and erecting 100 mm dia. cast iron double flange sluice valve complete with PN16 pressure rating, as per specification no. FF-VL/SV
Supplying and erecting 200 mm dia. cast iron double flange sluice valve complete with PN16 pressure rating, as per specification no. FF-VL/SV
Supplying and erecting 50 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV
Supplying & erecting cast iron double flange butterfly valve of size 75/80 mm dia. complete as per specification no. FF-VL/BFV
Supplying & erecting cast iron double flange butterfly valve of size 100 mm dia. complete as per specification no. FF-VL/BFV
Supplying & erecting cast iron double flange butterfly valve of size 150 mm dia. complete as per specification no. FF-VL/BFV
Supplying & erecting cast iron double flange butterfly valve of size 200 mm dia. complete as per specification no. FF-VL/BFV
Supplying and erecting cast iron double flange ball type NRV of size 75mm/80 mm dia complete as per specification no. FF- VL/NRV
Supplying and erecting cast iron double flange ball type NRV of size 100 mm dia complete as per specification no. FF-VL/NRV
Supplying and erecting cast iron double flange ball type NRV of size 150 mm dia complete as per specification no. FF-VL/NRV
Supplying and erecting cast iron double flange ball type NRV of size 200 mm dia complete as per specification no. FF-VL/NRV
Supplying & erecting gun metal gate valve of size 25 mm dia complete as per specification no. FF-VL/GV
Supplying and installing air vessel of 300 mm dia1.5m in height M.S. tank installed inside pump house / on terrace complete as per specification no. FF-FFA/ACT (1 nos for hydrant + 1 nos for sprinkler= 2 nos).
Supplying and erecting 20/25mm dia gun metal air release cock, with necessary G.I. coupling to be fitted on top of air vessel or on wet riser complete as per specification no. FF-FFA/ARV (7no. For Riser + Two for Air Vessel= 9 nos.
Supplying and erecting 100 mm dia. pressure gauge , 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve, erected with provided G.I. pipe, elbow etc. complete as per specification no. FF-FFA/PG
Supplying and erecting 12/15 mm dia pressure switch with provided isolation valve, G.I. nipple, elbow, etc complete as per specification no. FF-FFA/PS
Carrying out core cutting of size 3" to 5" dia x 15" length in the C.C./rock/stone wall with the help of specialized core cutting machine in proper manner and finishing the site as original.
Making trench in Hard murum/Tar road having 0.75 m depth and minimum 0.3m width as per IS for laying provided cables up to voltage level 1.1Kv cable complete as per specification No. CW-EXN-CTR
Making cement concrete foundation in 1:2:4 cement concrete with foundation bolts and nuts complete ( cost of wooden box is included) for pumps (1.2x 1.2 x0.8)= 1.15 x 5 = 5.76 cum for overhead tank foundation (1.8 x 1.8 x 0.3)=0.972 x 5=4.86 cum total (6.9+5.82)= 10.62 Cu-M. For Hydrant Line Pedastal of size 1.2 m X 0.6 m X 0.6 m = 0.432 cum per pedastal , total terrace overhead ring line length 720 m /pedastal support will be at 4 m each ,hence total qty would be - 80/4 = 20 Nos ,so 20 X 0.432 = 8.68 cum ( pump foundation 10.62 cum + Pedastal 8.68 cum = 19.3 cum total)
Supply,Instlaation,testingzincaluminite fire water storage tank having capacity 20 KL having structreaboce ground which gives positive suction to fire Pumps. The tank shall include all civil work including site prepartion , excavation , PCC which can load of tank including of 100% water.( for booster pump as per NBC).
Supplying and erecting iron, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match theswitchgears or as per directions by the authority ( separate Iron work calculation sheet attached).
Supplying and erecting stainless steel single outlet hydrant valve fitted with necessary accessories complete as per specification no. FF-VL/HV.
Supplying and installing wall mounting swinging hose reel drum fitted with 19 mm dia. 30m long high pressure polypropylene (Polyhose) along with necessary accessories complete as per specification no. FF-FFA/HV
Supplying fire fighting reinforced rubber lined (R.R.L.) hose pipe, 63mm dia, 15m in length, fitted with necessary accessories complete as per specification no. FF-FFA/RRL
Supplying & erecting stainless steel branch pipe 63 mm dia fitted with 20 mm dia detachable hexagonal nozzle complete as per specifications no. FF-FFA/NZ
Supplying and erecting brass orifice plate having 6 mm. thickness, 140 mm outer dia with required diameter of inner hole at every single outlet hydrant valve as per specification no. FF-FFA/OP (For Internal Hydrant).
Supplying and erecting M.S./CRCA cabinet for housing single hydrant valve of size ( 400 x 400 x 400)mm or hose pipe box of size ( 600 x 600 x 200)mm made from min. 1.5 mm thick CRCA sheet with angle iron work of min. of size (25 x 25 x 4) mm having front doors with viewing glass of size (200x150) mm and locking arrangement with necessary fixing material such as rubber bidding etc. duly painted in post box red colour( Code 538 of IS 5)
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 25 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 50 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 65 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 75/80 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 100 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 150 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 200 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying & erecting gun metal gate valve of size 20 mm dia complete as per specification no. FF-VL/GV
Supplying & erecting gun metal gate valve of size 25 mm dia complete as per specification no. FF-VL/GV
Supplying and installing corrugated SS flexible conduit of size 25mm dia for connecting sprinkler head with necessary fittings as per specifications having 1000mm long with UL/FM
Supplying, erecting, testing and commissioning of quartzoid bulb sprinkler, 15 mm (½") dia. NBCM Body chrome finished, 68º C fixed temperature rating with deflector disc of conventional construction complete as per specification no. FF-SPR.
Supplying, erecting, testing and commissioning of horizontal sidewall quartzoid bulb sprinkler, 15 mm (½") dia quartzoid bulb. NBCM Body chrome finished, 68º C fixed temperature rating with deflector disc of conventional construction complete as per specification no. FF-SPR/SS
Supplying and erecting fire resistant mortar (20 kg) with fire resistance class S90 as per National Electrical Code (NEC) SP30-2011 suitable to seal the openings of all kinds of cables, pipes and cable support system in steel, aluminium and plastic profiles ( except hollow core conductors). The residual openings shall be closed with filler, as per specification no FF-FRM. Note :- For estimating purpose consider 1 bag of 20kg to cover 300mm x 400mm area 150mm thick or 0.018 m3. ( Approx 780 rooms in Hospital, Each rooms having Fire sprinkler and other utility opening ,hence conidered one 20 kg bag per room. Total Set Required ( 300 X 400 X 150 = 1 room X 30 =30 Nos)
Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the 4 loop capacity and capable of supporting upto 250 devices and detectors per loop, with on-board LCD display with min 16 lines of text, operating at 230 V 50 HZ - AC with inbuilt Battery Backup of a minimum 24 hours in normal condition and 30 min in alarm condition, suitable provision for network connectivity, interfacing with third party equipment via a MODBUS/ OPC/ L-ON interface etc. conforming to IS 15908:2021, ,IS 2189: 2008, EN 54 & VDS / FM/ UL 864 (10th edition) with 3 years replacement warranty FF-AFAS/CP.
Supplying, installing, testing and commissioning of repeater panel with suitable battery backup of a minimum of 24 hours in normal condition and 30 min in alarm condition, 80 backlit alphanumeric LCD display with inbuilt buzzer to indicate fault/fire alarm, manual control keys for silence/mute and to reset the FACP from the repeater station. Panel size shall not more than 175 x 275 x 65 mm conforming to EN 54 or UL approved with 3 years equipment replacement warranty FF-AFAS/RP
Supplying, installing, testing and commissioning of addressable optical smoke detector, single/twin LED’s with 360 degree view, suitable for low voltage 15 to 32 V DC two wires supply, in-built locking mechanism to check the removal and pilferage of the detector, in built isolation mode, start up current 300µA and alarm condition current shall be maximum 6.5 mA, operating temperature 0°C to 50°C, humidity 0-95% RH, IP 41, conforming to IS 2189: 2008, 11360_1985_Reff2020 EN 54 or UL Approved with 3 years equipment replacement warranty FF-AFAS/SD
Supplying, installing, testing and commissioning of intelligent addressable thermal/heat detector with rate of rise cum fixed temperature thermistor complete with base as required, suitable for temperature variations from -20°C to 38°C for fixed-heat and rate-of-rise type detectors and 0°C to 66°C for high heat type detectors, in built isolation mode, suitable for offices/ceiling cable trenches/less ventilation area's etc. with 3 years equipment replacement warranty IS : 2175 - 1988 reaffirmed 2000, IS 15908:2021 standards FF-AFAS/SD.
Supplying, installing, testing and commissioning of addressable manual call points ( break glass type/pull station type), made of addressable break glass plastic square in shape surface/flush mounted with "Break Glass" massage embedded on the glass, complete erected with mounting base and required accessories conforming to EN 54 or UL listed with 3 years equipment replacement warranty FF-AFAS/MCP.
Supplying, installing, testing and commissioning of addressable fire control/relay module complete as required, with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 reed relays, EN 54 or UL Listed FF- AFAS/CRM
Supplying, installing, testing and commissioning of addressable fire monitor module complete as required. EN 54 or UL Listed with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 Reed relays FF-AFAS/MM
Supplying, installing, testing and commissioning of addressable fire isolator module complete as required. EN 54 /FM or UL Listed with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 Reed relays FF-AFAS/ISM
Supplying, installing, testing and commissioning of addressable horn cum strobe sound/ hooter, output frequency 500 to 1000 Hz with dB as per Chart given in IS 15908:2021, with flashing at 1 Hz over the strobe’s entire operating voltage range EN 54, conforming to IS 2189: 2008, IS 15908:2021 standards with 3 years equipment replacement warranty FF-AFAS/SSH.
Supplying, installing, testing and commissioning FR, XLPE armoured cable 2 core 1.5 sq.mm. copper conductor complete erected on wall/ ceiling complete as per specification no. CB-LT/CU
Supplying, installing, testing and commissioning FR, XLPE armoured cable 8 core 1.5 sq.mm. copper conductor complete erected on wall/ ceiling complete as per specification no. CB-LT/CU
Supplying, erecting, testing and commissioning 120 W amplifier suitable to operate on 230 Volts A.C. / 12 Volts D.C. supply complete as per specification no. FF- PA/AFR
Supplying, erecting, testing and commissioning 15 to 30 Watts sound column or ceiling mounted complete as per specification no. FF-PA/SOC
Supplying, erecting, testing and commissioning stand mounted/handheld type wired microphone having 2 mV/Pa sensitivity, impedance level limit 300 ohms and 50 - 16000 Hz suitable to operate in -10 deg C to +55 deg C with min. 7 metre shielded cable and 3 Pin Professional XLR Connector, stereo jack complete as per specification no. FF- PA/MIC
Supplying, erecting, testing and commissioning rust free microphone floor stand of chrome plating/powder coating or S.S. material , 500 mm to 1500 mm height and sturdy mechanism ensuring trouble free movement complete.
Supplying, erecting, testing and commissioning of 2 core shielded sound cable complete as per specification no. FF- PA/MCC
Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts routed in wall complete.
Supplying and erecting 4 kg clean agent gas Nitrogen pressurised controllable dicharge mechanism, pressure guage, Discharge hose and nozzle epoxy polyster powder coated as per IS 15683 ISI mark fire extinguisheroperating temperature (-)20 to (+) 55 C kg capacity suitable for A,B,C class of FIRE complete.
Supplying and erecting DCP Type 25 kg capacity trolley Mounted with controllable dicharge mechanism, pressure guage, Discharge hose and nozzle epoxy polyster powder coated as per IS 15683 ISI mark fire extinguisheroperating temperature (-)20 to (+) 55 C kg capacity suitable for A,B,C class of FIRE complete.
Supplying and erecting of fire Exit & Eire Exinguishersignlge Indicating the floor- numtber in words &syslem(Fire Exiinguisher& Accessories ) (Non CSR Approved by S.E.Office ,mumbai vide T.S letter no- 108 Date- 13/01/2022 )
Supplying , Installation , Testing And Commissioning of Hinged Metal fire door 120 min fire rated un insulated single 50mm THK Honey Comb Infill single double RBT 143 x 57mm frame Straight with anchor fast erness frame 1.0 & shutter 0.9 mm powder coated to ral shade SFP SS Ball bearing 4" x 3" x 3"mm hionghed for steel doors ingersoll rand briton 121, NCE. SES Door closer size 3 with standard ARM , sprayed silver finish SFP SS sashlock with 70mm back set and 24 mmfor end , SS lever handle 22x 125 mm on rose , Euro profile cylinder 70 mm with both side key 29 SS strike plate Escutchenosschott pyran fire rated clear Glass 6mm thick 240 x 340 33 Hinged Metal Fire Door 120 min fire Rated
Supplying and erecting PVC trunking (PVC casing-n-capping) of size 25 mm with accessories on wall/ceiling as per specification No: WG-MA/CON.
Supplying and erecting HMS PVC conduit FRLS grade 25 mm dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No: WG- MA/CC.
Supplying and erecting mains with 2x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting mains with 1x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting mains with 2x1.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW
Supplying and erecting mains with 1x1.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW
Supplying and erecting mains with 2x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting mains with 1x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Point wiring for light/fan/bell in 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm (2+1E) FRLSH grade copper wire with flush type switch and required accessories as per specification No: WG-PW/SW
Point wiring for light/bell/exhaust fan in 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm (2+1E) FRLSH grade copper wire, modular type switch, earthing and required accessories as per specification No: WG- PW/SW.
Point wiring for independent plug in 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm (2+1E ) FRLSH grade copper wire, modular type switch, earthing and required accessories as per specification No: WG- PW/SW
Supplying and erecting single pole and neutral distribution board (SPNDB), with 2 ways for incoming and 6 ways (6 poles) for outgoing SP MCBs, with door, 1.2mm thickness surface / flush mounted, IP 43 Protection on iron / GI frame as per specification no. SW-SWR/MCBDB
Supplying & erecting inverter LED batten 20W tube light fitting with polycarbonate housing, heat sink, integrated HF electronic driver, Min. 2600 mAhLithium ion Battery with charging time of 8-10 Hours and backup time of Min. 3 hrs. with minimum 25% of initial Watts having luminous efficacy of 100 lumen/watt, CRI>80, CCT of 6500K and THD<=20% having useful life of minimum 25000 hrs. with overheating protection with 2 years warranty.
Supplying and erecting fresh air cum exhaust fan of light duty 250 V A.C. 50 cycles 300mm. 1400 RPM rust proof body & blades, wire mesh, duly erected, complete.
Supplying and erecting modular type switch 16A duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type 3 pin 6 / 16A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting PVC Surface modular switch box with double mounting plate for 3 module duly erected.
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 95 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting &terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 300 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL (main incoming cable to main fire panel).
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 4 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU(for booster Pump)
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 6 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying & laying (including excavation) reinforced cement concrete pipe of IS 458:2003 NP-2 class of 150 mm internal diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete.
Providing & erecting 3 Pole MCCB 415V, 400A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure /panel as per specification no. SW- SWR/MCCB. Note : For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB. Hence 18563 X 20%= 3712.60/-
Supplying and laying (including excavation of suitable width & depth up to 90 cm) 146 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, to required depth complete.
Providing & erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 150 mm width & 100 mm height comprising all required standard accessories.
Providing & erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 300 mm width & 100 mm height comprising all required standard accessories.
Providing & erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 400 mm width & 100 mm height comprising all required standard accessories.
Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results as per specification no. EA-EP (earthig schedule: 2 nos for each 2 nos main fire pump for hydrant and sprinkler , 2nos for each 2 nos jockey pump for sprinkler and hydrant , 1 nos for main fire panel and 1 nos for disel engine pump).= total 6 nos of earthing.
Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required. As per specification no EA-EP.(25x5) (1kg/m x 60 m=60 kg)
Supplying, installation, testing and commissioning of main fire pump(MFP / EP) suitable for water discharge of 2280 to 2850 LPM at 120 to 90 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 75kW or of suitable kW capacity for manual/automatic operation and consisting of following : (a) Horizontal type, single stage, centrifugal/split casing pump of cast iron body & bronze impeller with stainless steel shaft(SS410 grade), mechanical seal conforming to IS 1520. (b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF- MFP/SSC/EP
Supplying, installation, testing and commissioning of jockey fire pump (JP) suitable for water discharge of 180 to 240 LPM at 110 to 90 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 11 kW or of suitable kW capacity for manual/automatic operation and consisting of following : (a) Horizontal/vertical type, multi stage, centrifugal casing pump of cast iron body & bronze impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520. (b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/JP
Supplying, installation, testing and commissioning of main fire pump (MFP/DP) suitable for water discharge of 2280 to 2850 LPM at 120 to 90 m head driven by 110 HP or suitable HP capacity diesel engine at required working speed suitable for automatic operation and consisting of following : (a) Horizontal type, single stage, centrifugal casing pump of cast iron body & bronze impeller with stainless steel shaft(SS410 grade), mechanical seal conforming to IS 1520. (b) Water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12/24 volts DC electric starting equipment with battery of required AH capacity with necessary charger suitable to work on 230v, 50Hz AC supply, diesel tank of minimum 150ltr capacity with first filling of diesel up to 100% level with necessary piping with valves up to engine , exhaust pipe extended up to 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications etc. as required. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with engine assembly and accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/SSC/DP
Supplying and erecting 100 mm dia Cast Iron end line strainer of Y-type flanged end pattern, PN16 pressure rating, SS screen, end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) for positive suction complete as per specification no. FF-VL/ELS ( 2 nos for jockey pump + 2 nos for booster pump=4 Nos.
Supplying and erecting 200 mm dia Cast Iron end line strainer of Y-type flanged end pattern, PN16 pressure rating, screen of SS end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) for positive suction complete as per specification no. FF- VL/ELS ( 1 nos main pump+1 nos for sprinkler pump+ 1 for disel pump= 3 Nos).
Supplying and erecting 100 mm dia. cast iron double flange sluice valve complete with PN16 pressure rating, as per specification no. FF-VL/SV
Supplying and erecting 150 mm dia. cast iron double flange sluice valve complete with PN16 pressure rating, as per specification no. FF-VL/SV
Supplying and erecting 200 mm dia. cast iron double flange sluice valve complete with PN16 pressure rating, as per specification no. FF-VL/SV
Supplying and erecting 50 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV
Supplying & erecting cast iron double flange butterfly valve of size 75/80 mm dia. complete as per specification no. FF-VL/BFV
Supplying & erecting cast iron double flange butterfly valve of size 100 mm dia. complete as per specification no. FF-VL/BFV
Supplying & erecting cast iron double flange butterfly valve of size 150 mm dia. complete as per specification no. FF-VL/BFV
Supplying & erecting cast iron double flange butterfly valve of size 200 mm dia. complete as per specification no. FF-VL/BFV
Supplying and erecting cast iron double flange ball type NRV of size 75mm/80 mm dia complete as per specification no. FF- VL/NRV
Supplying and erecting cast iron double flange ball type NRV of size 150 mm dia complete as per specification no. FF-VL/NRV
Supplying and erecting cast iron double flange ball type NRV of size 200 mm dia complete as per specification no. FF-VL/NRV
Supplying & erecting gun metal gate valve of size 20 mm dia complete as per specification no. FF-VL/GV
Supplying & erecting gun metal gate valve of size 25 mm dia complete as per specification no. FF-VL/GV
Supplying and erecting 150 mm dia fire brigade header suitable for supplying water in fire tank complete as per specification no. FF-FA/FBC
Supplying and erecting fire brigade header ( Siamese connection ) of 150 mm dia, for supplying water in fire tank complete as per specification no. FF-FA/FMC
Supplying and installing air vessel of 300 mm dia1.5m in height M.S. tank installed inside pump house / on terrace complete as per specification no. FF-FFA/ACT (1 nos for hydrant + 1 nos for sprinkler= 2 nos).
Supplying and erecting 20/25mm dia gun metal air release cock, with necessary G.I. coupling to be fitted on top of air vessel or on wet riser complete as per specification no. FF-FFA/ARV.
Supplying and erecting 100 mm dia. pressure gauge , 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve, erected with provided G.I. pipe, elbow etc. complete as per specification no. FF-FFA/PG
Supplying and erecting 12/15 mm dia pressure switch with provided isolation valve, G.I. nipple, elbow, etc complete as per specification no. FF-FFA/PS
Carrying out core cutting of size 3" to 5" dia x 15" length in the C.C./rock/stone wall with the help of specialized core cutting machine in proper manner and finishing the site as original.
Making trench in Hard murum/Tar road having 0.75 m depth and minimum 0.3mtr width as per IS for laying provided cables up to voltage level 1.1Kv cable complete as per specification No. CW-EXN-CTR
Making cement concrete foundation in 1:2:4 cement concrete with foundation bolts and nuts complete ( cost of wooden box is included) for pumps (1.2x 1.2 x0.8)= 1.15 x 5 = 5.76 cum for overhead tank foundation (1.8 x 1.8 x 0.3)=0.972 x 5=4.86 cum total (6.9+5.82)= 10.62 Cu-M. For Hydrant Line Pedastal of size 1.2 m X 0.6 m X 0.6 m = 0.432 cum per pedastal , Total ring line length 2984 m /pedastal support will be at 4 m each ,hence total qty would be - 2984/4 = 746 Nos ,so 746 X 0.432 = 322.28 cum ( pump foundation 10.62 cum + Pedastal 322.28 cum = 332.9 cum total)
Supplying and erecting iron, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority ( separate Iron work calculation sheet attached).
Supplying and erecting stainless steel single outlet hydrant valve fitted with necessary accessories complete as per specification no. FF-VL/HV.
Supplying fire fighting reinforced rubber lined (R.R.L.) hose pipe, 63mm dia, 15m in length, fitted with necessary accessories complete as per specification no. FF-FFA/RRL
Supplying & erecting stainless steel branch pipe 63 mm dia fitted with 20 mm dia detachable hexagonal nozzle complete as per specifications no. FF-FFA/NZ
Supplying and erecting brass orifice plate having 6 mm. thickness, 140 mm outer dia with required diameter of inner hole at every single outlet hydrant valve as per specification no. FF-FFA/OP (For Internal Hydrant).
Supplying and erecting M.S./CRCA cabinet for housing Floor Hydrant valve, hose pipe, hose reel and branch pipe (size 1000 x 736 x 736 mm.) made from 16 SWG sheet and angle iron 25 x 25 x 4 mm. having front doors with viewing glass (8"x6") and locking arrangement with necessary fixing material such as rubber bidding etc. duly painted in post box red colour( Code 538 of IS 5)
Supplying and erecting G.I. pipe ‘C’ class ERW 25 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe ‘C’ class ERW 50 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe ‘C’ class ERW 75/80 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe ‘C’ class ERW 100 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe ‘C’ class ERW 150 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe ‘C’ class ERW 200 mm dia with necessary fittings complete as per specification no. FF-PP
Providing coating of bitumen paint & 4mm thick wrapping for underground 150 mm ring main of fire fighting system.
Providing coating of bitumen paint & 4mm thick wrapping for underground 200 mm ring main of fire fighting system.
Supplying and erecting fire resistant mortar (20 kg) with fire resistance class S90 as per National Electrical Code (NEC) SP30-2011 suitable to seal the openings of all kinds of cables, pipes and cable support system in steel, aluminium and plastic profiles ( except hollow core conductors). The residual openings shall be closed with filler, as per specification no FF-FRM.
Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts routed in wall complete.
Supplying and erecting of fire Exit & Eire Exinguishersignlge Indicating the floor- numtber in words &syslem(Fire Exiinguisher& Accessories
Making cement concrete foundation including excavation (60 x 60 x 150) cm deep in 1:3:6 cement concrete, (20 to 25) mm stone metal with necessary curing and finishing complete.(for stay).
Supplying and erecting Gas Suppression system (Novec 1230-FK1230 Gas Suppression system with CCOE cylinder one no.32 liter capacity with filled Gas, Electrical,Manual,Nozzle and Gas Release panel with Smoke detector, as per Schedule-C Sr No.43 specification.
Supplying and erecting PVC trunking (PVC casing-n-capping) of size 25 mm with accessories on wall/ceiling as per specification No: WG-MA/CON.
Supplying and erecting mains with 3x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW
Supplying and erecting modular type switch 6A / 10A duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type 3 pin 6 / 16A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting PVC Surface modular switch box with double mounting plate for 3 module duly erected.
Supplying and erecting iron, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority ( separate Iron work calculation sheet attached).
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 4 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU(for booster Pump)
Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results as per specification no. EA-EP (earthig schedule: 2 nos for each 2 nos main fire pump for hydrant and sprinkler , 2nos for each 2 nos jockey pump for sprinkler and hydrant , 1 nos for main fire panel and 1 nos for disel engine pump).= total 6 nos of earthing.
Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required. As per specification no EA-EP.(25x5) (1kg/m x 40 m=40 kg)
Supplying, installation, testing and commissioning of booster fire pump [BP] suitable for water discharge of 900 LPM at 35 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 7.5 kW or of suitable kW capacity for manual/automatic operation and consisting of following : (a) Horizontal/vertical type, single/multi stage, centrifugal casing pump of cast iron body & bronze/CI impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520. (b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation on with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (d)Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/BP
For addition of booster pump for fire hydrant/sprinkler, add as follows in the basic cost of item no 13-5-1 towards necessary accessories, indicators etc. with necessary interlocking and updation of control logic..... for 5.5/ 7.5 kW centrifugal type booster pump 1no(1working) , add Rs…....
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 25 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 50 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 65 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 75/80 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 100 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 150 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting 100 mm dia Cast Iron end line strainer of Y-type flanged end pattern, PN16 pressure rating, SS screen, end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) for positive suction complete as per specification no. FF-VL/ELS
Supplying and erecting 100 mm dia. cast iron double flange sluice valve complete with PN16 pressure rating, as per specification no. FF-VL/SV
Supplying and erecting 50 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV
Supplying and erecting 75/80 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV
Supplying & erecting cast iron double flange butterfly valve of size 100 mm dia. complete as per specification no. FF-VL/BFV
Supplying & erecting cast iron double flange butterfly valve of size 150 mm dia. complete as per specification no. FF-VL/BFV
Supplying and erecting cast iron double flange ball type NRV of size 100 mm dia complete as per specification no. FF-VL/NRV
Supplying & erecting gun metal gate valve of size 25 mm dia complete as per specification no. FF-VL/GV
Supplying and erecting stainless steel single outlet hydrant valve fitted with necessary accessories complete as per specification no. FF-VL/HV.
Supplying and installing wall mounting swinging hose reel drum fitted with 19 mm dia. 30m long high pressure polypropylene (Polyhose) along with necessary accessories complete as per specification no. FF-FFA/HV
Supplying fire fighting reinforced rubber lined (R.R.L.) hose pipe, 63mm dia, 15m in length, fitted with necessary accessories complete as per specification no. FF-FFA/RRL
Supplying & erecting stainless steel branch pipe 63 mm dia fitted with 20 mm dia detachable hexagonal nozzle complete as per specifications no. FF-FFA/NZ
Supplying and erecting 20/25mm dia gun metal air release cock, with necessary G.I. coupling to be fitted on top of air vessel or on wet riser complete as per specification no. FF-FFA/ARV (7no. For Riser + Two for Air Vessel= 9 nos.
Supplying and erecting 100 mm dia. pressure gauge , 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve, erected with provided G.I. pipe, elbow etc. complete as per specification no. FF-FFA/PG
Supplying and erecting brass orifice plate having 6 mm. thickness, 140 mm outer dia with required diameter of inner hole at every single outlet hydrant valve as per specification no. FF-FFA/OP (For Internal Hydrant).
Supplying and erecting M.S./CRCA cabinet for housing Floor Hydrant valve, hose pipe, hose reel and branch pipe (size 1000 x 736 x 736 mm.) made from 16 SWG sheet and angle iron 25 x 25 x 4 mm. having front doors with viewing glass (8"x6") and locking arrangement with necessary fixing material such as rubber bidding etc. duly painted in post box red colour( Code 538 of IS 5) (BoX for Two set of Hose Pipe along with 1set of Branch Pipe).
Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the 4 loop capacity and capable of supporting upto 250 devices and detectors per loop, with on-board LCD display with min 16 lines of text, operating at 230 V 50 HZ - AC with inbuilt Battery Backup of a minimum 24 hours in normal condition and 30 min in alarm condition, suitable provision for network connectivity, interfacing with third party equipment via a MODBUS/ OPC/ L-ON interface etc. conforming to IS 15908:2021, ,IS 2189: 2008, EN 54 & VDS / FM/ UL 864 (10th edition) with 3 years replacement warranty FF-AFAS/CP.
Supplying, installing, testing and commissioning of repeater panel with suitable battery backup of a minimum of 24 hours in normal condition and 30 min in alarm condition, 80 backlit alphanumeric LCD display with inbuilt buzzer to indicate fault/fire alarm, manual control keys for silence/mute and to reset the FACP from the repeater station. Panel size shall not more than 175 x 275 x 65 mm conforming to EN 54 or UL approved with 3 years equipment replacement warranty FF-AFAS/RP
Supplying, installing, testing and commissioning of addressable optical smoke detector, single/twin LED’s with 360 degree view, suitable for low voltage 15 to 32 V DC two wires supply, in-built locking mechanism to check the removal and pilferage of the detector, in built isolation mode, start up current 300µA and alarm condition current shall be maximum 6.5 mA, operating temperature 0°C to 50°C, humidity 0-95% RH, IP 41, conforming to IS 2189: 2008, 11360_1985_Reff2020 EN 54 or UL Approved with 3 years equipment replacement warranty FF-AFAS/SD
Supplying, installing, testing and commissioning of intelligent addressable thermal/heat detector with rate of rise cum fixed temperature thermistor complete with base as required, suitable for temperature variations from -20°C to 38°C for fixed-heat and rate-of-rise type detectors and 0°C to 66°C for high heat type detectors, in built isolation mode, suitable for offices/ceiling cable trenches/less ventilation area's etc. with 3 years equipment replacement warranty IS : 2175 - 1988 reaffirmed 2000, IS 15908:2021 standards FF-AFAS/SD.
Supplying, installing, testing and commissioning of addressable manual call points ( break glass type/pull station type), made of addressable break glass plastic square in shape surface/flush mounted with "Break Glass" massage embedded on the glass, complete erected with mounting base and required accessories conforming to EN 54 or UL listed with 3 years equipment replacement warranty FF-AFAS/MCP.
Supplying, installing, testing and commissioning of addressable fire control/relay module complete as required, with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 reed relays, EN 54 or UL Listed FF- AFAS/CRM
Supplying, installing, testing and commissioning of addressable fire monitor module complete as required. EN 54 or UL Listed with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 Reed relays FF-AFAS/MM
Supplying, installing, testing and commissioning of addressable fire isolator module complete as required. EN 54 /FM or UL Listed with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 Reed relays FF-AFAS/ISM
Supplying, installing, testing and commissioning of addressable horn cum strobe sound/ hooter, output frequency 500 to 1000 Hz with dB as per Chart given in IS 15908:2021, with flashing at 1 Hz over the strobe’s entire operating voltage range EN 54, conforming to IS 2189: 2008, IS 15908:2021 standards with 3 years equipment replacement warranty FF-AFAS/SSH.
Supplying, installing, testing and commissioning FR, XLPE armoured cable 2 core 1.5 sq.mm. copper conductor complete erected on wall/ ceiling complete as per specification no. CB-LT/CU
Supplying, erecting, testing and commissioning 120 W amplifier suitable to operate on 230 Volts A.C. / 12 Volts D.C. supply complete as per specification no. FF- PA/AFR
Supplying, erecting, testing and commissioning 15 to 30 Watts sound column or ceiling mounted complete as per specification no. FF-PA/SOC
Supplying, erecting, testing and commissioning stand mounted/handheld type wired microphone having 2 mV/Pa sensitivity, impedance level limit 300 ohms and 50 - 16000 Hz suitable to operate in -10 deg C to +55 deg C with min. 7 metre shielded cable and 3 Pin Professional XLR Connector, stereo jack complete as per specification no. FF- PA/MIC
Supplying, erecting, testing and commissioning rust free microphone floor stand of chrome plating/powder coating or S.S. material , 500 mm to 1500 mm height and sturdy mechanism ensuring trouble free movement complete.
Supplying, erecting, testing and commissioning of 2 core shielded cable complete as per specification no. FF- PA/MCC
Supplying and installing corrugated SS flexible conduit of size 25mm dia for connecting sprinkler head with necessary fittings as per specifications having 1000mm long with UL/FM
Carrying out core cutting of size 3" to 5" dia x 15" length in the C.C./rock/stone wall with the help of specialized core cutting machine in proper manner and finishing the site as original.
Supplying, erecting, testing and commissioning of quartzoid bulb sprinkler, 15 mm (½") dia. NBCM Body chrome finished, 68º C fixed temperature rating with deflector disc of conventional construction complete as per specification no. FF-SPR.
Supplying, erecting, testing and commissioning of horizontal sidewall quartzoid bulb sprinkler, 15 mm (½") dia quartzoid bulb. NBCM Body chrome finished, 68º C fixed temperature rating with deflector disc of conventional construction complete as per specification no. FF-SPR/SS
Supplying and erecting fire resistant mortar (20 kg) with fire resistance class S90 as per National Electrical Code (NEC) SP30-2011 suitable to seal the openings of all kinds of cables, pipes and cable support system in steel, aluminium and plastic profiles ( except hollow core conductors). The residual openings shall be closed with filler, as per specification no FF-FRM. Note :- For estimating purpose consider 1 bag of 20kg to cover 300mm x 400mm area 150mm thick or 0.018 m3. ( Total 108 rooms in Hospital, Each rooms having Fire sprinkler and other utility opening ,hence conidered one 20 kg bag per room. Total Set Required ( 300 X 400 X 150 = 1 room X 38 =38 Nos)
Making trench in Hard murum/Tar road having 0.75 m depth and minimum 0.3m width as per IS for laying provided cables up to voltage level 1.1Kv cable complete as per specification No. CW-EXN-CTR
Making cement concrete foundation in 1:2:4 cement concrete with foundation bolts and nuts complete ( cost of wooden box is included) for pumps for pump (1.2x 1.2 x0.8)= 1.15 x 6 = 6.9 cum for overhead tank (1.8 x 1.8 x 0.9)=2.91 x 2= 5.82 cum total (6.9+5.82)= 12.72 Cu-M
Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts routed in wall complete.
Supplying and erecting 4 kg clean agent gas Nitrogen pressurised controllable dicharge mechanism, pressure guage, Discharge hose and nozzle epoxy polyster powder coated as per IS 15683 ISI mark fire extinguisheroperating temperature (-)20 to (+) 55 C kg capacity suitable for A,B,C class of FIRE complete.
Supplying and erecting of fire Exit & Eire Exinguishersignlge Indicating the floor- numtber in words &syslem(Fire Exiinguisher& Accessories
Supplying and erecting DCP Type 25 kg capacity trolley Mounted with controllable dicharge mechanism, pressure guage, Discharge hose and nozzle epoxy polyster powder coated as per IS 15683 ISI mark fire extinguisheroperating temperature (-)20 to (+) 55 C kg capacity suitable for A,B,C class of FIRE complete.
Supply, Installation, testing zinc aluminite fire water storage tank having capacity 10 KL having structreaboce ground which gives positive suction to fire Pumps. The tank shall include all civil work including site prepartion , excavation , PCC which can load of tank including of 100% water.( for booster pump as per NBC).
Supplying , Installation , Testing And Commissioning of Hinged Metal fire door 120 min fire rated un insulated single 50mm THK Honey Comb Infill single double RBT 143 x 57mm frame Straight with anchor fast erness frame 1.0 & shutter 0.9 mm powder coated to ral shade SFP SS Ball bearing 4" x 3" x 3"mm hionghed for steel doors ingersoll rand briton 121, NCE. SES Door closer size 3 with standard ARM , sprayed silver finish SFP SS sashlock with 70mm back set and 24 mmfor end , SS lever handle 22x 125 mm on rose , Euro profile cylinder 70 mm with both side key 29 SS strike plate Escutchenosschott pyran fire rated clear Glass 6mm thick 240 x 340 33 Hinged Metal Fire Door 120 min fire Rated
Supplying and erecting PVC trunking (PVC casing-n-capping) of size 25 mm with accessories on wall/ceiling as per specification No: WG-MA/CON.
Supplying and erecting mains with 3x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW
Supplying and erecting modular type switch 6A / 10A duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type 3 pin 6 / 16A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting PVC Surface modular switch box with double mounting plate for 3 module duly erected.
Supplying and erecting iron, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority ( separate Iron work calculation sheet attached).
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 4 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU(for booster Pump)
Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results as per specification no. EA-EP (earthig schedule: 2 nos for each 2 nos main fire pump for hydrant and sprinkler , 2nos for each 2 nos jockey pump for sprinkler and hydrant , 1 nos for main fire panel and 1 nos for disel engine pump).= total 6 nos of earthing.
Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required. As per specification no EA-EP.(25x5) (1kg/mtr x 50 mtr=50 kg)
Supplying, installation, testing and commissioning of booster fire pump [BP] suitable for water discharge of 900 LPM at 35 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 7.5 kW or of suitable kW capacity for manual/automatic operation and consisting of following : (a) Horizontal/vertical type, single/multi stage, centrifugal casing pump of cast iron body & bronze/CI impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520. (b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation on with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (d)Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/BP
For addition of booster pump for fire hydrant/sprinkler, add as follows in the basic cost of item no 13-5-1 towards necessary accessories, indicators etc. with necessary interlocking and updation of control logic..... for 5.5/ 7.5 kW centrifugal type booster pump 1no(1working) , add Rs…....
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 25 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 50 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 65 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 75/80 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 100 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 150 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting 100 mm dia Cast Iron end line strainer of Y-type flanged end pattern, PN16 pressure rating, SS screen, end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) for positive suction complete as per specification no. FF-VL/ELS
Supplying and erecting 100 mm dia. cast iron double flange sluice valve complete with PN16 pressure rating, as per specification no. FF-VL/SV
Supplying and erecting 50 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV
Supplying and erecting 75/80 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV
Supplying & erecting cast iron double flange butterfly valve of size 100 mm dia. complete as per specification no. FF-VL/BFV
Supplying & erecting cast iron double flange butterfly valve of size 150 mm dia. complete as per specification no. FF-VL/BFV
Supplying and erecting cast iron double flange ball type NRV of size 100 mm dia complete as per specification no. FF-VL/NRV
Supplying & erecting gun metal gate valve of size 25 mm dia complete as per specification no. FF-VL/GV
Supplying and erecting stainless steel single outlet hydrant valve fitted with necessary accessories complete as per specification no. FF-VL/HV.
Supplying and installing wall mounting swinging hose reel drum fitted with 19 mm dia. 30m long high pressure polypropylene (Polyhose) along with necessary accessories complete as per specification no. FF-FFA/HV
Supplying fire fighting reinforced rubber lined (R.R.L.) hose pipe, 63mm dia, 15m in length, fitted with necessary accessories complete as per specification no. FF-FFA/RRL
Supplying & erecting stainless steel branch pipe 63 mm dia fitted with 20 mm dia detachable hexagonal nozzle complete as per specifications no. FF-FFA/NZ
Supplying and erecting 20/25mm dia gun metal air release cock, with necessary G.I. coupling to be fitted on top of air vessel or on wet riser complete as per specification no. FF-FFA/ARV (7no. For Riser + Two for Air Vessel= 9 nos.
Supplying and erecting 100 mm dia. pressure gauge , 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve, erected with provided G.I. pipe, elbow etc. complete as per specification no. FF-FFA/PG
Supplying and erecting brass orifice plate having 6 mm. thickness, 140 mm outer dia with required diameter of inner hole at every single outlet hydrant valve as per specification no. FF-FFA/OP (For Internal Hydrant).
Supplying and erecting M.S./CRCA cabinet for housing Floor Hydrant valve, hose pipe, hose reel and branch pipe (size 1000 x 736 x 736 mm.) made from 16 SWG sheet and angle iron 25 x 25 x 4 mm. having front doors with viewing glass (8"x6") and locking arrangement with necessary fixing material such as rubber bidding etc. duly painted in post box red colour( Code 538 of IS 5) (BoX for Two set of Hose Pipe along with 1set of Branch Pipe).
Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the 4 loop capacity and capable of supporting upto 250 devices and detectors per loop, with on-board LCD display with min 16 lines of text, operating at 230 V 50 HZ - AC with inbuilt Battery Backup of a minimum 24 hours in normal condition and 30 min in alarm condition, suitable provision for network connectivity, interfacing with third party equipment via a MODBUS/ OPC/ L-ON interface etc. conforming to IS 15908:2021, ,IS 2189: 2008, EN 54 & VDS / FM/ UL 864 (10th edition) with 3 years replacement warranty FF-AFAS/CP.
Supplying, installing, testing and commissioning of repeater panel with suitable battery backup of a minimum of 24 hours in normal condition and 30 min in alarm condition, 80 backlit alphanumeric LCD display with inbuilt buzzer to indicate fault/fire alarm, manual control keys for silence/mute and to reset the FACP from the repeater station. Panel size shall not more than 175 x 275 x 65 mm conforming to EN 54 or UL approved with 3 years equipment replacement warranty FF-AFAS/RP
Supplying, installing, testing and commissioning of addressable optical smoke detector, single/twin LED’s with 360 degree view, suitable for low voltage 15 to 32 V DC two wires supply, in-built locking mechanism to check the removal and pilferage of the detector, in built isolation mode, start up current 300µA and alarm condition current shall be maximum 6.5 mA, operating temperature 0°C to 50°C, humidity 0-95% RH, IP 41, conforming to IS 2189: 2008, 11360_1985_Reff2020 EN 54 or UL Approved with 3 years equipment replacement warranty FF-AFAS/SD
Supplying, installing, testing and commissioning of intelligent addressable thermal/heat detector with rate of rise cum fixed temperature thermistor complete with base as required, suitable for temperature variations from -20°C to 38°C for fixed-heat and rate-of-rise type detectors and 0°C to 66°C for high heat type detectors, in built isolation mode, suitable for offices/ceiling cable trenches/less ventilation area's etc. with 3 years equipment replacement warranty IS : 2175 - 1988 reaffirmed 2000, IS 15908:2021 standards FF-AFAS/SD.
Supplying, installing, testing and commissioning of addressable manual call points ( break glass type/pull station type), made of addressable break glass plastic square in shape surface/flush mounted with "Break Glass" massage embedded on the glass, complete erected with mounting base and required accessories conforming to EN 54 or UL listed with 3 years equipment replacement warranty FF-AFAS/MCP.
Supplying, installing, testing and commissioning of addressable fire control/relay module complete as required, with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 reed relays, EN 54 or UL Listed FF- AFAS/CRM
Supplying, installing, testing and commissioning of addressable fire monitor module complete as required. EN 54 or UL Listed with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 Reed relays FF-AFAS/MM
Supplying, installing, testing and commissioning of addressable fire isolator module complete as required. EN 54 /FM or UL Listed with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 Reed relays FF-AFAS/ISM
Supplying, installing, testing and commissioning of addressable horn cum strobe sound/ hooter, output frequency 500 to 1000 Hz with dB as per Chart given in IS 15908:2021, with flashing at 1 Hz over the strobe’s entire operating voltage range EN 54, conforming to IS 2189: 2008, IS 15908:2021 standards with 3 years equipment replacement warranty FF-AFAS/SSH.
Supplying, installing, testing and commissioning FR, XLPE armoured cable 2 core 1.5 sq.mm. copper conductor complete erected on wall/ ceiling complete as per specification no. CB-LT/CU
Supplying, erecting, testing and commissioning 120 W amplifier suitable to operate on 230 Volts A.C. / 12 Volts D.C. supply complete as per specification no. FF- PA/AFR
Supplying, erecting, testing and commissioning 15 to 30 Watts sound column or ceiling mounted complete as per specification no. FF-PA/SOC
Supplying, erecting, testing and commissioning stand mounted/handheld type wired microphone having 2 mV/Pa sensitivity, impedance level limit 300 ohms and 50 - 16000 Hz suitable to operate in -10 deg C to +55 deg C with min. 7 metre shielded cable and 3 Pin Professional XLR Connector, stereo jack complete as per specification no. FF- PA/MIC
Supplying, erecting, testing and commissioning rust free microphone floor stand of chrome plating/powder coating or S.S. material , 500 mm to 1500 mm height and sturdy mechanism ensuring trouble free movement complete.
Supplying, erecting, testing and commissioning of 2 core shielded cable complete as per specification no. FF- PA/MCC
Supplying and installing corrugated SS flexible conduit of size 25mm dia for connecting sprinkler head with necessary fittings as per specifications having 1000mm long with UL/FM
Carrying out core cutting of size 3" to 5" dia x 15" length in the C.C./rock/stone wall with the help of specialized core cutting machine in proper manner and finishing the site as original.
Supplying, erecting, testing and commissioning of quartzoid bulb sprinkler, 15 mm (½") dia. NBCM Body chrome finished, 68º C fixed temperature rating with deflector disc of conventional construction complete as per specification no. FF-SPR.
Supplying, erecting, testing and commissioning of horizontal sidewall quartzoid bulb sprinkler, 15 mm (½") dia quartzoid bulb. NBCM Body chrome finished, 68º C fixed temperature rating with deflector disc of conventional construction complete as per specification no. FF-SPR/SS
Supplying and erecting fire resistant mortar (20 kg) with fire resistance class S90 as per National Electrical Code (NEC) SP30-2011 suitable to seal the openings of all kinds of cables, pipes and cable support system in steel, aluminium and plastic profiles ( except hollow core conductors). The residual openings shall be closed with filler, as per specification no FF-FRM. Note :- For estimating purpose consider 1 bag of 20kg to cover 300mm x 400mm area 150mm thick or 0.018 m3. ( Total 108 rooms in Hospital, Each rooms having Fire sprinkler and other utility opening ,hence conidered one 20 kg bag per room. Total Set Required ( 300 X 400 X 150 = 1 room X 50 =50 Nos)
Making trench in Hard murum/Tar road having 0.75 m depth and minimum 0.3mtr width as per IS for laying provided cables up to voltage level 1.1Kv cable complete as per specification No. CW-EXN-CTR
Making cement concrete foundation in 1:2:4 cement concrete with foundation bolts and nuts complete ( cost of wooden box is included) for pumps for pump (1.2x 1.2 x0.8)= 1.15 x 6 = 6.9 cum for overhead tank (1.8 x 1.8 x 0.9)=2.91 x 2= 5.82 cum total (6.9+5.82)= 12.72 Cu-M
Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts routed in wall complete.
Supplying and erecting 4 kg clean agent gas Nitrogen pressurised controllable dicharge mechanism, pressure guage, Discharge hose and nozzle epoxy polyster powder coated as per IS 15683 ISI mark fire extinguisheroperating temperature (-)20 to (+) 55 C kg capacity suitable for A,B,C class of FIRE complete.
Supplying and erecting DCP Type 25 kg capacity trolley Mounted with controllable dicharge mechanism, pressure guage, Discharge hose and nozzle epoxy polyster powder coated as per IS 15683 ISI mark fire extinguisheroperating temperature (-)20 to (+) 55 C kg capacity suitable for A,B,C class of FIRE complete.
Supplying and erecting of fire Exit & Eire Exinguishersignlge Indicating the floor- numtber in words &syslem(Fire Exiinguisher& Accessories ) (Non CSR Approved by S.E.Office ,mumbai vide T.S letter no- 108 Date- 13/01/2022 )
Supply, Installation, testing zinc aluminite fire water storage tank having capacity 10 KL having structreaboce ground which gives positive suction to fire Pumps. The tank shall include all civil work including site prepartion , excavation , PCC which can load of tank including of 100% water.( for booster pump as per NBC).
Supplying , Installation , Testing And Commissioning of Hinged Metal fire door 120 min fire rated un insulated single 50mm THK Honey Comb Infill single double RBT 143 x 57mm frame Straight with anchor fast erness frame 1.0 & shutter 0.9 mm powder coated to ral shade SFP SS Ball bearing 4" x 3" x 3"mm hionghed for steel doors ingersoll rand briton 121, NCE. SES Door closer size 3 with standard ARM , sprayed silver finish SFP SS sashlock with 70mm back set and 24 mmfor end , SS lever handle 22x 125 mm on rose , Euro profile cylinder 70 mm with both side key 29 SS strike plate Escutchenosschott pyran fire rated clear Glass 6mm thick 240 x 340 33 Hinged Metal Fire Door 120 min fire Rated
Supplying and erecting PVC trunking (PVC casing-n-capping) of size 25 mm with accessories on wall/ceiling as per specification No: WG-MA/CON.
Supplying and erecting mains with 3x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW
Supplying and erecting modular type switch 6A / 10A duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type 3 pin 6 / 16A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting PVC Surface modular switch box with double mounting plate for 3 module duly erected.
Supplying and erecting iron, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority ( separate Iron work calculation sheet attached).
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 4 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU(for booster Pump)
Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results as per specification no. EA-EP (earthig schedule: 2 nos for each 2 nos main fire pump for hydrant and sprinkler , 2nos for each 2 nos jockey pump for sprinkler and hydrant , 1 nos for main fire panel and 1 nos for disel engine pump).= total 6 nos of earthing.
Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required. As per specification no EA-EP.(25x5) (1kg/m x 50 m=50 kg)
Supplying, installation, testing and commissioning of booster fire pump [BP] suitable for water discharge of 900 LPM at 35 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 7.5 kW or of suitable kW capacity for manual/automatic operation and consisting of following : (a) Horizontal/vertical type, single/multi stage, centrifugal casing pump of cast iron body & bronze/CI impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520. (b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation on with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (d)Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/BP
For addition of booster pump for fire hydrant/sprinkler, add as follows in the basic cost of item no 13-5-1 towards necessary accessories, indicators etc. with necessary interlocking and updation of control logic..... for 5.5/ 7.5 kW centrifugal type booster pump 1no(1working) , add
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 25 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 75/80 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 100 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 150 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting 100 mm dia Cast Iron end line strainer of Y-type flanged end pattern, PN16 pressure rating, SS screen, end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) for positive suction complete as per specification no. FF-VL/ELS
Supplying and erecting 100 mm dia. cast iron double flange sluice valve complete with PN16 pressure rating, as per specification no. FF-VL/SV
Supplying and erecting 50 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV
Supplying and erecting 75/80 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV
Supplying & erecting cast iron double flange butterfly valve of size 100 mm dia. complete as per specification no. FF-VL/BFV
Supplying & erecting cast iron double flange butterfly valve of size 150 mm dia. complete as per specification no. FF-VL/BFV
Supplying and erecting cast iron double flange ball type NRV of size 100 mm dia complete as per specification no. FF-VL/NRV
Supplying & erecting gun metal gate valve of size 25 mm dia complete as per specification no. FF-VL/GV
Supplying and erecting stainless steel single outlet hydrant valve fitted with necessary accessories complete as per specification no. FF-VL/HV.
Supplying and installing wall mounting swinging hose reel drum fitted with 19 mm dia. 30m long high pressure polypropylene (Polyhose) along with necessary accessories complete as per specification no. FF-FFA/HV
Supplying fire fighting reinforced rubber lined (R.R.L.) hose pipe, 63mm dia, 15m in length, fitted with necessary accessories complete as per specification no. FF-FFA/RRL
Supplying & erecting stainless steel branch pipe 63 mm dia fitted with 20 mm dia detachable hexagonal nozzle complete as per specifications no. FF-FFA/NZ
Supplying and erecting 20/25mm dia gun metal air release cock, with necessary G.I. coupling to be fitted on top of air vessel or on wet riser complete as per specification no. FF-FFA/ARV (7no. For Riser + Two for Air Vessel= 9 nos.
Supplying and erecting 100 mm dia. pressure gauge , 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve, erected with provided G.I. pipe, elbow etc. complete as per specification no. FF-FFA/PG
Supplying and erecting brass orifice plate having 6 mm. thickness, 140 mm outer dia with required diameter of inner hole at every single outlet hydrant valve as per specification no. FF-FFA/OP (For Internal Hydrant).
Supplying and erecting M.S./CRCA cabinet for housing Floor Hydrant valve, hose pipe, hose reel and branch pipe (size 1000 x 736 x 736 mm.) made from 16 SWG sheet and angle iron 25 x 25 x 4 mm. having front doors with viewing glass (8"x6") and locking arrangement with necessary fixing material such as rubber bidding etc. duly painted in post box red colour( Code 538 of IS 5) (BoX for Two set of Hose Pipe along with 1set of Branch Pipe).
Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the 4 loop capacity and capable of supporting upto 250 devices and detectors per loop, with on-board LCD display with min 16 lines of text, operating at 230 V 50 HZ - AC with inbuilt Battery Backup of a minimum 24 hours in normal condition and 30 min in alarm condition, suitable provision for network connectivity, interfacing with third party equipment via a MODBUS/ OPC/ L-ON interface etc. conforming to IS 15908:2021, ,IS 2189: 2008, EN 54 & VDS / FM/ UL 864 (10th edition) with 3 years replacement warranty FF-AFAS/CP.
Supplying, installing, testing and commissioning of repeater panel with suitable battery backup of a minimum of 24 hours in normal condition and 30 min in alarm condition, 80 backlit alphanumeric LCD display with inbuilt buzzer to indicate fault/fire alarm, manual control keys for silence/mute and to reset the FACP from the repeater station. Panel size shall not more than 175 x 275 x 65 mm conforming to EN 54 or UL approved with 3 years equipment replacement warranty FF-AFAS/RP
Supplying, installing, testing and commissioning of addressable optical smoke detector, single/twin LED’s with 360 degree view, suitable for low voltage 15 to 32 V DC two wires supply, in-built locking mechanism to check the removal and pilferage of the detector, in built isolation mode, start up current 300µA and alarm condition current shall be maximum 6.5 mA, operating temperature 0°C to 50°C, humidity 0-95% RH, IP 41, conforming to IS 2189: 2008, 11360_1985_Reff2020 EN 54 or UL Approved with 3 years equipment replacement warranty FF-AFAS/SD
Supplying, installing, testing and commissioning of intelligent addressable thermal/heat detector with rate of rise cum fixed temperature thermistor complete with base as required, suitable for temperature variations from -20°C to 38°C for fixed-heat and rate-of-rise type detectors and 0°C to 66°C for high heat type detectors, in built isolation mode, suitable for offices/ceiling cable trenches/less ventilation area's etc. with 3 years equipment replacement warranty IS : 2175 - 1988 reaffirmed 2000, IS 15908:2021 standards FF-AFAS/SD.
Supplying, installing, testing and commissioning of addressable manual call points ( break glass type/pull station type), made of addressable break glass plastic square in shape surface/flush mounted with "Break Glass" massage embedded on the glass, complete erected with mounting base and required accessories conforming to EN 54 or UL listed with 3 years equipment replacement warranty FF-AFAS/MCP.
Supplying, installing, testing and commissioning of addressable fire control/relay module complete as required, with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 reed relays, EN 54 or UL Listed FF- AFAS/CRM
Supplying, installing, testing and commissioning of addressable fire monitor module complete as required. EN 54 or UL Listed with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 Reed relays FF-AFAS/MM
Supplying, installing, testing and commissioning of addressable fire isolator module complete as required. EN 54 /FM or UL Listed with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 Reed relays FF-AFAS/ISM
Supplying, installing, testing and commissioning of addressable horn cum strobe sound/ hooter, output frequency 500 to 1000 Hz with dB as per Chart given in IS 15908:2021, with flashing at 1 Hz over the strobe’s entire operating voltage range EN 54, conforming to IS 2189: 2008, IS 15908:2021 standards with 3 years equipment replacement warranty FF-AFAS/SSH.
Supplying, installing, testing and commissioning FR, XLPE armoured cable 2 core 1.5 sq.mm. copper conductor complete erected on wall/ ceiling complete as per specification no. CB-LT/CU
Supplying, erecting, testing and commissioning 120 W amplifier suitable to operate on 230 Volts A.C. / 12 Volts D.C. supply complete as per specification no. FF- PA/AFR
Supplying, erecting, testing and commissioning 15 to 30 Watts sound column or ceiling mounted complete as per specification no. FF-PA/SOC
Supplying, erecting, testing and commissioning stand mounted/handheld type wired microphone having 2 mV/Pa sensitivity, impedance level limit 300 ohms and 50 - 16000 Hz suitable to operate in -10 deg C to +55 deg C with min. 7 metre shielded cable and 3 Pin Professional XLR Connector, stereo jack complete as per specification no. FF- PA/MIC
Supplying, erecting, testing and commissioning rust free microphone floor stand of chrome plating/powder coating or S.S. material , 500 mm to 1500 mm height and sturdy mechanism ensuring trouble free movement complete.
Supplying, erecting, testing and commissioning of 2 core shielded cable complete as per specification no. FF- PA/MCC
Carrying out core cutting of size 3" to 5" dia x 15" length in the C.C./rock/stone wall with the help of specialized core cutting machine in proper manner and finishing the site as original.
Supplying and erecting fire resistant mortar (20 kg) with fire resistance class S90 as per National Electrical Code (NEC) SP30-2011 suitable to seal the openings of all kinds of cables, pipes and cable support system in steel, aluminium and plastic profiles ( except hollow core conductors). The residual openings shall be closed with filler, as per specification no FF-FRM. Note :- For estimating purpose consider 1 bag of 20kg to cover 300mm x 400mm area 150mm thick or 0.018 m3. ( Total 108 rooms in Hospital, Each rooms having Fire sprinkler and other utility opening ,hence conidered one 20 kg bag per room. Total Set Required ( 300 X 400 X 150 = 1 room X 20 =20Nos)
Making trench in Hard murum/Tar road having 0.75 m depth and minimum 0.3m width as per IS for laying provided cables up to voltage level 1.1Kv cable complete as per specification No. CW-EXN-CTR
Making cement concrete foundation in 1:2:4 cement concrete with foundation bolts and nuts complete ( cost of wooden box is included) for pumps for pump (1.2x 1.2 x0.8)= 1.15 x 6 = 6.9 cum for overhead tank (1.8 x 1.8 x 0.9)=2.91 x 2= 5.82 cum total (6.9+5.82)= 12.72 Cu-M
Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts routed in wall complete.
Supplying and erecting DCP Type 25 kg capacity trolley Mounted with controllable dicharge mechanism, pressure guage, Discharge hose and nozzle epoxy polyster powder coated as per IS 15683 ISI mark fire extinguisheroperating temperature (-)20 to (+) 55 C kg capacity suitable for A,B,C class of FIRE complete.
Supplying and erecting of fire Exit & Eire Exinguishersignlge Indicating the floor- numtber in words &syslem(Fire Exiinguisher& Accessories ) (Non CSR Approved by S.E.Office ,mumbai vide T.S letter no- 108 Date- 13/01/2022 )
Supply, Installation, testing zinc aluminite fire water storage tank having capacity 10 KL having structreaboce ground which gives positive suction to fire Pumps. The tank shall include all civil work including site prepartion , excavation , PCC which can load of tank including of 100% water.( for booster pump as per NBC).
Supplying , Installation , Testing And Commissioning of Hinged Metal fire door 120 min fire rated un insulated single 50mm THK Honey Comb Infill single double RBT 143 x 57mm frame Straight with anchor fast erness frame 1.0 & shutter 0.9 mm powder coated to ral shade SFP SS Ball bearing 4" x 3" x 3"mm hionghed for steel doors ingersoll rand briton 121, NCE. SES Door closer size 3 with standard ARM , sprayed silver finish SFP SS sashlock with 70mm back set and 24 mmfor end , SS lever handle 22x 125 mm on rose , Euro profile cylinder 70 mm with both side key 29 SS strike plate Escutchenosschott pyran fire rated clear Glass 6mm thick 240 x 340 33 Hinged Metal Fire Door 120 min fire Rated
Supplying and erecting PVC trunking (PVC casing-n-capping) of size 25 mm with accessories on wall/ceiling as per specification No: WG-MA/CON.
Supplying and erecting mains with 3x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW
Supplying and erecting modular type switch 6A / 10A duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type 3 pin 6 / 16A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting PVC Surface modular switch box with double mounting plate for 3 module duly erected.
Supplying and erecting iron, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority ( separate Iron work calculation sheet attached).
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 4 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU(for booster Pump)
Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results as per specification no. EA-EP (earthig schedule: 2 nos for each 2 nos main fire pump for hydrant and sprinkler , 2nos for each 2 nos jockey pump for sprinkler and hydrant , 1 nos for main fire panel and 1 nos for disel engine pump).= total 6 nos of earthing.
Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required. As per specification no EA-EP.(25x5) (1kg/mtr x 50 mtr=50 kg)
Supplying, installation, testing and commissioning of booster fire pump [BP] suitable for water discharge of 900 LPM at 35 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 7.5 kW or of suitable kW capacity for manual/automatic operation and consisting of following : (a) Horizontal/vertical type, single/multi stage, centrifugal casing pump of cast iron body & bronze/CI impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520. (b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation on with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (d)Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/BP
For addition of booster pump for fire hydrant/sprinkler, add as follows in the basic cost of item no 13-5-1 towards necessary accessories, indicators etc. with necessary interlocking and updation of control logic..... for 5.5/ 7.5 kW centrifugal type booster pump 2no(2working) , add Rs…....
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 25 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 50 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 65 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 75/80 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 100 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 150 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting 100 mm dia Cast Iron end line strainer of Y-type flanged end pattern, PN16 pressure rating, SS screen, end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) for positive suction complete as per specification no. FF-VL/ELS
Supplying and erecting 100 mm dia. cast iron double flange sluice valve complete with PN16 pressure rating, as per specification no. FF-VL/SV
Supplying and erecting 50 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV
Supplying and erecting 75/80 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV
Supplying & erecting cast iron double flange butterfly valve of size 100 mm dia. complete as per specification no. FF-VL/BFV
Supplying & erecting cast iron double flange butterfly valve of size 150 mm dia. complete as per specification no. FF-VL/BFV
Supplying and erecting cast iron double flange ball type NRV of size 100 mm dia complete as per specification no. FF-VL/NRV
Supplying & erecting gun metal gate valve of size 25 mm dia complete as per specification no. FF-VL/GV
Supplying and erecting stainless steel single outlet hydrant valve fitted with necessary accessories complete as per specification no. FF-VL/HV.
Supplying and installing wall mounting swinging hose reel drum fitted with 19 mm dia. 30m long high pressure polypropylene (Polyhose) along with necessary accessories complete as per specification no. FF-FFA/HV
Supplying fire fighting reinforced rubber lined (R.R.L.) hose pipe, 63mm dia, 15m in length, fitted with necessary accessories complete as per specification no. FF-FFA/RRL
Supplying & erecting stainless steel branch pipe 63 mm dia fitted with 20 mm dia detachable hexagonal nozzle complete as per specifications no. FF-FFA/NZ
Supplying and erecting 20/25mm dia gun metal air release cock, with necessary G.I. coupling to be fitted on top of air vessel or on wet riser complete as per specification no. FF-FFA/ARV (7no. For Riser + Two for Air Vessel= 9 nos.
Supplying and erecting 100 mm dia. pressure gauge , 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve, erected with provided G.I. pipe, elbow etc. complete as per specification no. FF-FFA/PG
Supplying and erecting brass orifice plate having 6 mm. thickness, 140 mm outer dia with required diameter of inner hole at every single outlet hydrant valve as per specification no. FF-FFA/OP (For Internal Hydrant).
Supplying and erecting M.S./CRCA cabinet for housing Floor Hydrant valve, hose pipe, hose reel and branch pipe (size 1000 x 736 x 736 mm.) made from 16 SWG sheet and angle iron 25 x 25 x 4 mm. having front doors with viewing glass (8"x6") and locking arrangement with necessary fixing material such as rubber bidding etc. duly painted in post box red colour( Code 538 of IS 5) (BoX for Two set of Hose Pipe along with 1set of Branch Pipe).
Supplying, installing, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the 8 loop capacity and capable of supporting upto 250 devices and detectors per loop, with on-board LCD display with min 16 lines of text, operating at 230 V 50 HZ - AC with inbuilt Battery Backup of a minimum 24 hours in normal condition and 30 min in alarm condition, suitable provision for network connectivity, interfacing with third party equipment via a MODBUS/ OPC/ L-ON interface etc. conforming to IS 15908:2021, IS 2189: 2008, EN 54 & VDS / FM/ UL 864 (10th edition) with 3 years replacement warranty FF-AFAS/CP
Supplying, installing, testing and commissioning of repeater panel with suitable battery backup of a minimum of 24 hours in normal condition and 30 min in alarm condition, 80 backlit alphanumeric LCD display with inbuilt buzzer to indicate fault/fire alarm, manual control keys for silence/mute and to reset the FACP from the repeater station. Panel size shall not more than 175 x 275 x 65 mm conforming to EN 54 or UL approved with 3 years equipment replacement warranty FF-AFAS/RP
Supplying, installing, testing and commissioning of addressable optical smoke detector, single/twin LED’s with 360 degree view, suitable for low voltage 15 to 32 V DC two wires supply, in-built locking mechanism to check the removal and pilferage of the detector, in built isolation mode, start up current 300µA and alarm condition current shall be maximum 6.5 mA, operating temperature 0°C to 50°C, humidity 0-95% RH, IP 41, conforming to IS 2189: 2008, 11360_1985_Reff2020 EN 54 or UL Approved with 3 years equipment replacement warranty FF-AFAS/SD
Supplying, installing, testing and commissioning of intelligent addressable thermal/heat detector with rate of rise cum fixed temperature thermistor complete with base as required, suitable for temperature variations from -20°C to 38°C for fixed-heat and rate-of-rise type detectors and 0°C to 66°C for high heat type detectors, in built isolation mode, suitable for offices/ceiling cable trenches/less ventilation area's etc. with 3 years equipment replacement warranty IS : 2175 - 1988 reaffirmed 2000, IS 15908:2021 standards FF-AFAS/SD.
Supplying, installing, testing and commissioning of addressable manual call points ( break glass type/pull station type), made of addressable break glass plastic square in shape surface/flush mounted with "Break Glass" massage embedded on the glass, complete erected with mounting base and required accessories conforming to EN 54 or UL listed with 3 years equipment replacement warranty FF-AFAS/MCP.
Supplying, installing, testing and commissioning of addressable fire control/relay module complete as required, with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 reed relays, EN 54 or UL Listed FF- AFAS/CRM
Supplying, installing, testing and commissioning of addressable fire monitor module complete as required. EN 54 or UL Listed with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 Reed relays FF-AFAS/MM
Supplying, installing, testing and commissioning of addressable fire isolator module complete as required. EN 54 /FM or UL Listed with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 Reed relays FF-AFAS/ISM
Supplying, installing, testing and commissioning of addressable horn cum strobe sound/ hooter, output frequency 500 to 1000 Hz with dB as per Chart given in IS 15908:2021, with flashing at 1 Hz over the strobe’s entire operating voltage range EN 54, conforming to IS 2189: 2008, IS 15908:2021 standards with 3 years equipment replacement warranty FF-AFAS/SSH.
Supplying, installing, testing and commissioning FR, XLPE armoured cable 2 core 1.5 sq.mm. copper conductor complete erected on wall/ ceiling complete as per specification no. CB-LT/CU
Supplying, erecting, testing and commissioning 120 W amplifier suitable to operate on 230 Volts A.C. / 12 Volts D.C. supply complete as per specification no. FF- PA/AFR
Supplying, erecting, testing and commissioning 15 to 30 Watts sound column or ceiling mounted complete as per specification no. FF-PA/SOC
Supplying, erecting, testing and commissioning stand mounted/handheld type wired microphone having 2 mV/Pa sensitivity, impedance level limit 300 ohms and 50 - 16000 Hz suitable to operate in -10 deg C to +55 deg C with min. 7 metre shielded cable and 3 Pin Professional XLR Connector, stereo jack complete as per specification no. FF- PA/MIC
Supplying, erecting, testing and commissioning rust free microphone floor stand of chrome plating/powder coating or S.S. material , 500 mm to 1500 mm height and sturdy mechanism ensuring trouble free movement complete.
Supplying, erecting, testing and commissioning of 2 core shielded cable complete as per specification no. FF- PA/MCC
Supplying and installing corrugated SS flexible conduit of size 25mm dia for connecting sprinkler head with necessary fittings as per specifications having 1000mm long with UL/FM
Carrying out core cutting of size 3" to 5" dia x 15" length in the C.C./rock/stone wall with the help of specialized core cutting machine in proper manner and finishing the site as original.
Supplying, erecting, testing and commissioning of quartzoid bulb sprinkler, 15 mm (½") dia. NBCM Body chrome finished, 68º C fixed temperature rating with deflector disc of conventional construction complete as per specification no. FF-SPR.
Supplying, erecting, testing and commissioning of horizontal sidewall quartzoid bulb sprinkler, 15 mm (½") dia quartzoid bulb. NBCM Body chrome finished, 68º C fixed temperature rating with deflector disc of conventional construction complete as per specification no. FF-SPR/SS
Supplying and erecting fire resistant mortar (20 kg) with fire resistance class S90 as per National Electrical Code (NEC) SP30-2011 suitable to seal the openings of all kinds of cables, pipes and cable support system in steel, aluminium and plastic profiles ( except hollow core conductors). The residual openings shall be closed with filler, as per specification no FF-FRM. Note :- For estimating purpose consider 1 bag of 20kg to cover 300mm x 400mm area 150mm thick or 0.018 m3. ( Total 108 rooms in Hospital, Each rooms having Fire sprinkler and other utility opening ,hence conidered one 20 kg bag per room. Total Set Required ( 300 X 400 X 150 = 1 room X 160 =160 Nos)
Making trench in Hard murum/Tar road having 0.75 m depth and minimum 0.3mtr width as per IS for laying provided cables up to voltage level 1.1Kv cable complete as per specification No. CW-EXN-CTR
Making cement concrete foundation in 1:2:4 cement concrete with foundation bolts and nuts complete ( cost of wooden box is included) for pumps for pump (1.2x 1.2 x0.8)= 1.15 x 6 = 6.9 cum for overhead tank (1.8 x 1.8 x 0.9)=2.91 x 2= 5.82 cum total (6.9+5.82)= 12.72 Cu-M
Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts routed in wall complete.
Supplying and erecting 4 kg clean agent gas Nitrogen pressurised controllable disharge mechanism, pressure guage, Discharge hose and nozzle epoxy polyster powder coated as per IS 15683 ISI mark fire extinguisher operating temperature (-)20 to (+) 55 C kg capacity suitable for A,B,C class of FIRE complete.
Supplying and erecting DCP Type 25 kg capacity trolley Mounted with controllable dicharge mechanism, pressure guage, Discharge hose and nozzle epoxy polyster powder coated as per IS 15683 ISI mark fire extinguisher operating temperature (-)20 to (+) 55 C kg capacity suitable for A,B,C class of FIRE complete.
Supplying and erecting of fire Exit & Eire Exinguisher signlge Indicating the floor- numtber in words &syslem( Fire Exiinguisher& Accessories ) (Non CSR
Supply, Installation, testing zinc aluminite fire water storage tank having capacity 10 KL having structreaboce ground which gives positive suction to fire Pumps. The tank shall include all civil work including site prepartion , excavation , PCC which can load of tank including of 100% water.( for booster pump as per NBC).
Supplying , Installation , Testing And Commissioning of Hinged Metal fire door 1200 x 2100 mm 120 min fire rated un insulated single 50mm THK Honey Comb Infill single double RBT 143 x 57mm frame Straight with anchor fast erness frame 1.0 & shutter 0.9 mm powder coated to ral shade SFP SS Ball bearing 4" x 3" x 3"mm hionghed for steel doors ingersoll rand briton 121, NCE. SES Door closer size 3 with standard ARM , sprayed silver finish SFP SS sashlock with 70mm back set and 24 mmfor end , SS lever handle 22x 125 mm on rose , Euro profile cylinder 70 mm with both side key 29 SS strike plate Escutchenosschott pyran fire rated clear Glass 6mm thick 240 x 340 33 Hinged Metal Fire Door 1200 x 2100 mm, 120 min fire Rated
Supplying, erecting ,Testing & commissioning Ceiling or wall Mounting type 630A Capacity at 40oC ambient temperature Sandwich type Aluminium Conductor tin plated at joints /Aluminium conductor Silver flashed copper bimetal contact having purity not less than 99.6% with suitable for (3L+ N) 415V, 50 Hz A.C Supply with 100% Neutral+ enclosure as integral earth (PE) with IP 54/55 Protection,36/40KA short circuit rating for 1sec, Insulation Class F (155 C) , casing made of minimum 1.5mm hot dipped / electro Galvanized /Epoxy powder coated steel sheet enclosure having Mechanical strength certification up to IK10 with required shade of paint having overall cross sectional area not more than 0.0170 sq. Mtr., complete assembly must comply to seismic zone 4, with necessary accessories Like suspension bracket, wall bracket holder/ fixing accessories with Horizontal / Vertical G.I. Support at required interval with External Double run 50x5mm Aluminium earthing strip or Internal Integral Earth complete confirming to IEC 61439-6 as per specification
Supplying, erecting ,Testing & commissioning Ceiling or wall Mounting type 800A Capacity at 400C ambient temperature Sandwich type Aluminium Conductor tin plated at joints /Aluminium conductor Silver flashed copper bimetal contact having purity not less than 99.6% with suitable for (3L+ N) 415V, 50 Hz A.C Supply with 100% Neutral+ enclosure as integral earth (PE) with IP 54/55 Protection,42/50KA short circuit rating for 1sec, Insulation Class F (155 C) , casing made of minimum 1.5mm hot / electro Galvanized /Epoxy powder coated steel sheet enclosure with required shade of paint having Mechanical strength certification up to IK10 overall cross sectional area not more than 0.0170 sq. Mtr., complete assembly must comply to seismic zone 4, with necessary accessories Like suspension bracket, wall bracket holder/ fixing accessories as per site requirement with Horizontal / Vertical G.I. Support at required interval with Double run External Double run 50x5mm Aluminium earthing strip or Internal Integral Earth complete confirming to IEC 61439-6 as per specification
Supplying, erecting ,Testing & commissioning Ceiling or wall Mounting type 1000A Capacity at 40oC ambient temperature Sandwich type Aluminium Conductor tin plated at joints /Aluminium conductor Silver flashed copper bimetal contact having purity not less than 99.6% with suitable for (3L+ N) 415V, 50 Hz A.C Supply with 100% Neutral+ enclosure as integral earth (PE) with IP 54/55 Protection,50KA short circuit rating for 1sec,Insulation Class F (155 C) , casing made of minimum 1.5mm hot / electro Galvanized /Epoxy powder coated steel sheet enclosure with required shade of paint having Mechanical strength certification up to IK10,overall cross sectional area not more than 0.0170 sq. Mtr., complete assembly must comply to seismic zone 4, with necessary accessories Like suspension bracket, wall bracket holder/ fixing accessories as per site requirement with Horizontal / Vertical G.I. Support at required interval with External Double run 50x5mm Aluminium earthing stripor Internal Integral Earth complete confirmingto IEC 61439-6 as per specification
Supplying, erecting ,Testing & commissioning Ceiling or wall Mounting type 1250A Capacity at 40oC ambient temperature Sandwich type Aluminium Conductor tin plated at joints /Aluminium conductor Silver flashed copper bimetal contact having purity not less than 99.6% with suitable for (3L+ N) 415V, 50 Hz A.C Supply with 100% Neutral+ enclosure as integral earth (PE) with IP 54/55 Protection,65KA short circuit rating for 1sec,Insulation Class F (155 C) ,casing made of minimum 1.5mm hot / electro Galvanized /Epoxy powder coated steel sheet enclosure with required shade of paint having Mechanical strength certification up to IK10 overall cross sectional area not more than 0.0225 sq. Mtr., complete assembly must comply to seismic zone 4, with necessary accessories Like suspension bracket, wall bracket holder/ fixing accessories as per site requirement with Horizontal / Vertical G.I. Support at requiredinterval with External Double run 50x5mm Aluminium earthing strip or Internal Integral Earth complete confirming to IEC 61439-6 as per specification
Supplying, installing, testing & commissioning of Tap off box with interlock arrangement on existing Air Insulated / Sandwich type bus trunking/ rising mains for 250A to 400A 3 phase 4 wire 415V, 50Hz AC Supply made with 1.5mm thick sheet metal enclosure (IP54/55) duly powder coated with provision of MCCB( without MCCB) complete as required confirming to IEC 61439-6 as per specification
Providing & erecting 4 Pole MCCB 415V, 250A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu) adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB NOTE
Providing & erecting 4 Pole MCCB 415V, 400A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure /panel as per specification no. SW- SWR/MCCB
Supplying, installing, testing and commissioning of Flange end with Adaptor box, as per site requirement suitable for Aluminium 630A 3 phase 4 wire 415V, 50 Hz A.C ,36/40kA short circuit rating for 1 sec Sandwich type Aluminium BBT. with necessary accessories complete
Supplying, installing, testing and commissioning of Flange end with Adaptor box, as per site requirement suitable for 800A 3 phase 4 wire 415V, 50 Hz A.C ,42/50kA short circuit rating for 1 sec Sandwich type Aluminium BBT with necessary accessories complete confirming to IEC 61439-6 as per specification
Supplying, installing, testing and commissioning of Flange end with Adaptor box, as per site requirement suitable for 1000A 3 phase 4 wire 415V, 50 Hz A.C ,50kA short circuit rating for 1 sec Sandwich type Aluminium BBT. with necessary accessories complete confirming to IEC 61439-6 as per specification
Supplying, installing, testing and commissioning of Flange end with Adaptor box, as per site requirement suitable for 1250A 3 phase 4 wire 415V, 50 Hz A.C ,65kA short circuit rating for 1 sec Sandwich type Aluminium BBT. with necessary accessories complete confirming to IEC 61439-6 as per specification
Supplying, installing & Commissioning Vertical or Horizontal Tee Elbow for Sandwich type Aluminium Compact bus trunking/ rising mains Suitable for 630A, 3 Phase 4 Wire 415 V, 50 Hz AC Supply Made of minimum 1.5mm Thick Galvanised sheet metal enclosure (IP54/55) duly powder coated with all necessary accessories complete
Supplying, installing & Commissioning Vertical or Horizontal 90 Degree Elbow for Sandwich type Aluminium Compact bus trunking/ rising mains Suitable for 630A, 3 Phase 4 Wire 415 V, 50 Hz AC Supply, 36/40kA short circuit rating for 1 sec Made of minimum 1.5mm Thick Galvanised sheet metal enclosure (IP54/55) duly powder coated with all necessary accessories complete confirming to IEC 61439-6 as per specification
Supplying, installing & Commissioning of Plug in Points on provided Sandwich type Aluminium Compact bus trunking/ rising mains Suitable for 630A, 3 Phase 4 Wire 415 V, 50 Hz AC Supply,,36/40KA short circuit rating for 1sec Made of minimum 1.5mm Thick Galvanised sheet metal enclosure (IP54/55) duly powder coated with all necessary accessories complete.
Supplying, installing & Commissioning of Plug in Points on provided Sandwich type Aluminium Compact bus trunking/ rising mains Suitable for 800A, 3 Phase 4 Wire 415 V, 50 Hz AC Supply,42/50KA short circuit rating for 1sec Made of minimum 1.5mm Thick Galvanised sheet metal enclosure (IP54/55) duly powder coated with all necessary accessories complete.
Supplying, erecting, testing and commissioning of diesel generating set with alternator of 750 kVA output continuous rating, 3 Phase, 415 V, 50c/s 0.8 p. f. A.C supply, a totally enclosed air cooled / liquid cooled multi-cylinder diesel engine developing suitable BHP at 1500 rpm with 10% overload for 1 hour in 12 hours, along with standard accessories, self-excited, self- regulated, screen protected alternator with static excitation system running at 1500 RPM as per IS 4722-2001 with voltage regulation +/- 5 %, with performance class G2 and maximum fuel consumption 126.4 Ltr/hr @75% loading. Both the engine and alternator direct coupled on a common fabricated steel base frame and mounted on anti-vibrating pads with standard control panel comprising meters, switchgears, indicators connected with suitable wires/cables, the complete set enclosed in composite acoustic enclosure as fully assembled integral unit made of 16 SWG CRCA sheet, sound absorbing material to restrict sound level up to 75 dB at 1.0 m, provided with first filling of oil, diesel not less than 990 Ltr etc. on provided M20 Grade CC Foundation and obtaining necessary approval from Electrical Inspector as per specification no. GEN-DG
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 6 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Providing & erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 300 mm width & 75 mm height complete with necessary coupler plates & hardware.
Supplying and laying (including excavation of suitable width & depth up to 90 cm) 200 mm outsidedia, double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, to required depth complete.
Providing and fixing reinforced cement concrete cover of size 60 cm x 45 cm with frame over inspection chamber etc. complete of medium duty (100 Kilogram).
Making cement concrete foundation in 1:2:4 cement concrete with foundation bolts and nuts complete. (cost of wooden box is included) DG -2.5mx3mx0.3=2.25*2=5
Supplying and erecting iron, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority.
Hiring charges for supplying and maintaining temporary 415V, 50 cycles AC generating set 250 kVA capacity with voltage regulation +/- 5 %, and complete set enclosed in composite acoustic enclosure to restrict sound level up to 75 dB at 1.0 m, with necessary fuel, mains, switchgears and accessories complete with continuous running on load/no load as per requirements complete with self certification.
Hiring charges for supplying and maintaining temporary 415V, 50 cycles AC generating set 250 kVA capacity with voltage regulation +/- 5 %, and complete set enclosed in composite acoustic enclosure to restrict sound level up to 75 dB at 1.0 m, with necessary fuel, mains, switchgears and accessories complete with continuous running on load/no load as per requirements complete with self certification. ( for additional 29 days for 1 Generator ) Foot note apply
Lumsum provision for the additional fuel (Fuel consumption at 75% load for 250 KVA DG set 42.6 Ltr/ hr x 1 nos. Hence total consumption 42.6 Ltr/ hr X additional 6 hours
Providing Services of skilled wireman having valid wireman licence for operation & maintenance of electrical installation for single shift for every day ( 60 Days X 3 Shift X 2 Person = 360days)
Supplying, installation and testing of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25 kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete, and recording the results Specification no. EA-MOBI
Supplying and erecting copper strip of high purity required size used for earthing on wall and/or any other purpose with necessary copper clamps fixed on wall painted with bituminous paint with joints required. As per specification no. EAEP.
Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP.
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 2 core 4 sq mm copper conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supply, Installation, Testing and commissioning of Lift Panel requirements ThePanel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.CableEntry From Bottom & Out From Buttom SideOf Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in-Charge. feeders with R , Y , B for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB's shall be EDO,LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details.Incomer:250A,4P,MCCB Outgoing Feeders:100A,3P,MCCB -6 NOS ,TP MCB ADD -63 A TP MCB-9 nos
Supply, Installation, Testing and commissioning of BEST METER PANEL For Fire requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in- Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB's shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details. Incomer:630A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 1Nos Outgoing Feeders: Trivector Meter - 1nos
Supply, Installation, Testing and commissioning of Fire Panel Change Over Panel requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in- Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB's shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details. Incomer: 400A,4P, ATS -1nos
Supply, Installation, Testing and commissioning of BEST PANEL requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge Panel should be Inspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in- Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB's shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details. Incomer:630A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 1Nos Trivector meter 440 V 50 Hz.-1 NOSBusbarsRating :630A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.
Supply, Installation, Testing and commissioning of MAIN LT PANEL North Side Section-1 requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in- Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB's shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details. Incomer:800A ACB- 4 nos , 1250ACB-2 NOS ,2000A ACB-1 nos BusbarsRating :2000A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter,Multifuctional Meter.
Supply, Installation, Testing and commissioning of MAIN LT PANEL North Side Section-2 requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in-Charge .feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB's shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details. Incomer:800A ACB- 4 nos , 1250ACB-1 NOS BusbarsRating :2000A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter,Multifuctional Meter.
Supply, Installation, Testing and commissioning of MAIN LT PANEL-South Side Section -1 requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in- Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB's shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details. Incomer:800A ACB- 4 nos , 1250ACB-2 NOS 2000ACB-1 NOS BusbarsRating :2000A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter,Multifuctional Meter.
Supply, Installation, Testing and commissioning of MAIN LT PANEL-South Side Section -2 requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in- Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB's shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details. Incomer:800A ACB- 4 nos , 1250ACB-2 NOS BusbarsRating :2000A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter,Multifuctional Meter.
Supply, Installation, Testing and commissioning of BEST PANEL requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should be Inspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in- Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB's shall be EDO. R LSIG. The panel should be as per IEC 61439. efer Electrical Main Single Line diagrams for panel details. Incomer:400A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 1Nos Trivector meter 440 V 50 Hz.-1 NOS BusbarsRating :400A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.
Supply, Installation, Testing and commissioning of OPTHAL DEPARTMENT DG PANEL requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in- Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB's shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details. Incomer:630A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 1Nos Trivector meter 440 V 50 Hz.-1 NOS BusbarsRating :630A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.Outgoing : 250A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 3Nos
Supply, Installation, Testing and commissioning of OPTHAL DEPARTMENT ATS PANEL-1 requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in-Charge feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB's shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details. Incomer:ON LOAD four pole automatic transfer switch, 415V,315A, 50 Hz-1Nos Trivector meter 440 V 50 Hz.-1 NOS BusbarsRating :315A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.Outgoing : 250A,4P,MCCB with 25KA Breaking Capacity with thermal realesewith Overload and Short circuit protection- 1Nos,100A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 3Nos,63 A TP MCB-5NOS,32 A DP MCB-6NOS,
Supply, Installation, Testing and commissioning of OPTHAL DEPARTMENT ATS PANEL-2 requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in-Charge feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB's shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details. Incomer:ON LOAD four pole automatic transfer switch, 415V,315A, 50 Hz-1Nos Trivector meter 440 V 50 Hz.-1 NOS BusbarsRating :315A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.Outgoing : 250A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 3Nos,100A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 3Nos,63 A DP MCB-6NOS,
Supply, Installation, Testing and commissioning of OPD GROUND FLOOR PANEL requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in-Charge feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB's shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details. Incomer::400A,4P,MCCB with 25KA Breaking Capacity with thermal realesewith Overload and Short circuit protection- 1Nos Trivector meter 440 V 50 Hz.-1 NOS BusbarsRating :400A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.Outgoing : 100A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 12Nos
Supply, Installation, Testing and commissioning of SKIN DEPARTMENT DGPANEL requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable EntryFrom Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved fromEngineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in-Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB's shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details. Incomer:630A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 1Nos Trivector meter 440 V 50 Hz.-1 NOS BusbarsRating :630A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.Outgoing : 250A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 4Nos
Supply, Installation, Testing and commissioning of SKIN DEPARTMENT ATS PANEL-1 requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in-Charge feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB's shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details. Incomer:ON LOAD four pole automatic transfer switch, 415V,315A, 50 Hz-1Nos Trivector meter 440 V 50 Hz.-1 NOS BusbarsRating :315A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.Outgoing : 250A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 2Nos,100A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 2Nos,63 A TP MCB-10NOS
Supply, Installation, Testing and commissioning of SKIN DEPARTMENT ATS PANEL-2 requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in-Charge feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB's shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details. Incomer:ON LOAD four pole automatic transfer switch, 415V,400A, 50 Hz-1Nos Trivector meter 440 V 50 Hz.-1 NOS BusbarsRating :400A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.Outgoing : 400A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 1Nos,100A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 3Nos MCB- 10NOS
Supply, Installation, Testing and commissioning of 300 BEDED DOCTORS QUARTERS GROUND FLOOR PANEL requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI -CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP-42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should be Inspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in- Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB's shall be EDO. Refer Electrical Main Single Line diagrams for panel details. Incomer::630A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 1Nos Trivector meter 440 V 50 Hz.-1 NOS BusbarsRating :630A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.Outgoing : 250A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 8Nos
Supply, Installation, Testing and commissioning of BALARAM DEPARTMENT DG PANEL requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI - CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP- 42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in- Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB's shall be EDO LSIG. The panel should be as per IEC 61439.. Refer Electrical Main Single Line diagrams for panel details. Incomer:630A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 1Nos Trivector meter 440 V 50 Hz.-1 NOS BusbarsRating :630A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.Outgoing : 250A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 6Nos
Supply, Installation, Testing and commissioning of BALARAM DEPARTMENT ATS PANEL-1 requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI - CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP- 42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in- Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB's shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details. Incomer:ON LOAD four pole automatic transfer switch, 415V,315A, 50 Hz- 1Nos Trivector meter 440 V 50 Hz.-1 NOS Busbars Rating :315A,3Phase,50KA,50Hz AL.Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.Outgoing : 100A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 4Nos
Supply, Installation, Testing and commissioning of BALARAM DEPARTMENT ATS PANEL-2 requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI - CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP- 42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in-Charge feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB's shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details. Incomer:ON LOAD four pole automatic transfer switch, 415V,315A, 50 Hz- 1Nos Trivector meter 440 V 50 Hz.-1 NOS Busbars Rating :315A,3Phase,50KA,50Hz AL.Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.Outgoing : 100A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 5Nos
Supply, Installation, Testing and commissioning of BALARAM DEPARTMENT ATS PANEL-3 requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated. Cable Entry From Bottom & Out FromButtom Side Of Panel. The minimum sizes ofsections of bus bars are given in Table VI - CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour HeatShrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP- 42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in- Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB's shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details. Incomer:ON LOAD four pole automatic transfer switch, 415V,315A, 50 Hz- 1Nos Trivector meter 440 V 50 Hz.-1 NOS BusbarsRating :315A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.Outgoing : 100A,4P,MCCB with 25KA Breaking Capacity with thermal realese with Overload and Short circuit protection- 5Nos
Supply, Installation, Testing and commissioning of BALARAM DEPARTMENT ATS PANEL-4 requirements The Panel Should Be Mfg. From CPRI Approved Panel Manufacturer ..Panel With 16 SWG, 7 Tank Processed, Epoxy Powder Coated.Cable Entry From Bottom & Out From Buttom Side Of Panel. The minimum sizes of sections of bus bars are given in Table VI - CPWD Standard. Each phase duly covered with Red, yellow, Blue and Black Colour Heat Shrink Sleeves.The Panel Should be Should be Indoor Type & Floor Mountable with IP- 42. Name Tag Plates Should Be Provided As Per The Requirement.Paint - Seminice Gray - Powder Coating. The Schematic Drawing for the Above Panel should be get approved from Engineer -in-Charge before manufacturing the Panel. The Panel should beInspected & Tested at Manufacturing Place before dispatch At Site from Engineer -in- Charge.feeders with R , Y , B Phase Indicating Lamp & MFM Meter compatible for BMS Monitoring .All Incoming feeders Should be with OV,UV& Earth leakage protection.All ACB's shall be EDO. LSIG. The panel should be as per IEC 61439. Refer Electrical Main Single Line diagrams for panel details. Incomer:ON LOAD four pole automatic transfer switch, 415V,315A, 50 Hz- 1Nos Trivector meter 440 V 50 Hz.-1 NOS BusbarsRating :315A,3Phase,50KA,50Hz AL. Busbar Metering R,Y,B, Trip Indication Lamp, Volt Meter, Ammeter Meter.Outgoing : 100A,4P,MCCB with 25KA Breaking Capacity with thermal realesewith Overload and Short circuit protection- 12Nos
Supplying and erecting 250 kVAr, 440 V 3 phase, 50 Hz., Contactor Logic & Intelligent Relay micro APFC passive filter panel, consisting of suitable steps of APP/MPP type capacitor units with Detuned (harmonic filter) reactors of suitable rating , APFC panel shall be compliance to IEC 61439 and power quality IEC 61921 standard as per specification no CP-ED/APFC
Providing & erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 300 mm width & 100 mm height comprising all required standard accessories.
Supplying, erecting &terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 50 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 70 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 95 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 120 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 150 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting &terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 185 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting &terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½core 240 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting &terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 300 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 10 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating XLPE insulated unarmoured cable 1100 V. 1 core 50 sq. mm. copper conductor complete erected with provided lugs, laid in provided control panel /distribution boards / pipe as per specification no. CB-LT/CU
Providing printed instruction chart for treating persons suffering from electric shock, printed in English & Marathi and duly laminated complete.
Supplying standard first aid box with necessary antiseptic cream, medicine for use on wounds due burn, crepe bandage, gauge bandage, medicated ready to use bandage (Band-Aid) adhesive tape for medicinal use, scissors, anti-septic solution, etc. (All above contents shall be of standard makes)
Supplying and fixing PVC synthetic elastomer electrically insulating mat with class A insulation conforming to IS: 15652 – 2006 having 2 mm thickness up to 3.3 kV
Point wiring for light/bell/exhaust fan in PVC trunking (casing-capping) with 1.5 sq.mm (2+1E) FRLSH grade copper wire, modular type switch, earthing and required accessories as per specification No: WG-PW/SW
Supplying and erecting modular type switch 16A duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type 3 pin 16A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete.
Providing temporary plug point with 3 phase industrial socket having CRCA sheet metal enclosure with 30A, 3 pin plug and earth socket and 30A, 3 pin, plug top with 30A, triple pole MCB, mains, switchgears with continuous earth wire up to three days
Supplying and erecting PVC Surface modular switch box with double mounting plate for 6 module duly erected.
Supplying and erecting mains with 2x1.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW
Supplying and erecting mains with 1x1.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW
Supplying and erecting mains with 2x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting mains with 1x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting mains with 2x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting mains with 1x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting HMS PVC conduit FRLS grade 25 mm dia. With PVC accessories on wall /ceiling as per specification No: WG-MA/CON.
Supplying and erecting PVC trunking (PVC casing-n-capping) of size 25 mm with accessories on wall/ceiling as per specification No: WG-MA/CON.
Supplying & erecting triple pole and neutral distribution board (TPNDB), SP/TP MCBs total 8 ways /24 poles, with door, 1.2mm thickness surface/flush mounted, IP 43 Protection on iron/GI frame (vertical busbar type) as per specification no. SW- SWR/MCBDB
Supplying, erecting & marking SPMCB 6A to 32A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW- SWR/MCB
Supplying, erecting & marking FPMCB 40A to 63A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
Supplying, erecting & commissioning 2 pole RCCB 16/25A, electromagnetic type with 30/100/300 mA sensitivity with earth leakage trip indication complete as per specification no. SW-RCCB/RCCB
Providing & erecting 4 Pole MCCB, 415 V, 100A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB with phase barriers on both sides, insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB
Providing & erecting 4 Pole MCCB, 415V, 200A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB
Supplying & erecting CRCA sheet metal enclosures of 1.2mm thickness with 30 A, 3 pin plug & earth socket and 30A, 3 pin plug top with 30A triple pole MCB having rated short - circuit breaking capacity (Icn) 10kA complete erected on angle iron / GI frame.
Supplying & erecting inverter LED batten 20W tube light fitting with polycarbonate housing, heat sink, integrated HF electronic driver, Min. 2600 mAh Lithium ion Battery with charging time of 8-10 Hours and backup time of Min. 3 hrs. with minimum 25% of initial Watts having luminous efficacy of 100 lumen/watt, CRI>80, CCT of 6500K and THD<=20% having useful life of minimum 25000 hrs. with overheating protection with 2 years warranty.
Supplying and erecting energy saving ceiling fan 230 V A.C. 50 cycles 1200 mm complete erected in position as per specification no. FG- FN/CF
Supplying and erecting metal work in CRCA sheet including Iron work for supports with fabrication of boxes, panel boards, etc. including cutting, bending, drilling, welding, riveting, treated with anti-rust treatment and duly powder coated or painted with one coat of red lead paint and 2 coats of enamel paint complete.
Dismentling of existing Air Insulated Busbar truncking of 800A with necessary security arrangements from south and north electrical service room with accessories and to kept in store room as per instructions of engineer in charge.
Dismantling of existing fluorescent fittings of any type & size.
Dismantling the existing ceiling fan /exhaust fan / cabin fan / bracket fan complete with accessories, G.I. down rod, frame etc. and making the site clear.
Dismantling the existing switchgears, DB, and bus bar of any size complete with/ without board or angle iron frame
Dismantling the existing cables of all types & size above 10 sq mm up to 50 sq.mm.
Providing & erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 300 mm width & 75 mm height complete with necessary coupler plates & hardware.
Providing & erecting hot dipped galvanised cover suitable for perforated type Cable tray manufactured from 18 SWG (1.2 mm thick) GI sheet of 300 mm width & 20 mm height complete with necessary hardware.
Supplying and fixing 9U wall mount rack (Dimension-DxWxH – 500x600x500 mm) as per specification No. WG-NAS/RAK
Supplying and fixing 42U floor mount server rack (Dimension-DxWxH – 800x600x1866 mm) as per specification No. WG-NAS/RAK
Supplying and fixing 24 port patch panel with tool-less keystone jacks in provided U Rack complete as per specification no. WG- NAS/PP
Supplying, fixing, and configuring 24 ports with 4 (SFP+) port, ethernet managed switch with web view/CLI, 6KV surge protection on ethernet port and console port for management in provided rack as per specification no. WG- NWC/GBS
Supplying, fixing, and configuring 20 SFP ports + 4 Combo SFP 10/100/1000 Base-T erected in provided rack complete.
Supplying and erecting PVC box trunking of size 75x75 mm. with accessories on wall/ceiling as per specification No: WG- MA/BOX.
Supplying and erecting LSZH armoured multimode optical fibre cable with 12 fibres, core dia 50/125 µm (OM3), suitable up to 10 GBPS ethernet distance at 850 nm of wavelength, on wall/ceiling or laid in provided pipe/trench as per specification No. WG- COC/OFC
Supplying and fixing 12 ports light guide unloaded interconnect unit, rack mounted type, with adapter panel for termination of optical fibre cables in provided U rack complete as per specification no. WG-NAS/ LIU
Supplying and installing cat-6 cable suitable for networking as per specification no. WG- COC/NC
Supplying and fixing SC/LC type multimode pigtails (OM3) for LIU to terminate OFC in LIU as per specification No. WG-NAS/LIU2
Supplying and fixing SC/LC type multimode duplex adapter to couple two connectors between OFC &Fibre switch/Fibre module as per specification no. WG-NAS/MMA
Supplying and plugging 3 m fibre patch cord LC-LC MM (50) OM3 LSZH duplex complete as per specification no. WG- COC/FPC
Supplying and plugging 3 m fibre patch cord LC-SC MM (50) OM4 LSZH duplex complete as per specification no. WG- COC/FPC
Supplying and erecting PVC trunking (PVC casing-n-capping) of size 32 mm with accessories on wall/ceiling as per specification No: WG-MA/CON.
Supplying, fixing, and configuring 1-port mini-GBIC SX MM fibre transceiver (up to 550m, support 3.3V power) erected in provided rack complete.
Supplying, fixing, and configuring modularised multi-service router 802.11/a/n/ac unified Wave 2.5 GHz, with RJ- 45 port, supporting 1 to 13 channels for 2.4 GHz, with unified wireless access point complete.
Supplying &erecting 50 pair telephone copper cable 0.5 mm dia. with high density polyethylene insulation, polyester taped, Nylon Rip Cord & grey colour sheathed with FR PVC, conforming to ITD specification S/WS 113C laid in provided PVC casing capping/conduit as per specification No. WG-TW
Supplying &erecting 100 pair telephone copper cable 0.5 mm dia. with high density polyethylene insulation, polyester taped, Nylon Rip Cord & grey colour sheathed with FR PVC, conforming to ITD specification S/WS 113C laid in provided PVC casing capping/conduit as per specification No. WG-TW
Supplying & erecting 0.5 mm dia, copper jumper wire as per specification No. WG- TW
Supplying, erecting &commissioning MDF Box 50x50 pairs made from min. 1.5mm thick MS sheet as per specification no. WG-TW
Supplying, erecting &commissioning MDF Box 400x400 pairs made from min. 1.5mm thick MS sheet as per specification no. WG- TW
Supplying, Erecting, Testing and Commissioning of ESE Lightning Arrester, Controlled Early Streamer Emission Air terminal (ESEAT) with following specifications: ESEAT Protection Radius - 107 Mtr. with suitable mast height, with triggering time of 60 micro second as per NFC 17-102 which emits local electrostatic field that develops naturally around the shaft as a thunderstorm begins to gather, The ESEAT air-terminal shall be tested to support a 200kA current (waveform 10/350 μs). Test to be performed in compliance with NFC 17 102 version 2011 The ESEAT Should be able to work in both (positive and negative) lightning polarities. The ESEAT shall be in Strict compliance with the new test guidelines as per 'Annex C' of the revised NFC 17 102 version 2011(As Amended up to date) for ESE lightning protection system.The ESEAT shall be made of Stainless Steel 304L/316 grade non- corrosive metallic components, Electronic Circuit, Capacitor Bank, Transformer, Amplifier, Sensor etc. to generate the Streamer.The ESEAT to be a fully autonomous system requiring no external power supply. The ESEAT shall be Testable on site, using proprietary testers. The ESEAT should be sustainably designed to mitigate its environmental impact. The ESEAT to be mounted on provided base & support arrangements and installed as per the Technical specifications & General Arrangements Drawing attached complete with testing Warranty: five year from the date of commissioning
Supplying and erecting ISI mark GI pipe 50 mm. dia ‘C” class position with accessories complete. Specification no. CW-PLB/GP this item proposed to installed as per the Technical specifications& General Arrangements Drawing attached complete with testing .
Supplying and erecting ISI mark GI pipe 65 mm. dia ‘C” class position with accessories complete. Specification no. CW-PLB/GP .this item proposed to installed as per the Technical specifications & General Arrangements Drawing attached complete with testing .
supplying and erecting heavy duty Galvanized mild steel pole coupler suitable for connecting C class GI pipe size 50 mm.dia& C class GI pipe size 50 mm.dia 65mm dia duly threaded or welded complete with necessary arrangements & erected in position complete with ensuring electrical conductivity this item proposed to installed as per the Technical specifications & General Arrangements Drawing attached complete with testing
Supplying and fixing base for ESEAT cum pole cap duly galvanized with necessary anticorrosive treatment fabricated from mild steel fixed to pole top by means of welding and fixed at position with required size & type threads suitable for mounting of ESEAT with 2nos earth terminals having min. 30x6mm cross section 50mm length each towards down direction for fixing 2nos down conductors with necessary welded GI nuts & bolts of required size with washer this item proposed to installed as per the Technical specifications & General Arrangements Drawing attached complete
Supplying and fixing Pole base plate made up of mild steel having minimum 250mm size and 10mm thick fixed to pole base by welding with min. 4nos triangular cross arms of min 6mm thick welded duly galvanized and fixed at position. With 4nos 20mm dia holes for erection on provided foundation this item proposed to installed as per the Technical specifications & General Arrangements Drawing attached complete
Making M- 20 grade reinforced cement concrete foundation by considering the safe soil bearing capacity at site as 10 T/sq.m at 1.5 m depth including supply of steel, concrete, excavation and fixing provided nut bolts with the help of template, duly plastered as per design complete (for 9m & 10m high octagonal /conical GI pole). this item proposed to installed as per the Technical specifications& General Arrangements Drawing attached complete with testing .
Supplying and erecting G.I. stay set for poles, including loop insulators at inaccessible height with anchor plate 300x300x6 mm., straining screws, G.l. stay wire 7/8 SWG, G.l. stay rod 20mmx1.8m length and pole clamps duly erected in provided cement concrete foundation complete.this item proposed to installed as per the Technical specifications & General Arrangements Drawing attached complete with testing .
Making cement concrete foundation including excavation (60 x 60 x 150) cm deep in 1:3:6 cement concrete, (20 to 25) mm stone metal with necessary curing and finishing complete.(for stay).
Supplying and erecting GI sheet 1.6mm (16 SWG) caution board of size 250 x 200 mm duly painted with red oxide and enamel paint in Marathi, Hindi and English erected at position for HV/EHV (11000 Volts) installation with compliance to IS 2551-1982 this item proposed to installed as per the Technical specifications& General Arrangements Drawing attached complete with testing .
Supplying and erecting Contra go up device fabricated from required size mild steel flat of 40x5 mm dult welded with mild steel drooping spikes of min. 200mm long completely galvanized erected on pole with necessary GI nut bolts complete. this item proposed to installed as per the Technical specifications& General Arrangements Drawing attached complete
Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP. Weight analysis 25 X 6 mm GI Strip , 1.2 Kg / mtr for total length 30 mt/LA total weight 1.2kg X 750 = 900(this item proposed to installed as per the Technical specifications & General Arrangements Drawing attached complete with testing . )
Supplying and erecting pole clamp made from required size MS flat for pole post galvanized & painted with one coat of red oxide and two coats of aluminium paint and erected with necessary GI bolts and nuts, complete suitable for erecting Test Joint & Lightning flash counter this item proposed to installed as per the Technical specifications & General Arrangements Drawing attached complete
Supplying and Erecting Test Joint[Test Clamp] mounted in between the Earth Electrode(EC) and Down Conductor(DC)at the height of about 2meter above ground level to be done as per relevant IS specifications designed and situated so as the resistance of Earth Electrode can be measured Test Clamp to be attached to pole with provided Pole clamp this item proposed to installed as per the Technical specifications & General Arrangements Drawing attached complete with testing.
Supply, Installation, Testing & Commissioning of minimum 2 Digit Digital Lightning Strike Counter(LSC) Electronically controlled and mounted on down conductor having following features: a. Strike detection range: 1 KA to 100 KA. b. Minimum current sensitivity (id/3): 500 A c. Protection class: IP 67 (Without Enclosure) d. Easy to monitor and install and No maintenance required. e. Standards applicable: IEC 62561 Lightning protection system components (LPSC) - Part 6: Requirements for lightning strike counters (LSC) Lightning strike Counter to be mounted at a height of about 2mtr from Ground level with provided Pole clamp this item proposed to installed as per the Technical specifications & General Arrangements Drawing attached complete with Testing
Supplying, erecting, testing & commissioning of Maintenance free earthing system suitable for lightning protection system. The earth pit comprises of 125 to 150mm inner dia bore up to suitable depth from ground surface and a high corrosion resistance material of minimum 250 micron copper bonded solid steel rod electrode of 2meter long having 17.2 mm dia. with necessary conductor clamps for Earth rod/Earth rod to tape connector clamp etc. as per site requirements. with backfill earthing compound with Ground Enhancing compound combination of minimum 30Kg as per IS 3043- 2018 and IEEE 80- 2000 with satisfactory Test report from Govt. owned Test Laboratory . The requirements of Ground enhancing Compund are as Follows: a ) The compound shall have Ionic property to create ions for easy conduction. b) The compound shall be enable to disperse the ions equally in the earth pits. c) The compound should expand so much to remove entrapped air (bad Conductor of electricity) and create a strong conduction between electrode and soil. d) The compound should diffuse in the soil to create conductive silicate. This Silicate should expand into the soil with the edge of the earth pits and result in progressive reduction of earth pit resistance. e) The compound should have a property to assist in absorbing humidity from the neighbouring soil to keep earth pit moist, which in turn helps better conduction. f) The compound should have the property to ensure moisture is retained throughout the year irrespective of the weather condition without addition of water during the life of the earth pit. g) The compound should be non toxic, non reactive, non explosive & non corrosive. h) The compound shall be permanent &maintenance free and in its “set form”, maintain constant earth resistance with time. this item proposed to installed as per the Technical specifications& General Arrangements Drawing attached complete with testing
Suppling & erecting HDPE (High Density Polyethylene) earthing pit inspection chamber with Cover having factory Built Holes for accessing Strip/Wires easily at two sides made of Environment friendly Withstand colour /UV unaffected Resistant materials, assuring durability and 5Ton load bearing capacity. Minimum Dimensions are 260mm at Top, 260mm at Bottom, 210mm Height this item proposed to installed as per the Technical specifications & General Arrangements Drawing attached complete with testing
Shanti,Bhakti,Tirupati Bldg 8A and Tirupati 8B Bldg SITC of Electric Traction Passenger Lift with Rated capacity :6 Passenger/408Kg Floors :- G+7 floor (8 Stops/8 Landings) ·Travel :- 4 mtrs·Location of Lift Machine:- /MRL·Rated speed :- 1.0mps VS·Car/Landing door clear opening of 800 mm wide x 2000 mm high ·Clear Car size of 1100mm wide x 1000mm deep x 2250mm high· Lift shaft available having clear size of 1800mm wide x 1700mm deep, 1500mm Pit depth, 5000mm Overhead.·Doors type :- COPO/TOPO Doors with frame made from SS 304 grade solid(non-cladded) sheet of 1.5mm thick in hairline finish for car and all landing doors with SS door architraves/frames The lift doors shall have minimum 1 hour fire rating (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory). Lift car enclosure made from SS 304 grade solid (non-cladded) sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. The lift car interior design shall be done as per the directions of engineer in charge. ·COP with SS face plate having metallic push buttons with Braille code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with / without attendant key switch, OWD with audio- visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car,LMR& FCC/ground floor.·LOP with SS face plate having recess/surface push button box for all landingswith scrolling UP/DN LED indicator having metallic push buttons with Braille code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings.·Lift controller based on microprocessor IOT/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port.The controller shall have necessary protections such as overcurrent, overvoltage, over speed, overheat for all devices including lift motor and travel direction protection, protection for phase loss at input or output etc. various operation modes such as maintenance, change direction by attendant, full load bypass, VIP call operation, self levelling operation, call cancel facility, auto return to home landing, fireman evacuation operation, earthquake operation, door open/close operation from COP etc. The system can record information ·Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work.·Minor civil work such as alteration work if any necessary for erection of landing door frames and it's accessories e.g. sill, header, hole pass etc complete with plaster finish, civil work for erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails, providing and fixing steel girders/RCC work having adequate strength for mounting and hoisting lift machine etc. complete as per specification no. LFT.·Fireman controller having fireman switch at fire Landing. ·CCTV surveillance system comprises of 2 nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for min. 90 days with min.18” FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge.·Lift Machine of Gearless PMSM of suitable kW with duty cycle of minimum 120 starts/hr (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory), with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength. for minimum 30 latest faults, with real- time clock management and handheld keypad with LCD screen for view and setting of parameters. The control panel duly ·ARD complete with necessary SMF VRLA batteries.·wired with proper size & strength, copper wire for power & control circuit, with provision for addition of floor/control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class. General: - Job includes entire procedure of obtaining all necessary erection permissions & "License to Work the Lift" from Electrical Inspector(Lifts) with submission to the Engineer In Charge. ·The above rate includes Fully Comprehensive AMC for one year from the date of commissioning
Dismantling the existing 6 Passenger lift of all types travelling G+7 floors (8 Landings/8 Stops) having with auto/manual operated doors for lift car & all landings with door frames, guide rails, controller, wiring buffers, Lift Machine, ropes complete with all allied accessories of Lift and making the site clear in all respect complete with refilling the holes with cement mortar & making the site as original this job includes transportation of the dismantled material up to division/section store and handing over to the section engineer/store keeper in charge complete.
APNA Ladies Hostel SITC of Electric Traction Passenger Lift with Rated capacity :5 Passenger/340Kg Floors :- G+5 floor (6 Stops/6 Landings) ·Travel :- 4 mtrs·Location of Lift Machine:- /MRL·Rated speed :- 1.0mps VS·Car/Landing door clear opening of 800 mm wide x 2000 mm high ·Clear Car size of 1100mm wide x 1000mm deep x 2250mm high· Lift shaft available having clear size of 1800mm wide x 1700mm deep, 1500mm Pit depth, 5000mm Overhead.·Doors type :- COPO/TOPO Doors with frame made from SS 304 grade solid(non-cladded) sheet of 1.5mm thick in hairline finish for car and all landing doors with SS door architraves/frames The lift doors shall have minimum 1 hour fire rating (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory). Lift car enclosure made from SS 304 grade solid (non-cladded) sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. The lift car interior design shall be done as per the directions of engineer in charge. ·COP with SS face plate having metallic push buttons with Braille code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with / without attendant key switch, OWD with audio- visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car,LMR& FCC/ground floor.·LOP with SS face plate having recess/surface push button box for all landingswith scrolling UP/DN LED indicator having metallic push buttons with Braille code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings.·Lift controller based on microprocessor IOT/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port.The controller shall have necessary protections such as overcurrent, overvoltage, over speed, overheat for all devices including lift motor and travel direction protection, protection for phase loss at input or output etc. various operation modes such as maintenance, change direction by attendant, full load bypass, VIP call operation, self levelling operation, call cancel facility, auto return to home landing, fireman evacuation operation, earthquake door open/close operation from COP etc. The system can record information ·Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work.·Minor civil work such as alteration work if any necessary for erection of landing door frames and it's accessories e.g. sill, header, hole pass etc complete with plaster finish, civil work for erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails, providing and fixing steel girders/RCC work having adequate strength for mounting and hoisting lift machine etc. complete as per specification no. LFT.·Fireman controller having fireman switch at fire Landing. ·CCTV surveillance system comprises of 2 nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for min. 90 days with min.18” FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge.·Lift Machine of Gearless PMSM of suitable kW with duty cycle of minimum 120 starts/hr (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory), with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength. for minimum 30 latest faults, with real- time clock management and handheld keypad with LCD screen for view and setting of parameters. The control panel duly ·ARD complete with necessary SMF VRLA batteries.·wired with proper size & strength, copper wire for power & control circuit, with provision for addition of floor/control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class. General: - Job includes entire procedure of obtaining all necessary erection permissions & "License to Work the Lift" from Electrical Inspector(Lifts) with submission to the Engineer In Charge. ·The above rate includes Fully Comprehensive AMC for one year from the date of commissioningoperation,
Dismantling the existing 5 Passenger lift of all types travelling G+5 floors (6 Landings/6 Stops) having with auto/manual operated doors for lift car & all landings with door frames, guide rails, controller, wiring buffers, Lift Machine, ropes complete with all allied accessories of Lift and making the site clear in all respect complete with refilling the holes with cement mortar & making the site as original this job includes transportation of the dismantled material up to division/section store and handing over to the section engineer/store keeper in charge complete.
METRON Building SITC of Electric Traction Passenger Lift with Rated capacity :5 Passenger/340Kg Floors :- G+4 floor (5 Stops/5 Landings) ·Travel :- 4 mtrs·Location of Lift Machine:- /MRL·Rated speed :- 1.0mps VS·Car/Landing door clear opening of 800 mm wide x 2000 mm high ·Clear Car size of 1100mm wide x 1000mm deep x 2250mm high· Lift shaft available having clear size of 1800mm wide x 1700mm deep, 1500mm Pit depth, 5000mm Overhead.·Doors type :- COPO/TOPO Doors with frame made from SS 304 grade solid(non-cladded) sheet of 1.5mm thick in hairline finish for car and all landing doors with SS door architraves/frames The lift doors shall have minimum 1 hour fire rating (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory). Lift car enclosure made from SS 304 grade solid (non-cladded) sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. The lift car interior design shall be done as per the directions of engineer in charge. ·COP with SS face plate having metallic push buttons with Braille code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with / without attendant key switch, OWD with audio- visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car,LMR& FCC/ground floor.·LOP with SS face plate having recess/surface push button box for all landingswith scrolling UP/DN LED indicator having metallic push buttons with Braille code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings.·Lift controller based on microprocessor IOT/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port.The controller shall have necessary protections such as overcurrent, overvoltage, over speed, overheat for all devices including lift motor and travel direction protection, protection for phase loss at input or output etc. various operation modes such as maintenance, change direction by attendant, full load bypass, VIP call operation, self levelling operation, call cancel facility, auto return to home landing, fireman evacuation operation, earthquake operation, door open/close operation from COP etc. The system can record information ·Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work.·Minor civil work such as alteration work if any necessary for erection of landing door frames and it's accessories e.g. sill, header, hole pass etc complete with plaster finish, civil work for erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails, providing and fixing steel girders/RCC work having adequate strength for mounting and hoisting lift machine etc. complete as per specification no. LFT.·Fireman controller having fireman switch at fire Landing. ·CCTV surveillance system comprises of 2 nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for min. 90 days with min.18” FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge.·Lift Machine of Gearless PMSM of suitable kW with duty cycle of minimum 120 starts/hr(with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory), with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength. for minimum 30 latest faults, with real- time clock management and handheld keypad with LCD screen for view and setting of parameters. The control panel duly ·ARD complete with necessary SMF VRLA batteries.·wired with proper size & strength, copper wire for power & control circuit, with provision for addition of floor/control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class. General: - Job includes entire procedure of obtaining all necessary erection permissions & "License to Work the Lift" from Electrical Inspector(Lifts) with submission to the Engineer In Charge. ·The above rate includes Fully Comprehensive AMC for one year from the date of commissioning
Dismantling the existing 5 Passenger lift of all types travelling G+4 floors (5 Landings/5 Stops) having with auto/manual operated doors for lift car & all landings with door frames, guide rails, controller, wiring buffers, Lift Machine, ropes complete with all allied accessories of Lift and making the site clear in all respect complete with refilling the holes with cement mortar & making the site as original this job includes transportation of the dismantled material up to division/section store and handing over to the section engineer/store keeper in charge complete.
Balaram Building SITC of Electric Traction Passenger Lift with Rated capacity :20 Passenger/1360Kg Floors :- G+4 floor (5 Stops/5 Landings) ·Travel :- 4 mtrs·Location of Lift Machine:- /MRL·Rated speed :- 1.0mps VS·Car/Landing door clear opening of 1200 mm wide x 2000 mm high ·Clear Car size of 1300mm wide x 2400mm deep x 2250mm high· Lift shaft available having clear size of 2300mm wide x 3100mm deep, 1500mm Pit depth, 5000mm Overhead.·Doors type :- COPO/TOPO Doors with frame made from SS 304 grade solid(non-cladded) sheet of 1.5mm thick in hairline finish for car and all landing doors with SS door architraves/frames The lift doors shall have minimum 1 hour fire rating (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory). Lift car enclosure made from SS 304 grade solid (non-cladded) sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. The lift car interior design shall be done as per the directions of engineer in charge. ·COP with SS face plate having metallic push buttons with Braille code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with / without attendant key switch, OWD with audio- visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor.·LOP with SS face plate having recess/surface push button box for all landingswith scrolling UP/DN LED indicator having metallic push buttons with Braille code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings.·Lift controller based on microprocessor IOT/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port. The controller shall have necessary protections such as overcurrent, overvoltage, over speed, overheat for all devices including lift motor and travel direction protection, protection for phase loss at input or output etc. various operation modes such as maintenance, change direction by attendant, full load bypass, VIP call operation, self levelling operation, call cancel facility, auto return to home landing, fireman evacuation operation, earthquake operation, door open/close operation from COP etc. The system can record information ·Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work.·Minor civil work such as alteration work if any necessary for erection of landing door frames and it's accessories e.g. sill, header, hole pass etc complete with plaster finish, civil work for erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails, providing and fixing steel girders/RCC work having adequate strength for mounting and hoisting lift machine etc. complete as per specification no. LFT.· Fireman controller having fireman switch at fire Landing. ·CCTV surveillance system comprises of 2 nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for min. 90 days with min.18” FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge.·Lift Machine of Gearless PMSM of suitable kW with duty cycle of minimum 120 starts/hr (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory), with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength. for minimum 30 latest faults, with real- time clock management and handheld keypad with LCD screen for view and setting of parameters. The control panel duly ·ARD complete with necessary SMF VRLA batteries.·wired with proper size & strength, copper wire for power & control circuit, with provision for addition of floor/control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class. General: - Job includes entire procedure of obtaining all necessary erection permissions & "License to Work the Lift" from Electrical Inspector(Lifts) with submission to the Engineer In Charge. ·The above rate includes Fully Comprehensive AMC for one year from the date of commissioning'
Dismantling the existing 20 Passenger/Stretcher/Goods lift of all types travelling G+4 floors (5 Landings/5Stops) having with auto/manual operated doors for lift car & all landings with door frames, guide rails, controller, wiring buffers, Lift Machine, ropes complete with all allied accessories of Lift and making the site clear in all respect complete with refilling the holes with cement mortar & making the site as original this job includes transportation of the dismantled material up to division/section store and handing over to the section engineer/store keeper in charge complete.
OPD Building SITC of Electric Traction Passenger Lift with Rated capacity :20 Passenger/1360Kg Floors :- G+2 floor (3 Stops/3 Landings) ·Travel :- 4 mtrs·Location of Lift Machine:- /MRL·Rated speed :- 1.0mps VS·Car/Landing door clear opening of 1200 mm wide x 2000 mm high ·Clear Car size of 1300mm wide x 2400mm deep x 2250mm high· Lift shaft available having clear size of 2300mm wide x 3100mm deep, 1500mm Pit depth, 5000mm Overhead.·Doors type :- COPO/TOPO Doors with frame made from SS 304 grade solid(non-cladded) sheet of 1.5mm thick in hairline finish for car and all landing doors with SS door architraves/frames The lift doors shall have minimum 1 hour fire rating (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory). Lift car enclosure made from SS 304 grade solid (non-cladded) sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. The lift car interior design shall be done as per the directions of engineer in charge. ·COP with SS face plate having metallic push buttons with Braille code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with / without attendant key switch, OWD with audio- visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car,LMR& FCC/ground floor.·LOP with SS face plate having recess/surface push button box for all landingswith scrolling UP/DN LED indicator having metallic push buttons with Braille code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings.·Lift controller based on microprocessor IOT/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port.The controller shall have necessary protections such as overcurrent, overvoltage, over speed, overheat for all devices including lift motor and travel direction protection, protection for phase loss at input or output etc. various operation modes such as maintenance, change direction by attendant, full load bypass, VIP call operation, self levelling operation, call cancel facility, auto return to home landing, fireman evacuation operation, earthquake operation, door open/close operation from COP etc. The system can record information ·Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work.·Minor civil work such as alteration work if any necessary for erection of landing door frames and it's accessories e.g. sill, header, hole pass etc complete with plaster finish, civil work for erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails, providing and fixing steel girders/RCC work having adequate strength for mounting and hoisting lift machine etc. complete as per specification no. LFT.· Fireman controller having fireman switch at fire Landing. ·CCTV surveillance system comprises of 2 nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for min. 90 days with min.18” FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge.·Lift Machine of Gearless PMSM of suitable kW with duty cycle of minimum 120 starts/hr (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory), with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength. for minimum 30 latest faults, with real- time clock management and handheld keypad with LCD screen for view and setting of parameters. The control panel duly ·ARD complete with necessary SMF VRLA batteries.·wired with proper size & strength, copper wire for power & control circuit, with provision for addition of floor/control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class. General: - Job includes entire procedure of obtaining all necessary erection permissions & "License to Work the Lift" from Electrical Inspector(Lifts) with submission to the Engineer In Charge. ·The above rate includes Fully Comprehensive AMC for one year from the date of commissioning For Lift having 1200mm wide x 2000mm high clear entrance in 1.5mm thick SS 304 grade solid (non- cladded) landing door [Two panel], this includes all necessary accessories like LOP's with UP/DN buttons-arrows- indicators, extension of guide rails, shaft wiring with trunking, traveling cables, main hoisting ropes/belts, & OSG rope landing doors with all accessories etc. necessary for the normal safe functioning of lift installation complete.
Dismantling the existing 20 Passenger/Stretcher/Goods lift of all types travelling G+2 floors (3 Landings/3Stops) having with auto/manual operated doors for lift car & all landings with door frames, guide rails, controller, wiring buffers, Lift Machine, ropes complete with all allied accessories of Lift and making the site clear in all respect complete with refilling the holes with cement mortar & making the site as original this job includes transportation of the dismantled material up to division/section store and handing over to the section engineer/store keeper in charge complete.
V D Skin Building SITC of Electric Traction Passenger Lift with Rated capacity :20 Passenger/1360Kg Floors :- G+2 floor (3 Stops/3 Landings) ·Travel :- 4 mtrs·Location of Lift Machine:- /MRL·Rated speed :- 1.0mps VS·Car/Landing door clear opening of 1200 mm wide x 2000 mm high ·Clear Car size of 1300mm wide x 2400mm deep x 2250mm high· Lift shaft available having clear size of 2300mm wide x 3100mm deep, 1500mm Pit depth, 5000mm Overhead.·Doors type :- COPO/TOPO Doors with frame made from SS 304 grade solid(non-cladded) sheet of 1.5mm thick in hairline finish for car and all landing doors with SS door architraves/frames The lift doors shall have minimum 1 hour fire rating (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory). Lift car enclosure made from SS 304 grade solid (non-cladded) sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. The lift car interior design shall be done as per the directions of engineer in charge. ·COP with SS face plate having metallic push buttons with Braille code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with / without attendant key switch, OWD with audio- visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car,LMR& FCC/ground floor.·LOP with SS face plate having recess/surface push button box for all landingswith scrolling UP/DN LED indicator having metallic push buttons with Braille code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings.·Lift controller based on microprocessor IOT/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port.The controller shall have necessary protections such as overcurrent, overvoltage, over speed, overheat for all devices including lift motor and travel direction protection, protection for phase loss at input or output etc. various operation modes such as maintenance, change direction by attendant, full load bypass, VIP call operation, self levelling operation, call cancel facility, auto return to home landing, fireman evacuation operation, earthquake operation, door open/close operation from COP etc. The system can record information ·Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work.·Minor civil work such as alteration work if any necessary for erection of landing door frames and it's accessories e.g. sill, header, hole pass etc complete with plaster finish, civil work for erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails, providing and fixing steel girders/RCC work having adequate strength for mounting and hoisting lift machine etc. complete as per specification no. LFT.·Fireman controller having fireman switch at fire Landing. ·CCTV surveillance system comprises of 2 nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for min. 90 days with min.18” FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge.·Lift Machine of Gearless PMSM of suitable kW with duty cycle of minimum 120 starts/hr (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory), with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength. for minimum 30 latest faults, with real- time clock management and handheld keypad with LCD screen for view and setting of parameters. The control panel duly ·ARD complete with necessary SMF VRLA batteries.·wired with proper size & strength, copper wire for power & control circuit, with provision for addition of floor/control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class. General: - Job includes entire procedure of obtaining all necessary erection permissions & "License to Work the Lift" from Electrical Inspector(Lifts) with submission to the Engineer In Charge. ·The above rate includes Fully Comprehensive AMC for one year from the date of commissioning
Dismantling the existing 20 Passenger/Stretcher/Goods lift of all types travelling G+2 floors (3 Landings/3Stops) having with auto/manual operated doors for lift car & all landings with door frames, guide rails, controller, wiring buffers, Lift Machine, ropes complete with all allied accessories of Lift and making the site clear in all respect complete with refilling the holes with cement mortar & making the site as original this job includes transportation of the dismantled material up to division/section store and handing over to the section engineer/store keeper in charge complete.
CJ Building SITC of Electric Traction Passenger Lift with Rated capacity :20 Passenger/1360Kg Floors :- G+3 floor (4 Stops/4 Landings) ·Travel :- 4 mtrs·Location of Lift Machine:- /MRL·Rated speed :- 1.0mps VS·Car/Landing door clear opening of 1200 mm wide x 2000 mm high ·Clear Car size of 1300mm wide x 2400mm deep x 2250mm high· Lift shaft available having clear size of 2300mm wide x 3100mm deep, 1500mm Pit depth, 5000mm Overhead.·Doors type :- COPO/TOPO Doors with frame made from SS 304 grade solid(non-cladded) sheet of 1.5mm thick in hairline finish for car and all landing doors with SS door architraves/frames The lift doors shall have minimum 1 hour fire rating (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory). Lift car enclosure made from SS 304 grade solid (non-cladded) sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. The lift car interior design shall be done as per the directions of engineer in charge. ·COP with SS face plate having metallic push buttons with Braille code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with / without attendant key switch, OWD with audio- visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car,LMR& FCC/ground floor.·LOP with SS face plate having recess/surface push button box for all landingswith scrolling UP/DN LED indicator having metallic push buttons with Braille code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings.·Lift controller based on microprocessor IOT/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port.The controller shall have necessary protections such as overcurrent, overvoltage, over speed, overheat for all devices including lift motor and travel direction protection, protection for phase loss at input or output etc. various operation modes such as maintenance, change direction by attendant, full load bypass, VIP call operation, self levelling operation, call cancel facility, auto return to home landing, fireman evacuation operation, earthquake operation, door open/close operation from COP etc. The system can record information ·Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work.·Minor civil work such as alteration work if any necessary for erection of landing door frames and it's accessories e.g. sill, header, hole pass etc complete with plaster finish, civil work for erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails, providing and fixing steel girders/RCC work having adequate strength for mounting and hoisting lift machine etc. complete as per specification no. LFT.·Fireman controller having fireman switch at fire Landing. ·CCTV surveillance system comprises of 2 nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for min. 90 days with min.18” FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge.·Lift Machine of Gearless PMSM of suitable kW with duty cycle of minimum 120 starts/hr (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory), with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength. for minimum 30 latest faults, with real- time clock management and handheld keypad with LCD screen for view and setting of parameters. The control panel duly ·ARD complete with necessary SMF VRLA batteries.·wired with proper size & strength, copper wire for power & control circuit, with provision for addition of floor/control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class. General: - Job includes entire procedure of obtaining all necessary erection permissions & "License to Work the Lift" from Electrical Inspector(Lifts) with submission to the Engineer In Charge. ·The above rate includes Fully Comprehensive AMC for one year from the date of commissioning
Dismantling the existing 20 Passenger/Stretcher/Goods lift of all types travelling G+3 floors (4 Landings/4Stops) having with auto/manual operated doors for lift car & all landings with door frames, guide rails, controller, wiring buffers, Lift Machine, ropes complete with all allied accessories of Lift and making the site clear in all respect complete with refilling the holes with cement mortar & making the site as original this job includes transportation of the dismantled material up to division/section store and handing over to the section engineer/store keeper in charge complete.
Providing removal of granite door photo frame at each landing door with plaster &carrying necessary repairs to lift Hoistway,LMR & pit as per requirements with extensionof the Lift pits depth & increasing Landing door height as per requirements by chiselling and finishing complete with providing RCC with necessary steel lintel suitable for mounting Lift Landing door Providing and applying white-wash in two coats to theinside Lift shafts, pit and LMR in an approved manner complete and providing anderection of the approved shade granite landing door photo frame as per the actual site requirements with necessary base plaster and finishing in an approved manner with disposal of the debris as per municipal corporation guidelines and making the site clean in allrespect for 6nos 13passnger Lift having minimum clear entrance of 900mm wide x 2200mm high traveling Gnd+6Upper Floors as per the following details & specifications Removing cement tiles, or marble or dado without bed concrete including stacking the materials as directed with all leads, lifts etc. complete Removing the existing cement plaster of any thickness without causing dust nuisance and stacking the debris or spreading in the compound and cleaning the site etc. complete. Excavating CC foundation by chiselling for preparing pit & clearing the site by removing debris & making the site as required complete. Making cement concrete foundation in 1:3:6 cement concrete, (20 to 25) mm. stone metal duly plastered with necessary curing for complete. Supplying and erecting iron work consisting of rods, bars, MS pipes, etc. for Steel in RCC or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materialsProviding internal cement plaster 20mm thick in two coats in cement mortar 1:5 withoutneeru finish, to concrete, brick surface, in all positions including scaffolding and curing etc.complete Providing and laying telephone black /Amba White / Cadburybrown /Ruby red / Ocean Brown granite stone of 18 to 20 mm thick for door frame On C.M. 1:6 including filling joints with polymer base filler nosing the sharp edges wherever necessary, curing, etc. Providing and applying white-wash in two coats on old / new plastered or masonry surfaces and asbestos cement sheets including scaffolding and preparing the surface by brushing and brooming down etc. complete. Removing any kind of debris including loading in truck & conveying to approoved dumping point beyond MCGM limits, unloading, spreading etc. complete
Supplying and erecting modular type switch 16A duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type 3 pin 16A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting PVC Surface modular switch box with double mounting plate for 4 module duly erected.
Point wiring for light/bell/exhaust fan in PVC trunking (casing-capping) with 1.5 sq.mm (2+1E) FRLSH grade copper wire, modular type switch, earthing and required accessories as per specification No: WG-PW/SW
Supplying and erecting bulk head LED fitting max. 10W with high transitivity diffuser with system lumens output of min. 1100 lumens, min. efficacy of 110 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., THD<10%, p.f. >0.95, operating range of 140- 260V, in built surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50, including driver, IP66, IK09 rated on provided PVC Block / wooden board with 3 years warranty.
Supplying and erecting CRCA powder coated corridor/passage light LED fitting (4 feet) Max. 17W with high transitivity diffuser with system lumens output of Min. 2000 lumens , min. efficacy of 120 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., Ripple<5%, THD<10%, p.f. >0.95, operating range of 120-270V, surge protection of 4 kV, Life class of 50,000 Hrs. at L70B50, including driver, with end caps on provided PVC Block / wooden board with 3 years warranty.
Supplying and erecting exhaust fan heavy duty 230 V, A.C. 50 cycles 375/380 mm. 900 RPM complete erected in position as per specification no. FG-FN/EXF
Supplying & erecting 22 SWG G.I sheet metal cawl sector shaped with 25 x 25 x 3 (mm) angle iron frame, metal mesh to avoid birds entry with necessary material, suitable for exhaust fan of 400 mm as per specification no FG-FAS/MSC
Supplying, erecting & marking SPMCB 6A to 32A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW- SWR/MCB
Supplying, erecting & marking DPMCB 6 A to 32 A, B-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
Supplying and erecting single pole and neutral distribution board (SPNDB), with 2 ways for incoming and 6 ways (6 poles) for outgoing SP MCBs, with door, 1.2mm thickness surface / flush mounted, IP 43 Protection on iron / GI frame as per specification no. SW- SWR/MCBDB
Supplying & erecting CRCA sheet metal one way enclosures of 1.2mm thickness suitable for DP MCB /TP MCB/FP MCB/RCCB/RCBO complete erected on angle iron/GI frame.
Supplying, fixing and commissioning 2 pole, RCBO 6/10/16/20/25A, with overcurrent, rated short-circuit breaking capacity (10 kA) and earth leakage protection, with 30/100/300 mA sensitivity and short circuit and earth leakage trip indication as per specification no SW- RCCB/RCBO
Supplying, fixing and commissioning 4 pole RCBO 32/40A, with overcurrent, rated short- circuit breaking capacity (10 kA) and earth leakage protection, with 30/100/300 mA sensitivity and short circuit and earth leakage trip indication as per specification no SW-RCCB/RCBO
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 10 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 2 core 2.5 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 2 core 4 sq mm copper conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, installation and testing of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25 kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete, and recording the results Specification no. EA-MOBI
Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP. =5*2*1=10mtr* 25x6 mm -1.2 kg/mtr =12 kg
Supplying and erecting GI wire of high purity of required sizes used for earthing or any other purposes on wall with necessary G. I. Clamps fixed on wall/cable/ conduit with screws complete. Outside of Building connection to GI Wire to flate =1 nos lift*2 Run*5 mtr each floor*8 floor+Horizontal distance 60mtr=140 mtr *0.103KG/MTR=27.81
Providing & erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 300 mm width & 100 mm height comprising all required standard accessories.
Dismantling of existing fluorescent fittings of any type & size.
Dismantling the existing ceiling fan /exhaust fan / cabin fan / bracket fan complete with accessories, G.I. down rod, frame etc. and making the site clear.
Dismantling the existing switchgears, DB, and bus bar of any size complete with/ without board or angle iron frame
Dismantling the existing cables of all types & size above 10 sq mm up to 50 sq.mm.
Shubham EPC Private Limited
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid