Loading…
Loading…
Tender Value
Refer Docs
EMD Value
₹1.1 L
Closing Date
6 Aug 2026, 2:00 pm
Electrical works in connection with "CPOH/KPA - Creation / Augmentation of intermediate/ periodic overhauling facilities for track machines."
ELEG-OT-1354-2026-27
ELEG-OT-1354-2026-27
Open
Works - General
12 Months
Unknown (Unspecified Location)
₹0
₹1.1 L
16 Jul 2026
16 Jul 2026
23 Jul 2026
I-NS Schedule - (Cabling and Wiring works)
Trenching and laying of cable underground by soil cutting through suitable dia HDPE pipe, without sand and 1 bricks including refilling of trench by excavated soil and make good of surface as its original condition, (The cable trench should be of minimum 1000 mm depth). (HDPE Pipe Make: Skipper/ Capital Polyplast/ Chaika Polymers/ Utkarsh/ Ashirvad/Arpan/Ori Plast) (L.T. Cable will be supplied by Railway)
Cable trenching, laying, refilling with bricks & sand, rising, jointing, socketing where necessary as per General Specification. (The cable trench should be of minimum 1000 mm depth). (L.T. Cable will be supplied by Railway)
Cable laying through 2" dia. GI Pipe along with supply of GI Pipe as per General Specification. (G.I. Pipe Make: TATA/ Jindal / Bansal ) (L.T. Cable will be supplied by Railway)
Drawing of L.T. cable through PF wall / Structure by cleating / clamping etc as per General Specification. (L.T. Cable will be supplied by Railway)" "Drawing of L.T. cable through PF wall / Structure by cleating / clamping etc as per General Specification. (L.T. Cable will be supplied by Railway)
Drawing of LT cable in Concealed way through PF wall / structure / building wall etc. as per General specification. 'L' hook should be provided at approx. every half meter length. (L.T.Cable will be supplied by Railway)
Drawing of LT cable through inside of GI Octagonal / Tubular pole for loop in & loop out as per General Specification. (L.T. Cable will be supplied by Railway)
L.T. epoxy cast straight through jointing kit suitable for L.T. XLPE insulated cable of size 4 core 150mm2 to 4 core x 300mm2, 1100V grade along with jointing. (Kit Make: Raychem RPG/Yamuna Densons/ 3M / Polycab)
L.T. epoxy cast straight through jointing kit suitable for L.T. XLPE insulated cable of size 4 core x 70 mm2 to 4 core x 120mm2, 1100V grade along with jointing. (Kit Make: Raychem RPG/Yamuna Densons/ 3M / Polycab)
Wiring of light point with 1.5 sq.mm PVC copper wire FRLSH through PVC conduit pipe from inside JB with porcelain fuse kit-kat / MCB of rating 16 A to top of G.I Octagonal pole 5.5 mt. long along with copper ECC of size 1.5mm2 as per General specification of IE Rule. (PVC Wire Make: Havells/ Gloster/ Polycab/ RR Kabel/ KEI/Mescab)
Wiring of Light and Fan points with 1.5 sq.mm., PVC insulated 1100V grade FRLSH single core, M/Strand 10 copper wire through suitable size (ISI marked) PVC conduit pipe/casing/concealed way along with ECC of 1no. 1.5 sq.mm. , PVC insulated single core, M/Strand FRLSH copper wire as per General specification of IE Rule. (PVC wire Make: Havells/Gloster/Polycab/RR Kabel/KEI/Mescab) (Switch & Plug Socket Make: Panasonic/ Anchor/ GM Modular/ Legrand/Crabtree/ Havells/Hager)
Wiring of 6 Amp plug board consisting with one 6A plug socket and one 6 amp switch by 2 nos. single core FRLSH grade, PVC insulated, copper conductor wire of size 1.5 mm2, 1100V grade for phase and neutral alongwith 1 no. 11 single core FRLSH grade, PVC insulated, copper conductor wire of size 1.5 mm2, 1100V grade for Earth Continuty Conductor (ECC) through suitable size (ISI marked) PVC conduit pipe/casing/ concealed way as per General specification of IE Rule. (PVC wire Make: Havells/Gloster/Polycab/RR Kabel/KEI/Mescab) (Switch & Plug Socket Make: Panasonic/ Anchor/ GM Modular/ Legrand/Crabtree/ Havells/Hager)
Supply and fixing of 3 pin, 5 amp, ceiling rose on the supplied metal box of size (75 mm x 75mm x 60 mm deep) on surface or in recess with suitable size of phenolic laminated sheet cover in front, painting etc. as required including 12 electrical connection for Light & Fan points with 2 nos. 1.5 sq.mm, 1100V grade Copper PVC FRLSH, Single core, Multi-strand wire(for phase and neutral) along with 1 no. single core FRLSH PVC insulated copper wire of size 1.5 sq.mm, 1100V grade for ECC through flexible PVC conduit from ceiling rose connected with Sub-main as per General specification of IE Rule. (PVC wire Make: Havells/Gloster/Polycab/RR Kabel/KEI/Mescab)
Supply and fixing of 3 pin, 5 amp, ceiling rose on the supplied metal box of size (75 mm x 75mm x 60 mm deep) on surface or in recess with suitable size of phenolic laminated sheet cover in front, painting etc. as required including 13 electrical connection for Light & Fan points with 2 nos. 2.5 sq.mm, 1100V grade Copper PVC FRLSH, Single core, Multi-strand wire(for phase and neutral) along with 1 no. single core FRLSH PVC insulated copper wire of size 1.5 sq.mm, 1100V grade for ECC through flexible PVC conduit from ceiling rose connected with Sub-main as per General specification of IE Rule. (PVC wire Make: Havells/Gloster/Polycab/RR Kabel/KEI/Mescab)
Supply, laying, and termination of sub-main wiring comprising 2 run of 4mm² single-core copper conductor 14 PVC FRLSH insulated wires, along with one run of 2.5mm² copper Earth Continuity Conductor (ECC), through suitable size (ISI marked) PVC conduit pipe/casing/ concealed way as per General specification of IE Rule. (PVC wire Make: Havells/Gloster/Polycab/RR Kabel/KEI/Mescab)
Supply, laying, and termination of sub-main wiring comprising 2 run of 4mm² single-core copper conductor PVC FRLSH insulated wires, along with one run of 2.5mm² copper Earth Continuity Conductor (ECC), through G.I. conduit pipe, for shed etc. as per General specification of IE Rule. (PVC wire Make: Havells/Gloster/Polycab/RR Kabel/KEI/Mescab)
Supply, laying, and termination of sub-main wiring comprising 2 run of 4mm² single-core copper conductor PVC FRLSH insulated wires, along with one run of 2.5mm² copper Earth Continuity Conductor (ECC), through G.I. conduit pipe, for shed etc. as per General specification of IE Rule. (PVC wire Make: Havells/Gloster/Polycab/RR Kabel/KEI/Mescab) Unit
II-NS Schedule - ( LED Luminaires ) (LED luminaries should cover a warranty of 60 Above/
Design of mounting layout ,Supply, installation of LED Flood light Luminaire 200W(approx), luminaire 1 efficacy>= 140lm/W with high pressure die cast housing complete with all accessories and conform to minimum IP65 protection rating or higher as per General Specification. Installation/fixing should be made with high cover shed etc. by suitable clamping arrangement etc. (LED Luminaries Make - Bajaj/ Philips/ Havells/Crompton/ Panasonic/ Orient/ Signify/Ecolink)
Design of mounting layout ,Supply, installation for LED street light luminaires of approximately 60W rating, 2 having a minimum luminous efficacy of 120lm/W. The luminaires shall be housed in pressure die-cast aluminium enclosures and conform to minimum IP65 protection rating or higher as per General Specification. Installation/fixing of street light fitting should be made with existing/supplied arm bracket of G.I. pole / Rail pole. (LED Luminaries Make - Bajaj/ Philips/ Havells/Crompton/ Panasonic/ Orient/ Signify/Ecolink)
Designing of mounting layout, Supply, installation, connection and commissioning of LED luminaire 4ft., 3 2X18W or above (min. IP:65, indoor type) including batten complete with all accessories as per General Specification including fixing with G. I. clamps made of G. I. Flat of suitable size & G. I. Nut, bolts etc. (LED Luminaries Make - Bajaj/ Philips/ Havells/Crompton/ Panasonic/ Orient/ Signify/Ecolink)
Design,Supply, installation and mounting layout for integrated LED TUBE LIGHT 4ft. luminaires 1 X 20W 4 (approx.) (Extruded Aluminium LED Batten) (IP:20) (indoor type) as per General Specification including fixing with G. I. clamps made of G. I. Flat of suitable size & G. I. Nut, bolts etc. (LED Luminaries Make - Bajaj/ Philips/ Havells/ Crompton/ Panasonic/ Orient/ Signify/Ecolink)
Design of mounting layout ,Supply, installation for LED street light luminaires of approximately 90W rating, 5 having a minimum luminous efficacy of 120lm/W. The luminaires shall be housed in pressure die-cast aluminium enclosures and conform to minimum IP65 protection rating or higher as per General Specification. Installation/fixing of street light fitting should be made with suitable dia. G. I. bend pipe with G. I. clamps made of G. I. Flat of suitable size & G. I. Nut, bolts etc. (LED Luminaries Make - Bajaj/ Philips/ Havells/ Crompton/ Panasonic/ Orient/ Signify/Ecolink) Unit Above/
III-NS Schedule - (General Electrical Works)
Supply, concrete foundation & erection of GI Octagonal Pole 5.5mtr. Pole section bottom dia 150mm, top dia 1 75mm, pole thickness-3mm with base plate 240 x 240x16mm with 4nos. foundation bolts having 25mm dia & of length 700mm along with single/double arm bracket as per General Specification. Loop in & loop out box to be provided inside the pole. Foundation and erection of G.I octagonal pole along with grouting of supplied 4 nos. foundation bolts as per Drg. No. Sr. DEE(G)'s Drg. No. SDAH/G/SS/115 dt. 23.10.09. (Make-B. P. Projects/Transrail/ Crompton/ Bajaj/ Utkarsh)
Supply, fixing, testing and commissioning of star rated BLDC Ceiling fan, 1200mm sweep, 3 blade (Blade 2 material :High grade Aluminium alloy),Service value:Minimum 7.5, 230V, 50 c/s, and all other accessories as per General Specification(With Remote) including fixing of ceiling fan with suitable clamping arrangement &'S' hook etc. (Make: Havells/ Usha/ Anchor/ Orient/ Crompton/ Bajaj/Atomberg)
Supply, Fixing with suitable G.I clamping arrangement, connection and commissioning of AC Wall Mounting Air Circulator Fan,3 blades, 750mm sweep, 230V, 50c/s complete with all accessories. (Make: Havells/Usha/ Anchor/ Orient/ Crompton/ Bajaj)" "Supply, Fixing with suitable G.I clamping arrangement, connection and commissioning of AC Wall Mounting Air Circulator Fan,3 blades, 750mm sweep, 230V, 50c/s complete with all accessories. (Make: Havells/Usha/ Anchor/ Orient/ Crompton/ Bajaj)
Supply & fixing of 16A MCB protected socket with sheet steel enclosure..MCB rating taken 6A-16A. (Switchgear Make: Siemens/ ABB/ Schneider/ Lauritz Knudsen/ C&S/ Havells/Legrand/ Hager)
Supply, Fixing, connection & commissioning of A.C. Exhaust Fan, 300 mm sweep, 230V, 50 c/s complete with all accessories including fixing with G. I. clamps made of G. I. flat of suitable size & G. I. Nut, Bolts alongwith necessary Masonry works. (Make: Havells/Usha/ Anchor/ Orient/ Crompton/ Bajaj)
Supply, installation, testing, and commissioning of 1 Phase, [2+4] way Distribution Board (Single door, 6 Prewired type) comprising of the following: a) MCB SPN 32A, B/Cap - 10 kA - 1 No. b) MCB SP 10/20A, B/Cap - 10 kA - 4 Nos. Work shall include complete wiring terminations, provision of all necessary mounting hardware, accessories, and interconnections, executed as per site conditions and in compliance with IS/IEC standards (Switchgear Make: Siemens/ ABB/ Schneider/ Lauritz Knudsen/ C&S/ Havells/Legrand/ Hager)
Supply, installation, testing, and commissioning of 3-phase, 4-way TP&N vertical type distribution board 7 (metal double door enclosure, IP:43 rated), comprising the following components: a) 1 No. MCCB, 4-pole, 50-63A, breaking capacity 25kA b) 12 Nos. MCB, single-pole, 16-32A, breaking capacity 10kA The distribution board shall be fixed using suitable ISI-marked G.I. fixtures and accessories, complete in all respects as per site conditions and conforming to relevant IS/IEC standards (Switchgear Make: Siemens/ ABB/ Schneider/ Lauritz Knudsen/ C&S/ Havells/Legrand/ Hager)
Supply & fixing of Electro Mechanical Timer Switch with Contactor unit of cap. 32A for Half Light & Full Light system for Time Switch complete within enclosure along with connection and testing of the same. (Make: Siemens/ ABB/ Schneider/ Lauritz Knudsen/ C&S/ Havells/Legrand/ Hager)
Supply, installation, testing, and commissioning of 4-pole MCCB rated for 50-63A, 415V, with a breaking 9 capacity of 25kA, housed in a suitable sheet steel enclosure. Work shall includes all mounting accessories, terminations, and enclosure fixing as per site conditions, conforming to IS/IEC standards. (Switchgear Make: Siemens/ ABB/ Schneider/ Lauritz Knudsen/ C&S/ Havells/Legrand/ Hager)
Supply, installation, testing, and commissioning of 4-pole MCCB rated for 80-100 A, 415V, with a breaking 10 capacity of 25kA, housed in a suitable sheet steel enclosure. Work shall includes all mounting accessories, terminations, and enclosure fixing as per site conditions, conforming to IS/IEC standards. (Switchgear Make: Siemens/ ABB/ Schneider/ Lauritz Knudsen/ C&S/ Havells/Legrand/ Hager)
Supply, installation, testing, and commissioning of 4-pole MCCB rated for 160-200A, 415V, with a breaking 11 capacity of 35kA, housed in a suitable sheet steel enclosure. Work shall includes all mounting accessories, terminations, and enclosure fixing as per site conditions, conforming to IS/IEC standards. (Switchgear Make: Siemens/ ABB/ Schneider/ Lauritz Knudsen/ C&S/ Havells/Legrand/ Hager)
Supply, installation, testing, and commissioning of 4-pole MCCB rated for 320-400A, 415V, with a breaking 12 capacity of 36kA, housed in a suitable sheet steel enclosure. Work shall includes all mounting accessories, terminations, and enclosure fixing as per site conditions, conforming to IS/IEC standards. (Switchgear Make: Siemens/ ABB/ Schneider/ Lauritz Knudsen/ C&S/ Havells/Legrand/ Hager)
Design, Supply, Installation, testing and commissioning of MS fabricated wall/floor mounted, hinged type cubicle panel board made of (14 SWG) MS sheet duly powder coated, comprising with the following :- a) MCCB, 320-400A, 4 Pole, 415V,B/Cap:36kA - 2 nos., b)MCCB, 250-320A, 4 Pole, 415V,B/Cap:36kA - 4 nos., c) MCCB, 80-100A, 4 Pole, 415V, 13 B/Cap:25kA - 2 nos. d)MCCB, 25-32A, 4 Pole, 415V, B/Cap:25kA - 4 nos. e) Copper Busbar 4 bar type, 600A - 1 set including internal electrical connections with suitable size of wire / bar and provision of digital type LT CT operated multifunction energy meter,3 ph,4 wire: 2 nos. ; Digital type Ammeters with CT and modular LED indicators etc. along with transportation charges. (Switchgear Make: Siemens/ ABB/ Schneider/ Lauritz Knudsen/ C&S/ Havells/Legrand/ Hager) (Meter Make: Selec/Secure/Lauritz Knudsen/ HPL/Schneider)
Supply and installation of medium duty GI Earth Pipe of 50 mm dia., 3 Mtr. long, including proper connection with 8 SWG GI wire using suitable clamps and fasteners etc., complete with testing, commissioning, and in conformity with relevant IS codes, electrical safety standards. (G.I. Pipe Make: TATA/ Jindal / Bansal )
Supply and installation of GI Standard Earth pipe, 40 mm dia, 2000 mm long, medium gauge complete with 15 provision of Earth pit and there connection with 4 SWG GI wire complete with testing and commissioning, strictly in accordance with relevant IS codes, electrical safety standards.as per Sr. DEE(G)/SDAH's Drg. No. SDAH/G/MISC/47 dt.21.11.2008(Alt-1). (G.I. Pipe Make: TATA/ Jindal / Bansal )
Dismantling of existing damaged Rail Pole/Tubular Pole. Rail Pole/Tubular Pole to be cut by Gas cutter from the least bottom level. Released Rail Pole to be stacked in an isolated area apart from platform. Released Tubular Pole to be deposited to the custody of concerned Sr. SEE (G) by the Firm. Exposed Cables to be cleared or buried in to the ground.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
FormatofGuaranteeBond.pdf
ATTACHMENT
2022_CE-I_CT_GCC-2022Policy14_07_20221.pdf
ATTACHMENT
GCC-April-2022.pdf
ATTACHMENT
LTHTElectricalBooklet.pdf
ATTACHMENT
LEDluminariesSpecifications_2.pdf
ATTACHMENT
OpenTenderDocument.pdf
ATTACHMENT
2026_03_13IndianRailwaysStandardGeneralConditionsofContractApril2022AdvanceCorrectionSlipNo_111.pdf Correction
ATTACHMENT
Advance
ATTACHMENT
2025_01_09IIndianRailwaysStandardGeneralConditionsofContractApril-2022AdvanceCorrectionSlipNo_9ACS-9.pdf
ATTACHMENT
2026_03_13IndianRailwaysStandardGeneralConditionsofContractApril2022AdvanceCorrectionSlipNo_111.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].