Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹43.9 LAccepted-AOC 159 KASIYADIH TANDWA CHATRA CHATRA JHARKHAND 825321 | CHATRA | JHARKHAND | 825321 | L1 | Accepted-AOC L1 bidder is techno commercially qualified. | |
| 2 | Rejected-Technical AT KARGALI BAZAR BERMO DIST BOKARO JHARKHAND PIN 829104 | BERMO | BOKARO | JHARKHAND | 829104 | - | Rejected-Technical Bid not opened as per NIT terms. | |
| 3 | Rejected-Technical AT GUNJARDIH BHANDARIDAH DIST BOKARO PIN 829132 | BHANDARIDAH | BOKARO | JHARKHAND | 829132 | - | Rejected-Technical Bid not opened as per NIT terms. |
Tender Value
Refer Docs
EMD Value
₹50,600
Closing Date
20 May 2023, 9:00 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Staff Officer (EnM)
Office of the General Manager, Dhori Area
Day to day extension/re-organisation of 3.3kV OH line in mine for shovels operation and pumping at SDOCM, Dhori Area
2023_CCL_278415_1
GM(D)/SO(EnM)/DA/2023-24/10
Open Tender
Electrical and Maintenance Works
Item Wise
365 days
Dhori Area
Please refer Tender documents.
2 documents required · 2 mandatory
₹50,600
29 May 2023
3 May 2023
22 May 2023
4 May 2023
20 May 2023
4 May 2023
4 May 2023 - 12 May 2023
Amount
Erection of steel tubular pole of length exceeding 10 mtrs but not exceeding 12 mtr in cement concrete 1:3:6 (1 cement :3 coarse sand :6 graded stone aggregate 40 mm nominal size ) foundation including excavation and refilling etc as required ( pole supply by department )
Erection of all aluminium conductor of 7/1.96 mm to 7/3.10 mm diameter including binding etc. as required.
Supplying and erection of galvanised stay set for 11 KV over head lines complete with 19/ 20 mm dia X 1.8 metres long stay rod, anchor plate of size 45 cm X 45 cm X 7.5 mm thick, thimble, stay clamps, turn buckle ( 20 mm X 600 mm ), 7/ 3.15 mm dia G.I. stay wire and 11 KV strain insulator etc in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size ) foundation including excavation and refilling etc. as required
Supplying and erection of 11 KV disc insulator for 11 KV over head lines with galvanised insulator fittings, ball and socket type and complete with galvanised strain clamps, bolts, nuts, washers etc. as required.
Supplying and erection of 11 KV pin insulator complete with large steel head G.I. pin, nuts, washers etc. as required
Erection of disc insulator for 11 KV over head lines as required.
Erection of pin insulator for 11 KV over head lines as required.
Supply and errection of 8 SWG GI wire for earth continuity
Supply and errection of 8 SWG GI wire for earth continuity and cradling
Erection of cradle wire
Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) cross arm for 2 wire over head line complete with clamps, bolts, nuts and washer etc including drilling of holes for insulator pins etc (as per drawing) and painting with primer and finished paint as required .
Erection of pole top/ straight two wire/ V shape two wire, angle iron/ channel iron, cross arm on steel tubular/ rail/ PCC pole for 11/22/ 33 KV as required.
Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) cross arm for two 11 KV over head line conductors complete with 50 mm X 50 mm X 6 mm (angle iron bracket welded to the channel iron and complete with 50 mm X 6mm M.S. flat iron clamps, bolts and nuts including drilling holes for insulator pins, bolts, nuts and washers etc (as per drawing) and painting with primer and finish paint as required
Erection of double pole 3 wire cross arm for 11KV over head lines as required.
Supplying and erection of a set of cross bracing FRLSame work for11 KV over head line double pole structure having four members fabricated out of 50 mm X 50 mm X 6 mm angle iron to form a rectangle of minimum size 1400 mm width X 2500 mm height, complete with 50 mm X 6mm M.S. flat iron clamps, bolts and nuts including drilling holes for insulator pins, bolts and nuts etc (as per drawing) and painting with primer and finish paint as required.
Supply and fixing of clamps, nut bolts etc
Dismantling of pole/ street light standard/ strut embedded in cement concrete foundation etc. as required.
Transporting of pole from dismantle place to proposed place
Dismantling of over head lines comprising of copper/ aluminiumover head conductor, G.I. wire, cross arms, insulators etc. as required
Laying of one number additional PVC insulated and PVC sheathed/ XLPE power cable of 11 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc. as required. Upto 120sqmmafter pole mounting for shovels at different time cable disconnection/connection from top of pole 55 times for marching of handling of power cable
Total impact of GST for the purpose of CTC
MAHTO ENTERPRISES
M/S SHIV PARBATI ENTERPRISES
stage.html
html • 0.04 MB
techsummary_288224.pdf
PDF • 3.97 MB
finsummary_288224.pdf
PDF • 3.97 MB
10Awo.pdf
PDF • 3.76 MB
BOQ Comparative Chart
xlsx • 0.01 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .