Loading…
Loading…
| # | Company | Amount |
|---|---|---|
| 1 | ₹3.8 Cr B L TOWER FIRST FLOOR OPP HOUSING BOARDE OFFICE BEHIND AAROGYA HOSPITAL SHANKAR NAGAR RAIPUR C G 492001 | ₹3.8 Cr |
Tender Value
₹4.7 Cr
EMD Value
₹4.7 L
Closing Date
1 Aug 2025, 11:00 amClosed
Renovation and Upgradation of Conventional OTs to Modular OTs at Ispat General Hospital, SAIL, RSP, Odisha
NBCC/SBG/ODISHA/NIT/25-26/034
NBCC/SBG/ODISHA/NIT/25-26/034
Open Tender-Domestic
Medical Equipments/Waste
Dhenkanal, Odisha
₹11,800
₹4.7 L
17 Jul 2026
8 Jul 2025
1 Aug 2025
1 Aug 2025
14 Aug 2025
Renovation and Up-gradation of Existing Six Nos. Conventional Operation Theatres (OTs) to Modular
Operation Theatre complex (OTs) at Ispat General Hospital, as modification, for M&HS department.
SAIL, RSP, Odisha, including two years warranty of all OTs and allied accessories/equipment
SUMMARY OF COST
Sl. No. Description of Item Non-schedule Total
Digitally signed by JAYA
Renovation and Up-gradation of Existing Six Nos. Conventional Operation Theatres (OTs) to Modular Operation Theatre complex (OTs) at Ispat General Hospital, as
modification, for M&HS department. SAIL, RSP, Odisha, including two years warranty of all OTs and allied accessories/equipment
SL No. CPWD DSR Description Unit TOTAL Rate as per Rate as per Amount of Amount of NS
1 NS-1 Providing and fixing Ceiling & Wall Panel :- 40 mm Puff panel with Front sqft 10000 531 5310000.00
panel PPGI 0.6mm thick & back panel PPGI 0.5mm thick . PUF density of
40kg/m3 (Make: Tata/JSW/JSPL)
2 NS-2 Providing and fixing Glass Panel on one side wall ( 6*6 ) with printing as each 6 413000 2478000.00
per the theme suggested by engineer incharge complete in all respect
3 NS-3 Ceilling & Wall painting : Jointless Coatings Filling of all Joints and sqft 10000 123.9 1239000.00
cavities with ESDEE/Asian paints/MRF Polyster putty for metal surface
and Sanded Flush to provide a jointless finish primer with metal primer
to give a bonding of paint and then sprayed with a water based liquid
plastic aseptic and self sterilizing wall coating system of
Jutton/MRF/SIKA/APOLLO , which protects against the growth of
micro- organism, such as mould,fungi, yeast and bacteria on its
surface, Equivalent to a minimum dry film thickness of 200+ micron
complete in all respect as per direction of engineer-in-charge
4 NS-4 Providing and fixing Vinyl Floor : seamless Antistatic (Static electrical sqft 3600 330.4 1189440.00
propensity as per EN 1815 <2 KV, Antibacterial ( >99% inhibits growth
of E-Coli-S-Aureaus- MRSA) Thermal Conductive ( Es per ISO 10456 -
EN 12524- W/(m.K) =0.25) flooring system, 2mm thick, with perfectly
curved flush covings, all joints welded properly with same material with
4" Skirting including floor Selfe leveling .( jeofloor/equivalent Roll)
complete in all respect as per direction of engineer-in-charge
5 NS-5.1 Providing and fixing Semi-Hermetically sealed Dual leaf swing door, each 4 129800 519200.00
approx. sizes 1800 x 2100 mm made of HPL faced on both sides,
viewing window with fire rated glass 300 x 300 mm, complete in all
respect as per direction of engineer-in-charge
NS-5.2 Providing and fixing Semi-Hermetically sealed sliding door, sizes approx. each 2 129800 259600.00
1500 x 2100 mm made of HPL faced on both sides, viewing window with
fire rated glass 300 x 300 mm, complete in all respect as per direction
of engineer-in-charge
6 NS-6 Supply and fixing Pressure Releaf Damper system complete in all each 6 21240 127440.00
respect as per direction of engineer-in-charge
7 NS-7 Supply and fixing ceiling mounted Clean room UV Light complete in all each 6 8260 49560.00
respect as per direction of engineer-in-charge
8 NS-8 Supply and fixingceiling mounted Clean room LED Light ( set of 8 pcs) each 6 51920 311520.00
complete in all respect as per direction of engineer-in-charge
9 NS-9 Supply and fixing wall mounted Magnetic Writing board complete in all each 6 9440 56640.00
respect as per direction of engineer-in-charge
10 NS-10 Supply and fixing wall mounted X-Ray viewing plate complete in all each 6 23600 141600.00
respect as per direction of engineer-in-charge
11 NS-11 Supply, installation, testing and commissioning of Digital Surgeon each 6 177000 1062000.00
Control Panel: Membran Type (a) Time Day Clock, (b)Time Elapse Day
Clock, (c) General Lighting System,d) Medical Gas Alarm Panel,(e) Hand
Free Telephone set (f) Temperature & Humidity Indicator, complete in
all respect as per direction of engineer-in-charge
12 NS-12 Supply, installation, testing and commissioning of Anesthesia each 6 377600 2265600.00
Pendent:Movable dual arm ceiling pendant(Type Surgeon) each will be
made of Aluminum sheets box, provision for Oxygen, compressed Air
7bar and 4 bar ,Vacuum, , N02 outlets, IV Pole, LAN points (EU-CE
Certified) complete in all respect as per direction of engineer-in-charge
13 NS-13 Supply, installation, testing and commissioning of Surgeon Pendant : each 6 424800 2548800.00
Movable dual arm ceiling pendant(Type Surgeon) each will be made of
SS 360, with electrical sockets and switches, drawers, shelfs ( EU-CE
Certified) complete in all respect as per direction of engineer-in-charge
14 NS-14 Supply, installation, testing and commissioning of Laminar Air Flow each 6 312700 1876200.00
System: Supply & Installation of Planair Ceiling system with
unidirectional airflow. Plenum unit, Holding structure & Top plenum are
made of Aluminium Sheet 1.5mm thk. with aluminum extrusion frame
for the air distribution system with miniplate hepa filter 99.97% filter,
The laminar flow system have Diffuser of SS 304, Size 2400 x 1800 x
400mm HEPA , complete in all respect as per direction of engineer-in-
15 NS-15 Supply, installation, testing and commissioning of powder coated sqm 12 9440 113280.00
extruded aluminium Return Air Grilles complete in all respect as per
direction of engineer-in-charge
16 NS-16 Supply, installation, testing and commissioning of Pass box stainless each 6 88500 531000.00
18 NS-18 Supply, installation, testing and commissioning of Wooden Work for job 1 944000 944000.00
MGPS whereever required as per the user ( Bed head panels & Mgps
work related inside recovery room and Coridoor area. Min. area 100
sqm.)complete inall respect as per direction of engineer-in-charge
19 NS-19 Supply, installation, testing and commissioning of Extra Door HPL swing each 6 129800 778800.00
double door For Coridoor complete inall respect as per direction of
engineer-in-charge
20 NS-20 Supply, installation, testing and commissioning of Extra Door PPGI single each 20 82600 1652000.00
leaf For All Gates
21 NS-21 Supply, installation, testing and commis complete inall respect as per job 6 944000 5664000.00
direction of engineer-in-chargesioning of OT Light Double Dome High
End ( USFDA & EU-CE certified).
22 NS-22 Supply, installation, testing and commissioning of Modular Recovery job 2 1416000 2832000.00
Room ( ICU Bed electrical 6, Bedside table 6pc, Bedside locker 6pc,
curtains, IV rods, Monitor stands 6 pc, Crashcarts 2 pc, Bed head panels
6) complete inall respect as per the requirement of client and direction
of engineer-in-charge
23 NS-23 Providing and fixing SS Storage Unit for equipments inside OT & each 2 944000 1888000.00
Equipment room (total 24 nos: 12 nos for 06 OTs as per Client
requirement and rest at store area/room), sizes etc. complete shall be
as per the direction of engineer-in charge
Digitally signed by JAYA
24 NS-24 Supply of 36 W recess mounted LED back-lit 2’x2’ with high efficient each 16 4838 77408.00
LED’s, CCT 5700 - 6500 K,CRI≥80, System lumen 100lm/W, Lumens ≥
3600, white powder coated CRCA with PMMA opal diffuser for glare free
& uniform lighting, minimum burning hour life >50000 hours. Driver
shall be of constant current type, operating temperature from -10 to
+45 degree celcius, power factor>0.95, rated voltage 220-240V AC
working range:- 140-270 V A'c , 50 Hz +_ 5%, AC supply. Surge
protection - Inbuilt 2.5KV. Complete in all respect with the entire
satisfaction of Engineer-in-Charge.
25 NS-25 Supply & erection of 20 watt LED Betten Tube Light, 4' long suitable each 16 637.2 10195.20
with 40000 burning hours for rated voltage 220-240VAC working range:-
140-270VA'c,50Hz+_5%, AC supply with aluminium alloy base,,frosted
polycarbonate diffusers with power factor>0.90, Total Harmonic
Distortion(THD)<20%, system current-0.085A, system efficiency>85%,
with operating temp.-
10°Cto45°C,LumenoutputforLEDtubeshouldbe>2000lumenandoveralllum
en/wattofluminaireshouldbegreaterthan80%,C.R.I.ofLED>80%withcorrel
atedcolourtemperature(CCT)of6500K,minimumburninghourlife>40000ho
urs,LEDviewingangle120Degreecompleteinallrespectwiththeentiresatisfac
tionoftheEngineer-in-incharge. Supply of Industrial General Purpose
4'long tube fitting suitable to house 1x20wLED tube rod 4'long,
Polycarbonate housing, rated voltage 240V and Ingress protection IP-20
complete in all respect with the entire satisfaction of the Engineer-in-
NS-26 incharge.
NS-26.1 Supplying, installation, testing & commissioning of floor/ceiling recessed
2 mm thick pregavanised sheet outlet junction box including providing
cover with provision to adjust overall height, knock outs on four sides to
accept raceways of specified sizes and cutouts to fix required outlets for
following size of race ways with painted GI plate ( Colour as approved
Architect/Consultant).
28 NS-27 Supply, installation, testing & commissioning Refrigerant 'Y'Joint Each 20 767 15340.00
(Pair) required for distribution of refrigerant in copper piping etc.
complete as per specifications.Make:Same as per selected VRV
29 NS-28 CONDENSATE DRAIN PIPING
Supply & installation, testing and commissioning of Rigid heavy
class PVC piping complete with fittings, supports as per
specifications and duly insulated with 6 mm thick nitrile rubber
tubular insulation with factory laminated GC cloth.
31 NS-29 UVGI System: the coil mounted Ultra Violet Germicidal Irradiation
(UVGI) System for providing protection from airborne infection and
maintaining Indoor Air Quality in AHU unit with the following
features and technical specifications.
• The system shall comprise of one or more individual lamps with
fixtures(Combinations of 883mm & 1553mm Only), with mounting
Frame which should be made of Corrosion free Extruded Al profile with
flexibility of lamp overlap to meet different coil sizes along with
flexibility of fixing the reflector on frames. The support frame shall be
adjustable to cover cooling coil of any height. All necessary
materials for frame, top and bottom mounting brackets, adjustable
vertical channels, joining brackets, screws, and hardware shall be
included in the assembly as ready to use.Provider: Philips,
Honeywell, Ruks, Steril Aire
• The lamp life shall be rated no less than 9000 hours with a
derating of less than 15% after 8000 hours.
• Lamp should have high UV-C efficacy of at least 31% (Ratio Of
UV-C wattage Vs Lamp Wattage)
• The average Irradiance level of greater than 4000 micro watt/cm2 to
be delivered by the system at a distance of 30cm from the
cooling coil (without reflectors to also improve the air contact time for
IAQ improvement)
• The lamps shall be Simple Connection with 4 pin harness.
• Ballast shall be high frequency electronic type and operate lamps at a
frequency above 42 kHz to avoid interference with infrared devices
and eliminate visible flicker.
• Lamp & Ballast should be from same OEM Manufacturer.
• Country of origin for Lamp & Ballast should be US/Europe/India
• Ballast shall not contain any Polychlorinated Biphenyl (PCB).
• One ballast to run two lamps of upto 75W. One lamp per ballast for
Same Ballast to cater all lamp wattages to avoid any Maintenance and
Serviceability issues.
• The Control panel shall have Manual on/off from panel,
Integration with AHU electrical circuit (Switch off when AHU off),
Integration with AHU door (Limit switch to Switch off UV system
when door open)
• System Life hours indicator (Lamp Level), buzzer on lamp failure, Red
light indication during system running to avoid accidental
NS-30 exposures
Ceiling MOUNTED AIR HANDLING UNITS WITH MIXING BOX
33 Supply, installation, testing and commissioning of Factory built double
skin VRF/ DX based Floor Mounted air handling units made of 43mm
thick panels consisting of pre coated G.I. casing of thickness 0.8mm
outside layer and 0.8mm thick plane GI inside layer with polyurethene
foam (PUF) insulation of density 38kg/m3 factory injected between
them by injection moulding machine, thermal break profile, complete
with blower section with blower DIDW backward curved centrifugal fan
with suitable static pressure, Multi rows (4/6/8 rows) deep VRF based
Cooling Coil Section (coil shall be with aluminium finned copper
tubes(tube thickness not less than 0.4mm)), 50mm thick prefilter
section equivalent to MERV-8 rating, Mixing Box section with R/A & F/A
Damper, belt drive package with TEFC drive motor (IE-3) with IP-54
protection and 415+/-, 10% volts, 50 Hz, 3 phase, A.C. supply, drain
connections with drain valve, insulated stainless steel drain pan, fire
rated flexible inside AHU, necessary vibration isolation arrangement,
gravity louvers etc,complete as per specifications of following
capacities.Suitable capacity of TPN isolator for FM AHU within MS
enclosure for AHU to be provided. Item including acoustic treatment
between duct and AHU for noise reduction complete in all respect as per
Digitally signed by JAYA
34 NS-31 Dismantling an dremoval of existing switch/sockets, wiring, cables, job 2 684400 1368800.00
conduits, fan, lights and other electrical, HVAC gadgets etc. count the
items and store them in servicible condition and handed over to client
RSPL. Item including removal of all existing OT lights (working/non-
working condition) and handing over to client. Making suitable
connection of existing oxygen/gas pipe line, suction pipe line with the
proposed OTs, clean the entire surface prior to start the new work of
electrical, HVAC and any other work of specialized in nature entire,
dismantle and shifting the operative existing equipment at the desired
location, as per the satisfaction of client/Engineer in charge, complete in
all respect as per the direction of Engineer in charge
35 NS-32 SITC of Multi para Monitor with 7 parameters ( ECG, Respiration rate, set 8 356886.28 2855090.24
Temperature, NIBP, Nellcor SPO2 ,ETCO2, IBP ) with 6 channel 10.4"
high resolution color LED display. Suitable for adult, pediatric and
neonatal applications. Should have Arhythmia and ST analysis with early
assesment of patients ventilator status through IPI. Satseconds Alarm
management to reduce false alarms complete in all respect as per
direction of Engineer-in-charge
36 NS-33 Supply, installation, testing and commissioning of 5-7 Feet SLEEK Air set 2 72055.52 144111.04
Curtain with 2 motors, 3 blowers and 0.5hp power with body made up of
Stainless steel including electrical connection plug etc. complete in all
respect as per direction of Engineer in charge
37 NS-34 Supply, installation, testing and commissioning of hospital PA system job 2 155675.04 311350.08
specially designed for medical centers, hospitals, operation theatre for
improved safety and efficiency. Sufficient numbers of PA speakers to be
provided overhead voice messaging for daily announcements as well as
voice notification alerts during a variety of emergency situations. In the
event of an emergency, a sound system with mic can instantly issue pre-
recorded or live voice instructions telling staff, patients and visitors
Public address system with a background music and paging system can
be very beneficial for hospitals and their different areas like office,
waiting room, doctor room, nurse room and cashier of different control
by master room. With the help of the paging system an Instant message
notification can be sent to the nurse about the emergency situations.
The work shall consists design of PA system with sufficient speakers,
micephone for delivering message at one point with requisite connection
and all other complete in all respect as per direction and requirement of
cleint/engineer-in-charge
38 NS-35 Cost of comprehensive Annual maintenance of the equipment mentioned
in this BOQ as per NS items number 5 to 17, 21, 22,
24,25,26,33,34,35,37,38,39,40 and for schedule item Sl. No. 68 to 77
after the standard defect liability period of one year after the date of
handing over of the work
39 10.25 Steel work welded in built up sections/ framed work, including cutting, Kgs 300 172.60 51780.00
hoisting, fixing in position and applying a priming coat of approved steel
primer using structural steel etc. as required.
10.25.2 In gratings, frames, guard bar, ladder, railings, brackets, gates and 0.00
40 15.23.1 Dismantling tile work in floors and roofs laid in cement mortar including sqm 272 73.4 19964.80
stacking material within 50 metres lead.
For thickness of tiles 10 mm to 25 mm
41 15.56 Dismantling old plaster or skirting raking out joints and cleaning the sqm 628 54.65 34320.20
surface for plaster including disposal of rubbish to the dumping ground
within 50 metres lead.
42 15.3 Demolishing R.C.C. work manually/ by mechanical means including cum 14 3551.25 49717.50
stacking of steel bars and disposal of unserviceable material within
50 metres lead as per direction of Engineer - in- charge.
43 15.7.4 Demolishing brick work manually/ by mechanical means including cum 14 2060.2 28842.80
stacking of serviceable material and disposal of unserviceable material
within 50 metres lead as per direction of Engineer-in-charge
In cement mortar
44 12.52 Providing and fixing tiled false ceiling of specified materials of size 0.00
595x595 mm in true horizontal level, suspended on inter locking
metal grid of hot dipped galvanized steel sections ( galvanized @
120 grams/ sqm, both side inclusive) consisting of main "T" runner
with suitably spaced joints to get required length and of size 24x38
mm made from 0.30 mm thick (minimum) sheet, spaced at 1200
mm center to center and cross "T" of size 24x25 mm made of 0.30
mm thick (minimum) sheet, 1200 mm long spaced between main
"T" at 600 mm center to center to form a grid of 1200x600 mm and
secondary cross "T" of length 600 mm and size 24x25 mm made of
0.30 mm thick (minimum) sheet to be interlocked at middle of the
1200x600 mm panel to form grids of 600x600 mm and wall angle of
size 24x24x0.3 mm and laying false ceiling tiles of approved texture
in the grid including, required cutting/making, opening for services
like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main
"T" runners to be suspended from ceiling using GI slotted cleats of
size 27 x 37 x 25 x1.6 mm fixed to ceiling with 12.5 mm dia and 50
mm long dash fasteners, 4 mm GI adjustable rods with galvanised
butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200 mm
center to center along main T, bottom exposed width of 24 mm of all
T-sections shall be pre-painted with polyester paint, all complete for
all heights as per specifications, drawings and as directed by
Engineer-in-charge.
Digitally signed by JAYA
45 12.52.3 12.5 mm thick square edge PVC Laminated Gypsum Tile of size sqm 90 2215.15 199363.50
595x595 mm, made of Gypsum plasterboard, manufactured from
natural gypsum as per IS 2095 part I and laminated with white 0.16mm
thick fire retardant
PVC film on the face side and 12micron metalized polyester on the back
side with all edges sealed with the face side PVC film which goes around
and wraps the edges and is bonded to the edges and the back side
metalized polyester film so as to make the tile a completely sealed unit.
Electrical works
46 DSR(2022)- Wiring for light point/ fan point/ exhaust fan point/ call bell point
1.1 with 1.5 sq.mm FRLS PVC insulated copper conductor single core
cable in surface / recessed Medium class PVC conduit, with modular
switch, modular plate, suitable GI box and earthing the point with 1.5
sq.mm FRLS PVC insulated copper conductor single core cable etc. as
47 DSR(2022)- Wiring for circuit/ submain wiring alongwith earth wire with the 0.00
1.14 following sizes of FRLS PVC insulated copper conductor, single core
cable in surface/ recessed Medium class PVC conduit as required
49 DSR(2022)- Supplying and fixing suitable size GI box with modular plate and cover Each 45 477 21465.00
1.31 in front on surface or in recess including providing and fixing 3 pin
5/6 Amp modular socket outlet and 5/6 A modular switch,
connection etc. as required.
50 DSR(2022)- Supplying and fixing suitable size GI box with modular plate and cover Each 45 586 26370.00
1.32 in front on surface or in recess including providing and fixing 6 pin
5/6 & 15/16 Amp modular socket outlet and 15/16 A modular
switch, connection etc. as required.
51 DSR(2022)- Supplying and fixing following way, horizontal type three pole and 0.00
2.4 neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess,
complete with tinned copper bus bar, neutral bus bar, earth bar, din bar,
interconnections, powder painted including earthing etc. as required.
(But without MCB/RCCB/
52 DSR(2022)- Supplying and fixing of following ways surface/ recess mounting, 0.00
2.5 vertical type, 415 V, TPN MCB distribution board of sheet steel, dust
protected, duly powder painted, inclusive of 200 A, tinned copper bus
bar, common neutral link, earth bar, din bar for mounting MCBs (but
without MCBs and incomer) as required. (Note : Vertical type MCB TPDB
is normally used where 3 phase outlets are required.)
53 DSR(2022)- Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, 0.00
2.1 miniature circuit breaker suitable for
inductive load of following poles in the existing MCB DB complete with
connections, testing and commissioning etc. as required.
56 DSR(2022)- Supplying and fixing single pole blanking plate in the existing MCB DB Each 20 13 260.00
2.11 complete etc. as required.
57 DSR(2022)- Supplying and fixing following rating, four pole, 415 V, isolator in the 0.00
2.13 existing MCB DB complete with
connections, testing and commissioning etc. as required.
58 DSR(2022)- Supplying and fixing following rating, double pole, (single phase and 0.00
2.14 neutral), 240 V, residual current circuit breaker (RCCB), having a
sensitivity current 30 mA in the existing MCB DB complete with
connections, testing and commissioning etc. as required.
59 DSR(2022)- Supplying and fixing TP sheet steel enclosure on surface/ recess along Each 9 1592 14328.00
2.17 with 16/25/32 A, 415 V “C” curve
TP MCB complete with connections, testing and commissioning etc. as
60 DSR(2022)- Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with Each 9 1621 14589.00
2.18 2 pole and earth, metal enclosed plug top alongwith 20 A, “C” curve, SP,
MCB, in sheet steel enclosure, on surface or in recess, with chained
metal cover for the socket out let and complete with connections,
testing and commissioning
etc. as required.
61 DSR(2022)- Supplying and fixing 20 A, 415 V, TPN Industrial type socket outlet, with Each 9 2590 23310.00
2.19 4 pole and earth, metal enclosed plug top alongwith 20 A, “C” curve,
TPMCB, in sheet steel enclosure, on surface or in recess, with chained
metal cover for the socket out let and complete with connections,
testing and commissioning etc. as
62 DSR(2022)- Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with Each 9 4107 36963.00
2.2 4 pole and earth, metal enclosed plug top alongwith 30 A, “C” curve,
TPMCB, in sheet steel enclosure, on surface or in recess, with chained
metal cover for the socket out let and complete with connections,
testing and commissioning etc. as
Digitally signed by JAYA
63 DSR(2022)- Installation, testing and commissioning of wall bracket / ceiling fittings Each 55 119 6545.00
1.35 of all sizes and shapes containing upto two GLS/CFL/LED lamps per
fitting complete with all accessories including connections etc. as
64 DSR(2022)- Supplying and installing following size of perforated Hot 0.00
4.6 DippedGalvanised Iron cable tray (galvanisation thickness not less than
50 microns) with perforation not more than 17.5%, in convenient
sections, joined with connectors, suspended from the ceiling with G.I.
suspenders including G.I. bolts & nuts, etc. as
65 DSR(2022)- Supplying and installing following size of perforated Hot Dipped 0.00
4.7 Galvanised Iron cable tray “bends” (galvanisation not less than 50
microns) with perforation not more than 17.5%, in convenient sections,
joined with connectors, suspended from the ceiling with G.I. suspenders
including G.I. bolts & nuts, etc.
66 DSR(2022)- Supplying and installing following size of perforated Hot Dipped 0.00
4.8 Galvanised Iron cable tray “Tee” (galvanisation not less than 50
microns) with perforation not more than 17.5%, in convenient sections,
joined with connectors, suspended from the ceiling
with G.I. suspenders including G.I. bolts & nuts, etc. as required.
67 DSR(2022)- Supplying and installing following size of perforated Hot Dipped 0.00
4.9 Galvanised Iron cable tray “Cross
member” (galvanisation not less than 50 microns) with perforation not
more than 17.5%, in convenient sections, joined with connectors,
the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as
68 DSR(2019)- Variable Refrigerant Volume / Flow Air-conditioning System 0.00
1.0 (Heating & Cooling both)
Supply,Installation,Testing & Commissioning of modular type 0.00
Variable Refrigerant Flow/Variable Refrigerant Volume air cooled
outdoor units suitable for cooling and heating both, having all
hermetically sealed inverter type Scroll Compressor
,microprocessor based Controller, top discharge type condensing
unit(s), with R-410A Refrigerant,vibration isolators,with suitable
foundation etc. complete as required.The unit shall deliver the
rated capacity at 39 Deg C AHRI Conditions and work even at
53°C ambient temperature without tripping.The unit shall be
suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power
supply.The compressor and VRF should be of same make, The
condensor fins should have anti corrosive and hydrophyllic coating from
factory having certification from third party ( TUV) . .The unit shall be
filled with first charge of the refrigerant and ready for use
The VRF system shall have free phase technology, which shall 0.00
correct phases automatically in case of phase reversal.
DSR(2019)- Supply, installation, testing and commissioning of 0.00
4.0 following minimum capacity and external static pressure
VRF/VRV floor mounted ductable type Indoor unit
equipped with washable synthetic media pre-filter, fan
section with low noise fan/dynamically balanced blower,
multispeed motor, coil section with DX copper coil, electronic
expansion valve, outer cabinet, vibration isolators, drain pan, other
necessary supports etc., suitable for operation on single phase AC
supply 230 V ± 10%, 50 Hz complete as required. The unit
shall have automatic force shut down provision in case of fire on
receiveing signal from BMS System.The cooling capacity of indoor
unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C
WB temperature.
DSR(2019)- Supply, Installation, testing and commissioning including 0.00
5.0 vaccumiazation and Nitrogen testing of following nominal sizes of
soft/hard drawn copper refrigerant piping for VRV/VRF system,
complete with fittings, with suitable adjustable ring type hanger
supports, jointing/brazing including accessories. Copper Pipe
.Copper Pipe insulated with Facotry Laminated 7mill glasscloth on closed
cell elastometric nitrile rubber tubular sleeves sections of specified
thickness as given below for Suction and Liquid lines.All accessories as
per specifications etc. as required :
Digitally signed by JAYA
70 DSR(2019)- 6.4 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 Rmt 50 245 12250.00
5.1 mm thick insulation
71 DSR(2019)- 9.5 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 Rmt 60 331 19860.00
5.2 mm thick insulation
72 DSR(2019)- 12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 Rmt 40 466 18640.00
5.3 mm thick insulation
72 DSR(2019)- 15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with Rmt 40 588 23520.00
5.4 19 mm thick insulation
74 DSR(2019)- 19 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 Rmt 55 707 38885.00
5.5 mm thick insulation
75 DSR(2019)- 22.2 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 Rmt 55 865 47575.00
5.6 mm thick insulation
76 DSR(2019)- 25.4 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 Rmt 60 1022 61320.00
5.7 mm thick insulation
77 DSR(2019)- 38.1 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with Rmt 65 1265 82225.00
5.11 19 mm thick insulation
DSR(2018)- Supply, installation, balancing and commissioning of factory 0.00
16.12.1 fabricated GSS sheet metal rectangular/round ducting 120 GSM
complete with neoprene rubber gaskets, elbows, splitter
dampers, vanes, hangers, supports etc. as per approved drawings and
specifications of following sheet thickness complete as
80 DSR(2018)- Supplying & fixing of powder coated extruded aluminium Sqmt 4 5910 23640.00
16.16 Return/Exhaust Air Grills with louvers but without volume control
dampers as per specifications.
81 DSR(2018)- Supplying & fixing of powder coated extruded aluminium Supply Sqmt 4 9105 36420.00
16.15 Air Grills with aluminium volume control dampers as per
specifications.
DSR(2018)- Supplying and fixing of following thickness duly laminated 0.00
16.23 aluminum foil of mat finish closed cell Nitrile rubber (Class "O")
insulation on existing duct after applying suitable adhesive for
Nitrile rubber. The joints shall be sealed with 50 mm wide and 3
mm thick self adhesive nitrile rubber tape insulation complete as
per specifications and as required
82 DSR(2018)- 19 mm thickness insulation (For Supply & Return air duct) Sq.m 280 754 211120.00
83 DSR 2022- Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe set 4 7472 29888.00
5.4 from earth electrode including connection with G.I. nut, bolt, spring,
washer excavation and re-filling etc. as required.
84 DSR 2022- Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe mete 40 706 28240.00
5.11 from earth electrode including connection with G.I. nut, bolt, spring, r
washer excavation and re-filling etc. as required.
85 DSR 2022- Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for mete 350 1162 406700.00
5.15 connections etc. as required. r
Digitally signed by JAYA
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
NIT-34.pdf
Tender Document
SCC.pdf
Tender Document
GCC2022.pdf
Tender Document
Physical Milestone.pdf
Tender Document
Technical Specifications.pdf
Tender Document
REV_Tender BOQ_.pdf
Tender Document
REV_APPROVE MAKE LIST.pdf
Tender Document
addendum-12768b213e6a-Addendum002.pdf
pdf • 0.10 MB
corrigendum-4000-Corrigendum01.pdf
pdf • 0.09 MB
addendum-d1f2af7764b1-Addendum001.pdf
pdf • 0.10 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .