Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹86.5 LAccepted-AOC NO 1 2 BIG STREET SAKKARAMALLUR VILLAGE POST ARCOT TALUK RANIPET DISTRICT 632 511 | TIRUVANNAMALAI | TAMIL NADU | 632511 | L1 | Accepted-AOC WORK AWARDED | |
| 2 | L2₹89.1 L+₹1.1 L (1.23%)Rejected-AOC | L2 | Rejected-AOC SECOND LOWEST | |
| 3 | L3₹90.0 L+₹1.9 L (2.18%)Rejected-AOC | L3 | Rejected-AOC THIRD LOWEST |
| Sl No | Description | Qty | Unit | SURESHBABU L1 | SABARINATHAN L3 | R BALAMURUGAN L2 |
|---|---|---|---|---|---|---|
| 1.00 | RMG Unit : Supply, Erection, testing and commissioning of 11KV 25 KA 630Amps 3 Panel HT OUTDOOR RING MAIN GEAR Switch board suitable for indoor installation comprising two incomer panels with Air Break/ load Breaks switches and one outgoing panel with Vacuum Circuit Breaker complete as per specification with Mechanical inter lock between incomers (1)Supply and Erection of draw out type 11KV 25 KA 630 Amps Horizontal draw out./Horizontal Isolation VACCUM CIRCUIT BREAKER fitted with motor ( 230 V AC) operated spring charged Mechanism, with ON and Off mechanical indicator Anti pumping Device, 110V DC shunt trip and closing coils ( DC source of supply to be derived from a power pack suitable for three Tripping and two closing operations incorporated on Incoming panel only) Mechanical Operation counter, 4 No + NC spare Aux contact with contact multiplication contractor for customer use. Automatic safety shitter, Mechanical close/Trip Knob, Mechanical ON/OFF Indication, operating Handle, 230V AC to 110V DC power pack operating handle, (2)Supply and Erection of 11KV 630 Amps 25 KA HT Air Break/Load Break switch with mechanically inter locked each switch, front operated spring assisted manual closing mechanism 2NO + 2NC Aux. contact (3)11 KV /Root 3/110V Root3-Three phase 3 Limb 50 VA class 0.2 Resin cast Draw out type potential Transformer complete with HT and LT HRC fuses with sealing arrangement – 3Nos, (4)Current Transformer of suitable Ratio/5-5A Dual core ( Core1-5VA clas 0.2 for metering & crore 2-15 VA 5 P 20 for protection – 3Nos, (5)Meters: Analog Ammeter with 5 position selector switch-1no Analog Voltmeter with selector switch-1No cut out provision to receive digital Tri Vector Meter L & T or secure to be provided., | 1 | No | 7,90,000 ₹7,90,000 Lowest | 8,02,510 ₹8,02,510 | 7,94,790 ₹7,94,790 |
| 1.01(6)Protection: IDMT two over current and one earth fault Relay with high set Inst. Elements 1.3 seconds-1No Master Trip relay Megawin MVAJH 13 equivalent – 1No., (7)Breaker ON/OFF indication LED type-2Nos Auto Trip/Healthy Trip and spring charged indication LED type – 3Nos phase indicating Lamps, (8)TNC Breaker control switch-1No Local Remote selector switch -1No push button for trip Healthy -1No, (9)Panel Mounting Surge Arrester-9KV, 10KA, (10)630Amps copper Bus bar PVC sleeved & required panel earthing, (11)Common for switch gear, MCB’s for AC/DC control Heater ON/OFF switch with space Heater and thermostat, single phases switch socket, cubicle illumination TL Lamp,Door switch fully covered Test Terminal block of IMP Make ( wherever applicable), (12)MS sheet steel enclosure for outdoor Installation powder coated with Siemens Gray finish, (13)Provision through bottom entry to receive Incoming or Outgoing cable Termination kit (Make : Mega win/System Control | ||||||
| 2.00 | Indoor Three Panel Consumer VCB: Supply, erection, testing, commissioning and of 11KV 25KA HT Three panel Vacuum Circuit Breaker Switch, Indoor type for installation, board comprising one Incomer VCB and 2 Nos Outgoing 630A 500MVA VCB.1.Draw out type 11KV 500MVA 630A Horizontal Draw out/ Horizontal Isolation VCB operated with spring charged mechanism.Anti Pumping device ,110V DC Shunt Trip and closing Coils (DC source of supply to be derived from a Power pack suitable for 3 Tripping and Two closing operation counter, 4NO + 4NC spare Aux. Contact for customer use, Automatic safety shutter, Mechanical Close/ Trip knob, Mechanical ON/OFF indication, Operating Handle, 110V AC-110V DC Power Pack etc. (Incom-1 & Outgoing-2Nos) Core(Core 1-15VA class 1 for metering and core 2-15VA 5P 10 for Protection) Incoming 1 No, Current Transformers of 30/5-5 Amps Dual Core (Core 1-15VA Class 1 for Metering and Core 2-15VA 5P 10 for Protection)(Outgoing-1) 4.Meters: 2. 11KV/Root 3/ 110V/ Root3- Three Phase, 3 Limb 200VA Class 1 Resin Cast Draw out type Potential transformers complete with HT and LT HRC fuses. (Incoming-1 No) Digital Voltmeter with selector switch (Incoming 1 No) Digital Trivector of L&T/Secure make (Incom-1No) Digital Power Factor Meter (Incom-1 No) Digital Frquency Meter (Incom-1 No) 5. Protection: TP ND IDMT 2OC + 1EF Relay with Highest inst.Elements similar like Megawin type MCDG 61 (Incom-1No) 6. TP ND IDMT 2OC + 1 EF Relay similar like Megawin type MCDG 31 Master trip Relay Megawin MVAJH 13 (Incom-1No & Out-1 No) 7. Breaker ON/OFF/Auto Trip/Healthy/Spring Charged Indication Lamp LED Type, | 1 | No | 13,50,000 ₹13,50,000 Lowest | 13,70,780 ₹13,70,780 | 13,57,600 ₹13,57,600 |
| 2.018. Phase Indication Lamps R,Y,B(Incomings 3Nos), 9. Control Wiring, 10. 800Amps Copper Bus bar PVC Sleeved and required panel copper earthing., 11. Control switch TNC (Incoming-1 No, Outgoing -1No), 12.Trip Circuit healthy Push Button(Incoming-1 No, Outgoing -1No), 13.Common for Switch gear, MCB's for AC DC Control, Heater ON/OFF Switch with space Heater and thermostat Single phase switch socket, cubicle illumination lamp, Disconnecting type terminal Block etc., 14. MS Sheet enclosure for Indoor Installations Powder. | ||||||
| 3.00 | Type ONAN type Transformer: Supply, erection, testing and Commissioning of 630 KVA 22KV/ 433V,copper wound off load tap changing copper wound Indoor type distribution transformer ONAN type of cooling conforming to relevant IS 1180- Level 2 and fitted with the following and standard accessories. (A) HV cable end box suitable for connecting 3 core 300 sq.mm11KVXLPE HT cable. (B)LT Cable end box suitable for connection 4 runs of 3 ½ x 300 sq.mm LTUG cables.
(C)Tapping on primary winding for voltage variation +5%to -5% steps 2.5%. (D)Neutral on L.V. side, (E) The transformer should be supplied with first filling of oil All removable covers shall be provided with weather proof, hot oil resistant, resistance gasket to prevent leakage of water into core and oil from the tank (Make: Voltech/ CREL or equivalent). | 1 | No | 20,20,000 ₹20,20,000 Lowest | 20,43,030 ₹20,43,030 | 20,23,390 ₹20,23,390 |
| 4.00 | Design, Supply, erection, testing and commissioning of 1250A MV panel board suitable for operation on 415 V 3 phase, 50 Hz A.C supply, dust and vermin proof and accommodating the following ACB as Incomer unit with the following items of work complete to satisfy the latest IE rules and CEIG guidelines with Bus bar chambers, Main switches chambers and cable entry chambers.
Bus bar chamber: Supply and fixing of suitable bus bar chamber made up of 16SWG MS sheet steel(1.8mm) with 3” X 1/2” tinned copper bus bar for 3 phases and neutral (75mm x 12mm) and 2 Nos. of earth bus of size 1” X 1/4 tinned copper bus(25mm x 6mm) on suitable bus bar insulator(Epoxy insulator) with maximum creepage distance and supported on MS Base channel frame work of size 18*3*2–1Set.
Main Switches Chamber: Incoming (1)Supply and fixing of 1 No. 1250A 4pole Draw out ACB of Microprocessor board EDO Type ( Cat. no:SL96074) basic rating 4 pole 433V LT ACB confirming to IS13947–2 IEC 60947–2 with suitable capacity and breaking capacity of drawout 65 KA breaking capacity with all accessories for standard horizontal manual draw out type ACB equipped with auxiliary contacts and all accessories for closing and opening operation with Microprocessor Based SR 18 G relay, over current trip device adjustable to LTD, STD and release for over current protection UV release with time delay, EF release short circuit protection, Mains CTs for 3 phases lockout, features, separate mold base for each pole for easy maintenance all relevant protection safety accessories as per CEIG, IE rules in force with inter connection and terminations as required in specification. | 1 | Set | 9,90,000 ₹9,90,000 Lowest | 10,04,120 ₹10,04,120 | 9,94,460 ₹9,94,460 |
| 4.01Outgoing (1)Supply and fixing of 800A TPN Double break switch with HRC Fuse—1 Nos, (2) Supply and fixing of 630A TPN Double break switch with HRC Fuse—3Nos, (3) Supply and fixing of 400A TPN Double break switch with HRC Fuse—3 Nos, (4)Supply and fixing of 250A TPN Double break switch with HRC Fuse—4 Nos. Inter connecting the all LT ACB’s and Switches to bus bar with suitable insulated tinned copper flats and painting/PVC sleeve color coding of phases and neutral indication. Double Earth connection of the switches and ACB’s to earth bus using suitable tinned copper flats by 2 runs of 1” X 1/4”. Supply and fixing of RYB LED lamp arrangements with toggle switches to control each phases and with rigid connection in suitable separate compartments within the cubicle as per CEIG rules with 1set, supply and fixing Electronic Trivector meter EC,300N class 0.5 flush mounting L&T or equivalent make–ModelER300N. Supply and fixing of danger board with Siemens grey powder coating with super scribing the names of places to which supply is fed feeder sizes of cables direction of cables etc. Erection of panel board complete with suitable foundation bolts and nuts including suitable M.S Channel, concreting ,testing and commissioning (L&T,C&S,SIEMENS,ABB) | ||||||
| 5.00 | Supply and erection of 400 Amps capacity dust and vermin proof cubical panel board size of 5'X 5' X 2' made up of 16 SWG CRCA sheet steel for outer body, with doors, switch supports and seperations etc., and with supply and fixing of the following interior switch with bus bar chamber complete with Bus Bar (a) 25 X 12 mm tinned cu. Flat for 3 phase , neutral and (b) 25 x 10mm tinned cu flat for Inter connections (c) 25 x 6mm tinned cu flat for earth connections with bus bar insulators complete with the following tinned Cu flat should be used between busbar and switches for interconnection
Interconnection of bus bars : (1)400A TPN switch bus bar for Interconnection 25mmX12mm copper flat, (2)315A & 250A TPN switch bus bar for Interconnection 25mmX10mm copper flat, (3)125 A TPN outgoing switch disconnector fuse units 25mm X6mm tinned cu. Flat supply and fixing of KWh meter (Submeter) & indication lamps. The panel should be fabricated as per IE rules & CEIG specification.The housing accommodate the following switches. Incoming Switch : (1)400 A TPN Incoming switch disconnector fuse units interior only with HRC fuses double break- 1 Nos, Outgoing Switch Switches : (3)315A A TPN Incoming switch disconnector fuse units interior only with HRC fuses double break- 2 Nos, (2)250A A TPN Incoming switch disconnector fuse units interior only with HRC fuses double break- 2 Nos, (3)125 A TPN outgoing switch disconnector fuse units interior only with HRC fuses double break-3 Nos. The panel board should be painted with two coats of high quality epoxy paint over one coat of red oxide primer with superscriptions. (lettering and numbering) The above cubical panel board rest on suitable angle iron base. | 1 | No | 1,43,825 ₹1,43,825 Lowest | 1,49,540 ₹1,49,540 | 1,48,110 ₹1,48,110 |
| 5.01Outgoing : (1)Supply and fixing of 630A TPN Double break switch with HRC Fuse—2 Nos, (2) Supply and fixing of 400A TPN Double break switch with HRC Fuse—3 Nos. Inter connecting the all LT ACB’s and Switches to bus bar with suitable insulated tinned copper flats and painting/PVC sleeve color coding of phases and neutral indication. Double Earth connection of the switches and ACB’s to earth bus using suitable tinned copper flats by 2 runs of 1” X 1/4”. Supply and fixing of RYB LED lamp arrangements with toggle switches to control each phases and with rigid connection in suitable separate compartments within the cubicle as per CEIG rules with 1set, supply and fixing Electronic Trivector meter EC,300N class 0.5 flush mounting L&T or equivalent make–ModelER300N., Supply and fixing of danger board with Siemens grey powder coating with super scribing the names of places to which supply is fed feeder sizes of cables direction of cables etc. Erection of panel board complete with suitable foundation bolts and nuts including suitable M.S Channel, concreting, testing and commissioning (L&T,C&S,SIEMENS,ABB) | ||||||
| 6.00 | 400A DG ATS Panel Spec:- 400A Motorized Changeover (ATS)– 01No, Auto/ Manual selector- 01No, Voltage Monitoring Relay– 1No, Dg Auto Remote Start& Stop Controls- 01Set, Digital VAF Meter with CT-01 Set,12V SMPS Battery Charger-01No, Status Indicator- 01Set, EB/ DG MCB Incomer- 01Set, Outgoing Power Bolted Terminal -01No, Control Accessories- 01Set, 1.6mm MS powder coated Enclosure- 01No, Control / Power wiring All in One Panel. | 1 | No | 1,50,040 ₹1,50,040 Lowest | 1,56,000 ₹1,56,000 | 1,54,500 ₹1,54,500 |
Tender Value
₹86.5 L
EMD Value
₹53,500
Closing Date
23 Jul 2025, 3:00 pmClosed
SUPERINTENDING ENGINEER
O/o. The SE, PWD Buildings C and M Circle, Vellore
Provision of RMG Panel, Transformer and MV panel arrangements to the Government Hospital at Sriperumbudur in Kancheepuram District
2025_PWD_582818_1
9/VLR-CLE/25-26/30.06.2025
Open Tender
Electrical Works
Lump-sum
90 days
SRIPERUMBUDUR IN KANCHEEPURAM DISTRICT
Please refer Tender documents.
8 documents required · 8 mandatory
₹0
₹53,500
17 Nov 2025
18 Jul 2025
23 Jul 2025
18 Jul 2025
23 Jul 2025
18 Jul 2025
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .