Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹26.5 LAccepted-AOC 13 218 MASJID EXTEN SADAR BAZAR | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹27.6 L+₹1.1 L (4.22%)Rejected-Finance GALI NO 2 H NO 45 2ND FLOOR NANAK VIHAR COLONY LAL KUAN GHAZIABAD UTTAR PRADESH 201009 | GHAZIABAD | GHAZIABAD | UTTAR PRADESH | 201009 | L2 | Rejected-Finance Not Being L1 | |
| 3 | L3₹29.1 L+₹2.6 L (9.78%)Rejected-Finance GROUND FLOOR F 11 PHASE II MAYAPURI WEST DELHI DELHI 110064 | DELHI | WEST DELHI | DELHI | 110064 | L3 | Rejected-Finance Not Being L1 | |
| 4 | L4₹35.6 L+₹9.1 L (34.3%)Rejected-Finance 20 8 EWS PREETAM NAGAR COLONY ALLAHABAD | PRAYAGRAJ | UTTAR PRADESH | 211001 | L4 | Rejected-Finance Not Being L1 |
| Sl No | Description | Qty | Unit | verma enterprises L1 | MOHIT ENTERPRISES L4 | AMIT ENTERPRISES L3 | A K ENGINEERING COMPANY L2 |
|---|---|---|---|---|---|---|---|
| 1.00 | Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth in soft/loose soil for foundation, etc, or for shafts, wells, drain pipes not exceeding 10 sqm on plan and getting out, complete, all as specified and as directed. | 214 | Cum | 149 ₹31,886 | 59 ₹12,626 Lowest | 100 ₹21,400 | 80 ₹17,120 |
| 2.00 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick, complete, all as specified and as directed. | 182 | Cum | 49 ₹8,918 | 19 ₹3,458 Lowest | 20 ₹3,640 | 80 ₹14,560 |
| 3.00 | Removing surplus soil to a distance not exceeding 50 m and deposited where directed at a level not exceeding 1.50 m above the starting point, complete, all as specified and as directed. | 32 | Cum | 99 ₹3,168 | 19 ₹608 Lowest | 20 ₹640 | 80 ₹2,560 |
| 4.00 | Taking up the of size of 80 mm bore CI/DI/GI water mains (including all fittings) with spigot & socket ends and lead/tyton joints including burning out lead joints and recovering lead all as specified and directed. | 96 | RM | 9 ₹864 Lowest | 19 ₹1,824 | 20 ₹1,920 | 30 ₹2,880 |
| 5.00 | All as per Srl item No.4.00 here-in-before but 100 mm bore. | 61 | RM | 19 ₹1,159 Lowest | 19 ₹1,159 Lowest | 30 ₹1,830 | 33 ₹2,013 |
| 6.00 | All as per Srl item No.4.00 here-in-before but 150 mm bore | 11 | RM | 29 ₹319 | 19 ₹209 Lowest | 40 ₹440 | 50 ₹550 |
| 7.00 | Re-laying only in trenches for the pipe 80 mm bore GI/CI/DI pipes with socket and spigot ends, cleaning thoroughly and removal of all blockages if any complete all as specified and directed by Engr-in-Charge.
Note :The cost of jointing material i.e titon ring/gasket/run lead and nut bolts etc are deemed are deemed to be including in the rate quoted by the tenderer. | 11 | RM | 29 ₹319 Lowest | 39 ₹429 | 100 ₹1,100 | 30 ₹330 |
| 8.00 | All as per Srl item No.7.00 here-in-before but 100 mm bore. | 5.5 | RM | 39 ₹214.5 | 49 ₹269.5 | 100 ₹550 | 33 ₹181.5 Lowest |
| 9.00 | All as per Srl item No.7.00 here-in-before but 150 mm bore. | 5.5 | RM | 99 ₹544.5 | 59 ₹324.5 | 100 ₹550 | 50 ₹275 Lowest |
| 10.00 | Supplying, laying, jointing, testing and commmisioning for the size of 80 mm bore DI pipe as per IS 8329, class K-9 with inside cement mortar lining with spigot and socket ends laid in trenches all complete all as specified and as directed at site .
Note : - The cost of jointing material i.e titon ring/gasket/run lead and nut bolts etc are deemed to be including in the rate quoted by the tenderer. | 90 | RM | 1,099 ₹98,910 | 1,199 ₹1,07,910 | 999 ₹89,910 | 650 ₹58,500 Lowest |
Tender Value
₹39 L
EMD Value
₹78,000
Closing Date
5 Feb 2026, 6:00 pmClosed
GE South Delhi Cantt
GE South Delhi Cantt-10
REPAIR/MAINT OF EXTERNAL WATER SUPPLY RISING AND DISTRIBUTION PIPE LINES, INSTALLATIONS, BORE WELLS, PUMP HOUSES AND CONNECTED ALLIED WKS AT MANESAR ARMY CAMP, DUNDHERA MIL STN AND INDUBINOLA UNIVERSITY UNDER AGE E/M OF GE (SOUTH) DELHI CANTT-10
2026_MES_748703_1
GE/TOKEN-103/2025-26
Open Tender
Civil Works
Item Rate
180 days
GE SOUTH DELHI CANTT
As per tender documents
11 documents required · 11 mandatory
₹500
GE South Delhi Cantt
₹78,000
Yes
20 Mar 2026
15 Jan 2026
9 Feb 2026
15 Jan 2026
5 Feb 2026
29 Jan 2026
Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth in soft/loose soil for foundation, etc, or for shafts, wells, drain pipes not exceeding 10 sqm on plan and getting out, complete, all as specified and as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick, complete, all as specified and as directed.
Removing surplus soil to a distance not exceeding 50 m and deposited where directed at a level not exceeding 1.50 m above the starting point, complete, all as specified and as directed.
Taking up the of size of 80 mm bore CI/DI/GI water mains (including all fittings) with spigot & socket ends and lead/tyton joints including burning out lead joints and recovering lead all as specified and directed.
All as per Srl item No.4.00 here-in-before but 100 mm bore.
All as per Srl item No.4.00 here-in-before but 150 mm bore
Re-laying only in trenches for the pipe 80 mm bore GI/CI/DI pipes with socket and spigot ends, cleaning thoroughly and removal of all blockages if any complete all as specified and directed by Engr-in-Charge. Note :The cost of jointing material i.e titon ring/gasket/run lead and nut bolts etc are deemed are deemed to be including in the rate quoted by the tenderer.
All as per Srl item No.7.00 here-in-before but 100 mm bore.
All as per Srl item No.7.00 here-in-before but 150 mm bore.
Supplying, laying, jointing, testing and commmisioning for the size of 80 mm bore DI pipe as per IS 8329, class K-9 with inside cement mortar lining with spigot and socket ends laid in trenches all complete all as specified and as directed at site . Note : - The cost of jointing material i.e titon ring/gasket/run lead and nut bolts etc are deemed to be including in the rate quoted by the tenderer.
All as per Srl item No.10.00 here-in-before but 100 mm bore.
All as per Srl item No.10.00 here-in-before 150 mm bore.
M & L for DI fittings/specials such as, bends tapers any type, (straight, bend, increasing, decreasing or double socket etc) Tee pieces single branch, 'Y' junction, double branch, cross (all sockets or socket and spigot) collars, caps and plugs of size up to 150mm bore complete, all as specified and directed.
All as per Srl item No.13.00 here-in-before but size from 200 mm bore to 300 mm bore
Taking up or down galvanised pipe with connected fittings for cleaning,refixing or removing to storeyard complete the bore of 15 mm, complete all as specified and as directed.
All as per Srl item No.15.00 here-in-before but 20 mm bore.
All as per Srl item No.15.00 here-in-before but 25 mm bore.
All as per Srl item No.15.00 here-in-before but 40 mm bore.
All as per Srl item No.15.00 here-in-before but 50 mm bore.
Relaying and fixing GI pipe with connected fittings after removal of scalling, cleaning and flushing etc including supply and fixing of new fittings i.e bends, collers,Tees, reduces etc for 15 mm bore pipe, complete, all as specified and directed. Note: all type GI fittings deemed in this quoted rate.
All as per Srl item No.20.00 here-in-before but 20 mm bore.
All as per Srl item No.20.00 here-in-before but 25 mm bore.
All as per Srl item No.20.00 here-in-before but 40 mm bore.
All as per Srl item No.20.00 here-in-before but 50 mm bore.
Supply and laying/fixing of 15 mm bore GI water tubing, medium grade, galvanised (ISI marked as IS-1239), with all fittings including short lengths, fixed to walls, concealed in wall and ceiling or laid in floor trench complete with all fittings (such as bends, elbows, Tee, short pieces, connectors, back nuts, diminishing pieces, caps and plugs, unions etc), complete, all as specified and directed .
All as per Srl item No.25.00 here-in-before but 20 mm bore.
All as per Srl item No.25.00 here-in-before but 25 mm bore.
All as per Srl item No.25.00 here-in-before but 40 mm bore.
All as per Srl item No.25.00 here-in-before but 50 mm bore.
All as per Srl item No.25.00 here-in-before but 80 mm bore.
All as per Srl item No.25.00 here-in-before but 100 mm bore.
All as per Srl item No.25.00 here-in-before but 150 mm bore.
Supply and fixing in replacement of Gun metal globe or gate valves, with iron wheel head screwed both ends for iron pipe of 15 mm bore and fixed, complete, all as specified and as directed.
All as per Srl item No.33.00 here-in-before but 20 mm bore.
All as per Srl item No.33.00 here-in-before but 25 mm bore.
All as per Srl item No.33.00 here-in-before but 40 mm bore.
All as per Srl item No.33.00 here-in-before but 50 mm bore.
Supply and fixing in replacement of CI/DI sluice valve of 80 mm dia with flanged ends class PN 1 .6 with iron wheel, stainless steel spindle and check nut confirming to IS :14846 incl all jointing materials such as nuts, bolts, washers and gaskets etc complete all as directed.
All as per Srl item No.38.00 here-in-before but 100 mm dia.
All as per Srl item No.38.00 here-in-before but 150 mm dia.
Repair/maint of water leakage from 150mm bore of CI/DI pipe line & pipe joint in ground and open carefully the joint portion of the of the pipe line duly excavated the trench and burning out the defective run lead joint in existing of CI pipe/fitting and provision of new lead joint in site using the retrieved lead as obtaining from burning out of joint and adding of fresh lead if required to make the joint 100% water leak proof including returning, filling and ramming the excavated materials after satisfactory, joint/leak chacking all as directed. Note : - The jointing material i.e rubber gasket, run lead shall be measured and paid separately in relevant Sch 'A' items.
All as per Srl item No.41.00 here-in-before but 100 mm bore pipe line.
All as per Srl item No.41.00 here-in-before but 80 mm bore pipe line.
M&L for Run lead joint including jointing material for CI/DI pipe of the size 80 mm bore, complete all specified and directed.
All as per Srl item No.44.00 here-in-before but 100 mm bore.
All as per Srl item No.44.00 here-in-before but 150 mm bore.
Material and labour for Rubber Gasket Joint (Tyton Joint) including jointing material for DI/CI pipe of the size of 80 mm bore complete all as specified and as directed.
All as per Srl item No.47.00 here-in-before but 100 mm bore.
All as per Srl item No.47.00 here-in-before but 150 mm bore.
Repair/rectification of GI Pipe leakage by replacing short piece length up to 0.50 mtr in wall/floors etc and excavation upto 1 cum as in trenches and including providing unions, reducers,nipples etc for 15 mm bore pipe and making necessary connections to make it functional complete all as specified and as directed. Note: The GI fittings shall be measured and paid separately in relevant Sch 'A' items.
All as per Srl item No.50.00 here-in-before but 20 mm bore pipe.
All as per Srl item No.50.00 here-in-before but 25 mm bore pipe.
All as per Srl item No.50.00 here-in-before but 40 mm bore pipe.
All as per Srl item No.50.00 here-in-before but 50 mm bore pipe.
Supply and fixing GI fittings (like band, elbow, reducer, tee, union, socket, nipple etc) for fixing with GI pipe size of 15 mm to 25 mm complete all as specified and as directed.
All as per Srl item No.55.00 here-in-before but 40 mm to 100 mm.
Supplying, laying, jointing, welding & testing MS Pipe (Heavy duty class 'C') laid in trenches or on floors for connections to centrifugal pump sets for suction, pump to header and to connect out going water main CI/DI pipe line size of 100 mm bore all as specified and directed by Engr-in-Charge. Note:- (i) MS Flanges and Flange joints complete with jointing materials shall be measured and paid separately in Sch 'A' relevant items.
All as per Srl item No.57.00 here-in-before but 150 mm bore.
Supply only MS flanges of 80/100 mm bore not less than 10-14 mm thick duly welded on ends of MS pipe all as specified and as directed.
All as per Srl item No.59.00 here-in-before but 150/200 mm bore.
M&L for Flanged Joints with rubber or fibre board gasket including nuts, bolts and double washers of size of 80 mm bore complete all as specified and as directed.
All as per serial item No 61.00 here-in-before but 100 mm bore.
All as per serial item No 61.00 here-in-before but 150 mm bore.
Supply & fixing of CI/DI Non Return valve siz of 80 mm bore without by pass arrangement, swing type, confirming to IS 5312, flanged ends pressure rating PN 1.0 complete including taking out unsv NRV complete all as specified and as directed. Note:- Flanged joints complete with jointing material shall deemed in the unit rate of item.
All as per Srl item No. 64.00 here-in-before but 100 mm bore.
All as per Srl item No. 64.00 here-in-before but 150 mm bore.
Supply and fixing CI/DI foot valve size of 80 mm bore flanged ends, swing type opration with rubber sheet, as per IS:4038 including taking out unsv foot valve all as specified and as directed. Note:- Flanged joints complete with jointing material shall deemed in the unit rate of item.
All as per Srl item No. 67.00 here-in-before but 100 mm bore.
All as per Srl item No. 67.00 here-in-before but150 mm bore.
Supply, installation and testing of flanged ends water meter ISI marked woltman type, Class 'B' of size 100 mm bore and making good connection with flanged ends, with gasket rubber sheet and nut & bolts fixing in horizontal/inclind/vertical position, including taking out unsv water meter complete all as specified and as directed at site. Note :- Flange joints including jointing materials shall deemed in the unit rate of item.
Taking down only existing leakaged/breakdown CI/GI/DI pipe, joints, bends, elbow, tees, rubber joints upto 200 mm dia for leakages recticifation complete all as specified and as directed. Note: Soil excavation, removal, re filling and connected fittings shall be measured and paid separately in relevant sch Items.
M&L for in replacement flanged ends 'Y' strainer/dirt box size of 100 mm bore with stainless steel mesh suitable for water meter to avoid foreign material entering into meter and making good connection with flanged ends, with gasket rubber sheet and nut & bolts fixing in horizontal/inclind/vertical position, including taking out old unsv strainer/dirt box complete all as as directed at site. Note :- The cost of flange joints and jointing materials are deemed in this quoted rate.
Supply, lowering and fixing in replacement of GI Column pipe heavy duty flanged & drilled ISI marked 80 mm bore, as per IS-1239, 3 Mtr long, GI flange 12mm thick, slots cutting in flanges for passing of submersible cable including all jointing material such as bolts, nuts, washers & packing sheet and connecting compete all as specified and as directed.
All as per Srl item No. 73.00 here-in-before but 50 mm bore.
Material and labour for development of tube well for improvement of water yield by 630 CFM compressor including taking out existing submersible pump set complete with pipe and cable and lowering the same after water yield improvement including necessary T&P and minor spare parts complete all as specified.
M & L for lifting of submersible pumping set of any capacity from deep bore well of any depth with chain and pulley/machine plant arrangement including lowering down the submersible pump set after repair complete all as specified and directed. Note: All break downs should be done with in 24 hours without any interpution of water supply system to troops. If not rectified with in time period will be arrange alternate suitable capacity of submersible pump set up to complete the break down and the coplete job cost is deemed in this quoted rate.
M & L for opening the defective submersible pump set and motor of 5 HP to 12.5 HP repairing the same by replacing the unserviceable parts including machine/ lathe work and re-assembling the pump set in original position with required insulating material to make it fully functional complete all as specified and as directed by Engr-in-Charge. Note:- All spare parts as required for repair/overhauling shall be measured and paid separately under relevant item of Schedule 'A' and the spares should be suitable to as per above existing model & make.
Supply only the following spares of submersible pump set capacity of 5 HP to 7.5 HP, 3 phase complete all as specified and directed:-
CI Stage bowl.
GM neck ring.
Remetling of GM impeller turning.
GM DOL bush.
SS stud with nut.
Water seal
Revolving disc
Impeller stainless steel or as per existing
Impeller key.
CI DOL piece.
SS coupling with key.
CI Suction piece.
GM sand guard.
Supply only the following spares of submersible pump set capacity 7.5 to -12.5 HP, complete all as specified and directed.
CI Stage bowl.
GM neck ring.
Remetling of GM impeller turning.
GM DOL bush.
SS stud with nut.
Impeller stainless steel or as per existing
Impeller key.
CI DOL piece.
SS coupling with key.
CI Suction piece.
GM sand guard.
S & F in replacement submersible cable flat 6 Sqmm 3 core for bore well of any depth with fitting and connections complete all as specified and as directed.
Material and labour for dismantling the centrifugal/booster pump set and motor capacity of 5 HP to 25 HP from the foundation after disconnection of water and electric connection, transporting the pump to the workshop for replacement of unserviceable/worn out parts and reassembling same and the pump motor fixing on the foundation making proper allignment of pump set and motor making water and electric connection testing, commissioning with two coats of suitable painting complete to the entire satisfaction of Engr-in-charge . Note:- All spare parts as required for repair/overhauling shall be measured and paid separately under relevant item of Schedule 'A' and the spares should be suitable to as per above existing model & make.
M & L for openinng the centrifugal pump set of capacity 5.00 to 25 HP including taking down/out the burnt winding wire cleaning the slots,rewinding the motor with super enamelled copper winding wire of existing gauge,weight etc,repairing the same by replacing the unserviceable parts including machine/lathe work and re- assembling the pumpset in original position with required insulating material to make it fully functional complete all as specified and as directed.
Supply only the following spares of centrifugal /booster pumping set of capacity up to 25 HP complete all as specified and directed.
Bush complete all as specified and directed.
Bearing
Brass Impeller
Glands packing complete all as specified and directed.
Alignment of motor shaft including Lathe work complete all as specified and directed.
Alignment of motor shaft including Lathe work complete all as specified and directed.
Pump & motor connector coupling as per existing complete all as specified and directed.
M&L for cleaning of semi under ground sump of storage capacity of water up to 100000 gallons thoroughly by removing mud, dirt etc. from the sump by the following method complete all as specified and directed:- (a) Cleaning inner surface of the tank by scraping with steel wire brushes and removing mud and sludge collected in and outside of the tank and removing sludge to a distance not exceeding 50 meter. (b) Washing with clean water thoroughly complete tank internally and finally cleaning with bleaching powder. (c) writing date of cleaning on the sump.
M&L for cleaning of semi under ground sump of storage capacity of water up to 30000 gallons thoroughly by removing mud, dirt etc. from the sump by the following method complete all as specified and directed:- (a) Cleaning inner surface of the tank by scraping with steel wire brushes and removing mud and sludge collected in and outside of the tank and removing sludge to a distance not exceeding 50 meter. (b) Washing with clean water thoroughly complete tank internally and finally cleaning with bleaching powder. (c) writing date of cleaning on the sump.
Taking out old UNSV cable and supply & laying underground cable in trenches/existing cable duct/ cable tray, PVC heavy duty electric cable with copper conductor sizes of 25 sqmm single core confirming to IS : 7098 (Pt-I) 1988 and copper lugs for connecting cable at end of motor & starter complete all as indicated and as directed.
Supply and laying underground cable in trenches/existing cable duct/ cable tray, PVC heavy duty electric cable with copper conductor sizes of 16 sqmm single core confirming to IS : 7098 (Pt-I) 1988 and copper lugs for connecting cable at end of motor & starter complete all as indicated and as directed.
Supply & laying in replacement of GI perforated cable tray 1 mm thick and size of 100 x 75 x 10 mm for PVC heavy duty electric cable with copper conductor from motor to starter complete all as indicated and as directed. Note: The cost for fixing of cable tray to supporting nut bolts, hanger rods, MS angles, sendering & welding work etc as per site requirement is including in the quoted rate.
S&F in replacement of fully automatic star delta starter with sheet metal encloser ML-2 with relay range 20-32 Amp suitable for 25 HP centrifugal pump complete all as specified and asdirected.
S&F in replacement of fully automatic star delta starter with sheet metal encloser ML-1 with relay range 10-16 Amp suitable for 15 HP centrifugal pump complete all as specified and asdirected.
S&F in replacement of fully automatic star delta starter with sheet metal encloser ML-1 with relay range 9-14 Amp suitable for 10.5 HP centrifugal pump complete all as specified and asdirected.
S & F in replacement of old unserviceable overload relay MN 4-6/ MN 6-10 /MN 9-14 Amps and connected internal wiring complete all as specified and asdirected. Note:- The rate is inclusive of connection out the starter before replacement of overload relay and make the connection after replacement of overload realy.
S & F in replacement of old unserviceable overload relay MN 20-32 Amps and connected internal wiring complete all as specified and as directed. Note:- The rate is inclusive of connection out the starter before replacement of relay and make the connection after replacement of realy.
S & F in replacement of old unserviceable contactor MNX 18 Amps and connected internal wiring complete all as specified and as directed. Note:- The rate is inclusive of connection out the starter before replacement of contactor and make the connection after replacement of contactor.
S & F in replacement of old unserviceable contactor MNX 25 Amps and connected internal wiring complete all as specified and as directed. Note:- The rate is inclusive of connection out the starter before replacement of contactor and make the connection after replacement of contactor.
S & F in replacement of old unserviceable contactor MNX 32 Amps and connected internal wiring complete all as specified and as directed. Note:- The rate is inclusive of connection out the starter before replacement of contactor and make the connection after replacement of contactor.
S & F in replacement of old unserviceable contactor MNX 40 Amps and connected internal wiring complete all as specified and asdirected. Note:- The rate is inclusive of connection out the starter before replacement of contactor and make the connection after replacement of contactor.
S & F in replacement of old unserviceable single phase preventor and connected internal wiring suitable for 10 HP motor starter complete all as specified and as directed. Note:- The rate is inclusive of connection out the starter before replacement of single phase preventorr and make the connection after replacement of single phase preventor.
S & F in replacement of old unserviceable single phase preventor and connected internal wiring suitable for 15 HP motor starter complete all as specified and asdirected. Note:- The rate is inclusive of connection out the starter before replacement of single phase preventorr and make the connection after replacement of single phase preventor.
S & F in replacement of old unserviceable phase sequence corrector relay 440V , 50 HZ Supply suitable for 15 HP motor starter and connected internal wiring complete all as specified and as directed. Note:- The rate is inclusive of connection out the starter before replacement of phase sequencer and make the connection after replacement of phase sequencer.
S & F in replacement of old unserviceable phase sequence corrector relay 440 Volts, 50 HZ suitable for 10 HP motor starter and connected internal wiring complete all as specified and as directed. Note:- The rate is inclusive of connection out the starter before replacement of phase sequencer and make the connection after replacement of phase sequencer.
S & F in replacement of old unserviceable phase sequence corrector relay 440 Volts, 50HZ suitable for 7.5 HP motor starter and connected internal wiring complete all as specified and as directed. Note:- The rate is inclusive of connection out the starter before replacement of phase sequencer and make the connection after replacement of phase sequencer.
S & F in replacement of old unserviceabel digital voltmeter of range 0-500 volts and connected internal wiring suitable for submersible/ booster/ sewage motor starter complete all as specified and as directed.
S & F in replacement of old unserviceabel digital Ammeter of range 0-100 Amps and connected internal wiring suitable for submersible/booster/ sewage motor starter complete all as specified and as directed.
S & F in replacement of old unserviceable indication lamp in R,Y,B colour and connected internal wiringin for motor starter complete all as specified and as directed.
S & F in replacement of old unserviceable Rotary switch and connected internal wiring for motor starter complete all as specified and as directed.
S & F in replacement of old unserviceable push button and connected internal wiring for motor starter complete all as specified and as directed.
Material and labour for fixing of water pressure gauge (0-5 Kg/cm square) 100mm dial size including boring, threading, welding in CI/DI/GI of any sizes and connected with suitable size of U type MS/CP pipe with ON OFF cock complete all as specified and as directed.
Material and labour for PCC (1:3:6) type C-2 (using 40 mm graded stone aggregate) as in foundation of brick pillar to support the pipe line including demolition of old PCC and removing the debris from site complete all as specified and as directed.
Material and labour for Brick work with sub class 'B' bricks straight or curved on plan exc. 6M mean radius built in CM (1:4) as in brick pillar of required size and shape to support the pipe line including demolition of old brickwork & removing from site complete all as specified and as directed.
Material and labour for rendering 10 mm thick with cement mortar (1:6) on fair faces of brick work / concrete surfaces, finished the surface even and fair complete all as specified and as directed.
M&L for spray painting (including bringing compressor of suitable size at site) old painted steel or iron surface of (12.5 to 35 KVA) DG set complete with engine, alternator, radiator, exhaust hood and other satandard fittings & attachments (excluding diesel tank) as per existing colour scheme and pattern with atleast one coats of synthetic enameled paint after duly preparing the surface by cleaning with scrapers and emrey paper to the entire satisfaction of Engr-in-charge all as specified.
M & L for spray painting (including bringing compressor of suitable size at site) old painted steel or iron surface of centrifugal pumping set 5 to 25 HP complete with motor, pump, base frame and other satandard fittings & attachments as per existing colour scheme and pattern with atleast one coats of synthetic enameled paint after duly preparing the surface by cleaning with scrapers and emrey paper to the entire satisfaction of Engr-in-charge all as specified.
M&L for Servicing of DG set upto 35 KVA of any make at Khanpur Army camp by taking out U/S spares, Cleaning by brushing to remove dust including cleaning of filter,Checking of all nuts, bolts tightening whereever necessary, check up engine oil level, coolant level and Labour for top up if necessary, adjustment belt tension,Tuning of engine, adjustment of speed, alternator voltage, frequency etc greasing oiling and checking For smooth functioning of DG Set. Note :- 1. Any spares,Engine oil,coolant,unserviceable spares required to be replaced shall be measured paid for separately under respective items. 2. Minor spares like nuts,bolts etc cost up to Rs 200 shall be included in the rate quoted above
M&L for "B" Check DG set upto 35 KVA of any make at Khanpur Army camp by taking out U/S spares, Cleaning by brushing to remove dust including labour for Changing engine oil, coolant etc to max level, adjustment belt tension,Tuning of engine, adjustment of speed, alternator voltage, frequency etc greasing oiling and checking For smooth functioning of DG Set. Note :- Any spares,Engine oil,coolant,unserviceable spares required to be replaced shall be measured and paid separately under respective items .
M &L in replacement of oil filter set for 20 to 35 KVA DG set complete all as specified and directed.
M &L in replacement starter key switch for 20 to 35 KVA DG set complete all as specified and directed.
M &L in replacement of Battery Terminal made of brass nut & bolt complete all as specified and directed.
Repair and calibration to fuel injection pump & nozzle for 20 to 35 KVA DG set complete all as specified and directed.
M &L in replacement of fuel filter set for 20 to 35 KVA complete all as specified and directed.
M &L in replacement of pipe (Fuel line) set for 20 to 35 KVA complete all as specified and directed.
M &L in replacement of radiator hose pipe set for 20 to 35 KVA complete all as specified and directed.
M&L in replacement engine oil as per manufacturers suggested grade complete all as specified and directed.
M&L for Topping up of coolant complete all as specified and directed.
Supply and fixing in replacement of temperature gauge for DG Set make: (As per sample) all as specified and directed.
S&F in replacement Off load Changeover Switch - AC 23 (side handle) in sheet enclosure, 415 Vac, 50 Hz. 4 pole 100 Amp/415 volts on load side handle operated type inclduing taking down old change over complete all as specified and as directed.
S&F in replacement of battery 120 Ah,12 Volts maintencance free including battery termail alongwith connectiing wire of suitable gauge upto 2 mtr length min as required on site complete all as specified and as directed.
Disconnecting, isolating, electrically unserviceable DOL starter 3 phase 440 volts of any make & type and taking down from wall/panel board of 5 to 7.5 HP pumps and keeping aside for disposal, complete all as specified and as directed.
Supply and fixing in replacement of DOLstarter to capacity of 5 HP to 7.5 HP submersible pump 3 Phase 415 volts, as per existing complete all as specified and as directed.
Disconnect and taking out old LT panel and Supply installation, commissioning and testing of LT panel, Outdoor type, floor mounted, weather vermin proof factory made, CPRI approved, facricated out of 3.15 mm thick mild steel sheet mounted, on frame of mild steel angle iron 40 mm x 40 mm x 6 mm, 45 cms above the ground level duly supported with mild steel angle iron 50 mm x 50 mm x 6 mm thick in PCC foundation (1:2:4), type B-I, using 20 mm graded crushed stone aggregate, LT panel shall be totally enclosed with front double door and rear opening with IP-54 protection as per IS/8623 duly powder coated for 433 volts, 3 phase, 4 wire having TPN copper bus bars suitable for 200 Amps load duly drilled holes for connections, RYB insulated with different colour code and sleeved insulators complete prewired and cable connection with copper conductor wire upto copper bus bars including all incoming and outgoing cable connection with suitable size of copper lugs/gland complete suitable for 2 Nosx 7.5 HP nonclog sewage submersible pump set complete al as specified and directed by Engr-in-Charge and also comprissing of following:- (Location Sewage Pump House No.1) (i) 01 No x MCCB 100 A 04 pole - 25 Ka, 01 Nos.(Incoming) (ii) 4 Pole copper bus bar suitable of capacity 200 A (RYB -set ) (iii) 3 x Nos Digital multifunctional meter showing Amp, Volt, power factor and KW reading (iv) 01 x set R-Y-B Neon indicator lamp panel mounting type (set of 03 ) (v) 01 x No Phase sequence correctner (vi) 02 x Nos DOL starter suitable for 7.5 HP. (vii) 03 x Nos MCCB 32 A 04 pole - 16 K, - 3 Nos (Outgoing) (viii) 01 No x on load change over switch range 63 Amps, 4 pole, 415 Volt. (ix) 03 Nos x CT 15 VA 200 / 05 Amp BAR primary type wound CL - 01
Disconnect and taking out old LT panel and Supply installation, commissioning and testing of LT panel, Outdoor type, floor mounted, weather vermin proof factory made, CPRI approved, facricated out of 3.15 mm thick mild steel sheet mounted, on frame of mild steel angle iron 40 mm x 40 mm x 6 mm, 45 cms above the ground level duly supported with mild steel angle iron 50 mm x 50 mm x 6 mm thick in PCC foundation (1:2:4), type B-I, using 20 mm graded crushed stone aggregate, LT panel shall be totally enclosed with front double door and rear opening with IP-54 protection as per IS/8623 duly powder coated for 433 volts, 3 phase, 4 wire having TPN copper bus bars suitable for 200 Amps load duly drilled holes for connections, RYB insulated with different colour code and sleeved insulators complete prewired and cable connection with copper conductor wire upto copper bus bars including all incoming and outgoing cable connection with suitable size of copper lugs/gland complete suitable for 1 No x 10 HP submersible pump set complete al as specified and directed by Engr-in-Charge and also comprissing of following:- ( Location: Dundhera Bore well No.03 & 04) (i) 01 No x MCCB 100 A 04 pole - 25 Ka, 01 Nos.(Incoming) (ii) 4 Pole copper bus bar suitable of capacity 200 A (RYB -set ) (iii) 2 x Nos Digital multifunctional meter showing Amp, Volt, power factor and KW reading. (iv) 01 x set R-Y-B Neon indicator lamp panel mounting type (set of 03 ) (v) 01 x No Phase sequence correctner (vi) 01 x Nos Star Delta starter suitable for 10 HP submersible pump set. (vii) 01 x Nos MCCB 63 A 04 pole - 16 Ka, - 3 Nos (Outgoing) (viii) 03 Nos x CT 15 VA 200 / 05 Amp BAR primary type wound CL - 01
Disconnect and taking out old LT panel and Supply installation, commissioning and testing of LT panel, Outdoor type, floor mounted, weather vermin proof factory made, CPRI approved, facricated out of 3.15 mm thick mild steel sheet mounted, on frame of mild steel angle iron 40 mm x 40 mm x 6 mm, 45 cms above the ground level duly supported with mild steel angle iron 50 mm x 50 mm x 6 mm thick in PCC foundation (1:2:4), type B-I, using 20 mm graded crushed stone aggregate, LT panel shall be totally enclosed with front double door and rear opening with IP-54 protection as per IS/8623 duly powder coated for 433 volts, 3 phase, 4 wire having TPN copper bus bars suitable for 200 Amps load duly drilled holes for connections, RYB insulated with different colour code and sleeved insulators complete prewired and cable connection with copper conductor wire upto copper bus bars including all incoming and outgoing cable connection with suitable size of copper lugs/gland complete suitable for 1 Nosx 5 HP submersible pump set complete al as specified and directed by Engr-in-Charge and also comprissing of following::- (Location: Manesar Bore Well No.1) (i) MCCB 63 A 04 pole - 25 Ka 01 Nos, 01 Nos.(Incoming) (ii) 4 Pole copper bus bar suitable of capacity 200 A (RYB -set ) (iii) 2 x Nos Digital multifunctional meter showing Amp, Volt, power fqactor and KW reading ( 02 Nos). (iv) 1 x set R-Y-B Neon indicator lamp panel mounting type (set of 03 ) (v) 1 x No Phase sequence correctner (vi) 1 x No DOL starter suitable for 5 HP. (vii) 01 x Nos MCCB 32 A 04 pole, 16 Ka, - 3 Nos (Outgoing) (viii) 03 Nos x CT 15 VA 200 / 05 Amp BAR primary type wound CL - 01
M&L filling of dry sand under and around LT cable to provide sand cushioing and in sub stn ducts/trenches complete all as directed.
M&L for brick well burnt locally available sub class 'B' laid over sand cushioning to cable in trenches keeping width of brick parallel to the length of cable complete all as specified and directed.
Taking out old UNSV and supply, laying, jointing and testing of XLPE insulated, armoured, heavy duty LT under ground cable 1100 Volts grade with aluminium conductor laid in trenches, on poles, through pipes, fixed to walls etc cross sectional area for 25 Sqmm 3.5 Core, complete, all as specified and directed.
All as per serial iten No. 136.00 here-in-before but 10 Sqmm 2 Core.
All as per serial iten No. 136.00 here-in-before but 10 Sqmm 4 Core.
All as per serial iten No. 136.00 here-in-before but 25 Sqmm 3.5 Core.
All as per serial iten No. 136.00 here-in-before but 35 Sqmm 3.5 Core.
All as per serial iten No. 136.00 here-in-before but 50 Sqmm 3.5 Core.
All as per serial iten No. 136.00 here-in-before but 70 Sqmm 3.5 Core.
S & F in replacement of MS angles,cross arm, bracings, supports, clamps and back plate fabricated from structural steel section, including nut , bolts , washers, welding , bendings cold or hot, drilling hole for both in any shape or size as indicated or directed and inclusive of one prime coat, one under coat and one finishing coat of paint incl taking down the old unserviceable cross arms complete all as directed. Note: welding, cendring, painting as per site requirement is deemed in this quoted rate.
M & L for construction of Brick Masonry valve chamber of size 600x600x600mm (Internal dimensions) with PCC 1:4:8 foundation 150mm thick, brick work built in CM 1:6, PCC 1:3:6 coping 50mm thick, plastering 15mm thick in CM 1:6 to all internal and exposed surfaces including excavation earthwork in hard/dense soil, MS sheet cover 4mm thick and MS equal angle iron 50mmx50mmx6mm frame as per existing size with locking arrangement embedded in PCC suitable for 25/40/50mm gate valve and painting to MS cover with two coats of synthetic enamel paint over one coat of red oxide primer etc complete all per ground requirement including dismantling old/damaged valve pits.
All as per serial iten No. 144.00 here-in-before but size of 900x900x900mm (Internal dimensions).
M & L for Cutting out the burnt out cable end and reconnecting with providing new lugs,tapes etc for cable size 25 sqmm 3.5 core to 50 sqmm 3.5 core complete all as specified and directed.
M & L for Cutting out the burnt out cable end and reconnecting with providing new lugs,tapes etc for cable size 75 sqmm 3.5 core to 120 sqmm 3.5 core complete all as specified and directed.
M&L for replacement of connection junction box made out of 1.6mm thick MS sheet front openable, weather & vermin proof incl painting two coats of synthetic enamels paint over coat of red oxide primer. Connection box shall be suitable for housing & incl AI bus bar 25 Amps Cap 2 Nos. MCB SP6 Amps-01 No and having provision of cable hole in bottom for two to three cables of size 10 Sqmm 2 core armoured cable connection boxshall be fitted on street light pole and fixing arrangements i.e MS clamps etc deemed to be provided by the contractor, size of box 300x150x100mm
Supply and fixing in replacement of moulded case circuit breaker Four pole 160 Amps 25 KA capacity 415V 50Hz with adjustable thermal and fixed magnetic relay incl taking out the old unserviceable complete all as specified and as directed.
All as per serial iten No. 150.00 here-in-before but 125 Amps.
All as per serial iten No. 150.00 here-in-before but 100 Amps.
All as per serial iten No. 150.00 here-in-before but 63 Amps.
S&F in repair 60 watt street light (Building security light) LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP-66,IK-10, CRI >80, under voltage and over voltage protection, EMI-EMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90C), complete all as specified and as directed.
S&F in repair 70/72 watt street light (Building security light) LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP-66,IK-10, CRI >80, under voltage and over voltage protection, EMI-EMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90C), complete all as specified and as directed.
Supply and fix in repair of GI pipe's bracket suitable for fixing of bldg security LED light fitting of 45 Watts including grouting and fixing the same on wall for installation of light fitting with necessary clamps, nut, bolts & washer and painting by synthetic enameled good quality paint in white/grey colour over one coat of red oxide primer until unless smoothness of bracket complete all as specified and as directed. Note :- GI pipe should be 25 mm bore with medium grade and the same to be moulded in 45 degree angle at the 1m height to fix the street/ building security light fitting.
S&F in replacement of rotational moulded polyethylene HDPE water storage tank of capacity 500 ltr (Cylendrical, vertical with closed top with double layer conf to IS-12701-96 complete including provision of all inlet,outlet,overflow and drain pipe fitting complete all as directed.
All as per item No 157.00 here-in-before but capacity 1000 ltr.
Taking out old unsv exsting centrifugal pump set and depost to EM store yard and Supply, install, commissioning of centrifugal monoblock pump set electric driven, 3 Ph, 415 Volt, 50 Hz of motor capacity 15 KW/20 HP, Frame No ND160L, Pump capacity 90 Cum/Hr, Head: 34 Mtrs, RPM 1465 Model as per existing Make : Wilo/ Kirloskar or equavalent inclusive of providing PCC foundation, suction & discharge flanged type MS pipe heavy grade as per OEM from UG Sump to pump and pump to header, foot avlve, NRV,sluice valve framed structure, etc complete all as directed by EIC Note:- (i) The cost of material i.e sluice valves, NRVs, rubber gasket, flanges, iron angles, PCC & Brick work, MS coloumn pipe, cable shall be measured and paid separately in relevant Sch 'A' items. (ii) The cost of materials i.e welding, shundring, painting & testing are deemed in this quoted rate.
Disconnect and taking out old LT panel and Supply installation, commissioning and testing of LT panel, Indoor type, floor mounted, weather vermin proof factory made, CPRI approved, facricated out of 3.15 mm thick mild steel sheet mounted, on frame of mild steel angle iron 40 mm x 40 mm x 6 mm, 45 cms above the ground level duly supported with mild steel angle iron 50 mm x 50 mm x 6 mm thick in PCC foundation (1:2:4), type B-I, using 20 mm graded crushed stone aggregate, LT panel shall be totally enclosed with front double door and rear opening with IP-54 protection as per IS/8623 duly powder coated for 433 volts, 3 phase, 4 wire having TPN copper bus bars suitable for 200 Amps load duly drilled holes for connections, RYB insulated with different colour code and sleeved insulators complete prewired and cable connection with copper conductor wire upto copper bus bars including all incoming and outgoing cable connection with suitable size of copper lugs/gland complete suitable for 2 Nosx 7.5 HP centrifugal pump set complete al as specified and directed by Engr-in-Charge and also comprissing of following:- (Location: Manesar Booster Pump House) (i) MCCB 100 A 04 pole - 25 Ka 01 No (Incoming) (ii) 4 Pole copper bus bar suitable of capacity 200 A (RYB -set ) (iii) 2 x Nos Digital multifunctional meter showing Amp, Volt, power factor and KW reading ( 02 Nos). (iv) 1 x set R-Y-B Neon indicator lamp panel mounting type (set of 03 ) (v) 1 x No Phase sequence correctner (vi) 2 x No DOL starter suitable for 7.5 HP. (vii) 02 x Nos MCCB 63 A 04 pole - 16 Ka, - 3 Nos (Outgoing) (viii) 01 No x on load change over switch range 63 Amps, 4 pole, 415 Volt. (ix) 03 Nos x CT 15 VA 200 / 05 Amp BAR primary type wound CL - 01
Taking out old unserviceable PVC cables and supply and fixing of FR PVC round sheathed alluminium conductor (flexible) industrial cable,1100 Volts confirm to IS 694 fixing/ laying on poles, through pipes, fixed to walls etc cross sectional area of 1.5 Sqmm 2 Core, complete all as specified and directed.
All as per srl item No.161.00 here-in-before but 2.5 Sqmm 2 Core.
All as per srl item No.161.00 here-in-before but 4 Sqmm 2 Core.
All as per srl item No.161.00 here-in-before but 6 Sqmm 2 Core.
All as per srl item No.161.00 here-in-before but 10 Sqmm 2 Core.
Taking out old unserviceable PVC conduit of any size from poles/wall/surface etc and supply and fixing of PVC conduit of min 20 mm dia medium grade as per IS with connected supporting brackets/clamps for fixing/ laying on poles, floor, wall suitable with existing fixtures etc complete all as specified and as directed.
M&L for making MS pipe header as per site requirement i.e1 x Nos of 150/200 mm dia pipe length 3 - 4 mtr for main line, 3 x Nos of 80/100 mm dia pipe length 4-6 mtr for incoming to main line, 3 x Nos of 80/100 mm dia pipe length 1.5-2.5 mtr for outgoing/distribution line, fixing of sluice valves, NRVs, water meters, pressure guage, priming line 20 mm from over head tank to pumps etc, complete required welding, shundreng, where ever required to shape in existing position vertical/horizontal, connecting flanged end, gaskets in length of 3 mtr/6 mtr, MS pipe heavy duty, supporting PCC/Brick work and painting of two coats red oxide, one coat synthetic enamel paint blue colour and testing after connecting complete all as directedon by inserting of new tees, branches etc complete all as specified and directed by Engr-in-Charge. Note : - (i) The cost of material i.e sluice valves, NRVs, water meters, pressure guage,rubber gasket, flanges, iron angles, PCC & Brick work shall be measured and paid separately in relevant Sch 'A' items. (ii) The cost of materials i.e MS pipe of relevant size, welding, shundring, painting & testing are deemed in this quoted rate.
Supply only chloroscope for water testing range of 0.1 ppm to 2.0 ppm complete all as specified and as directed.
Supply only ORTO-TOLUDINE regent solution in 500 ml bottle complete all as specified and as directed.
Supply only ALTOCH-GP high strength calcium based granular disinfectant for chlorination of water complete all as specified and as directed.
Supply & fixing first Aid kit (PVC container) No-3 as per the specification including first aid medical treatment materials complete all as specified and as directed.
M&L for replacement lead pig/wool, complete all as specified and as directed.
M&L for replacement spurn Yarn, complete all as specified and as directed.
Supply and fixing in replacement Nuts, Bolts and Washers 25 to 150 mm long of 6 to 20 mm dia, complete all as specified and as directed.
Supply and fixing in replacement 3mm thick rubber gasket, complete all as specified and as directed.
Supply and fix in replacement Bib tap of 15 mm dia chromium plated with fency type suitable to fix with iron pipe or furrel complete ll as specified and as directed.
Supply and fix in replacement PVC float valve, high pressure, with polythene float and flynut complete, screwed for iron/PPR pipe of size 20 mm bore complete ll as specified and as directed.
Supply and fix in replacement PVC float valve, high pressure, with polythene float and flynut complete, screwed for iron/PPR pipe of size 25 mm bore .complete ll as specified and as directed.
M&L for Preventive maintenance of electric motor driven Chlorine dosing system any make including cleaning of electrode rode , HDPE/FRP tank of capacity up to 100 Ltr tank and checking functioality and performance of level gauge , dosing pump , High pressure single head motor ,pressure gauge, power pack incl oiling and greasing of all moving partscomplete all as specified and as directed.Note : Old unserviceable Spare parts required to be replaced for smooth functioning of work shall be measured & paid separately under respective items here-in-after as supply only.
Supply only of following spare parts for hypodosing system of dosing rate upto 2.88Ltr/Hr at 08 Bar and of power supply 230V, 50Hz , 12W complete all as specified and as directed.
Antisyphon Valves complete with ball, seal & spring
Ball (PTFE)
Back spring (Large)
Back spring (small)
Cable groumet
Foot valve assembly complete with ball seal & spring
Head (PP/PVC)
Pipe (Discharge/ suction)
FRP Tank 100 Ltr
M&L for Comprehensive, preventive and periodical maintenance of RO Plant (01 Nos) of capacity 1000 LPH Make: AQUAFRESH installed at Dundahera Mil station in reliable, safe and efficient manner by regular examining, lubricating and adjusting the mechanical and electrical driving equipment including repacement of defective / spares parts as "Supply only" and testing on completion to the entire satisfaction of Engr-in-charge complete all as specified and as directed. Note: (i) Spare parts will be measured & paid separately. (ii) All the complaints will be rectified within 24 hrs from the time of receipt of complaint. If contractor fails to rectify the complaint within 24 hrs from the time of receipt of complaint, the compensation / penalty of Rs 500.00 per complaint per day shall be recovered from the contractor's dues.
Removing the existing media and supply and filling of dual media of same size as removed for DMF of RO plant at Dundahera Army camp without damaging the plant, pipelines and other accessories and leading the removed media upto 2km complete all as specified and as directed.
Removing the existing media and supply and filling of carbon media for activated carbon filter of RO plant at Dundahera Army camp without damaging the plant, pipelines and other accessories and leading the removed media upto 2km complete all as specified and as directed.
Supply only in repair micron filter (1000 LPH/20 inch) to remove particle up to 20 micron and reduce silt density index further to acceptable levels complete all as specified and as directed.
Supply only in repair reverse osmosis membrane system (brackish water) to remove major part of TDS (85 - 95%) with sundry fitting, arrangement & skid to meet adequate permate of minimum 50% recovery complete all as specified and as directed.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.76 MB
BOQ_838480.xls
BOQ • 1.85 MB
Sch_of_Credit_DS-103.pdf
Additional Documents • 0.25 MB
Tender_103.pdf
Tender Documents • 1.10 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .