| Sl No | Description | Qty | Unit | ANNAI ELECTRICALS L3 | KARTHIKEYAN ELECTRICALS L1 | SASTHA ELECTRICALS L2 |
|---|---|---|---|---|---|---|
| 1.00 | Design, Engineering, supply, fabrication, erection, testing, commissioning and handing over of 1 No 13 persons capacity passenger lift Gearless with machine room (KONE / OTIS /JHONSON) speed 1.5m/s with stainless steel panels, disable friendly, microprocessor based controller, VVF drive fire rated doors and ARD (for Differently abled persons withnecessary accessibility features as per standards) as per the following technical specifications with free Guarantee period of one year from the date of commissioning.
Technical specifications:
1. Type of lift : Passenger lift
2. Capacity of lift : 13 persons capacity passenger lift
3. Speed : 1.50 Meter/Sec
4. Type of Drive: specific variable voltage variable frequency V3F drive with enhanced ride comfort and leveling functions.
5. No. of floors: Ground + 1 floor
6. Leveling Accuracy: High level | 1 | No. | 20,33,000 ₹20.3 L | 19,57,000 ₹19.6 L | 20,04,500 ₹20.0 L |
| 1.017. Construction of Car: 18 SWG high quality stainless steel car, powder coated stretcher impact protection car size 2400 mm(D) x 1600 mm(W). 8. Position of machine: Directly above the lift well 9. No. of landing entrance: 2Nos 10. No. of car entrance: one in front only 11. Car entrance door: power operated. 12. Car entrance door: power operated center opening sliding 18 SWG stainless steel vandal proof door with provision for emergency key opening at all landings. 13. Lift well : existing (as per IS) 2700mm wide x 2300mm Deep | ||||||
| 1.0214. Car clear opening: as required (as per IS 14665) (part I) – 2000) 1200mm Height 15. Power supply: 400/415 V, 3 phase, 50 Cy/sec., A.C. supply for power and 230 V, 50 HZ, single phase, AC supply for light. 16. Control: Micro computer (Micro processor) based simplex selective collective control with/without attendant. 17. Car fitting: Glare free LED lighting with 300mm sweep cabin fan with elegant look and with comfortable ventilation inside the car. 18. Lift well: R.C.C. construction with brick masonry | ||||||
| 1.0319. Indication: UP/Down digital direction and position indicator for all landing and in car 20. Emergency alarm bell: Battery operated alarm bell to be provided with Automatic charging device 21. Emergency light: Battery operated light to be provided with Automatic charging device 22. Fire Man’s switch: To be provided at ground floor | ||||||
| 1.0423. Minor builders work: included in the scope. 24. Scaffolding: Included in the scope 25. Sill angles and facia plates: included in the scope 26. Steel for lift machinery: Included in the scope | ||||||
| 1.0527. Servicing and maintenance: Free comprehensive servicing and maintenance should be provided by lift contractor during the guarantee period of one year. 28. Automatic Rescue device: To facilitate the landing of the lift to the nearest floor at the time of power failure. This shall consist of suitable type battery system with charger, invertor, under voltage protection system etc., complete with all accessories. | ||||||
| 1.0629. Provision of intercom with phone: To be provided by lift contractor with one handset in the lift car and another handset in the lift machine room with telecom exchange unite with one trunk and three extension linked proton 103 matrix telecom unit and required length of single twisted pair with thickness of 0.5 mm to 1 mm connecting the handsets and telecom exchange unit. 30. Lift License: Preparation of Drawing, payment of charges to CEIG and insurance policies if any and obtaining CEIG safety certificate as per lift act should be done by lift contractor. 31. Floor announciator with music. 32. Special features: a. Infra red door sensor with full height screen. b. Full width half height rear panel mirror. c. Tubular stainless steel hand rail in cars. | ||||||
| 1.07d. Voltage stabilizer for circuit control. e. Stainless. Steel signal fixtures. f. Vandal proof S.S. Button with S.S. cover g. SS door frames for landing doors. h. VF door operator. i. Call Register signal | ||||||
| 1.08j. Stainless steel facia plate for car operating panel and landing fixtures. k. On – Off switch for fan and light l. Over load warning indicator with audio announcement 33. Other standard features: Over speed governor, phase failure and phase reversal relay, T. Guide brackets for car and counter weight, rubber padding under winding unit, motor of adequate capacity, electro mechanical door locks emergency keyside supporting angles, motor over load protection devices final limit switch main suspension ropes counter weights lifting joist for mounting the machineries | ||||||
| 1.0934. Site testing in accordance with IS 14665 should be carried out at the time of handing over. 35. Supply of operation and maintenance manual with necessary tools for operation. 36. Guarantee: Free Guarantee for the materials and workmanship of equipments complete should be offered by lift firm for a period of one year from the date of commissioning.(KONE / OTIS /JHONSON) | ||||||
Tender Value
₹23.6 L
EMD Value
₹21,800
Closing Date
11 Feb 2026, 3:00 pmClosed
Superintending Engineer
Office of Superintending Engineer PWD Buildings construction and maintenance circle Madurai
Providing 1No of 13 Person Passenger Lift for Differently abled Person to the Combined Court building at Peraiyur in Madurai District
2026_PWD_649040_1
49SE/Bldgs C and M Circle Madurai 2025-26 dated 27.01.2026
Open Tender
Electrical Works
90 days
Peraiyur, Madurai District
Please refer Tender documents.
3 documents required · 3 mandatory
₹0
₹21,800
10 Jun 2026
2 Feb 2026
11 Feb 2026
2 Feb 2026
11 Feb 2026
2 Feb 2026
Design, Engineering, supply, fabrication, erection, testing, commissioning and handing over of 1 No 13 persons capacity passenger lift Gearless with machine room (KONE / OTIS /JHONSON) speed 1.5m/s with stainless steel panels, disable friendly, microprocessor based controller, VVF drive fire rated doors and ARD (for Differently abled persons withnecessary accessibility features as per standards) as per the following technical specifications with free Guarantee period of one year from the date of commissioning. Technical specifications: 1. Type of lift : Passenger lift 2. Capacity of lift : 13 persons capacity passenger lift 3. Speed : 1.50 Meter/Sec 4. Type of Drive: specific variable voltage variable frequency V3F drive with enhanced ride comfort and leveling functions. 5. No. of floors: Ground + 1 floor 6. Leveling Accuracy: High level
7. Construction of Car: 18 SWG high quality stainless steel car, powder coated stretcher impact protection car size 2400 mm(D) x 1600 mm(W). 8. Position of machine: Directly above the lift well 9. No. of landing entrance: 2Nos 10. No. of car entrance: one in front only 11. Car entrance door: power operated. 12. Car entrance door: power operated center opening sliding 18 SWG stainless steel vandal proof door with provision for emergency key opening at all landings. 13. Lift well : existing (as per IS) 2700mm wide x 2300mm Deep
19. Indication: UP/Down digital direction and position indicator for all landing and in car 20. Emergency alarm bell: Battery operated alarm bell to be provided with Automatic charging device 21. Emergency light: Battery operated light to be provided with Automatic charging device 22. Fire Man’s switch: To be provided at ground floor
23. Minor builders work: included in the scope. 24. Scaffolding: Included in the scope 25. Sill angles and facia plates: included in the scope 26. Steel for lift machinery: Included in the scope
27. Servicing and maintenance: Free comprehensive servicing and maintenance should be provided by lift contractor during the guarantee period of one year. 28. Automatic Rescue device: To facilitate the landing of the lift to the nearest floor at the time of power failure. This shall consist of suitable type battery system with charger, invertor, under voltage protection system etc., complete with all accessories.
29. Provision of intercom with phone: To be provided by lift contractor with one handset in the lift car and another handset in the lift machine room with telecom exchange unite with one trunk and three extension linked proton 103 matrix telecom unit and required length of single twisted pair with thickness of 0.5 mm to 1 mm connecting the handsets and telecom exchange unit. 30. Lift License: Preparation of Drawing, payment of charges to CEIG and insurance policies if any and obtaining CEIG safety certificate as per lift act should be done by lift contractor. 31. Floor announciator with music. 32. Special features: a. Infra red door sensor with full height screen. b. Full width half height rear panel mirror. c. Tubular stainless steel hand rail in cars.
d. Voltage stabilizer for circuit control. e. Stainless. Steel signal fixtures. f. Vandal proof S.S. Button with S.S. cover g. SS door frames for landing doors. h. VF door operator. i. Call Register signal
j. Stainless steel facia plate for car operating panel and landing fixtures. k. On – Off switch for fan and light l. Over load warning indicator with audio announcement 33. Other standard features: Over speed governor, phase failure and phase reversal relay, T. Guide brackets for car and counter weight, rubber padding under winding unit, motor of adequate capacity, electro mechanical door locks emergency keyside supporting angles, motor over load protection devices final limit switch main suspension ropes counter weights lifting joist for mounting the machineries
34. Site testing in accordance with IS 14665 should be carried out at the time of handing over. 35. Supply of operation and maintenance manual with necessary tools for operation. 36. Guarantee: Free Guarantee for the materials and workmanship of equipments complete should be offered by lift firm for a period of one year from the date of commissioning.(KONE / OTIS /JHONSON)
Supply and fixing of WT bulk head fitting with guard suitable with 7W / 9W LED bulb.
Supply and fixing of 5A / 15A 3 pin combined flush type wall socket with 15A flush type switch on suitable MS Box with painting.
Supply and run of 2 of 4 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100V grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 4 sq.mm copper wire and making good of the concealed portion with suitable colour.
Supply and fixing of 1no. 6/16A two module socket, 1 no. 16A one module switch with module cover plate (plastic) on suitable module concealed Box (GI) in flush with wall with connections. Higher End.
Supply and run of 2 of 4sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100V grade in suitable heavy gauge MS coundit pipe on wall and ceiling with continous earth wire connection of 4 sq.mm copper wire with painting of suitable colour.
Supply and fixing of 32A DP MCB in sheet enclosure in flush with wall with earth connection. [The MCB and metal enclosure should be of Higher End].
Supply and fixing of 8 way single pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1 no. 32A DP MCB switch as incoming and 6 nos. 6A to 32A SP MCB as outgoing in flush with wall with earth connection only. Higher End.
Supply and Run of 2 of 6 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100V grade in suitable gauge MS conduit pipe on wall and ceiling with continuous earth wire connection of 6 sq mm copper wire with painting of suitable colour.
Supply and fixing of 63A TPN switch disconnector fuse units in sheet steel enclosure with HRC fuses double brEak on suitable angle iron frame work with MS cable entry boxes with Earth connection only.
Supply and fixing of 63A TPN Switch Disconnector Fuse Units interior only cubicals with HRC Fuses Double Break, interconnections of 3/4" x 1/8" tinned copper flat with sleeves from bus to 63A TPN switch and no.8 SWG copper conductor for switch earthing and necessary connection complete.
Supply and fixing of 63A FP MCB in sheet enclosure in flush with wall with earth connection. [The MCB and metal enclosure should be of Higher End].
Supply and clamping of 3-1/2 x 25 sq.mm. aluminium PVC LTUG armoured cable on post or on wall with MS clamps.
Supply and fixing of brass cable gland for 3-1/2 x 25 sq.mm. aluminium PVC armoured LTUG cable with earth connection.
Supply and providing cable end termination of 3-1/2 x 25 sq.mm. aluminium PVC LTUG aluminium armoured cable with necessary aluminium cable sockets by crimping etc with electrical connection complete.
Earthing as per the ISI specification with an earth electrode of 2.1mt class 'B' GI pipe of dia not less than 40mm, with copper earth plate of size 125mm x 50mm x 6mm, with necessary funneling arrangements with necessary masonry work and with 38mm RCC cover slab for the brick masonry.
Supply and run of 0.3 mtr length 25 x 3 mm tinned copper flat with necessary procelain insulator supports on wall for earth connection.
Supply and Run of 1 of No.8 SWG copper wire in suitable PVC rigid pipe on wall / floor / ground for earth connection.
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.04 MB
BOQ_778103.xls
BOQ • 0.28 MB
Formperaiyurelectrical.pdf
Tender Documents • 1.36 MB
Download all tender documents and submit your bid