THE DIRECTOR
CSIR - NAL, KODIHALLI, BENGALURU
Replacement of old feeder pillars 3 and 6 and associated works at CSIR NAL, Kodihalli campus, Bengaluru 560017
2026_CSIR_298579_1
ESS/K/4281
Open Tender
Electrical Works
Item Rate
90 days
CSIR - NATIONAL AEROSPACE LABORATORIES
Please refer tender documents
10 documents required · 10 mandatory
₹500
DIRECTOR, CSIR-NAL, BENGALURU
₹76,615
20 Nov 2026
20 Nov 2026
4 Dec 2026
20 Nov 2026
3 Dec 2026
20 Nov 2026
90 days
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply of outdoor type floor mounted single front double door LT feeder pillar with 800A, TPN Aluminium bus bar etc., The feeder pillar shall be compartmental type with IP 55 protection. The details of the power feeders & other accessories will be as follows:
Incoming :
a. 630A 4pole ON load manual changeover switch(COS) with rotary handle -1 No. (Note :The outgoing connection of COS shall be connected to 630A incomer MCCB using suitable size bus bars.)
b.630A, 4 pole, 415V, 50Hz, 25 kA MCCB, with RHOM having microprocessor based release, S/C, O/C and E/F protections. - 1 No
b. Multi data meter having current, voltage, frequency, power factor, kW etc.,. with suitable rated CTs, with necessary terminal block having short links facility, indication lamps for showing on / off / trip indications of incomer feeder with necessary control MCB. -1 Set | 1 | No | - | - |
| 1.01 | c. Electronic three phase trivector meter with suitable rated, 0.5 class accuracy CT's with necessary terminal block having short links facility. -1 Set
d. Mains Indication lamps with necessary control MCB for incomer 630A MCCB feeder - 1 set
Outgoing :
400A 3 pole, 415V, 50Hz, 25 kA MCCB, with RHOM having built in thermal magnetic, adjustable O/C and fixed S/C protection - 2 Nos
300A,3 pole, 415V, 50Hz, 25 kA MCCB, with RHOM having built in thermal magnetic adjustable O/C and fixed S/C protection. - 2 Nos
200A, 3 pole, 415V, 50Hz, 25 kA MCCB, with RHOM having built in thermal magnetic adjustable O/C and fixed S/C protection. - 2 Nos | - | - | - | - |
| 1.02 | All the above switch gears and its accessories shall be mounted in suitable size of enclosure made out of using 2 mm thick CRCA sheet steel for load bearing & 1.6 mm for non load bearing members as per standard practice. All the MCCBs incoming & out going sides shall be inter connected using suitable rated bus bar with necessary spreader links as required. The view port shall be provided infront of the door for indication lamps and meters at the incomer metering section. The provision shall be made available for terminating of cable of size 2R x 4C x 400 Sq.mm & 2R x 4C x 400 Sq.mm Al.conductor XLPE insulated armoured cable for Source :1 and Source:2 of the change over switch (COS) for incoming. The cable 4C x 300,400sq.mm Al.conductor XLPE insulated armoured cable for all outgoing feeders. The cable entry for incomer and all outgoing shall be at the bottom. Also necessary gland plates shall be provided using 3 mm thick sheet steel as required. All the panel doors shall be earthed with suitable size green wire as per standard practice. The suitable size aluminium earth bar shall be provided at bottom of the panel as per standard practice. The enclosure shall be painted with powder coated Siemens grey paint as per standard practice. The GA shall get approval before fabrication. | - | - | - | - |
| 2 | Supply of outdoor type floor mounted single front double door LT feeder pillar with 800A, TPN Aluminium bus bar etc., The feeder pillar shall be compartmental type with IP 55 protection. The details of the power feeders & other accessories will be as follows:
Incoming :
a. 630A 4pole off load manual changeover switch(COS) with rotary handle -1 No. (Note :The outgoing connection of COS shall be connected to 630A incomer MCCB using suitable size bus bars.)
b.630A, 4 pole, 415V, 50Hz, 25 kA MCCB, with RHOM having microprocessor based release, S/C, O/C and E/F protections. - 1 No
b. Multi data meter having current, voltage, frequency, power factor, kW etc.,. with suitable rated CTs, with necessary terminal block having short links facility, indication lamps for showing on / off / trip indications of incomer feeder with necessary control MCB. -1 Set | 1 | No | - | - |
| 2.01 | c. Electronic three phase trivector meter with suitable rated, 0.5 class accuracy CT's with necessary terminal block having short links facility. -1 Set
d. Mains Indication lamps with necessary control MCB for incomer 630A MCCB feeder - 1 set
Outgoing :
250A 3 pole, 415V, 50Hz, 25 kA MCCB, with RHOM having having built in thermal magnetic, adjustable O/C and fixed S/C Protection - 2 Nos
200A,3 pole, 415V, 50Hz, 25 kA MCCB, with RHOM having having built in thermal magnetic, adjustable O/C and fixed S/C Protection - 2 Nos
160A, 3 pole, 415V, 50Hz, 25 kA MCCB, with RHOM having having buit in thermal magnetic, adjustable O/C and fixed S/C Protection. - 4 Nos | - | - | - | - |
| 2.02 | All the above switch gears and its accessories shall be mounted in suitable size of enclosure made out of using 2 mm thick CRCA sheet steel for load bearing & 1.6 mm for non load bearing members as per standard practice. All the MCCBs incoming & out going sides shall be inter connected using suitable rated bus bar with necessary spreader links as required. The view port shall be provided infront of the door for indication lamps and meters at the incommer metering section only. The provision shall be made available for terminating of cable of size 2R x 4C x 400 Sq.mm & 2R x 4C x 400 Sq.mm Al.conductor XLPE insulated armoured cable for Source :1 and Source :S2 of the change over switch (COS). The cable 4C x 240,150 & 95 Sq.mm Al.conductor XLPE insulated armoured cable for all outgoing feeders. The cable entry for incommer and all outgoing shall be at the bottom. Also necessary gland plates shall be provided using 3 mm thick sheet steel as required. All the panel doors shall be earthed with suitable size green wire as per standard practice.The suitable size aluminium earth bar shall be provided at bottom of the panel as per standard practice. The enclosure shall be painted with powder coated siemens gray paint as per standard practice. The GA shall get approval before fabrication. | - | - | - | - |
| 3 | Installation testing and commissioning of LT feeder piller as specified under item no 1 & 2 on the floor using necessary cement concreate pedestals construction and angle iron frame, bolt,nut & fasteners etc., all complete as per the site requirement and as directed by Engineer in charge all complete as required. | 2 | Job | - | - |
| 4 | Dismantalling of existing feeder pillar including disconnection of existing incomming and outgoing cables from the feeder pillar. Also the existing extra looped cable were buried near feeder pillar. The same cables to be lifted after removing of cable match the surrounding of earth as per the site requirement. The existing cables will be reconnected for the item no:1 & 2. The dismantalled feeder panel shall be shifted to central stroes of distance 70-80meters as directed by Engineer in charge as required. | 2 | Job | - | - |
| 5Supply of following size of multistrand aluminum conductor, XLPE Insulated, cores laid up, tape PVC inner sheathed, flat GI/steel armored with PVC sheathed power cable of 1.1kV grade as per IS - 7098 (part-I) - 1988 as required. | |||||
| 5.1 | 3.5Cx300sq.mm(A2XFY) | 340 | Meter | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.40 MB
TD4281.pdf
Tender Documents • 2.50 MB
BOQ_347768.xls
BOQ • 0.44 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .