Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.2 LAccepted-AOC 28 SAMBHU BABU LANE KOLKATA 700014 | KOLKATA | KOLKATA | WEST BENGAL | 700014 | L1 | Accepted-AOC AOC issued | |
| 2 | L2₹2.4 L+₹20,425 (9.19%)Rejected-Finance 24C GOABAGAN LANE KOLKATA 700 006 | KOLKATA | KOLKATA | WEST BENGAL | 700006 | L2 | Rejected-Finance That the bid is not L1 | |
| 3 | L3₹2.5 L+₹32,581 (14.7%)Rejected-Finance 24A RABINDRA SARANI KOLKATA 700 073 | KOLKATA | KOLKATA | WEST BENGAL | 700073 | L3 | Rejected-Finance That the bid is not L1 |
Tender Value
Refer Docs
EMD Value
₹6,000
Closing Date
21 Jun 2024, 1:00 pmClosed
Assistant Engineer, KMC Electrical Sub-Division
OFFICE OF THE ASISTANT ENGINEER Kolkata Medical College Electrical Sub-Division, P.W.Dte.Green Building, MCH Campus 88, College Street, Kolkata-700073.
Establishment of two mail and two female beds for DR TB Ward Under Kolkata Medical College and Hospital. Part A... Electrical Installation Work.
2024_WBPWD_691187_1
WBPWD/AE/KMCESD/NIQ-03/24-25
Open Tender
ELECTRICAL WORKS ORG
Item Rate
15 days
Kolkata
Please refer Tender documents.
5 documents required · 5 mandatory
₹6,000
7 Jan 2025
10 Jun 2024
24 Jun 2024
14 Jun 2024
21 Jun 2024
14 Jun 2024
Amount
EI Work:- Dismantling the existing E.I. work by Co's own tools & tackles and take unnecessary items away from site by maintening normalcy as far as possible as per direction of EIC .
A. Distribution wiring:--- Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FRLS' PVC insulated & unsheathed copper wire (MK: RR Kable/ Polycab/ Havels/ Glostar/KEI) partly in 20mm size PVC rigid conduit 'FR' (Precision make) [for ceiling portion only] and in 19mm bore, 3mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board on wall complete with 2 no. “Ph & N” copper bar incl. bakelite/ Perspex top cover 3 mm thick and incl. 175x100x65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish [only PVC Rigid Conduit on ceiling and remaining portion concealed] Average run 12 mtr.
Cutting channel of 40 mm x 40 mm size on masonry wall incl. S&F heavy gauge polythene pipe dia as stated below, by means of iron hooks and supplying and drawing 18 SWG GI Wire as fish wire incl. mending good damages to building works a)19 mm dia 3 mm thick polythene pipe without earth continuity wire. [3(a)/E-2]
Cutting channel of 43 mm x 43 mm size on masonry wall incl. S&F heavy gauge polythene pipe dia as stated below, by means of iron hooks and supplying and drawing 18 SWG GI Wire as fish wire incl. mending good damages to building works A) 25 mm dia 3 mm thick polythene pipe without earth continuity wire
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (MK: RR Kable/ Polycab/ Hevels/ Glostar/KEI) of the following sizes in the prelaid polythene pipe as per GS. a) 3 x (1.5 sqmm) [1(b) / E- 9 ]
b) 2x(2.5 sqmm)+1x(1.5 sqmm) For computer board & power plag [ 1(s) / E-9 ]
c) 2x(4 sqmm)+1x (2.5 sqmm) [ 1(v) / E- 9 ]
d) 2x 84/0.3 (6 sqmm) + 1 x 56/0.3 (4 sqmm) ECC For connection of HTPN To SPNDB
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (MK: RR Kable, Polycab, Hevels) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required a) 2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC
b) 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC
c) 2x(4 sqmm)+1x (2.5 sqmm)
d) 2x 84/0.3 (6 sqmm) + 1 x 56/0.3 (4 sqmm) ECC For connection of HTPN To SPNDB
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes .vide pg no F-5 item no. 9 a)2.5 sqmm
b) 4 sqmm
c) 6 sqmm
B. BDB, PDB, VTPN etc:--- Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall as per GS.( Make - Legrand/L&T/Schneider/ABB/Siemens ) a) 6 Way [ 14 / D- 10 ]
Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. a. 2+12 Way[ Make- Legrand/L&T/Schneider/ABB/Siemens ] [ 13 / D- 9 ]
Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection as perGS [Make-Legrand/L&T/Schneider/ABB/Siemens ] mentioned below a. 40A DP [ 6 / D- 5 ]
b. 63A FP [ 6 / D- 5 ]
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connections per GS [ Make -Legrand/L&T/Schneider/ABB/Siemens ] a) 6-32 SP [ 7 / D- 6]
Supplying and fixing double door sheet steel (16SWG), powder coated cable end box for TPN DB horizontal / vertical enclosure with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish with nuts bolts etc incl. provision for earthing attachment [ Make -Legrand/L&T/Schneider/ABB/Siemens ] a. 6way HTPN
C. Plug & Sockets:--- Distn. wiring in 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Finolex FR LS) to 240 V 6A 5 pin plug point incl. S&F 240 V 6A 3 pin type plug socket & switch (Anchor) as per gs a) On Board
Supply & Fixing 240V, 2 nos. 6A Piano Key socket and switch (MK: Anchor) on sheet metal switch board concealed in wall incl. S & F 175 x 100 x 65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover, incl. Ph, N, E Cu Bar and making necessary connections as required as to GS.
Supply & Fixing 240 V, 3 nos. 6A, & 1 no. 20A plug socket (MK: Anchor) with separate 3 nos. 6 A & 1 no. 20A Piano key type switch with indicator & 16A sp MCB (MK: Havells) on sheet metal switch board embedded in wall incl. S & F 240x200x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required
Supply & Fixing 240V, 20A, plug socket with separate 20 A Piano key type switch (Anchor) and 1 no. 6A Piano Key socket with switch on sheet metal switch board concealed in wall incl. S & F 200 x 150 x 65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover, incl. Ph, N, E Cu Bar and making necessary connections as required as to GS.
D. Supply of cables :--- Supplying and Delivery of following sizes Al. armoured PVC/XLPE cable (make--Havells/gloster/KEI/Polycab/RR kable) as mentioned below : a) 4 core 35 sqmm (from VTPNDB to PDB)
E. Laying of cables :--- Laying of 4 core 35 sqmm Al. armoured PVC/XLPE cable (Havells/ Glostar /KEI) with 2X10 SWG GI wire making hole etc. as necy., mending good damages and painting as mentioned below : (from VTPNDB to PBDB) Vide page no F-1,F-3 Item no 2 & 5 a. on wall by clamp
b. Concealed in wall
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below : vide pg no F-4 item no. 7.C a) 4 core 35 sqmm
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials . vide pg no F-5 item no. 8a & 9 : a) 4 core 35 sqm
Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required a) 65 mm dia
F. Supply of Light Fittings :--- S &D 4 feet single commercial LED type fluorescent light fittings (make-- Philips TMC 502 1xT-LED 22W/ CG Eco- I IGP161LT8-16 1XT8/Wipro WIO921208P) complete with all accessories with 1 x 18 Wt. LED Tube lamp corresponding to ( Make- Philips MAS LED Tube 18W, 2100lm 865 T8 (ve)/ Crompton LT8-20-865-(2) ULTRON/ Wipro LL13-181-65SESL1-G1)
S &D 4 feet twin commercial LED type fluorescent light fittings (make-- Philips TMC 502 2xT-LED 22W/ CG Eco- I IGP161LT8-16 2XT8/Wipro WIO921208P)complete with all accessories with 2 x 18 Wt (make- Crompton LT8-20-865-(2) ULTRON/Eqv Philips) LED Tube lamp corresponding to( Make- Philips MAS LED Tube 18W, 2100lm 865 T8 (ve)/ Crompton LT8-20-865-(2) ULTRON/ Wipro LL13-181-65SESL1-G1)
G. Fixing of Light Fittings :--- Fixing only single/twin fluorescent light fittings suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp (125mmx125mm) as per G S Vide page no C-2, Item no 17
Extra for suspension exceeding 25 cm with S&F additional 2 no. 20 mm dia EI conduit (14 SWG) supports & necy. PVC insulated wire and painting etc. as required by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length as per G S Vide page no C2 Item no 16
H. Supply of fans :--- S & D of 240 V ,1200 mm sweep ceiling fan , air delivery 230 CMH, (make-- Usha Striker 1 star/CG Riviera Hi speed 1 star Orient Falcon-425 SHS) complete with blades , canopy ,fork ,rubber bush, down rod, 1000mm safety wire & S3 capacitor etc.
S & D 250 V 50 HZ, 80watt, 18" (450 mm) high flo ( air delivery-- 4500 CFM, RPM-- 1400) non-oscillating type metal body Wall Bracket fan with inbuilt regulator, double ball bearing, intergally cast LM6 impeller (Make -EPC) .
S & D 230V, 1420 RPM heavy duty exhaust fan (Make-- EPC/USHA,S. Ph TURBO Heavy duty, 1400 RPM, ISI Grey/ Orient Heavy duty/CG EXHD300-4-1) of following sizes 12" (300mm)
I. Fixing of fans :--- Supply & Fixing 240V, fan regulator (Step type) (mk-Anchor) on existing sheet metal switch board with top cover plate incl. making necy. connections etc.
Supplying & Fixing MS fan clam of two piece type for RC ceiling as per approved specification, fabricated from 40 mm x 9 mm MS flat including making good damages to building roof with satisfactory finishing and painting Vide page no D 14 Item no 29
Fixing only ceiling fan complete with blades, canopy, fork, rubber bush, etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire as per G.S. Vide page no C-3, Item no 21.a.
S & F fan down rod (14 SWG) incl. necessary connection wire (2X1.5sqmm cu wire) and painting the down rod as per direction of EIC
fixing only 18" (450 mm) Wall Bracket fan on (10'' x 12'' ) size wooden board in built on wall by S & F rag bolts ,nuts and washers (6 mm dia x 62 mm long) or as required incl. S & F 24/.20 PVC insulated flexible copper wire 0.5 mt. Length as per direction of EIC.
fixing only 12'' exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust of dia incl. Fixing louver shutter on wall with necy. bolts & nuts (6 mm dia x 62 mm long) as per GS
Special Terms and Conditions 1. It is stated that the above work place is existing COVID Hospital, In case of any mishap or accidental to any staff that deputed by the agency the whole responsibility is to be borne by the concern agency. 2. The Agency shall be responsible for provisioning of all COVID safety measures including regular sanitiziation of work places, vaccination of employees and compliance of stated directive and COVID appropriate norms. 3. All the issues related to the safety of the staffs should be taken care by the agency itself. (Defect Libilities period for 01 year from the date of completion of work) (Rate should be quotated including all taxes and duties)
ALPHA ELECTRICALS
STANDARD BUILDERS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .