Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹60.9 LAccepted-AOC 70 VARDHMAN NAGAR A P O SHYAM NAGAR AJMER ROAD JAIPUR PIN 342019 | JAIPUR | 342019 | L1 | Accepted-AOC LOWEST AND REASONABLE | |
| 2 | L2₹62.7 L+₹1.9 L (3.07%)Rejected-Finance | L2 | Rejected-Finance NOT LOWEST |
Tender Value
Refer Docs
EMD Value
₹1.1 L
Closing Date
9 Feb 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE JAIPUR
HQ CWE JAIPUR
UPGRADATION OF ELECTRICAL SYSTEM AT SEWAR FORT AT BHARATPUR MIL STN
2020_MES_402421_2
CWE/82024/BPR/E8
Open Tender
Miscellaneous Works
Item Rate
270 days
BHARATPUR
please refer tender documents
5 documents required · 5 mandatory
₹1,000
Yes
GE BHARATPUR
₹1.1 L
Yes
13 Mar 2021
12 Jan 2021
11 Feb 2021
12 Jan 2021
9 Feb 2021
25 Jan 2021
60 days
Amount
SUB STATION BLDG
Surface excavation not exceeding 30 cm deep and averaging 15 cm deep and getting out in soft/loose soil etc complete all as specified and directed.
Excavating in trenches not exceeding1.5 metre wide and not exceeding 1.5 metre in depth for foundation etc or for shafts, wells, cess pits, manholes, pier holes, laying cables erection of poles / struts/stays etc not exceeding 10 Sqm on plan not exceeding 1.5 metre in depth and getting out in soft / loose soil.
Excavating in trenches not exceeding1.5 metre wide and not exceeding 3 metre in depth for foundation etc or for shafts, wells, cess pits, manholes, pier holes, laying cables erection of poles / struts/stays etc not exceeding 10 Sqm on plan not exceeding 1.5 metre in depth and getting out in soft / loose soil.
Removing of excavated material (soil) to a distance not exceeding 50 metres and depositing where directed at a level not exceeding 1.50metre above the starting point.
Returning, filling in including spreading, labelling, watering and well ramming in layers not exceeding 25 cm thick etc complete all as specified and directed.
Sand filling under floors or in foundations including watering and consolidation except sand etc complete all as specified and directed.
M&L hardcore of broken stone or boulders gauge not exceeding 63 mm, deposited, spread and levelled in layers not exceeding 15 cm thick, watered and rammed to a true surface with material and labour etc complete all as specified and directed.
M&L treating the top surface of filled earth at the rate of 5 litres of emulsion per square metre of surface etc complete all as specified and directed.
M&L treating the soil under plinth protection at the rate 5 litres of emulsion per square metre of surface area etc complete all as specified and directed.
M&L anti-termite treatment along the external wall below concrete or masonry apron using chemical emulsion 2.25 litres per linear metre including drilling and plugging holes etc. in apron etc complete all as specified and directed.
M&L cement concrete in foundations, filling and mass concrete type D2, (1:4:8) using 40 mm graded aggregate etc complete all as specified and directed.
M&L reinforced cement concrete M-25 using 20 mm graded stone aggregate in foundations, including rafts, footings, foundation beams; plinth beams; bases for columns, etc.; basement slabs, under-reamed piles and mass concrete etc complete all as specified & directed.
M&L reinforced cement concrete M-25 using 20 mm graded stone aggregate in Columns, pillars, piers, posts and struts and the like etc complete all as specified & directed.
M&L reinforced cement concrete M-25 using 20 mm graded stone aggregate Beams, cantilevers, bressummers, lintels over 1.5m span etc complete all as specified & directed.
M&L reinforced cement concrete M-25 using 20 mm graded stone aggregate in slabs supported on walls, beams and columns in floors, roofs, landings, balconies, canopies, deck slabs and in shelves etc complete all as specified & directed.
M&L formwork to sides of concrete foundation, footings, bases of columns, raft and raft beams, sides and soffits (if any) of foundation and plinth beams; and similar work; vertical or to batter rough finished surface of concrete flat etc complete all as specified & directed.
M&L formwork to sides of pillars, posts, structs, piers, columns and stanchions rough finished surface of concrete Square, rectangular or polygonal etc complete all as specified & directed.
M&L formwork to sides and soffits of floor or roof beams, beam haunchings, girders, bressummers, lintels, cantilivers, shelves including supports, overhangs, etc. also splays between floors and beams, etc. rough finished surface of concrete flat etc complete all as specified & directed.
M&L formwork to soffits of suspended slabs such as roof slabs, floor slabs, landings and similar work not exceeding 200mm th (Horizontal or sloping) Rough finished surface of concrete flat. etc complete all as specified & directed.
M&L TMT bars 10mm dia and over cut to length bent to shape required including cranking bending spirally for hooping for columns hooking ends and binding with mild steel wire (annealed) not less than 0.9mm dia or securing with clips etc complete all as per specified and directed.
M&L TMT bars 6mm to 8mm dia and over cut to length bent to shape required including cranking bending spirally for hooping for columns hooking ends and binding with mild steel wire (annealed) not less than 0.9mm dia or securing with clips etc complete all as per specified and directed.
M&L TMT bars mild steel bars 5mm dia and over upto and including 10mm dia cut to length bent to shape required including cracking, bending in stirrups, spacers and binders and binding with mild steel wire (annealed) not less than 0.9 mm dia or securing with clips etc complete all as specified & directed.
M&L for Brick work sub class B bricks straight or curved on plan exceeding 6 mtr mean radius built in cement mortar (1:6) etc complete all as specified and directed.
S&F steel window with side hung shutters factory made including projecting type hinges with steel handle and steel peg stay complete with glazing bars dovetailed or welded including one shop coat of zinc chrome primer etc complete all as specified and directed. (Note: Mild steel wire cloth shall be measured and paid separately under respective items)
S&F steel window with side hung shutters factory made including projecting type hinges with steel handle and steel peg stay complete without glazing bars dovetailed or welded including one shop coat of zinc chrome primer etc complete all as specified and directed. (Note: Mild steel wire cloth shall be measured and paid separately under respective items)
S&F factory made steel ventilator with top hung shutter including hinges, steel peg stay and handle including one shop coat of zinc chrome primer complete all as specified & directed.
S&F 3mm thickness sheet glass, ordinary quality and glazing with oil putty in square not exceeding 0.5sq.m in each pane etc complete all as specified and directed.
S&F galvanised mild steel wire cloth, 0.56mm nominal dia of wire and average width of aperture 1.18mm and fixed with tinned tacks, or galvanised wire staples etc complete all as specified and directed.
M&L 50mm thick plain cement concrete type C-1 (1:3:6) using 20mm graded stone aggregates as in plinth protections etc complete all as per specified and directed.
S&F Steel rolling shutters ( thickness of laths 1.25 mm), without ball bearing, as specified including top cover, anchoring rod, hasp and staple and one shop coat of primer ; erected in position as indicated, complete ; push pull or manual type etc complete all as per specified and directed.
S&F Flat Iron at junction of wall and columns etc complete all as per specified and directed.
M&L for rendering 15 mm thick in CM (1:6) on brickwork or concrete surfaces as in internal surfaces finished even and smooth without using extra cement complete all as specified and directed.
M&L for rendering 5 mm thick in CM (1:4) using WPC over 10mm thick in CM (1:6) plaster on brickwork or concrete surfaces as in external surfaces finished even and smooth without using extra cement complete all as specified and directed.
Supply only Integral water proofing compound.
M&L for rendering 5mm thick in CM (1:3) on ceiling/RCC facia including finished even & smooth without using extra cement complete all as specified and directed.
M&L preparing new plastered surfaces and applying three coats of white wash on ceiling etc. complete all as per specified and directed.
M&L for preparation of new plastered wall surfaces and applying two coat of oil emulsion distemper of any tint including providing 3mm wall care putty approved shade on walls by hand roller etc complete all as specified and directed.
M&L for preparation surfaces and applying two coats of cement base paint to external surfaces of walls etc complete all as specified and directed.
M&L for preparation surfaces and applying two coats of synthetic enamel paint over a coat of red oxide primer to steel surfaces etc complete all as specified and directed.
M&L providing and applying fibre reinforced elastomeric liquid water proofing membrane with resilient acrylic polymers having sun reflectivity index (SRI) of 105 on top of concrete roof in three coats @ 10.76 litre per 10 Sqm. One coat of self-priming of elastomeric waterproofing liquid (dilution with water in the ratio of 3:1) and two coats of undiluted elastomeric waterproofing liquid (dry film thickness of complete application/ system not less than 500 microns). The operation shall be carried out after scrapping and property cleaning the surface to remove loose particles with wire brushes, including providing screed bed or bedding layer 15mm thick in cement mortar 1:4 with WPC on roof surfaces finished even & smooth without using extra cement over cement slurry over existing roof @ 3Kg/Sqm etc complete in all respect as per the direction of Engineer-in-Charge. Note:- WPC shall be measured and paid separately.
M&L machine cut Kota stone slab flooring 20-25 mm thick as in cooking platform, treads of steps and similar works in single piece not exceeding 1.5m in length laid over 20 mm thick cement screed base laid in CM (1:6) and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete all as specified & as directed.
M&L 75mm thick cement concrete,(1:4:8) type D2 using 40 mm graded aggregate in subbase under floor over rammed earth etc complete all as specified and directed.
M&L machine cut 20-25 mm thick Kota stone on vertical surface of wall, riser, skirting, dedo and pillar over 15 mm thick laid in cement mortar (1:4) and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete all as specified & as directed.
M&L providing precast cement concrete type B1 (1:2:4) using 20mm graded stone aggregate in landings cover slabs (for manholes etc.) chullah, hoods, chajjas, water troughs mangers, shelves and similar articles with plain faces except blocks or slabs set in cement mortar (1:4) etc complete all as specified and directed.
S&F rolled mild steel in plates ( Plain or chequered ) channels, square cut or notched (ordinary and counter sunk ) forming holes, without any attachment rolled mild steel Fe - 410-W (Gde-E-250) quality "B" etc complete all as specified and directed.
S&F in repair PVC (SWR) pipes single socketed, in any length with rubber ring joints, fixed to walls, type 'B', ISI marked of 110mm bore etc complete all as specified and directed.
S&F 110mm bore PVC (SWR) pipes single socketed,in any length with rubber ring joints, laid in trenches or in floors etc complete all as specified and directed.
M&L 100 mm thick plain cement concrete type B-1 (1:2:4) using 20mm graded stone aggregates as in flooring, finished even and fair without using extra cement etc complete all as specified and directed.
M&L Glazed ceramic coloured tiles 350x250x7mm/ 450x300x7mm thick, on vertical surfaces such as skirting, dados and risers to steps ,wall etc set over 15 mm thick cement plaster in CM (1:4) and pointed in white or coloured cement to match the shade of tiles etc complete all as specified and directed.
M&L Non skid ceramic tiles (coloured) 7 to 8mm thick (squares/rectangular) area of each tile exceeding 0.06 sqm but not exceeding 0.11 sqm, in floors etc. set over 15mm thick screed in CM 1:6 and jointed in neat cement slurry and pointed in white or coloured cement to match etc complete all as specified and directed.
S&F capacity 500 Litres rotational moulded polyethylene water storage tanks double layered (cylindrical vertical with closed top) hoisted and fixed in position all as specified in SSR Part I including providing 20mm ball brass valve high pressure with polythene float and fly nut screwed for iron pipe or brass ferrule and making connection for inlet and outlet and fixed etc complete all as specified & directed.
S&F vitreous china squatting pan, `Orrisa' pattern, size 580 x440 mm white, with integral foot rests (excluding flushing cistern and flush pipe) including connection to trap and flushing pipe antisyphonage pipe etc complete all as specified & directed.
S&F PVC valve less syphonic action type flushing cistern 10 litres capacity, low level white with inlet ball valve float and handle including brackets and flush pipe of polyethylene of low or high density or PVC,32mm dia suitable for low level cistern etc complete all as specified & directed.
S&F swivel shower of PTMT any colour for fixing with 15mm pipe. (Minimum weight 40gms) etc complete all as specified & directed.
S&F for GI tubing medium grade with all fitting 15 mm bore fixed to wall or concealed or fitted to ceiling or laid under floor etc complete all as specified & directed.
S&F for GI tubing medium grade with all fitting 20 mm bore fixed to wall or concealed or fitted to ceiling or laid under floor etc complete all as specified & directed.
S&F of solid PVC door frame of size 50mmx47mm made out of 5mm plain colour PVC sheet reinforced with MS square tube, fixing in opening complete all as specified and directed.
S&F in the frames at site factory made solid panel PVC door shutter 30mm thick (style) consisting of frame made out of MS tubes for top & bottom rails. MS frame shall be covered with heat moulded plain colour PVC 'C' channel having a PVC sheet strip of 20mm width stuck inside with solvent cement for stiles and plain colour PVC sheets for top rail, lock rail & bottom rail on either side & as gap insert for top rail & bottom rail; Panelling of plain colour PVC sheet to be fitted in the M.S. frame welded/sealed to the stiles & rails with suitable PVC sheet beading, and joined together with solvent cement all as specified SSR 2010 (Part-II) and Particular specification.etc complete all as specified and directed.
S&F of 35 mm thick 2nd class hardwood (hollock) factory made plain framed, panelled shutters (two No. of panels) with lock rail and panel of 9mm BWP commercial ply or 12 mm veneered particle board with commercial veneering on both faces size of members as per IS 1003 Part-I, kiln seasoned and chemically pressure treated. The shutter shall be fitted to chowkhat as directed by Engineer-in-Charge.
S&F of 35 mm thick 2nd class hardwood (hollock) factory made glazed and skeleton shutters open rebated and prepared to receive glass, gauge etc (without sash bars), edges of framing plain, chamfered or rounded, fitted with cut and mitred beads for securing glass, gauge etc., sizes of members of shutters as specified in SSR Part-I, Section 8, clause 8.24(a) complete. The shutter shall be fitted to chowkhat as directed by Engineer-in-Charge.
S&F butt hinges of size 100mm medium weight cold rolled mild steel and fixed etc complete all as specified and directed.
S&F butt hinges of size 75mm medium weight cold rolled mild steel and fixed etc complete all as specified and directed.
S&F mild steel barrel tower bolts, stove enamelled black with bright bolt and fixed length of bolt 150mm etc complete all as specified and directed.
S&F mild steel pressed handles, ovel type, stove enamelled black and fixed size of handle 150mm etc complete all as specified and directed.
M&L mild steel sliding door length of bolt 300mm bolts, plate type, stove enamelled black with bright bolt not less than 12mm dia with and including a minimum of 6 bolts and nuts, four on bolt plate and two on staple plate and fixed etc complete all as specified and directed.
S&F 150mm extruded aluminium alloy handles, fabricated type, anodised and fixed etc complete all as specified and directed.
S&F aluminium, anodised, barrel tower bolts of extruded section and fixed length of bolt 150mm etc complete all as specified and directed.
S&F framed work such as grills, gratings, etc, with ends of bars shouldered and / or riveted, or forged into spikes ; framed guard bars ; barred iron doors ; ladders; framed balusters; walkways ; railings ; framework of water tanks and similar work conforming to Fe-290 Gde E-165.
S&F bib taps 15mm dia cast copper alloy with crutch or butterfly handle, screwed down, screwed for iron pipe or for brass ferrule and fixed etc complete all as specified & directed.
M&L preparing new or old untreated wooden surfaces of any description exceeding 10 cm width or girth and applying two coats of synthetic enamel paint over a coat of pink primer etc complete all as specified and directed.
M&L salt glazed stone ware drain pipes laid in trenches and jointed as specified; Internal diameter of pipe 150 mm etc complete all as specified and directed.
M&L for hume pipe septic tank for 10 users (horizontal type) by centrifugal process designed to carry sewage and sullage water, excavation in any type of soil, PCC type D2 (1:4:8) using 40mm graded aggregate below foundation vent shaft, connections etc complete all as specified and directed.
M&L for point wiring with 1100 volts grade PVC insulated FRLS multistranded copper conductor cable 1.5 Sq mm (Phase - Red, Neutral - Black) and earth continuity conductor 1.5 Sq mm (Green) drawn into and including concealed rigid non-metallic PVC conduit medium grade not less than 20 mm dia ISI marked ivory colour with all conduit fittings / fixing accessories and unwelded sunken galvanized pressed steel terminal boxes of thickness not less than 1.0 mm covered with 3 mm thick phenolic laminated white sheet cover for mounting switches, sockets, fan regulators as required for the following :-
(a) One light point controlled by one switch.
(b) One fan point controlled by one switch.
(c) One socket outlet 6 amp controlled by one switch on the same board with other switches.
(d) One socket outlet 6 amp controlled by one switch on independent board.
Ditto as per above item No 73 above but with multi stranded copper conductor cable 2.5 Sqmm size for 3 pin 16 Amps switch socket outlet on independent board including 2.5 Sqmm copper cable PVC insulated FRLS unsheathed copper continuous earth wire including connecting to common earth dolly.
S&F socket outlet 2 in 1, 3 pin 6 & 16 amp flush type multipurpose etc complete all as specified and directed.
S&F socket outlet 2 in 1, 2 & 3 pin, 6 amp, flush type multipurpose etc complete all as specified and directed.
S&F switch piano flush button single pole one way 6 Amp etc complete all as specified and directed.
S&F ceiling rose surface Bakelite 50X40mm three terminal ISI marked including suitable size of PVC board etc complete all as specified and directed.
S&F step type electronic fan regulator EME type 450 watts etc. complete all as specified and directed.
S&F MCB distribution board, powder coated, CRCA steel sheet, degree of protection IP 43, IK-09 with reversible double door, recess mounted, having insulated 200 Amps tinned copper bus bar, neutral bus bar, earth bar, din bar, detachable gland plate, interconnection, earthing connection, blanking plates in unused spaces as required for the SPN, 240 volts, 8 ways (Double door) etc. complete all as specified and directed
S&F MCBs of 'C' series having breaking capacity 10KA, ISI marked including required wiring connections with copper lugs of suitable size provided in MCB DBs as required for the following :-
(a) Isolator SP 10 to 40 Amps 240 Volts
(b) Isolator SPN 40 Amps 240 Volts
S&F Linear LED T8 tubular lamp of 20 watt with extruded aluminium body, PC diffuser and inbuilt driver with Batten suitable for LED T8 lamps, complete with all accessories internally pre-wired and including connecting to ceiling rose with three core flexible copper conductor cable of size 1Sqmm etc. complete all as specified and directed. Make: Crompton Cat Part No:LTT8-20+DMLN1LT8-16 or equivalent as mentioned in Appx ‘B’
S&F batten holder, insulated polycarbonate body with back plate including suitable size of PVC round block etc. complete all as specified and directed.
S&F in replacement ceiling fan of 1200 mm sweep with five star rating etc complete all as specified and directed. Make: Havells Efficiencia Neo (BLDC26W) or equivalent in Bajaj/ Crompton /Philips.
S&F in replacement exhaust fan of 380 mm, 1400 rpm with five star rating etc complete all as specified and directed. Make: Havells Cat No Turbo Force SP or equivalent in Bajaj/ Crompton /Philips.
Cutting chases pinning in making good to facings if required & pointing in CM 1:3 to ends or edges or edges of landings steps, cills, sunshades shelves and cutting chases for concealed water tubing or concealed conduit wiring, etc., and making good cutting not exceeding 10 cm girth in stone concrete block or slab wall. etc complete all as specified & directed.
Supply & fix 25 watts LED street light fittings new generation energy saving ,environmental friendly ,long life, versatile pressure die cast aluminium IP66 with 10KV surge protection road way, luminaire with high power LED as light source with warranty option of 5 years and suitable drivers etc and connecting with 4.0 sq.mm multistranded aluminium conductor PVC insulated twin core weather proof cable from fittings to overhead lines or to the junction box and fixing to complete all as specified and directed. Make :-Crompton Cat No LSTS-25-CDL-M or equivalent as mentioned in Appx ‘B’.
M&L for earthing with galvanized steel earth plate electrode 600mmx 600mmx6mm thick buried directly in ground (earth pit not less than 2.25 meter deep below normal ground level) with the top edge of the plate not less than 1.5m below normal ground level connected to galvanized earth lead wire 4mm dia by means of steel bolts, nuts, check nuts and washers all as shown in electrical plate No. 03 of SSR Part -I connected to earthing point and including 15mm bore light grade G.I. protection pipe (up to 7.5 meter from edge of the pit), PCC pit in mix 1:3:6 type C1 with PCC 1:2:4 type B-1, 40mm thick cover, watering arrangement with funnel and wire mesh and 20mm bore light grade G.I. watering pipe, common salt and charcoal filling, necessary excavation and earth work including testing on completion.
Supply & spread unwashed dry river sand for sand cushioning and covering the underground cable in trenches. Note: - Punning thickness shall be measured.
M&L brick protection cover to underground cable (with old size sub class 'B' bricks) with width equal to length of brick laid dry and flat abutting each other with gaps between adjacent brick not exceeding 10mm etc complete all as specified and directed.
EXTERNAL ELECTRIFICATION
Supply , install, testing and commissioning of indoor type HT vacuum circuit breakers panel having 2 No VCB's (1 No Incoming and one Out going VCBs) in single enclosure with side cable box for outgoing of each capacity 11 KV, Minimum 630 Amps, three Phase, 3 wire, 50 Hz, having 26.3 KA breaking capacity, all specified as per IEC 62271-100 & IEC 62271-200 totally enclosed single bus bar for each phase, floor mounting, metal clad, flush fronted, horizontal draw out type, horizontal. isolation type, Indoor extensible type, with Electrical and Mechanical interlock and automatic safety shutter gear including padlocking arrangement, isolation plugs, assembly of 3 vacuum interrupters, with epoxy support insulations and self - aligning finger type isolating contacts, truck having integral racking with necessary interlocks ( for insertion and withdrawal of VCB), manual and automatic motor charged independent closing/ tripping spring , trip free operating mechanism with closing and tripping push buttons and mechanical breaker , all standard fitting and accessories of following :-
SPECIFICATION FOR VCB:-
(a) Bus bar chamber with 3 phase copper bus bar 1000 Amps rating duly insulated - 01 Set ( set of three).
(b) Electrical trip coil 30 V DC /110V DC - 1 No
(c) Electrical shunt coil 30 V DC/110VDC - 01 No
(d) CT Chamber incorporating 3 Nos single phase resin cast current transformer ratio 200/100/5-5 class 1.0 for metering & class 5P10 for protection and burdon 15 VA , 11 KV, 25 KA for 1 sec - 1 No
(e) 3 Phase, 3 Limb draw out type bus connected Epoxy potential transformer, ratio 11KV/√3/110V/√3 AC accuracy 1.0, Burdon 50 VA - 01 No.
(f) Digital ammeter 0 to 200 Amp,( 100% of CT ratio)for 3 phase -01 No.
(g) Digital voltmeter rating 0 to 12 KV, for 3 phase - 01 No
(h) DIGITAL Load manager for amps, volts, KW, KVA, KVAR, and PF Make :Conserve EM 6400 or Make: Secure Ellite 443 - 01 No
(j)Three phase over current and earth fault digital numeric relay (over current (INST 50) & IDMT - 51 - 3 pole & earth fault (INST (50N) & INST (50N) & IDMT 51N - single pole) & negative sequence 46 auxiliary supply 20-110V AC/DC CT output contacts 2 Nos + NC, rating-5, O/C Is= 20-200% in step of 5% E/F Os=5-80% in step of 5%. with common port ,the features and specification confirming to Make: Model No. MI COM P 122 of AREVA or equivalent in ABB -REJ601/ Seimen 7SR10.
(k) Auxiliary relay with 6 N/O & 6 N/C of Make Alstom/ABB/L&T - 1No
(l) Master trip circuit of Make Alstom/ABB/L&T- 1No
(m) TNC switch and LR switch - 1No
(n) Heat control switch - 1 No
(o) RYB, ON/Off , spring charred and discharged & VCB trip indications- 1 set
(p) Space heater with thermo state & toggle switch - 1 No
(q) Operating counter - 1 No
(r) Rear and side cable box suitable for 95/ 120 Sq.mm 3 core XLPE cable
(s) Spring charging motor with starter 230V AC - 1 No
(t) Pluggable anti-pumping relay type CRM 4 with base- 1No
(u) Pluggable AC fail relay type CRM 4 with base -1 No
(v) Pluggable DC fail relay type CRM 4 with base -1 No
(w) CB contact multifunction relay type PSU14(52X) -1No
(x) 12W annunciator + hooter- 1 set
(y) Power pack 230V AC-110V DC
(z) Control MCB/ Fuse set - 1set
(aa) Panel illumination lamp with door limit switch - 1set
(ab) Push button for TCH - 1 No
(ac) 9 KV , 10 KA , surge arrestor - 1 set of three
(ad) Indicating lamp - 1 set
NOTES: - (i) VCB shall be extensible type. (ii)The contractor shall get the approval of GE for the make of the VCBs they plan to procure. (iii)Prior to manufacturing the general arrangement drawing design details of the VCB panel shall be got approved by GE. (iv) Electrical shunt coil 30 V DC/110VDC – 01 No (v) Erections commissioning and civil work (Plinth protection) with PCC /Brick work for installation of VCB is deemed to be included with unit rate. The plinth protection details as per the manufacturer instructions.
Supply, laying, testing and commissioning of cable XLPE insulated (Earthed), screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts grade, of size 3 core 95 sq mm Note:- Earth work, sand cushioning and brick protection shall be measured and paid separately.
Supply laying testing and commissioning of XLPE insulated LT U/G cable heavy duty , 1100 volts grade armoured and PVC sheathed with multistranded aluminium conductor laid in trenches or fixed on wall (including saddle clip) or poles drawn through pipes complete of following sizes:-
(a) 10 sq. mm 2 core
(b) 16 sq. mm 4 core
(c) 185 sq. mm 3.5 core
(d) 400 Sq. mm 3.5 core
Supply installed testing and commissioning outdoor type, Self standing made out of 3.15mm CRCA sheet duly power coated, double door, front and back openable, APFC panel compartmental type with APFC relay 8 stage with heavy duty MPP capacitor bank 200 KVAR (5 KVAR-1No, 10 KVAR-02 Nos, 25KVAR-01 No, 50 KVAR-03 Nos ) with thyrister control module and MCCB TP of 16 KA of 1.5 time of rating correct of capacitor suitable for each control and MCCB TP 400 Amp 35 KA as incomer including control CT & control wiring complete having following accessories including control wiring with HR FRLS copper wire complete all as specified and directed.
(i) Compact modular bolted design, removable side and back panels with option of top and bottom cable entry.
(ii) Capacitor installed in removable assemblies for ease of operation and maintenance.
(iii) Incoming of APFC panel of MCCB TPN 400 Amps, 35 KA breaking capacity with high electrolytic grade Aluminium bus bar iof suitable rating.
(iv) 200 KVAR (5 KVAR-1No, 10 KVAR-02 Nos, 25KVAR-01 No, 50 KVAR-03 Nos) with thyrister control module and MCCB TP of 16 KA of 1.5 time of rating current of each capacitor suitable for each control. ( each capacitor bank equipped with discharge resister) & 7% detuned harmonics filter reactor.
(v) High performance microprocessor based 3 phase APFC relay 8 stage with Auto/Manual Option.
(vi) In built 3 phase power analyzer , Amp meter, volt meter and PF meter (each have 1 No)
(vii) Capacitor duty contactors with high thermal current carrying capacity and early make contacts to reduce inrush current for enhancing life of capacitors.
(viii) Induced air system provided with axial flow fan/ centrifugal fan.
(ix) Bottom cable entry system available with front glass for viewing controller and analyzer from front
S&F 45 watts LED street light fittings new generation energy saving ,environmental friendly ,long life, versatile pressure die cast aluminium IP66 with 10KV surge protection road way, luminaire with high power LED as light source with warranty option of 5 years and suitable drivers etc and connecting with 2 x 1 sq mm multistranded PVC insulated copper conductor with PVC Conduit 20mm dia from fittings to the junction box and fixing etc complete all as specified and directed. Make :- Make of Crompton greaves Cat part No LSTP-45-CDL or equivalent as mentioned in Appx ‘B’.
Supply, install, test and commissioning factory made THERMOPLASTIC CABLE JUNCTION BOXES IP 66/67 “weather proof”, with terminals for outdoor installation (with knockouts for cable entry) of size 205 x 255 x 112 mm depth with cable entry size of 10-25 sqmm with terminal etc complete all as specified and directed. Make: Hansel Cat part No: KF 2525 G or equivalent make in Legrand/FIBOX(SOLID PC 2528 13G).
S&F street light GI bracket of 0.6 mtr long made out of 40mm dia light grade GI pipe bend to shape of 120 degree end welded at required including 02 Nos MS clamp of FL 40 x 6mm including nuts, fastner bolts & washers complete necessary fixing arrangements on wall as directed.
Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of 50 sqmm to 95 sqmm.
Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of 50 sqmm to 95 sqmm.
Supply, installation, testing & commissioning of transformer of capacity 250 KVA step down outdoor type copper wounded 11/0.433 KV (at no load) AC 3 phase 50HZ on secondary side double wound oil immersed naturally all air cooled (ONAN COOLED) with external cooling tubes /radiator, delta connected as on primary and star connected with natural brought on secondary) side and having tapping at (±) 2.5%,(±) 5% (±) 7.5% to be changed by hand operated OFF LOAD tap changing gear. The maximum temperature rise should not exceed 45 degree centigrade in oil and 50 degree centigrade in HV/ LV winding when measured by the resistance method after continuous full load run in ambient temperature the transformer shall confirming to IS 1180 Part-I:2014; Level-3 and comprising of following accessories complete all as specified and as directed.
(a) HV side Cable box with 03 Nos porcelains HV bushing with arching horns on HV side suitable for 11 KV completewith bushing rods and nuts washers and cable glands suitable for reception of out 3 core 95 Sqmm cable 3 runs, HT Cable 11000 Volts grade XLPE insulated heavy duty including gland complete.
(b) 01 No cable end box on LV secondary side consisting of 05 Nos porcelain bushing (One No neutral earth, One No Neutral and Three No for phase connected bushing) with bushing rods and nuts washers and cable glands suitable for reception of out 3.5 core 400 Sqmm cable 3 runs, LT 1100 Volts grade XLPE insulated heavy duty including gland joint complete.
(c) Oil conservator with filter type drain valve and oil level gauge.
(d) Dehydrating breather with first filling of dehydrating agent.
(e) Explosive vent.
(f) Thermometer pocket including temperature gauge.
(g) Two earthing terminals on tank body to facilitate fixing of 32x6mm GI strips.
(h) One No thermometer dial type vapour pressure type having range 0-120 degree centigrade with maximum temperature indicator and re-setting device to maximum temperature including needle of temperature gauge: Max reading painted terminal.
(i) Rating plate with terminal plate.
(j) Oil level gauge.
(k) Oil drain filter valve.
(l) Oil filling hole on top cover with plug.
(m) Air release valve/plug.
(n) 4 Nos plain solid cast steel detachable rollers.
(o) First fill of transformer oil conforming to relevant ISI and tested upto 60 KV dielectric strength.
(p)Two Nos lifting hook at side of transformer
(q) 1No Breather duly filled with silicate crystals capacity 500g
Note: Providing platform for transformer of size 3.0x3.0x1.5m high from GL including excavation in trenches not less than 1 mtr, PCC 1:5:10 type E2 for foundation, brick work in cm 1:6, PCC 1:2:4 type B1 in copping, plaster 10mm thick in cm 1:6 om brick /complete surface PCC 1:4:8 type D2 sub base 75mm thick, as in flour PCC 1:2:4 type B1 100mm thick floor using extra cement returning filling and removal on surplus soil, including 2 Nos ISMB 100mm channel painting with 2 coat aluminium paint over a coat of red oxide primer and 3 coats of white washing on cement work for fixing transformer including ramp of suitable size mounting of transformer etc complete all as specified and as directed.
Supply & lay G I tubing light grade in protection of cable at road crossing /hard standing/pole protection fixed with clamps as per site requirement etc all as specified and directed for following sizes :-
(a) 40 mm dia
(b) 100 mm dia
M & L earthing complete with galvanised steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5m below ground level, connecting to the Galvanised iron earth strip 32 x 6mm dia, by means of nuts, bolts, check nuts and washer etc of galvanised iron and earth lead protected by provision of GI pipe medium grade 40mm bore from earth electrode to test point incl provn of concrete pit in PCC (1:2:4) type B-1 using 20mm graded stone aggregates with 40mm thick cover of RCC (1:2:4) reinforced with XPM sheet (weight not less than 4Kg/Sqm) and frame of angle iron 25 x 25 x 6mm with lugs 2 Nos and with 8mm dia MS bar handle made to shape, GI pipe medium grade 20mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge of earth plate, common salt and charcoal filling test point with fixing arrangement, funnel, wire mesh and earth work in hard/dense soil, returning in and removal of surplus soil to a distance not exceeding 50mtr, complete all as specified in electrical plate No 3 of SSR Part I and connection to earth test point including testing on completion all as directed. Note:- The cost of 7.5m long galvanised iron earth strip of 32 x 6mm size and protection pipe of 40mm bore GI light grade is deemed to be included in quoted unit rate.
M&L for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required GI strip 32mmx6mm etc complete all as specified and directed.
Supply, install, testing and commissioning factory made (CPRI test certified) LT panel box (KIOSK) outdoor type platform mounted suitable for 415 volt , 3 phases, 4 wire , 50 Hz AC supply system all as specified and directed having busbar chamber with insulated AL bus bars 150 amps rating installed on porcelain insulators, the panel shall be dust and vermin proof double door made of 3.15 mm CRCA MS sheet outer & inner 3.15 mm thick and individual compartment for MCCB/MCB & volt/Amps meter and 40 x 40 x 6 mm thick angle iron for base frame work. The complete feeder pillar box should be powder coated including internal wiring with PVC insulated solid copper conductor FRLS cables appropriate size but not less than 4 Sqmm. Front and back opening type with approx size for cable entry with double door shutter including locking arrangement as per manufacturers with 2 Keys. (a) Incoming:- MCCB 4 pole 100 A , 415V,16 KA - 01 No. (b) Outgoing:-MCB SPN 40 Amp 240 Volt - 6 Nos (c) Busbar aluminium 150 Amps capacity Note: space of outgoing MCCB 1 No to be provided and panel mounted on 60cm height PCC platform.
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine for laying underground pipe up 100mm dia etc complete all as specified and directed. Note :- GI pipe shall be measured and paid in concern Item
Shifting of APFC panel from existing site to new site upto 500 Mtr including carrying out minor maintenance/repairs as required of all the systems etc complete all as specified and directed.
M&L HV polymer surge/ Lightning arresters gap less Metal oxide type complete with all fittings, station class, and discharge capacity 10 kilo amp, suitable for system voltage upto 12KV etc complete all as specified and directed.
M&L for PCC (1:3:6) type C2 using 40mm grade stone aggregate in base & foundation of pole including necessary form work etc complete all as specified and directed.
M&L for PCC 1:2:4 type B1 using 20mm graded stone aggregate in coping of existing/new poles / foundation for poles, struts, posts etc including necessary form work, finished the exposed surfaces fair and even without using extra cement etc complete all as specified and directed.
Supplying, Erecting and fixing in replacement Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-55 (11.0 metres long) and providing 3 Nos of 30cm wide circular bands with black & yellow paint starting from plinth level at a gap of 30 cm in between 2 bands and numbering of poles, in yellow paint over black painted back ground at a height of 2m from bottom of pole with 5 cm large bold letters 5cm wide, etc complete all as specified and directed.
M & L cross arms, bracing ,support clamps and back plate fabricated from structural steel sections including nuts bolts washers welding bending cold or hot drilling holes for bolts in any shape or size as indicated or directed and inclusive of one primer coat one under coat and one finishing coat of aluminium paint. etc complete all as specified and directed.
M&L for anti climbing device, comprising 2.24 mm dia galvanised steel 2-strand barbed wire with 2.00mm dia barbs wrapped spirally round poles, to a length of 0.5 to 1.0 metre clamped and properly secured or as ordered etc complete all as specified and directed. (clamps measured separately).
M&L pin type, porcelain, vitreous brown, white or green insulator (HT), 150mm height and 150 mm dia, 11000 volts grade including one galvanised MS spindle, two GI washers and one GI nut, etc complete all as specified and directed.
M/L ACSR over head Aluminium conductor steel reinforced of any size all as specified and directed including stringing through RCC/Steel tubular poles, fixing on insulators, jumpering with aluminium binding wire including taking down old etc complete all as specified and directed.
M&L for Danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and fixed with MS clamps, bolts and nuts of approved size, for HT, 25X20 cm size. etc complete all as specified and directed.
Supply, installing, testing and commissioning of Air break, gang operated, triple pole switch, outdoor, rotating type, horizontal mounting type (ISI marked), mechanically operated, mounted on insulators and frame work with operating mechanism worked from ground level with locking arrangements including Godrej pattern 65mm pad locks with two keys, complete suitable for HT 11 KV, 50 Hz AC supply including necessary electric connections complete all as specified and directed by Engineer-in-Charge of following rating :-
(a) 400 amp rating complete with fuse carriers and HT fuse elements.
Supply, fabricate and Install as in replacement of double sided glow sign board of size 2.4 mtr x2 mtr x0.4 mtr, made out of 25 mm bore MS pipe 'H' frame, covered with PGI sheet 24SWG gauge on all sides except front side, front side with flex sheet duly digital print embossing as directed by Engineer-in charge showing location /details of power house /tech area as directed and writing of letters (Block, Roman, Italic), in two or three rows, the same letters should be printed on both sides of the sign board, fixed with aluminium equal angle 25 x 25 x 3 mm thick fixed with screws and providing inside LED tube light fittings 1 x 9 Watt - 4 Nos for glowing the sign board at night with necessary internal electrical connections fixed on wall/pole and the sign board shall be fixed with MS channel 40 x 40 x 4 mm thick by means of nuts, bolts and grouted in ground up to 1.5 Mtr above GL and 0.45 below GL with 50 mm dia GI pipe stand embedded in PCC bed block of size 300x300x450mm with PCC 1:3:6 type C1 using 20 mm graded stone aggregate and the MS frames/ pipes shall be given two coats of synthetic enamel paint over a coat of red oxide primer etc complete all as specified and directed.
S&F expulsion fuse(drop out fuse unit) 3 pole separate channel mounted above 50 and upto 100 amps, suitable for 11000V etc complete all as specified and directed.
Carefully dismantling the existing meters from inside the panel box/wall along with disconnecting the incoming supply cable etc complete all as specified and directed and submit in E/M store yard.
S&F of new Single phase Smart Energy meter (10 - 60A) with in-built GPRS/GSM / RF communication module for Automatic Meter Monitoring and outer box. The meter should have in-built relay so that it can remotely or through mobile application/ web application ON/OFF by Engineer-in-Charge from any place in the world. . As per requirement, the Engineer-In-Charge should be able to configure same meter through software to work as Prepaid, Post-paid and Net Meter. The communication protocol between the meter and the software should be open source DLMS protocol (as following by Govt. utilities) so that meter should not be dependent on meter manufacturer. Meter should be compliance with IS-16444 Mounting Wall type (Smart Energy Meter standard, defined by Central Electricity Authority, Govt of India) and certified with IS13779 etc complete all as specified and directed. Note:- The Engineer-in-charge should be able to remotely generate the bill without visiting the field. The bill can be generated day wise / week wise / month wise and it should be configurable so that the MES administration can include electricity consumption charge, meter fixed charge, water charge, lease charge and any other charge as applicable. The price should include the GPRS Data charge for 12 months. Make: L&T / Landis Gyr / Secure Meter.
S&F of new Three phase Smart Energy meter (10 - 60A) with in-built GPRS/GSM / RF communication module for Automatic Meter Monitoring with outer box. The meter should have in-built relay so that it can remotely or through mobile application/ web application ON/OFF by Engineer-in-Charge from any place in the world. . As per requirement, the Engineer-In-Charge should be able to configure same meter through software to work as Prepaid, Post-paid and Net Meter. The communication protocol between the meter and the software should be open source DLMS protocol (as following by Govt. utilities) so that meter should not be dependent on meter manufacturer. Meter should be compliance with IS-16444 Mounting Wall type (Smart Energy Meter standard, defined by Central Electricity Authority, Govt of India) and certified with IS13779. etc complete all as specified and directed. Make: L&T / Landis Gyr / Secure Meter.
Supply and Installation of IP-67 protection Data Concentrator Units (DCU) compatible for remote Automatic Metering Infrastructure (AMI) solution and capable for communicating with the smart energy meter in the corresponding frequency band and with the data server through GPRS/Ethernet. It would have internal memory to store data of at least 200 modules. It would have inbuilt battery back-up. It would have IP-67 protection. It would support auto discovery of the meters and self healing mechanism for the breaks in the RF Network. Make : Secure, L&T, Schneider, Cyan Connode.
Supply of the following :- (a) 01 No Desktop of Make Del, HP,Lenovo, (Minimum Intel Core i5, 7Gen, 1 TB HDD, 19” Monitor, 6 GB RAM). (b) CD/DVD writer wireless Mouse and Keyboard), (c) 01 No Laser Jet printer cum scanner (Printing 18 pages per minute) of Make HP,Canon, Lenovo (d) 01 No UPS system with 15 Minutes power back of make V-gaurd/Intex/Microtek.
Three year comprehensive maintenance including operating costs. They would include the following: - (a) Monthly SIM charges for the DCU: The contractor would ensure supply of appropriate SIMs to ensure necessary signal availability. The contractor would change the SIM or SIM provider as required. In case of network issues, the contractor would liaison with the telecom service providers for necessary resolution. (b) Hardware AMC : This would include necessary repair and replacement of the hardware including DCU and Meters including display or data connectivity issues. (c) Software AMC: This would include necessary upgradations in the software such as support to the chrome browser changes, android version changes, IOS version changes. These changes happen on frequent basis and the software would support all the changes.
Supply and Configuration of the Web based Software with following modules :- Make : Secure, L&T, Schneider, Innologix.
(a) Meter Data Management Module: The meter data management module would be responsible for collecting the data from the concentrator and make the data available to the billing system. The meter data management system would capture and provide the following data : (i) 30 min instantaneous data from all the meters for seven parameters – Cumulative Energy, Cumulative Apparent Energy (as applicable) Power, Current, Voltage, Power Factor and Frequency. (ii) Monthly billing survey data for cum energy and max demand.
(b) Postpaid/ Prepaid Billing Module: The billing module would collect the data from the meter data management module, calculate the energy consumption, calculate billing determinant and make energy data/ billing data available to admin and end users. The billing module would include functionalities for tariff setup, bill format setup, bill adjustment, occupation billing and vacation billing. It would allow postpaid and prepaid functionality as required.
(c) Occupation and Vacation Module: The system would support occupation/ vacation and billing reports. The software would be collecting data from DCU. The software would provide access to staff as well as the occupant for the data.
(d) Website: There would be a dedicated website for the AGE and BSO team to view all the data and information. The designated users in MES would have the admin access to the application. The MES staff would also have the access of the key information on an android mobiles app (for admin use).
(e) Customer Portal: The system would include a customer portal for the resident/ occupant to log in an view their own energy/ billing data. There would be android and iOS mobile apps for the user to monitor its own data on regular basis.
(f) Energy Accounting Module: The system would include features of energy accounting. The system would be able to account for total energy block wise, facility wise and would also allow calculations of unaccounted energy in case total energy meter is also available.
(g) Communication module: The system would provide communication of energy data and bills via print, Email and SMS methods.
(h) Meter Master Data: The system would support meter master data repository. The system would support meter replacement process.
(j) Excel Support: The system would support export of metering and billing data in excel format.
Note : Two year defect liability would include configuration of replaced/ repaired hardware, remote network monitoring, software AMC
Fixing only chain link fencing including line wires any mesh size and type of standard rails straining bolts etc. including provision of binding wire etc complete all as specified and directed.
S&F mild steel screw bolt (machine made) dia of neck 11 to 15mm with hexagonal or square heads at one end and screwed the other or screwed both ends each screwed end to be fitted with washers and one hexagonal or square nut exceeding 10cm and not exceeding 15cm long.
S & F mild steel work such as in angle iron flat iron fillets hand rails half round or other steel section or core for wooden hand rail straight portion drilled and countersunk for baluster running bars for doors, baluster, noising to steps including embedding in concrete an screwing etc. wind ties for roof including securing bolts post and struts in fencing including cutting tops to shape as directed drilling holes notching for wire including all necessary works.
Machine pressed precast concrete interlock power any shape and size confirming to IS 15658 2006 of 60mm thick M-35 grade with green cement and pigment including providing 100mm PCC type D2 (1:4:8) using 40mm graded stone aggregate etc complete all as specified and directed.
Supply and Fix MS LT cable rote indicator duly embossed LT Voltage including and fix on Precast PCC (PCC 1:2:4, type B1 using 20mm graded stone aggregate) block of size 30cm x 20cm x 60cm in coping of existing/new poles / foundation for poles, struts, posts etc including necessary form work, finished the exposed surfaces fair and even without using extra cement complete.
Supply only chain link fencing MS galvanized 4mm dia GI any size.
krishna Associate
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .