Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.6 LAccepted-AOC KASHIJORA P O BENAPUR DIST PASCHIM MEDINIPUR | BENAPUR | PASCHIM MEDINIPUR | WEST BENGAL | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹32.6 L+₹9.0 L (38.3%)Rejected-Finance | L2 | Rejected-Finance NOT BEING L1 | |
| 3 | L3₹45.1 L+₹21.5 L (91.5%)Rejected-Finance VILL PO KOTA VIA PANAGARH BAZAR DIST BURDWAN WB PIN 713148 | BURDWAN | BURDWAN | WEST BENGAL | 713148 | L3 | Rejected-Finance NOT BEING L1 |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
17 Oct 2022, 6:00 pmClosed
GE AF KALAIKUNDA
PO Kalaikunda Air Field Dist Paschim Medinipore St West Bengal Pin 721303
REPAIR/MAINT OF BORE WELL, PUMP SETS, PUMP HOUSE, PANEL BOARD, FILTER PLANT AND CONNECTED ALLIED WORKS AND REPAIR/MAINTENANCE OF DIFFERENT SIZE OF CI/GI WATER PIPE LINE, GATE VALVE/SLUICE VALVE AND MISC WORKS AT AFS SALUA UNDER GE (AF) KALAIKUNDA
2022_MES_546353_2
8790/E8
Open Tender
Electrical and Maintenance Works
Item Rate
365 days
AF STN SALUA
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE AF KALAIKUNDA
₹40,000
Yes
24 Nov 2022
28 Sept 2022
18 Oct 2022
28 Sept 2022
17 Oct 2022
4 Oct 2022
Amount
Comprehensive maintenance as per Original Equipment Manufacturer's (OEMs) reccommendations for a period of twelve months for 20/25 HP capacity submersible pump sets installed at various locations through OEMs Authorised Service Centre Engineers or through OEMs Certified Agencies by overhauling/servicing cleaning thoroughly discharge/suction cases, impellers ,shaft and assembling pump carefully after replacement of suction strainer, 'O' ring, wearing ring, Bearing bush upper & lower, valve seat, valve ring, required quantity of impeller, machining works ( if any) including applying two coats of synthetic enamel paint over a coat of red oxide primer after preparation of pump external surface complete with and including(a) Lifting of defective submersible pumping set of any make and capacity from bore well after providing lifting tools , chain pulley etc. as required carefully, by disconnecting/dismantling all electric connections, column pipes, steel ropes/chain and keeping them under safe custody for reuse all complete and (b) Lowering of repaired /overhauled/reminded submersible pumping set of any make and capacity inside bore wells after proper coupling of pump and motor , fixing old/new chain with clamp, connecting/refixing existing/new column pipe lines with new rubber gasket 3 mm thick, nuts, bolts & washers carefully with the help of chain pulley etc. & carefully re-connecting all electric/water lines and testing on load to the entire satisfaction of Engineer-in-charge complete all as specified and directed. [Make: Calama/Kriloskar/CRI/KSB/Crompton Greaves] NOTE : (i) The cost of transportation of the defective submersible pumping sets( pump or motor ) from site to OEM workshop & back is deemed to be included in the quoted rates. (ii) Column pipe//supporting chain required deemed to be included in Quoated rates (iii) Rewinding shall be measured separately (iv) refixing of column pipe to be done after proper descaling (iii) Repair of motor and pump measured separately however if any repair which is not catered in BOQ and it is necessary to making the pump functional shall be provided by contractor without any extra cost. (iv) refixing of column pipe to be done after proper descalin (v) Each maintenance job shall be covered period of 12 Months..(vi) All minor spares required for making the pump functional shall be provided by contractor without any extra cost.(vii) Breakdown Maintenance : The Authorised Service Engineer of OEM or OEM Certified Agencies will carry out all breakdown maintenance after receiving information (written or oral) from GE kalaikunda officials or their representatives.The OEM's authorised service representative or OEM certified agencies will carry out the required repairs of the units and appraise GE, Engineer-in-Charge and JE the status of the break down repair at site. No payment shall be made on account of any breakdown service to the machinary/equipments during comprehensive maintenence period. (viii) The Service Engineer will be called in case of any breakdown and the same shall be attended within 24 Hours of lodging of complaint, failing which a penal recovery of Rs.200.00 (Rupees Two Hundred Only) per day till such time the unit is attended and complaint is resolved,will be recovered from the outstanding dues to the Contract (vi) Cost of minor items like insulating tape,gland packing materials, metal washers, fibre/rubber washers, screws, small nuts & bolts and like shall be deemed to be inclusive of the quoated rate.
All as per item No. 01 here-in-before but capacity 7.5 HP open hole submersible pump/.Non clogging sewage pump complete as specified and directed.
M & L for rewinding of burnt submersible motor 25/20 HP, 3 phase ,415 V, 50 Hz of any make through authorised services centre of OEM with water proof insulated copper conductor of the same specification as per old one after dismantling / cutting out burnt windings from stator assembly, cleaning slots properly complete with insulating slots packing, sleeves, papers & reassembling stator and rotor after replacement of worn out spares/matching works including painting with two coats of synthetic enamel paint over a coat of red oxide primer after preparation of motor external surface and water proof jointing for submersible cable 3 core, with replacement of oil seal, sand guard, bolt gasket, cable packing ring, circlip, bearing bush upper & lower etc. complete as specified and directed.
All as per item No. 03 here-in-before but capacity 7.5 HP open hole submersible pump/ Non clogging sewage pump complete as specified and directed.
Supply only Bowl CI submersible motor of capacity of 5 to 25HP as per Original Equipment Manufacturer's (OEMs) reccommendations through OEMs Authorised Service Centre Engineers or through OEMs Certified Agencies as approved by GE [Make: Calama/Kriloskar/CRI/KSB/Crompton Greaves/]
Supply & fix in replacement of sleeves (S/S) submersible motor of capacity of 5 to 25HP as per Original Equipment Manufacturer's (OEMs) reccommendations through OEMs Authorised Service Centre Engineers or through OEMs Certified Agencies as approved by GE [Make: Calama/Kriloskar/CRI/KSB/Crompton Greaves/]
Supply & fix of rubber bush submersible motor of capacity of 5 to 25HP as per Original Equipment Manufacturer's (OEMs) reccommendations through OEMs Authorised Service Centre Engineers or through OEMs Certified Agencies as approved by GE [Make: Calama/Kriloskar/CRI/KSB/Crompton Greaves/]
Supply & fix stud nut of submersible motor of capacity of 5 to 25HP as per Original Equipment Manufacturer's (OEMs) reccommendations through OEMs Authorised Service Centre Engineers or through OEMs Certified Agencies as approved by GE [Make: Calama/Kriloskar/CRI/KSB/Crompton Greaves/]
Supply & fix neck ring of submersible motor of capacity of 5 to 25HP as per Original Equipment Manufacturer's (OEMs) reccommendations through OEMs Authorised Service Centre Engineers or through OEMs Certified Agencies as approved by GE [Make: Calama/Kriloskar/CRI/KSB/Crompton Greaves/]
Supply & fix thrust bearing of submersible motor of capacity of 5 to 25HP as per Original Equipment Manufacturer's (OEMs) reccommendations through OEMs Authorised Service Centre Engineers or through OEMs Certified Agencies as approved by GE [Make: Calama/Kriloskar/CRI/KSB/Crompton Greaves/]
M & L for disconnection of electrical connections de-couplings from centrifugal pump, unscrewing foundation nuts, bolts & washers of squirrel cage induction motor from foundation base plate and taking out carefully for comprehensive maintenance as per Original Equipment Manufacturer's (OEMs) reccommendations for a period of twelve monthsof 15 HP (3 phase, 415V, 50C/S, AC Supply) of any make overhauling, servicing, cleaning thoroughly cases, impellers ,shaft, bearing housing, gland packing, descaling all derts and assembling after repair with required machining works ( if any), new key, new both end bearings, old bearing cover, new gland packing with old gland cover, old/new impeller, stuffing box stud, rubber coupling including applying two coats of synthetic enamel paint over a coat of red oxide primer after preparation of pump external surface, inluding rewinding of burnt centrifugal pump 15 HP of any make through authorised services centre of OEM with water proof insulated copper conductor of the same specification as per old one after dismantling / cutting out burnt windings from stator assembly, cleaning slots properly complete , and refixing after repair, jointing coupling with pump, electrically connected, setting proper alignment with pump with old/new nuts, bolts & washers, rubber coupling joint and testing complete (iii) Repair of motor and pump measured separately however if any repair which is not catered in BOQ and it is necessary to making the pump functional shall be provided by contractor without any extra cost. (v) Each maintenance job shall be covered period of 12 Months..(vi) All minor spares required for making the pump functional shall be provided by contractor without any extra cost.(vii) Breakdown Maintenance : The Authorised Service Engineer of OEM or OEM Certified Agencies will carry out all breakdown maintenance after receiving information (written or oral) from GE kalaikunda officials or their representatives.The OEM's authorised service representative or OEM certified agencies will carry out the required repairs of the units and appraise GE, Engineer-in-Charge and JE the status of the break down repair at site. No payment shall be made on account of any breakdown service to the machinary/equipments during comprehensive maintenence period. (viii) The Service Engineer will be called in case of any breakdown and the same shall be attended within 24 Hours of lodging of complaint, failing which a penal recovery of Rs.200.00 (Rupees Two Hundred Only) per day till such time the unit is attended and complaint is resolved,will be recovered from the outstanding dues to the Contract (vi) Cost of minor items like insulating tape,gland packing materials, metal washers, fibre/rubber washers, screws, small nuts & bolts and like shall be deemed to be inclusive of the quoated rate.
All as per item No. 11 here-in-before but capacity 7.5 HP open hole pump/Non clogging sewage pump complete all as specified and directed.
Supply & fix Rotor shaft with couplings and seals of above pump of capacity 5 to 15 HP as per Original Equipment Manufacturer's (OEMs) reccommendations through OEMs Authorised Service Centre Engineers or through OEMs Certified Agencies as approved by GE [Make: Calama/Kriloskar/CRI/KSB/Crompton Greaves/]
S&F in replacement of marking tape as per OEM specification complete all as specified and directed.
S&F in replacement of ' O ' Ring and gasket centrifugal pump/open hole pump/Non clogging sewage pump of capacity 5 to 15 HP as per Original Equipment Manufacturer's (OEMs) reccommendations through OEMs Authorised Service Centre Engineers or through OEMs Certified Agencies as approved by GE [Make: Calama/Kriloskar/CRI/KSB/Crompton Greaves/]
S&F in replacement of Radial bearing upper centrifugal pump/open hole pump/Non clogging sewage pump of capacity 5 to 15 HP as per Original Equipment Manufacturer's (OEMs) reccommendations through OEMs Authorised Service Centre Engineers or through OEMs Certified Agencies as approved by GE [Make: Calama/Kriloskar/CRI/KSB/Crompton Greaves/]
S&F in replacement of radial bearing lower centrifugal pump/open hole pump/Non clogging sewage pump of capacity 5 to 15 HP as per Original Equipment Manufacturer's (OEMs) reccommendations through OEMs Authorised Service Centre Engineers or through OEMs Certified Agencies as approved by GE [Make: Calama/Kriloskar/CRI/KSB/Crompton Greaves/]
S&F in replacement of pump bearing centrifugal pump/open hole pump/Non clogging sewage pump of capacity 5 to 15 HP as per Original Equipment Manufacturer's (OEMs) reccommendations through OEMs Authorised Service Centre Engineers or through OEMs Certified Agencies as approved by GE [Make: Calama/Kriloskar/CRI/KSB/Crompton Greaves/]
S&F in replacement of Shaft key centrifugal pump/open hole pump/Non clogging sewage pump of capacity 5 to 15 HP as per Original Equipment Manufacturer's (OEMs) reccommendations through OEMs Authorised Service Centre Engineers or through OEMs Certified Agencies as approved by GE [Make: Calama/Kriloskar/CRI/KSB/Crompton Greaves/]
M & L flushing of existing bore well of depth up to 150mtr, and with compressor air/back washing using GI pipe 20/25 mm size for a minimum period of 6 hrs or upto the time all sludge are flushed out till clear water is obtained. Conducting Yield test with ‘V’ notch of submersible pump set in the bore well complete all as directed
S & F in repairs submersible cable flat PVC insulation of type C and having PVC sheath of type ST2, flexible conductor, FR-LSH, 3 core of size 6 sqmm complete all as specified and as directed.
M & L for cleaning and washing of inside portion of RCC OH reservoirs/Water tank of Capacity of Round/ Square type of Capacity 100000 gallons (including 02 chambers) up to 25 mtr height ,located in domestic area, with Anti-bacterial agent consisting of following process: - Dewatering the tank by mechanical means as directed, de-silting and removing of left over dirty water up to 100 to 150 mm in the bottom of the tank and sludge with special sludge pump, cleaning of walls and ceiling with special mechanized high pressure jet machines by rotary jet system at 100-120 Bar pressure (120 Kg /sq cm) which dislodges the layer of dirt, algae, fungus stuck on its surface usage of scrubbing machines for old stains and cleaning chemicals if required of make Eureka Forbes Ltd or equivalent as approved by GE, floor of the dirty tank should be thoroughly cleaned up by fry jet cleaner to accumulate all dirt ,the remaining sludge should than be removed by sludge pumps, the dirt silt and other foreign material should further be removed by Industrial Vacuum Cleaners to make the floor totally dirt free, application/spraying of Anti-Bacterial chemicals to ensure total sterilization of tank from the inside, inside of the tank should be treated with specially developed 4 ft long ultraviolet Radiator to kill further floating bacteria/virus in order to make the tank totally clean, bacteria free and safe for storage of drinking water. All the above operations should be executed by trained workers and technicians, properly dressed along with gum boots, to work as per the direction of Engineer in charge. and writing "Date of cleaning and Next due date of cleaning" on the column of tank at specified location with and including necessarry scalfolding and safety measure complete all as specified and directed.
All as per item No. 22 here-in-before but capacity of 50000 gallons, complete all as specified and as directed
All as per item No. 22 here-in-before but capacity of 20000 gallons, at Aerator deck to flux mixer complete all as specified and as directed .
All as per item No. 22 here-in-before but at Sedimentation tank (28000 Gallons /h) complete all as specified and as directed .
All as per item No. 22 here-in-before but at Filter bed (28000 Gallons ) complete all as specified and as directed .Note for item No. 22 to 26 : (i) Removing of bee heavs and cleaning of vegitation grown on tank shall be done by the contractor without any extra charge. (ii) All T&P required at site for cleaning of tank shall be arranged by the contractor without any extra cost.. (iii) All safety measures, safety belts, helments and other safety tools required at site for the trademens deployed for cleaning of tanks (under ground and over head RCC tanks) shall be provided by the contractor without any extra cost. (iv) Contractor has to clean the tank after tanking permission from Eng in Charge in one week advance. (v) Contractor shall use dewatering pump and industrial vaccume cleaner for cleaning of tank. (vi) Contractor shall deploy sufficient labour for cleaning the tank with stipulate time period of same day so that water supply from that tank would not be hampered. (vii) Contractor has to submit the photos of inside tank before cleaning and after cleaning to the Eng in Charge before claiming for payment. (viiii) Contractor shall provide ACP sheet of size 400 mm x 400 mm on each tank for writing date of cleaning of tank and next due date of cleaning on blue base with white colour. (IX) It is mandatory that contractor shall submit the insurance certificate minimum 10 Lakh sum assured of all staff/employee employed by him for the above mentioned works.
Cleaning of PVC water tanks of capacity exceeding 300 litres but not exceeding 500 litres including chemical treatment with Anti-bacterial agent consisting of following process: - Dewatering the tank with submersible pump, de-silting and removing of left over dirty water up to 100 to 150 mm in the bottom of the tank and sludge with special sludge pump, cleaning of walls and ceiling with special mechanized high pressure jet machines by rotary jet system at 100-120 Bar pressure (120 Kg /sq cm) which dislodges the layer of dirt, algae, fungus stuck on its surface usage of scrubbing machines for old stains and cleaning chemicals if required of make Eureka Forbes Ltd, floor of the dirty tank should be thoroughly cleaned up by fry jet cleaner to accumulate all dirt ,the remaining sludge should than be removed by sludge pumps, the dirt silt and other foreign material should further be removed by Industrial Vacuum Cleaners to make the floor totally dirt free, application/spraying of Anti-Bacterial chemicals to ensure total sterilization of tank from the inside, inside of the tank should be treated with specially developed 4 ft long ultraviolet Radiator to kill further floating bacteria/virus in order to make the tank totally clean, bacteria free and safe for storage of drinking water. All the above operations should be executed by trained workers and technicians, properly dressed along with gum boots, to work as per the direction of Engineer in charge.
Cleaning of PVC water tanks of capacity exceeding 500 litres but not exceeding 1000 litres including chemical treatment with Anti-bacterial agent consisting of following process: - Dewatering the tank with submersible pump, de-silting and removing of left over dirty water up to 100 to 150 mm in the bottom of the tank and sludge with special sludge pump, cleaning of walls and ceiling with special mechanized high pressure jet machines by rotary jet system at 100-120 Bar pressure (120 Kg /sq cm) which dislodges the layer of dirt, algae, fungus stuck on its surface usage of scrubbing machines for old stains and cleaning chemicals if required of make Eureka Forbes Ltd or equivalent as approved by GE, floor of the dirty tank should be thoroughly cleaned up by fry jet cleaner to accumulate all dirt ,the remaining sludge should than be removed by sludge pumps, the dirt silt and other foreign material should further be removed by Industrial Vacuum Cleaners to make the floor totally dirt free, application/spraying of Anti-Bacterial chemicals to ensure total sterilization of tank from the inside, inside of the tank should be treated with specially developed 4 ft long ultraviolet Radiator to kill further floating bacteria/virus in order to make the tank totally clean, bacteria free and safe for storage of drinking water. All the above operations should be executed by trained workers and technicians, properly dressed along with gum boots, to work as per the direction of Engineer in charge.
Horizontal boring of holes, under road/ pavement / hard standing etc.,not exceeding 10 Metres in length, in any type of soil, suitable for passing through 20mm to 80 mm bore, galvanised steel tubing,complete all as specified and directed.
S&F in replacement of PVC flexible pipe of size 100mm including clamps and its nuts to be fitted in sewage pumps complete all as specified and as directed.
Supply only Ferric Alum Gde I for purification of water containing lead ( as Pb) 30 ppm maximum confirming to IS 299/ 1989 complete all as specified and as directed.
Supply only calcium hypochlorite granule 65 % to 70 % chlorine grade I in air tight sealed plastic bags for treatment of drinking water complete all as specified and as directed. Note :- 1. Approval of chemical ( calcium hypochlorite) shall be given after verification of test certificates and their chemical analysis , strength in terms of quantity of chlorine content. 2. The brand/make of chlorination chemical must be certified by Govt. Laboratory and confirming compliance of specification , suitable for drinking water.
Supply only Chlorine test kit/ iron test kit against old u/s kit with coloured sample complete with all testing fitments and OT solution in rexine finish box complete all as specified and as directed.
Testing of drinking water sample for servicable borewell No 3,6,7 and after treated water of filter plant of this station with under mention test by authorised lab ie, IIT Kharagpur or District water testing laborotory kharagpur as approved by GE and Test report shall be submitted to GE along with RAR/FB, India :- CHEMICAL TEST :- (a) PH Valve,Temperature,Turbidity,Total hardess (as caco3) mg/l, Alkalinity, TDs ppt. Max,Iron mg/l ,Nitrate mg/l,Chloride mg/l,Residual chlorire mg/l, Fluoride mg/l. BACTERIALOGICAL:- (b) Coliform orgnisms, Faecal coliforms.
Reparing/servicing of existing of engine oil of Air compressor ( air blower ) fitted with 5 HP 440 V AC 1440 rpm TEFC motor cap: 200 cfm complete all as specified and directed.
Supply and Fix in repairs,moulded case circuit breakers (MCCBs),conforming to IEC 60947-2& IEC 60947-2, AC 415V, TPN, with current rating 160 Amps and 35 KA breaking capacity Icu at 415V, AC, 50Hz, with adjustable Over Load setting: 0.8 - 1.0 x In and adjustable Short Circuit setting: 6-10 x In,complete all as specified and directed. [Cat No. DZ1T0160DXD1A of Make “L&T” or equivalent Model of Make Siemens/ Legrand / ABB.]
Supply & Fix fully automatic star delta Submersible pump starter in sheet steel enclouser suitable for 25 HP pump set , 3 phase , 415 volt , 50 Hz , including making all electrical connection to run the pump and taking out old unserviceable complete all as specified and directed by Engr-In-Charge. Make:- C&S Cat Part No- BE3-SPSDDX254 322 or equivalent in L&T/BCH
Supply & Fix DOL pump starter in sheet steel enclouser suitable for 7.5 HP pump set , 3 phase , 415 volt , 50 Hz including making all electrical connection to run the pump and taking out old unserviceable starter complete all as specified and directed by Engr-In-Charge. Make:- C&S, Cat part No - BE1SPSDDX204 321-HM or equivalent in L&T/BCH
S& F in replacement of brass vertical check valve of size 80 mm for 5 HP/7.5 HP pump complete all as specified and directed
Material and labour for fixing GM globe/gate valve 50 mm bore with iron wheel head, screwed both ends for iron/PPR pipes, ISI marked, conf to IS including taking down old complete all as specified and directed by Engr in charge. Make : ZOLOTO / LEADER/ KARTAR. Note: Union or long screw have to provided before fixing of gate valve. (ii) Contractor has to submit the test certificate and purchase voucher of valves before claiming payment.
Material and labour for fixing GM globe/gate valve 40 mm bore with iron wheel head, screwed both ends for iron/PPR pipes, ISI marked, conf to IS including taking down old complete all as specified and directed by Engr in charge. Make : ZOLOTO / LEADER/ KARTAR. Note: Union or long screw have to provided before fixing of gate valve. (ii) Contractor has to submit the test certificate and purchase voucher of valves before claiming payment.
Material and labour for fixing GM globe/gate valve 25 mm bore with iron wheel head, screwed both ends for iron/PPR pipes, ISI marked, conf to IS including taking down old complete all as specified and directed by Engr in charge. Make : ZOLOTO / LEADER/ KARTAR. Note: Union or long screw have to provided before fixing of gate valve. (ii) Contractor has to submit the test certificate and purchase voucher of valves before claiming payment.
Material and labour for fixing GM globe/gate valve 20 mm bore with iron wheel head, screwed both ends for iron/PPR pipes, ISI marked, conf to IS including taking down old complete all as specified and directed by Engr in charge. Make : ZOLOTO / LEADER/ KARTAR. Note: Union or long screw have to provided before fixing of gate valve. (ii) Contractor has to submit the test certificate and purchase voucher of valves before claiming payment.
Supply and fixing sluice valve 200 mm bore, ISI marked, as per IS 14846: 2000 , with valid CMLNo. , Batch No. and Manufacturer Serial No., class PN 1.6 with brass spindle, brass check nut, with fiber board gasket, bolts, nuts and washers for fixing the valve in position, in valve pit chambers or location as directed and specified by Engr-in-charge. Make Uphadhya / Kirloskar/ Leader or equivalent make as catered in PS Note : Contractor has to submit the test certificate and Purchase Voucher of valves before claiming the payment..
Supply and fixing sluice valve 150 mm bore, ISI marked, as per IS 14846: 2000 , with valid CMLNo. , Batch No. and Manufacturer Serial No., class PN 1.6 with brass spindle, brass check nut, with fiber board gasket, bolts, nuts and washers for fixing the valve in position, in valve pit chambers or location as directed and specified by Engr-in-charge. Make Uphadhya / Kirloskar/ Leader or equivalent make as catered in PS Note : Contractor has to submit the test certificate and Purchase Voucher of valves before claiming the payment..
Supply and fixing sluice valve 100 mm bore, ISI marked, as per IS 14846: 2000 , with valid CMLNo. , Batch No. and Manufacturer Serial No., class PN 1.6 with brass spindle, brass check nut, with fiber board gasket, bolts, nuts and washers for fixing the valve in position, in valve pit chambers or location as directed and specified by Engr-in-charge. Make Uphadhya / Kirloskar/ Leader or equivalent make as catered in PS Note : Contractor has to submit the test certificate and Purchase Voucher of valves before claiming the payment..
Supply and fixing sluice valve 80 mm bore, ISI marked, as per IS 14846: 2000 , with valid CMLNo. , Batch No. and Manufacturer Serial No., class PN 1.6 with brass spindle, brass check nut, with fiber board gasket, bolts, nuts and washers for fixing the valve in position, in valve pit chambers or location as directed and specified by Engr-in-charge. Make Uphadhya / Kirloskar/ Leader or equivalent make as catered in PS Note : Contractor has to submit the test certificate and Purchase Voucher of valves before claiming the payment..
Material and labour for Joint with rubber or leather gasket for flanged pipes/Sluice Valve/NRV/ARV and any other type of valve and fittings of dia 100mm bore with incl nut, bolts, washers etc. and taking out old unserviceable complete all as specified and Engr-in-Charge.
All as per item No.48 here-in-before but Bore of pipe 80 mm complete all as specified and as directed.
All as per item No.48 here-in-before but Bore of pipe 150 mm complete all as specified and as directed.
All as per item No.48 here-in-before but Bore of pipe 200 mm complete all as specified and as directed.
Taking down unserviceable sluice valve/ Butter fly vlave/ NRV/foot valve and their fitments like gasket , bolt/nuts of size 80 to 200 mm bore without damaging the valve chamber and pipe line complete all as specified and directed by Engineer-In-charge
Materials and Labour for valve pit cover using brick masonry with fly ash brick valve chamber of internal size 1.5 M x1.5M x1.0 M with 23 cm thick wall in CM 1:6 including excavation if required, earth work in any strata & PCC 1:4:8 foundation type D-2, 75 mm thick including 20 mm thick PCC 1:2:4 type B1 in & plastering the internal surface with 10 mm thick cement mortar 1:4 if required & replacing old 3.15 mm MS sheet chamber cover double opening arrangement center lock system with 40x40x6mm angle iron frame duly painted with two coat of black bituminous paint over one coat of red oxide primer with and inluding demolition of existing complete all as directed by Engr in Chargre.
Cleaning the vegetation incl grass, bushes, small trees & all vegetation growth complete incl digging out roots of bushes around installation /sump/OH tanks/ valve chamber incl leveling the surface by removing debris to a distance n.exc 50 mtr all as directed.
Materials and Labour for, cast iron fittings for spigot and socketed cast iron pipes for water mains upto 150 mm bore,such as Bends (any type, radius and angle) tapers any type, (straight, bend, increasing,decreasing or double socket etc.) Tee pieces single branch. "Y" junction, double branch, cross (all sockets or socket and spigot) collars, caps and plugs, complete all as specified and directed.
Materials and Labour for,run lead joint for cast iron spigot and socket pipes and fittings for water mains ,200 mm bore, including burning out lead joints in position and including removing old lead from site, complete all as specified and directed. ( NOTE:- Earthwork shall be included in quoated rates)
All as per item No. 56 above but 150 mm dia.complete all as specified and as directed.
All as per item No. 56 above but 100 mm dia.complete all as specified and as directed.
Materials and Labour for,run lead joint for cast iron spigot and socket pipes and fittings for water mains ,80 mm bore, including burning out lead joints in position and including removing old lead from site, complete all as specified and directed. ( NOTE:- Earthwork shall be included in quoated rates)
Supply and Fix in repairs,ball valves, high pressure of PTMT with epoxy coated aluminium rod & high density plastic ball screwed for iron pipe 20 mm bore and fixed (Minimum weight 210 grams), complete all as specified and directed. [Make: Prayag Polymer Pvt Ltd Cat No.151 or equivalent Model of Make RS Industries:Polytuf/ Microplast Polymers Pvt Ltd]
Supply and Fix in repairs,ball valves, high pressure of PTMT with epoxy coated aluminium rod & high density plastic ball screwed for iron pipe 25 mm bore and fixed (Minimum weight 455 grams), complete all as specified and directed. [Make: Prayag Polymer Pvt Ltd Cat No.152 or equivalent Model of Make RS Industries: Polytuf/ Microplast Polymers Pvt Ltd]
Supply and fix in repair water level indicator made of aluminium base, marked with white Radium paint connected with steel wire rope 4 mm dia to counter weight showing level of water containing in tank including 8" dia brass float ball , and greasing of revolving pully of as per site requirement and fixed to pillar of water tank complete all as specified and directed by Engr-in-Charge Note : (i) All T&P required at site for fixing water level indicator on over head Tank at 18/21 mtr height shall be arranged by contractor and necessarry safety measure taken (ii) To remove the Bee Hives for fixing the guadge on water tank of height 18/21 mtr shall be contractor responsbility with any extra cost.
S&F in replacement of 4mm dia steel wire rope for water level indicator of various overhead tanks installed in AF station salua all as specified and directed by Engr-in charge.
Supply and fixing in repair Non return (Reflux valve) 150 mm dia , flap type ISI marked,as per IS 13095: 1991,both end flanged including fiber board gasket, bolts, nuts and washers for fixing the valve in position, or location as directed and specified by Engr-in-charge . Make : Uphadhya / Kirloskar/ Leader
Excavation in trenches in soft/loose or any type of soil n. exc 1.5 mtr wide and not exceeding 1.5 mtr depth and getting out all excavated materials and forming bottom surface to required level gradient for laying of water tubing complete all as specified and as directed.
Returning filling in soft/loose soil or any type of soil, including, spreading levelling watering and well ramming in layers not exc. 25 cm complete all as specified and directed.
Removing excavated soils to a distance not exceeding 50 Metres and depositing where directed at a level n. exc. 1.5 M above the starting point complete all asspecified and directed.
Taking up or down of old galvanised steel water tubing medium grade in walls, floors or ceilings/trenches etc including all fitting cleaning of serviceable pipe and segregating for re-use and removing unserviceable pipes from site of work complete all as specified and directed by Engr-in-Charge.
(a) 20 mm bore GI pipe complete
(b) 25 mm bore GI pipe complete
(c) 40 mm GI pipe complete
(d) 50 mm GI pipe complete
(e) 80 mm GI pipe complete
Supply and laying galvanised steel water tubing medium grade as per IS-1239 (Part-1) 2004 including all fittings conforming to IS 1239 (Part-2): 2011 in walls, floors or ceilings/trenches etc in new or old alignment complete with GI pipe clamp all as specified and as directed by Engr-in-Charge. Make: TATA/JINDAL or equivalent make as catered in PS Note: (i) Union or long screw have to provided at starting / end point of jointing pipe line . (ii) Contractor has to submit the test certificate and purchase voucher of pipes before claiming payment. (iii) Contractor shall provide MS/GI clamp for fixing the pipe on wall on every 10 cm without any extra cost.
(a) 20 mm bore GI pipe complete
(b) 25 mm bore GI pipe complete
(c) 40 mm GI pipe complete
(d) 50 mm GI pipe complete
(e) 80 mm GI pipe complete
VICKY ENTERPRISE
NATIONAL CONSTRUCTION CO
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .