Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹2.4 LAccepted-AOC | 1 | Accepted-AOC LOWEST FIRST | |
| 2 | 2₹2.5 L+₹7,890 (3.31%)Rejected-AOC 113 F BLOCK HOUSE NUMBER 113 F BLOCK PANKI KANPUR NAGAR UTTAR PRADESH 208020 | KANPUR NAGAR | UTTAR PRADESH | 208020 | 2 | Rejected-AOC LOWEST SECOND | |
| 3 | 3₹2.5 L+₹15,490 (6.49%)Rejected-AOC 222 346 LUKERGANJ LUKERGANJ LUKERGANJ ALLAHABAD UTTAR PRADESH 211003 | PRAYAGRAJ | UTTAR PRADESH | 211003 | 3 | Rejected-AOC LOWEST THIRD |
Tender Value
₹2.5 L
EMD Value
₹3,000
Closing Date
24 Apr 2025, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Suprintending Engineer
Superintending Engineer Electricity Transmission Circle I 57 George Town Prayagraj 211002 PH- 0532-2256499/9415311005
Replacement of damage 33 KV Numerical relay of capacitor bank and 33 KV Tripple feeder panel installed at 132 KV Substation Bindki under Electy. Trans. Division- Fatehpur.
2025_UPTCL_1026217_1
55-ETC-I(A)/ 2024-2025
Open Tender
Electrical Works
Item Rate
60 days
Fatehpur
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
SE ETC-I PRAYAGRAJ
₹3,000
30 Jul 2025
8 Apr 2025
25 Apr 2025
8 Apr 2025
24 Apr 2025
8 Apr 2025
Amount
Supply and replacement of old, used & defective 33KV Numerical basedover current & E/F and under voltage, over voltage and Nutral Displacement relays suitable for33KV triple feeder C&Rpanel and capacitor bank unit (ABB make) installed at 132KV S/S Bindki by complete retrofitting of below given relay. The work include following works:-
Supply of numeric based non directional over current & E/F (IDMT) relay (50/51N) also time delayed O/C, E/Ffeather (RS-485) of ABB/SIEMENS/ Schneider make relay having at least 6BI, 7BOwith one alarm output, having auxiliary current 1A suitable for 110V auxiliary voltage, and communication interface RS-485/USB& also having Neutral Displacement relay (NDR-59N) with provision for both alarm trip setting and relay must be suitable for SCADA interfacing for33KV C&R panel of 2x5 MVAR capacitor bank unit as per sample at 132KV S/S Bindki. This job also includes retrofitting of new relay by cutting the MS Sheet of relay’s size and mounting it with proper drilling and tightening with nut bolt and painting the used MS Sheet with same colour as panel. Dismantling of old defected relay, Rewiring in relay panel with proper dressing ferruling and termination in C&R Panel. Rewiring in relay panelwith proper dressing and also provide software of relay in CD Testing and commissioning. Installation, Testing & commissioning of above relay must be under the scope of contractor. Testing kit, man power and T&P will be provided by Contractor at his own risk and cost.
Supply of numeric based under voltage, over voltage along with trip circuit supervision relay in R,Y&B phase made of ABB/SIEMENS/ Schneider make relay having at least 6BI, 7BO (RS-485)with one alarm output, having auxiliary current 1A suitable for 110V auxiliary voltage and relay must be suitable for SCADA interfacing 33KV ABB Make C&R panel of 2x5 MVAR capacitor bank unit at 132KV S/S Bindki.This job also includes retrofitting of new relay by cutting the MS Sheet of relay’s size and mounting it with proper drilling and tightening with nut bolt and painting the used MS Sheet with same colour as panel. Dismantling of old defected relay, Rewiring in relay panel with proper dressing ferruling and termination in C&R Panel. Rewiring in relay panel with proper dressing and also provide software of relay in CD Testing and commissioning. Installation, Testing & commissioning of above relay must be under the scope of contractor. Testing kit, man power and T&P will be provided by Contractor at his own risk and cost.
Supply and fixing of numeric based relay used for Neutral Displacement relay (NDR-59N) at 33KV 10MVAR Capacitor Bank installed at 132KV S/S Bindkihaving non directional over current and E/F (IDMT) relay (50/51N) also time delayed O/C, E/F feature of ABB/SIEMENS/SCHEIDER or standard make as per UPPTCL Guideline. Relay having at least 6BI, 7BO with one alarm output, having auxiliary current 1A suitable for 110V DCauxiliary voltage, having provision for both alarm trip setting and relay must be suitable for SCADA interfacingof 33 KV C&R panel of 2x5 MVAR capacitor bank unit as per sample.This job also includes retrofitting of new relay by cutting the MS Sheet of relay’s size and mounting it with proper drilling and tightening with nut bolt and painting the used MS Sheet with same colour as panel. Dismantling of old defected relay, Rewiring in relay panel with proper dressing ferruling and termination in C&R Panel. Rewiring in relay panel with proper dressing and also provide software of relay in CD Testing and commissioning. Installation, Testing & commissioning of above relay must be under the scope of contractor. Testing kit, man power and T&P will be provided by Contractor at his own risk and cost.
Supply of numeric based non directional over current & E/F (IDMT) relay (50/51N) also time delayed O/C, E/Ffeatureof of ABB/SIEMENS/ Schneider make for various 33KV Tripple feeder relaypanel installed at substation having (i)at least 6BI, 7BO with one alarm output, (ii) having auxiliary current 1A suitable for 110V auxiliary voltage, (iii) communication interface RS-485/USB (iv)Having inst. E/F & O/C and also time delay O/C & E/F Features(v) Relay must be suitable for SCADA interfacing for 33KV triple feeder C&R panel at 132KV S/S Bindki. This job also includes retrofitting of new relay by cutting the MS Sheet of relay’s size and mounting it with proper drilling and tightening with nut bolt and painting the used MS Sheet with same colour as panel. Dismantling of old defected relay, Rewiring in relay panel with proper dressing ferruling and termination in C&R Panel. Rewiring in relay panel with proper dressing and proper interfacing with SCADA System and also provide software of relay in CD Testing and commissioning. Installation, Testing & commissioning of above relay must be under the scope of contractor. Testing kit, man power and T&P and required material will be provided by Contractor at his own risk and cost. Any license/software required for configuration of SCADA system shall be in the scope of contractor.
B.R. ENTERPRISES (BID ID -5143284)
M/S New Sharma Electricals (BID ID -5143341)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .