Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹45.3 LAccepted-AOC | L1 | Accepted-AOC Lowest bid value | |
| 2 | L2₹45.6 L+₹31,515.50 (0.70%)Rejected-AOC HOUSE NO 99 3RD FLOOR SK JAIN BUILDING KALIBARI ROAD DIMAPUR 797112 NAGALAND | DIMAPUR | DIMAPUR | NAGALAND | 797112 | L2 | Rejected-AOC Higher bid value | |
| 3 | L3₹46.0 L+₹71,763.30 (1.58%)Rejected-AOC | L3 | Rejected-AOC Higher bid value | |
| 4 | L4₹46.1 L+₹77,836.60 (1.72%)Rejected-AOC | L4 | Rejected-AOC Higher bid value |
Tender Value
₹44 L
EMD Value
₹88,000
Closing Date
28 Nov 2024, 6:00 pmClosed
GE 868 EWS
GE 868 EWS PIN- 913 868 C/o 99 APO
REPAIR MAINT OF DG SETS STABLIZERS AMF PANELS AND CONNECTED WK IN THE AREA OF AGE EM AT RMS
2024_MES_681980_1
8809/C/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
RANGAPAHAR
Class D
Category b(i)
2 documents required · 2 mandatory
₹500
GE 868 EWS
₹88,000
3 Dec 2024
1 Nov 2024
30 Nov 2024
1 Nov 2024
28 Nov 2024
14 Nov 2024
1 Nov 2024 - 7 Nov 2024
Amount
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m depth for foundation of poles, cables etc, not exc 10 sqm on plan and getting out in soft/ loose soil including taking out brick protection etc complete all as specified
Returning filling in trenches including spreading leveling watering and well ramming in layers not exceeding 25 cm thick all etc complete all as specified and as directed.
Removing of excavated material (soil) not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point all etc complete all as specified and as directed.
M&L for spread fine river sand in trenches complete all as specified ans as directed. Note: For measurement purpose, punned down thickness shall only be taken.
M&L for laying brick sub class 'B' old size burnt bricks for cable protection of size 230mmx115mmx75mm complete all as specified and as directed
Supply and fixing galvanised iron tubing 40 mm bore, light grade with all fittings for passing of under ground cable including taking down old pipe etc complete all as specified and as directed.
All as per Ser item No 6.00 (here-in-before) but 50mm bore
Material and labour for dismantling the servo volatge satbiliser in position upto capacity 400 KVA including taking down all incoming/ outgoing connection and lifting of core from the stabiliser for identification of fault and reassembling after rectification of fault. Note:- Spares reqd for replacement shall be paid under the respective item as under.
M & L for servicing of servo voltage stablizer including refresh the all connection, greasing, and following testing:- (i) Testing of oil (ii) testing of insulation resistance (ii) testing of leakage current and output voltage all as specified and directed by Engr in charege.( Note : if oil found unsv the oil replaced with fresh transformer oil and transformer oil shall be paid under the respective item as under)
S & F in replacement of defective electronic circuit card (PCB) and making electrical connection for servo voltage stablizer of any make and cap upto 400 KVA complete all as specified and as directed.
S & F in replacement of defective microproccessor based contro card for each phase and making electrical connection for servo voltage stablizer of any make and cap upto 400 KVA complete all as specified and as directed.
S & F in replacement of defective trigger transformer and making electrical connection for servo voltage stablizer of any make and cap upto 400 KVA complete all as specified and as directed.
S & F in replacement of defective servo motor 3 Kg torque and making electrical connection complete all as specified and as directed.
All as per Ser item No 13.00 (here-in-before) but 10 Kg torque
S & F in replacement of RC network for servo motor 3 Kg torque and making electrical connection complete all as specified and as directed.
All as per Ser item No 15.00 (here-in-before) but 10 Kg torque
S & F in replacement of unserviceable carbon brush suitable for servo voltage stablizer of any make and cap upto 400 KVA complete all as specified and as directed and making all electrical connections complete all as specified and as directed.
S & F in replacement of Dimmerstat for servo voltage stablizer of any make and cap upto 100 KVA and making electrical connection complete app as specified and directed by Engr-in-Charge.
All as per Ser item No 18.00 (here-in-before) but dimmerstat cap 100-150 KVA.
All as per Ser item No 18.00 (here-in-before) but dimmerstst cap 200-400 KVA
Repalcement of main transformer for servo voltage stablizer of any make and cap upto 400 KVA and making electrical connection etc complete all as specified and as directed.
Supply only transformer oil strength not less than 40 KV at 4mm gap etc complete all as specified and as directed.
Supply, laying & testing XLPE insulated screened PVC bedded galvanised steel strip or wire armoured, electric power cable (Heavy duty) with stranded aluminium conductor 1100 volts grade of size 35 Sqmm 3.5 core incl taking out old unsv cable from trenches all as specified and as directed.
All as per Ser item No 23.00 (here-in-before) but 50 sqmm 3.5 core size.
All as per Ser item No 23.00 (here-in-before) but 70 sqmm 3.5 core size.
M&L for PVC/XLPE insulated twin core aluminum stranded conductor round/flat cable size 10 Sqmm 1100 Volts grade served with an sheathing of PVC tape and overall PVC shaetehed in service connection suspended by insulating hangers not more than 1 mtr apart including 4mm GI suspension wire incl taking down old unsv cable.
All as per Ser item No 26.00 (here-in-before) but 16 Sqmm
Material and Labour for Earthing complete with galvanized steel earth plate 60cm x 60cmx6mm thick electrode, burried directly in ground (earth pit not less than 2.25 meters deep below ground level) with top edge of earth plate at a depth not less than 1.5 mtrs below normal ground level, connected to GI wire 4mm size up to test point by means of nuts, bults, check nuts and washers of GI including excavation and earth work, PCC (1:3:6) type C1 pit 20mm dia GI pipe, medium grade watering pipe and 15 mm bore GI pipe, light grade for protection of earth wire, 50mm thick RCC 1:2:4 type B-1 cover reinforced with 8mm dia TMT bars @ 15cm C/C both ways and with handle made out of 10mm dia bars, funnel, wire mesh etc complete as shown in electrical Plate No 03 of SSR Part-I connected to earthing test point all as specified or indicated including testing on completion complete all as specified and directed
All as per Ser item No 28.00 (here-in-before) but using galvanised iron strip 32x6mm as earthing lead.
Supply and Fixing of MCCB, 4 pole, 250 Amps, 415 V, 36 KA breaking capacity, thermal magnetic release type including taking down old one etc complete all as specified and as directed.
All as per Ser item No 30.00 (here-in-before) but MCCB, 200 amps 4 pole.
All as per Ser item No 30.00 (here-in-before) MCCB,, 160 Amps 4 pole ,
All as per Ser item No 30.00 (here-in-before) but MCCB, 125 Amps, 4 pole
Supply and fixing 415V 10KA 'B' curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the DB complete with connection testing and commissioning TPN/FP 40 to 100 AMP etc complete all as specified and as directed.
Supply and fixing 415V 10KA 'B' curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the DB complete with connection testing and commissioning TP 63 Amp all as specified and directed by Engr-in-Charge.
Supply and fixing amp rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the MCB DB complete with connection testing and commissioning SPN 40 to 63 AMP all as specfied and directed by Engr-in-Charge.
Preparation of old painted surfaces of voltage stabiliser after scraping existing painted surfaces and priming with one coat of red oxide over two coats synthetic enamel colored as approved by engr -in - charge and GE etc complete all as specified and as directed.
Repair/ Replacement of maintenance free starting battery 12 volts, 26AH including copper terminal and lugs all as specified and directed by engineer in charge. etc complete all as specified and as directed.
Repair of Thyristor type NASU system (Make: CCR ) by providing OEM service engineer including repairing/replacing of defective CCRs by identifying the fault, replacement of defective PCBs and other components and complete checking Thyristor type NASU capacity 4KW Note: (i) All the components reqd for repairing to make ther CCR serviceable shall be provided by the contractor and measured separately.. (ii) The CCR shall be repaired and serviced by OEMs Rep/ his auth rep only.
Calibration of Thyristor type NASU system (Make: CCR ) by providing OEM service engineer including servicing complete all as directed . Note: (i) Calibration and servicing of CCR will be carried out quarterly. (ii) Each CCR test will be carried out and calibration report will be submitted to department. (iii) The CCR shall be calibrated and serviced by OEMs Rep/ his auth rep only. (iv) Servicing includes dusting, cleaning, checking of all conection and making the connection healty.
Supply of Main contract card including RMS to DC converter card and taking out unsv card complete all a specified.
Supply of Over current trip and taking out unsv card complete all a specified.
Supply of Relay card-02 Nos and taking out unsv card complete all a specified.
Supply of TTM card and taking out unsv card complete all a specified.
Supply of 24 Volt DC plug in type relay and taking out unsv relay complete all a specified.
Supply of 48 volt DC plug in type relay suitable for 11 pin socket and taking out unsv relay complete all a specified.
Supply of 240 volt AC plug in type relay and taking out unsv relay complete all a specified.
Supply of of thyristor 65 RK 160 and taking out unsv part complete all a specified.
Supply of HRC fuse link 32 Amps Set of 02 Nos and taking out unsv fuse complete all a specified.
Supply of HRC fuse link 4 Amp and taking out unsv fuse complete all a specified.
Supply of 02 pole 8 way brilliancy switch Rotary , MB type and taking out unsv switch complete all as specified.
Supply of Power transistors MJ 11016 (Set of 02 Nos) and taking out unsv part complete all a specified.
Supply of 30 Amp conductor (Mode: 3TF33) suitable for 4Kwh NASU and taking out unsv part complete all a specified.
Supply of high speed semi conductor protection fuse GSB 50 suitable for 4 KW CCR etc complete all as specified and as directed.
Supply and fix digital true RMS meter 10 amp for CCR etc complete all as specified and as directed.
Supply and fix digital true meter 100 micor amp DC coil moving meter (96x 96) all as specfied and directed
Supply and fix lighting arrestor 4.5 KV grade suitable for 4 KW CCR etc complete all as specified and as directed.
Supply and fix LED lamp Green, yellow and red as per existing suitable for 4 KW CCR etc complete all as specified and as directed.
Taking out the connection from mains and carried out bypass arrangement and disconnectin the connection of Online UPS upto 30 KVA and transporting to workshop and return back after repair with replacement of following items all as required and directed at site .Note :Cost of Item will be paid seperately
Supply only the cared IGBT card with fixing etc all as specified and directed.
Supply only the driver card complete etc all as specified and directed.
Supply only control card complete etc all as specified and directed
Supply only the Transformer copper wound suitable as per sample all as specified and directed
Repair/Maintenance to of Mechical laundary plant including replacement of whole wiring and control panel for superfab make washer complete all as specified and as directed.
Replacement of Rubber buffer,Spring Set and balancing for hydro extractor 15Kg superfab complete all as specified and as directed.
Replacement Periodic Servicing,inspection and overhauling of front load washing machine,hydro extractor,drying tumbler and flatbed press complete all as specified and directed.
Repair/ Replacement of maintenance free starting battery 12 volts,42 AH etc all as specified and directed by engineer in charge. MAKE : EXIDE/ AMARON
S &F in replacement On load change over switch 4 pole, 250 Amp rating, 415 Volts, with steel enclosure and front handle type including connection lugs and testing complete etc all as specified and directed. Make-Havells/standard or equIvalnet.
S & F in replacement On load change over switch 4 pole, 160 Amp rating, 415 Volts, with steel enclosure and front handle type including connection with lugs and testing complete etc all as specified and directed. Make-Havells/standard or equIvalent.
S & F in replacement Manual change over switch 4 pole, 200 Amp rating, 415 Volts, with steel enclosure and Side handle operated type including connection with Lugs and testing complete etc all as specified and directed.
M & L for repair/ replacement of unserviceable components/ parts (such as power circuit board (PCB) time relay, socket outlet, regulators/toggle switch, voltmeter ,indicator lamp, circuit wiring fuse etc) for of voltage stablizer cap 4-5 KVA etc complete all as specified and as directed.
Sunpply and fixing of 4.00 Sqmm 4 core multi stranded copper conductor cable (FRLSH) 1100 Volt grade drawn through 20/25 mm dia PVC Casing Caping after and inclduing taking down existing submain wiring complete all as specified and as directed.
Supply and fix airfield halogen light of 6 Amp cat part No 58373 all as specified and directed by Engr-in-charge.
M & L for repair/ replacement of unsv contactor, relay, wiring kit suitable for 100 to 160 KVA AMF panel or as per sample all as specified and directed by Engr-in -Charge.
VAISHNO ASSOCIATES (BID ID -3175493)
M/s K P Enterprises (BID ID -3176235)
M/S VIKASH TRADERS (BID ID -3176370)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .