Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.8 LAccepted-AOC 28 DOCTOR LANE | L1 | Accepted-AOC lowest bidder | |
| 2 | L2₹14.1 L+₹29,128 (2.11%)Rejected-Finance VILL DAKSHIN SHIBGANJ P O AND P S PATHARPRATIMA DIST SOUTH 24 PARGANAS | SOUTH 24 PARGANAS | WEST BENGAL | L2 | Rejected-Finance bidder is not L1 | |
| 3 | L3₹14.2 L+₹37,503 (2.72%)Rejected-Finance CHATTAPADMAPUR RAMNAGAR DIST PURBA MEDINIPUR | PURBA MEDINIPUR | L3 | Rejected-Finance bidder is not L1 |
Tender Value
Refer Docs
EMD Value
₹28,316
Closing Date
25 Jun 2025, 11:00 amClosed
Executive Engineer CKHED PWD
Central Kolkata Health Electrical Division, P.W.Dte. P-5, CIT Road, 2nd Floor, Moulali, Kolkata
EI Installation work including SITC of Fire Detection system at Basement of DN DE Homeopathic Medical College and Hospital.
2025_WBPWD_856351_1
WBPWD/EE-I/CKHED/eNIT14/25-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
40 days
CKH El sub divn
Please refer Tender documents.
3 documents required · 3 mandatory
₹28,316
central kolkata health electrical division
7 Aug 2025
30 May 2025
27 Jun 2025
30 May 2025
25 Jun 2025
4 Jun 2025
4 Jun 2025
Amount
Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall as per GS. [Make : Legrand/ Siemens / L&T/ ABB/ Schneider ]
Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall as per GS. [Make : Legrand/ Siemens / L&T/ ABB/ Schneider ] (For distribution of SPNDB, FCU, 16/25 A power plug, )
Supplying and fixing double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall / flushed in wall as per GS.[Make : Legrand/ Siemens / L&T/ ABB/ Schneider] (For distribution of HTPN DB, 3 phase AC & other 3 PH point)
4 Way ( Up to 160 A )
Supplying and fixing double door sheet steel (16SWG), powder coated cable end box for TPN DB horizontal / vertical enclosure with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish with nuts bolts etc incl. provision for earthing attachment.
4 /6 Way HTPN
Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection as per GS. [Make : Legrand/ Siemens / L&T/ ABB/ Schneider ]
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connectionas per GS [[Make : Legrand/ Siemens / L&T/ ABB/ Schneider ] ]
40/63A TP for VTPN DB
Supplying and fixing 415 V Four Pole MCCB of Breaking capacity 25kA/35kA in existing Vertical DBs/ MCCB enclosure including necessary connection as per GS. [Make : Legrand/ Siemens / L&T/ ABB/ Schneider ]
100 A FP (4W VTPN)
Supply & Fixing 240 V, 4 nos. 6 A, 3 pin Modular type plug socket with 4 nos. 6A Modular type switch (Brand approved by EIC), 16A Modular switch type MCB (C-Curve) and Indicator without plug top on 2 row 18 Module GI Modular type switch board with 2 row 18 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy.connections with PVC Cu wire and earth continuity wire etc. (For computer board and medical instruments)
Supply & Fixing 240 V, 2 nos. 6 A, 3 pin Modular type plug socket with 2 nos. 6A Modular type switch (Brand approved by EIC), without plug top on 6 Module GI Modular type switch board with 6 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy.connections with PVC Cu wire and earth continuity wire etc. (For mobile charging & water purifier from SPNDB)
Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket (Brand approved by EIC) with 16A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc
Distribution wiring in 2 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1x22/0.3 (1.5 sqmm) single corestranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Brand approved by EIC) fixed on Modular GI switch board with top cover plate and 2 no. suitable size “Ph & N” copper bar & earthing attachment fixed on wall incl. mending good damages to original finish.
Averag run - 8 Mtr.
Distribution wiring in 1.1 KV grade 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1.1 KV grade 1 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire as ECC, to 6A 3 pin Modular type plug socket & switch (Brand approved by EIC) on 4 Module GI switch board with 3/4 Module top cover plate on wall incl. necy. connection making earthing attachment, painting and mending good damages to building works.
On Board
Average run 4.5 mtr
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire of the following sizes in the prelaid polythene/G.I. pipe as per GS. [ Make :Havells/ Finolex/Polycab/ Gloster/ KEI/ RR Kabel]
3 x 1.5 sq. mm [6 A plug & Computer board & FCU]
2 x 2.5 sq. mm + 1 x 1.5 sq. mm [for 16 A Power plug, ]
2 x 6 sq. mm + 1 x 4 sq. mm [ PDB to SPN DB]
Supplying and fixing PVC Rigid Conduit 'FR' [Precision Make] on wall, ceiling with saddles and other accessories as required and mending good damages to building works.(For power points, SPNDB, TPNDB).
20mm size
25mm size
Supplying & Fixing sheet metal inspection box (16 SWG) of the following sizes(in mm ) flushed in wall as per GS (For power points, SPNDB, TPNDB)
Finishing of the PVC insulated wire ends by socketting with pin/ring type copper sockets and insulated tapes etc., including supplying sockets, tapes.
3 x 1.5 sq. mm
2 x 2.5 sq. mm + 1 x 1.5 sq. mm
2 x 6 sq. mm + 1 x 4 sq. mm
Supply of 4 Core XLPE Insulated & Sheathed Armoured Aluminium Conductor cables for Working Voltage up to 1100 Volts of following sizes [ Make : Havells/ Gloster/ Polycab/ KEI/RR Kabel]
4C 50 sqmm
4C 25 sqmm
Laying of cable from 3/3½ core 35 sqmm to 50 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making holes etc. as necy., mending good damages and painting
4C 50 sqmm
4C 25 sqmm
Supplying and fixing compression type gland and finishing those for following XLPE / PVC armoured cable (2/ 4 / 3.5)Core as per GS.
4C 50 sqmm
4C 25 sqmm
Supplying and fixing 100A , 415V , TPN SFU with sheet steel enclosure on flat iron/angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating. [make .siemens/L&T/Havells]
Supply & Deliver of 4 feet Industrial box type single LED fitting including S & D of 1X20 wattt LED( Polycarbonate) with glare free light distribution with CCT (5000K-6500 K) , with minimum luminious efficacy ≥105 & <120 lumen/watt or better. The LED Lamp and accessories shall have BEE Certification.
Supply & Delivery of 4 feet Industrial box type Twin LED fitting including S &D of 2X20 wattt LED( Polycarbonate) with glare free light distribution with CCT (5000K-6500 K) , with minimum luminious efficacy ≥105 & <120 lumen/watt or better. The LED Lamp and accessories shall have BEE Certification.
Supply& Delivery of 240V 9 W LED lamp with CCT (5000K-6500 K) , with minimum luminious efficacy ≥105 & <120 lumen/watt or better. The LED Lamp and accessories shall have BEE Certification.
Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length.
Fixing only single / twin fluorescent light fitting complete with all accessories directly on wall/ceiling/HW round block and suitable size of MS fastener.
Fixing only lamp to batten point.
Extra for suspension exceeding 25 cm with S&F additional 2 no. 20 mm dia EI conduit as per GS.
S & D 1200mm sweep AC ceiling fan with out regulator, complete with P2 burst proof Capacitor, Down rod, blades, canopy, rigidly connected Safty Tie wire etc. Incl. other accessories as necessary. (Make - Cromton / Usha / Orient)
S & D of 230V , 50Hz , 450 mm sweep heavy duty full metal body wall bracket fan (Cabin fan) complete with all accessories. ( Make -EPC/crompton/orient/usha )
Supply of Heavy Duty Exhaust fans complete with all accessories having the following Model / Cat No. ( Make -EPC Electrical Pvt. Ltd. )
12"( 300 mm ) Speed 1420 RPM
Supplying & Fixing of Box type fan clamp of 150mm dia & 80mm depth made of 16 SWG CRCA sheet with one end duly sealed by cover, properly welded, incl. S&F 12mm dia 600mm long MS rod duly bent by heat treatment at the centre position of rod to grip fan bobbin properly, incl. binding the rod and fan box with reinforcement by 22 SWG steel binding wire, incl. supplying & covering the box with alkathene sheet, placed in order to prevent concrete from entering the box.
Supplying & Fixing MS fan clamp of two piece type for RC ceiling as per approved specification, fabricated from 40 mm x 9 mm MS flat including making good damages to building roof with satisfactory finishing and painting – (As per Drawing no. 475 of PWD Specification Book – May 1991)
Supply & Fixing 240V, Modular Socket (2 Module) type fan regulator (Step type) (Brand as per EIC.) on existing Modular GI switch board as per GS
Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc as per GS
Engraving the deptt. number with 10 mm lettering on the body as per GS
Extra for additional one letter incl. hifen, stroke and stop as per GS
Painting upto 10 letters of the engraved number with approved black /red paint as required as per GS
Extra painting for additional one letter of the engraved number as per GS
Fixing only cabin fan on wall/ceiling by S&F rag bolts, nuts & washers (6 mm dia x 62 mm long) or as reqd. incl. S&F 24/0.20 PVC insulated flexible copper wire 0.5 mt. length.
Fixing only exhaust fan after making holes in wall as per GS
Supply & Fixing louver shutter ( Aluminum)on wall with necy. bolts & nuts (6 mm dia x 62 mm long) as per GS
Supplying & Fixing 240 V AC/DC superior type Ding-Dong Call Bell (Anchor) on HW board incl. S&F HW board.
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: By ISI-Medium GI pipe
Excavation of soil for installation of Earth Electrode and filling & ramming. For Morrum Soil
Extra for treatment of soil by using salt & charcoal or coke for plate electrode
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe.
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 50 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required
Connecting the equipments to earth busbar including S & F GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages.Stranded GI wire-7/14 SWG
Connecting the equipments body to earth busbar including S & F 25 mm x 6 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc.
Supply, Installation,Testing & Commisioning of Micropresssor controlled Addressable Multisensor detector IP 42 ( VDS / UL /ERTL/ LPCB / FM approved ) with inbuilt optical smoke sensors and heat detector sensor with inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note : Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator per detector is to be provided extra without extra cost) the detectors should have built in response indicator with LED indicator. The detector should have 360 degree optical view with single / multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall not damage the detectors. (Approved Make : Cerberus Pro / Honeywell/Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST )
Supply, Installation,Testing & Commisioning of Addressable Manual Call Point ( VDS / UL /ERTL/ LPCB / FM approved ) with in built short circuit fault isolator as per NFPA style 7 wiring complete as required. (Approved Make : Cerberus Pro / Honeywell/Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST )
Supply, Installation, Testing & Commissioning of IP Addressable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe (strength of light 10 cd) complete with inbuilt short circuit fault isolator. Degree of protection IP65 ( VDS / UL /ERTL/ LPCB / FM approved) approved. (Approved Make: Cerberus Pro/Honeywell/ Johnson Controls / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/ GST )
Supplying, installation, testing and commissioning of LED type Response Indicator ( VDS / UL /ERTL/ LPCB / FM approved) having 2 Nos. red coloured LED lamps including connections etc. (Approved Make : Cerberus Pro/Honeywell/ Johnson Controls / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/ GST/System Sensor/Agni Suraksha )
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Finolex/Gloster/ RR Kable/Polycab ) through 19 mm dia PVC 'FR' type Rigid Conduit pipe with necessary arrangement as per G.S. (Make : Precision/ AKG/ Universal/ Polycab) on the surface of the wall.
Supply, Installation,Testing & Commisioning of Microprocessor based addressable fully networkable fire alarm control panel ( VDS / UL /ERTL/ LPCB / FM approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, conplying to IS 2189:2008 or its latest amendments, and with minimum 600 character alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. The panel should have extra loop card slot for expansion of capcity twice.
The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 60 minutes during Emergency condition, with integral battery charger complete in all respect as required.
The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 modbus. The FACP shall have provision for interfacing with the public address system, remote computer and BMS interface.The system must be preloaded with licenced software. (Approved Make : Approved Make : Cerberus Pro / Honeywell/Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST)
NOTE :- 1) The Fire Alarm system shall comply with latest requirements of -- (i) National Fire Protection Association (NFPA) Standards, (ii) IS 2189 , (iii) NFPA 70 National Electric Code, (iv) NFPA 72 National Fire Alarm & Signaling Code , (v) Local Statutory Regulations , (vi) Manufacturer Recommendation. vii) System should be integrated with the components like FACP, Detectors, MCP, Hooter, Monitor Module, Relay Module, etc. and all these components should be of same brand.
TESTS :- 1) The system shall be tested and commissioned by a qualified competent, trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2) Before energizing the cables and wires, inspection and check for correct connections, and test for short circuits, ground faults, continuity, and insulation and other tests as per applicable Indian/International standards must be done.
TERMS & CONDITIONS :-
The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.
Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill. If any refurbished material is supplied and installed, penal action will be taken as per existing rules
Rate should be quoted incl. of all taxes and cess.
Defect Liability period : 1 year
B. ENGINEERING CO. (BID ID -6631647)
TAPAN ELECTRICS (BID ID -6631596)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .