Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.1 LAccepted-AOC 15 15 KHERIYA BHAN PURANI CHAWANI GWALIOR GWALIOR GWALIOR MADHYA PRADESH 474010 | GWALIOR | MADHYA PRADESH | 474010 | L1 | Accepted-AOC L1 bidder and quoted rates are reasonable. | |
| 2 | L2₹21.8 L+₹27,450 (1.27%)Rejected-Finance C 40 BHAGAT SINGH NAGAR BHIND ROAD GWALIOR MP 474005 | NA | NA | 474005 | L2 | Rejected-Finance Not Lowest | |
| 3 | L3₹22.3 L+₹73,940 (3.43%)Rejected-Finance NARMADA COLONY BARADARI CHOURAHA MORAR GWALIOR 474006 | GWALIOR | MADHYA PRADESH | 474006 | L3 | Rejected-Finance Not Lowest | |
| 4 | L4₹24.6 L+₹3.0 L (13.9%)Rejected-Finance 23 A MORAR ENCLAVE GOLA KA MANDIR MORAR GWALIOR MP 474005 | GWALIOR | GWALIOR | MP | 474005 | L4 | Rejected-Finance Not Lowest | |
| 5 | L5₹24.6 L+₹3.0 L (14.0%)Rejected-Finance | L5 | Rejected-Finance Not Lowest |
| Sl No | Description | Qty | Unit | MONA GENERATOR SEVICES PVT. LTD. L9 | M/S KAPIL CONSTRUCTION CO L8 | somyaenterprises L5 | M/s Tirupati construction L3 | M/S Rajeev Construction L4 | M/S uneversal agency L7 | SHRI HARI CONSTRUCTION L2 | SIDDHIDATRI CONSTRUCTION L6 | AUTOMATION AND SWITCHGEAR PANELS L1 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Supply and erection of Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9.00 meters long) including painting of poles with two coats of aluminium paint over a coat of red oxide primer on all exposed surfaces and black bituminous paint on embedded portion and Zebra marking on pole with black paint up to one meter height above PCC coping including pasting of radium reflector band / strips (Make: 3M or equivalent) of 5cm wide in Green (02 Nos) & White (01 No.) colour shall be provided at a height of 1.25mtr from coping of pole and writing the pole number in black colour on yellow background at a suitable place on the pole including taking down existing unserviceable pole of any description complete all as specified and directed.
(Note: Excavation and concrete shall be measured and paid separately). | 35 | Each | 23,503 ₹8,22,605 | 16,500 ₹5,77,500 | 14,500 ₹5,07,500 | 17,000 ₹5,95,000 | 17,000 ₹5,95,000 | 18,000 ₹6,30,000 | 14,900 ₹5,21,500 | 16,500 ₹5,77,500 | 13,000 ₹4,55,000 Lowest |
| 2.00 | Supply & fix Junction box of size 280 X 170 X 130 mm Hinged (L) wiith 2 way connector mounted on epoxy insulators for looping of cable for 1 Phase and 1neutral fixed on pole with the help of MS nuts bolts and MS clamps-2 Nos of size 40 mm X 4 mm thick with one No MCB SP 6 Amp capacity mounted on din rail inside box. work also includes making suitable hole in pole to take out connections to fitting if required at site and provisioning of 1.0 sqmm 3.0 core flexible PVC insulated copper cable from junction box to connector of street light complete all as specified and directed. | 35 | Each | 1,204 ₹42,140 | 500 ₹17,500 Lowest | 2,400 ₹84,000 | 800 ₹28,000 | 1,500 ₹52,500 | 1,000 ₹35,000 | 850 ₹29,750 | 1,250 ₹43,750 | 1,250 ₹43,750 |
| 3.00 | M&L for removal of street light along with bracket carefully and refixing on new poles including connection complete all as specified and directed. | 35 | Each Job | 194 ₹6,790 | 100 ₹3,500 | 500 ₹17,500 | 250 ₹8,750 | 250 ₹8,750 | 300 ₹10,500 | 200 ₹7,000 | 2,700 ₹94,500 | 50 ₹1,750 Lowest |
| 4.00 | M&L for aluminium conductor steel reinforced (ACSR) on pole stringing properly on insulators and binding with aluminium binding wire, jumper set complete for any size (Ferret, Wessal, Squirel) of conductor complete all as specified and as direcetd.
(NOTE:- Measurement and payment shall be made by measuring horizontal distance between centre of two adjustant poles and adding 3% extra for sag, joints and jumpers etc) | 3 | Per Qtl | 36,793 ₹1,10,379 | 33,600 ₹1,00,800 | 8,500 ₹25,500 Lowest | 17,000 ₹51,000 | 25,000 ₹75,000 | 12,000 ₹36,000 | 21,000 ₹63,000 | 8,500 ₹25,500 Lowest | 18,000 ₹54,000 |
| 5.00 | M & L for cross arms, bracing, supports, clamps and back plated fabricated from structural steel sections including nuts, bolts, washers, welding bending cold or hot drilling holes for bolts in any shape or size as directed inclusive of 2 coats of aluminium paint over a coat of red oxide primer after dismantling old unserviceable cross arms complete all as specified and as directed. | 1.2 | Qtl | 10,547 ₹12,656.4 | 10,200 ₹12,240 | 7,500 ₹9,000 | 3,000 ₹3,600 Lowest | 12,000 ₹14,400 | 12,000 ₹14,400 | 7,000 ₹8,400 | 6,800 ₹8,160 | 9,000 ₹10,800 |
| 6.00 | M&L for stay assembly 16/20mm dia rod complete with accessories as shown in electrical plate No 1 (Loop type insulator, stay clamps, excavation and concrete measured separately) complete all as specified and directed. | 6 | Each | 3,036 ₹18,216 | 4,500 ₹27,000 | 1,800 ₹10,800 | 1,500 ₹9,000 | 1,100 ₹6,600 | 800 ₹4,800 Lowest | 2,000 ₹12,000 | 900 ₹5,400 | 2,500 ₹15,000 |
| 7.00 | M&L Galvanised steel wire 3.15 or 4mm dia stranded 7/1.6mm complete all as specified and directed | 0.5 | Qtl | 12,259 ₹6,129.5 | 10,200 ₹5,100 | 6,500 ₹3,250 | 5,000 ₹2,500 | 15,000 ₹7,500 | 12,000 ₹6,000 | 14,000 ₹7,000 | 2,400 ₹1,200 Lowest | 12,000 ₹6,000 |
| 8.00 | M&L Loop type insulator, vitreous porcelain,white, brown or green Small size, with overall dimensions 65 x 90mm, clearance of hole 16mm complete all as specified and directed. | 12 | Each | 428 ₹5,136 | 130 ₹1,560 | 800 ₹9,600 | 65 ₹780 | 50 ₹600 Lowest | 700 ₹8,400 | 200 ₹2,400 | 280 ₹3,360 | 220 ₹2,640 |
| 9.00 | S&F Pin type, porcelain, vitreous, white,brown or green insulator in repair including one galvanised mild steel spindle,two galvanised iron washers and one galvanised iron nut, 50mm height, 65mm dia for 550 volts grade complete all as specified and directed. | 60 | Each | 322 ₹19,320 | 128 ₹7,680 | 900 ₹54,000 | 70 ₹4,200 | 50 ₹3,000 | 100 ₹6,000 | 150 ₹9,000 | 25 ₹1,500 Lowest | 220 ₹13,200 |
| 10.00 | S&F Shackle Type, Porcelain, vitreous, white, brown or green insulator in repair with working pressure 550 V,Height 50 mm and Max. dia 65 mm including galvanised mild steel straps, washers, insulator bolts, washers and nuts complete all as specified and directed. | 12 | Each | 342 ₹4,104 | 90 ₹1,080 | 900 ₹10,800 | 15 ₹180 Lowest | 100 ₹1,200 | 100 ₹1,200 | 450 ₹5,400 | 310 ₹3,720 | 220 ₹2,640 |
Tender Value
₹26.8 L
EMD Value
₹53,643
Closing Date
5 Jan 2026, 6:00 pmClosed
Garrison Engineer Gwalior
Garrison Engineer Gwalior Morar Cantt
SPL REPAIR / REPLACEMENT OF UNSERVICEABLE ELECTRIC POLES AND ALLIED ITEMS IN AGE B/R-II AT MORAR CANTT AND INSTALLATION OF PANEL (HIGH TENSION CABLE) AT ARMY PUBLIC SCHOOL UNDER GE GWALIOR
2025_MES_744682_1
8247/GWL/E8
Open Tender
Civil Works
Item Rate
180 days
Garrison Engineer Gwalior
Please refer tender documents
9 documents required · 9 mandatory
₹500
Yes
Garrison Engineer Gwalior
₹53,643
Yes
19 Feb 2026
16 Dec 2025
7 Jan 2026
16 Dec 2025
5 Jan 2026
31 Dec 2025
Amount
Supply and erection of Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9.00 meters long) including painting of poles with two coats of aluminium paint over a coat of red oxide primer on all exposed surfaces and black bituminous paint on embedded portion and Zebra marking on pole with black paint up to one meter height above PCC coping including pasting of radium reflector band / strips (Make: 3M or equivalent) of 5cm wide in Green (02 Nos) & White (01 No.) colour shall be provided at a height of 1.25mtr from coping of pole and writing the pole number in black colour on yellow background at a suitable place on the pole including taking down existing unserviceable pole of any description complete all as specified and directed. (Note: Excavation and concrete shall be measured and paid separately).
Supply & fix Junction box of size 280 X 170 X 130 mm Hinged (L) wiith 2 way connector mounted on epoxy insulators for looping of cable for 1 Phase and 1neutral fixed on pole with the help of MS nuts bolts and MS clamps-2 Nos of size 40 mm X 4 mm thick with one No MCB SP 6 Amp capacity mounted on din rail inside box. work also includes making suitable hole in pole to take out connections to fitting if required at site and provisioning of 1.0 sqmm 3.0 core flexible PVC insulated copper cable from junction box to connector of street light complete all as specified and directed.
M&L for removal of street light along with bracket carefully and refixing on new poles including connection complete all as specified and directed.
M&L for aluminium conductor steel reinforced (ACSR) on pole stringing properly on insulators and binding with aluminium binding wire, jumper set complete for any size (Ferret, Wessal, Squirel) of conductor complete all as specified and as direcetd. (NOTE:- Measurement and payment shall be made by measuring horizontal distance between centre of two adjustant poles and adding 3% extra for sag, joints and jumpers etc)
M & L for cross arms, bracing, supports, clamps and back plated fabricated from structural steel sections including nuts, bolts, washers, welding bending cold or hot drilling holes for bolts in any shape or size as directed inclusive of 2 coats of aluminium paint over a coat of red oxide primer after dismantling old unserviceable cross arms complete all as specified and as directed.
M&L for stay assembly 16/20mm dia rod complete with accessories as shown in electrical plate No 1 (Loop type insulator, stay clamps, excavation and concrete measured separately) complete all as specified and directed.
M&L Galvanised steel wire 3.15 or 4mm dia stranded 7/1.6mm complete all as specified and directed
M&L Loop type insulator, vitreous porcelain,white, brown or green Small size, with overall dimensions 65 x 90mm, clearance of hole 16mm complete all as specified and directed.
S&F Pin type, porcelain, vitreous, white,brown or green insulator in repair including one galvanised mild steel spindle,two galvanised iron washers and one galvanised iron nut, 50mm height, 65mm dia for 550 volts grade complete all as specified and directed.
S&F Shackle Type, Porcelain, vitreous, white, brown or green insulator in repair with working pressure 550 V,Height 50 mm and Max. dia 65 mm including galvanised mild steel straps, washers, insulator bolts, washers and nuts complete all as specified and directed.
Supply and lay cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of following sizes complete all as specified and directed. :-
(a) 10 Sqmm 2 core
(b) 25 Sqmm 4 core
(c) 35 Sqmm 3.5 core
(d) 50 Sqmm 3.5 core
(e) 70 Sqmm 3.5 core
(f) 95 Sqmm 3.5 core
(g) 150 Sqmm 3.5 core
(h) 240 Sqmm 3.5 core
S&F GI pipe light grade of dia 50, mm laying in road and along with poles for cable protection complete with all fitting laid in tranches complete all as specified and directed.
Cable route indicator of size 100mm dia embossed as LT round shaped 10mm thick with marking of 1.1 KV, LT welded bolted on angle iron of 25x25 of 60cm length grouted in PCC (1:3:6) type C-2 using block size of 150x150x150mm embedded in ground including not exceeding earth work complete all as specified and directed.
M&L for earthing complete with galvanized steel earth plate electrode 60cmX60cmX6mm thick buried directly in ground, earth pit not less than 2.25m deep below normal GL with top edge of the earth plate not less than 1.25m below GL connected with earth strip 32 x 6 by means of check nuts, bolts, nuts, washers of GI or steel all as shown in plate no. 3 of MES sch. Pt 0I, connected to main switch board all as specified and testing on completion including provision of earth strip protected by galvanized iron 15 mm dia light grade including all excavation, earth work, PCC, RCC cover, watering by funnel etc. complete including testing on completion complete all as specified directed
All as per item no 14 above but using 4 mm GI wire complete all as specifed directed.
Material and labour for cutting the existing bituminous road/ hard standing to size not exceeding 45 cm wide and depth not less than 45 cm for passing of UG cable through GI pipe and making good the disturbed surface filled with excavated material and top 200 mm depth with plain cement concreet 1:2:4 type C1 (using 20mm graded stone aggregate) completed all as specified and directed.
ditto as per item No 17 above but comprising of following items Feeder Panel - No 01 a) Aluminium bus bar capacity 400 Amps for Phase-R-Y-B-3 Nos & one for neutral -1 No b) MCCB FP 250 Amp 25 kA -01 No (I/C) c) MCCB FP 100 Amps 25 kA - 03 Nos (O/G ) d) MCB SPN 16 Amps 10 kA - 01 No (O/G)
ditto as per item No 17 above but comprising of following items Feeder Panel - No 02 (a) Aluminium bus bar capacity 150 Amps for Phase-R-Y-B-3 Nos & one for neutral -1 No (b) MCCB FP 100 Amps 25 kA - 01 Nos (I/C) (c) MCCB FP 40 Amps 16 kA - 04 No (d) MCB SPN 16 Amps 10 kA - 01 No (O/G)
Ditto as per item No 17 above but comprising of following items Bus Bar Panel a) Aluminium bus bar capacity 200 Amps for Phase-R-Y-B-3 Nos & one for neutral -1 No b) MCCB FP 125 Amps 25 kA - 01 Nos (I/C)
Dismantling & taking down ACSR conductor of any size after taking necessary shut down for 11KV OH line by loosening the binding wires jumpers ect complete all as specified and as directed.
Dismantling GI wire of size 4 sqmm etc. complete and setting aside complete all as specified & directed.
Dismantling insulators any type, any size setting aside complete all as specified & directed.
Dismantling & taking down Main Panel any size setting aside complete all as specified & directed.
Dismantling and Taking down Old cable of all sizes XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of all sizes complete all as specified and directed. .
Dismantling concrete poles / struts, any size complete all as specified and directed.
Dismantling stay assembly complete all as specified and directed. (demolition of concrete, etc. and excavationmeasured separately)
Excavation in trenches not exceeding 1.5m wide and not exc 1.5m depth and getting out in soft/loose soil complete all as specified and as directed.
Excavation in trenches not exceeding 1.5m wide and exc 1.5m depth and getting out in soft/loose soil complete all as specified and as directed.
Returning, filling, including spreading, leveling, watering and well ramming in layers not exc. 25cmin soft/loose soil complete all as specified and as directed.
Removal of excavated soil to a distance not exc 50 m and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed.
M&L for sand cushioning in trenches for cable protection including consolidation complete all as specified and directed.
Supplying and laying un reinforced precast concrete cable cover, Class LV, Type I, flat, size 250mm x 150mm x 40mm complete all as specified and directed
M&L for PCC 1:4:8, type D2 (using 40mm graded stone aggregate) as in foundation filling and mass concrete all as specified and directed.
M&L for PCC 1:3:6, type C2 (using 40mm graded stone aggregate) as in foundation, filling and mass concrete complete all as specified and directed.
M&L for PCC 1:2:4 type B-0 (using 12.5 mm graded BT stone aggregate) as in bed block for hold fast or coping including necessary form work complete all as specified and directed.
Design, Fabricate, Supply, Installation, Testing & Commissioning of indoor type dust proof & vermin proof cubical panel board compartmentalized with separate bus bar and cable alley chambers suitable for 3 phase, 4 wire, 415 volts, 50 Hz, Ac supply system as per latest IS/IEC standards & regulations, factory fabricated in an approved factory (manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3 mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02 Nos) LT 415/440 Volts, and Including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate.Detachable gland plates including double compression stainless manufacturer's name plate shall be riveted on external doors of feeder pillar box with naturally air cooled Aluminum bus bar 4 strips suitable for 200 Amps with detachable gland plate for incoming and outgoing cable including termination of cable ends both incoming and outgoing with sufficient working space inside including installing, testing and commissioning complete all as specified and as directed consisting of following:- (a) Electrolytic aluminium bus bar 1200 Amps in distant colour with epoxy supported insulators - 01 Job (04 Nos). (b ACB 4 Pole, 415 V, with Thermal Magnetic Release (Manual Fixed type) of capacity 630 Amps - 01 No © MCCB 4 Pole, 415 V, Adjustable type, 200 Amps(ICS = 100% ICU) with breaking capacity 36 KA-03 Nos (Outgoing) (d) Changeover with capacity of 200 Amp-02 Nos. (e) R,Y & B Phase indication lamp LED type ( Set of three ),22.5 mm dia,230 V protected with MCB SP 2 Amp Showing 3 Phase Supply - 01 set (f) multifunction meter for measure,current of amp,voltage and frequency,KW,PF,KWH,KVAR.
Material and labour for earthing complete(Including Testing) with galvanized steel earth plate electrode 600mm X 600mm X 6mm buried directly in ground vertically to a depth not less than 2.25 metre below normal ground level (with top edge of earth plate not less than 1.5 metre below ground level) connected to galvanized iron earth strip 25x4 mm (main earthing lead) by means of galvanized bolts, nuts and washers all as shown in electrical plate No 3 of MES Schedule Part-I (2009) with connected to earth test point & to main switch board with & including adequate quantity of charcoal dust and common salt alround earth plate & 40 mm dia GI pipe medium grade for earth lead protection pipe for suitable length and GI pipe 20 mm dia medium grade for watering pipe with funnel & wire mesh including necessary earth work and PCC (1: 3 : 6) type C-1 (using 20mm graded stone aggregate) for earth pit , internal surface of concrete shall be given 10mm thick plaster in CM 1:4 and 40 mm thick precast RCC cover in 1 : 2 : 4 type B1 (using 20mm graded stone aggregate) with 3 Nos 8 mm dia TMT bars both ways with 12mm dia round bar handle complete all as specified & directed. NOTE: Earth strip and its protection pipe upto and including 7.5 mtr only from the top of earth electrode are included under this item and additional earth strip/protection pipe etc.
Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required ut 25x4mm galvanised iron strip complete all as specified and directed.
SHRI HARI CONSTRUCTION (BID ID -3522347)
M/s Tirupati construction (BID ID -3516763)
M/S Rajeev Construction (BID ID -3516800)
somyaenterprises (BID ID -3516695)
SIDDHIDATRI CONSTRUCTION (BID ID -3515765)
M/S uneversal agency (BID ID -3516585)
M/S KAPIL CONSTRUCTION CO (BID ID -3516488)
MONA GENERATOR SEVICES PVT. LTD. (BID ID -3516399)
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.33 MB
8247Tenderdocus.pdf
Tender Documents • 1.66 MB
BOQ_833842.xls
BOQ • 0.38 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .