Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.2 LAccepted-AOC AIRPORT ROAD SKALZANGLING LEH LADAKH 194101 | LEH LADAKH | LADAKH | 194101 | L1 | Accepted-AOC Being Lowest Bidder | |
| 2 | L2₹31.4 L+₹21,571 (0.69%)Rejected-Finance | L2 | Rejected-Finance Other than L1 | |
| 3 | L3₹32.0 L+₹87,120 (2.80%)Rejected-Finance R O Y K PURA QAZIGUND ANANTNAG 192221 J K | ANANTNAG | JAMMU AND KASHMIR | 192221 | L3 | Rejected-Finance Other than L1 | |
| 4 | L4₹32.1 L+₹94,564.80 (3.03%)Rejected-Finance | L4 | Rejected-Finance Other than L1 | |
| 5 | L5₹37.3 L+₹6.2 L (19.7%)Rejected-Finance 30 B 1 DEEN DAYAL NAGAR NAWABGANJ DEEN DAYAL NAGAR KANPUR NAGAR UTTAR PRADESH 208002 | KANPUR NAGAR | UTTAR PRADESH | 208002 | L5 | Rejected-Finance Other than L1 |
Tender Value
₹49.5 L
EMD Value
₹99,000
Closing Date
2 Dec 2022, 6:00 pmClosed
Col V S Sengar
HQ 138 Works Engineers PIN-914138 C/O 56 APO
REPAIR/MAINTENANCE TO STREET LIGHTS LT PANEL BOARD FEEDER PILLAR BOXES JUNCTION BOXES REMOVAL OF LT PANEL BD AND CONNECTED WORKS SERVICES AT KARU AND SHESHARSHATHANG UNDER GE 860 EWS
2022_MES_562628_1
138WE/L-58/2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE 860 EWS
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE 860 EWS
₹99,000
Yes
26 Dec 2022
11 Nov 2022
9 Dec 2022
11 Nov 2022
2 Dec 2022
25 Nov 2022
Amount
S&F, in replacement, MCCB, 415 volts, 04 pole, 63 Amps, 16 KA, ICS = 100% ICU, with Thermal - Magnetic Release, including spreader terminals, phase barriers, complete all as specified and directed by Engr-in-Charge.
S&F, in replacement, MCCB, 415 volts, 04 pole, 100 Amps, 35 KA, ICS = 100% ICU, with Thermal - Magnetic Release, including spreader terminals, phase barriers, complete all as specified and directed by Engr-in-Charge.
S&F, in replacement, MCCB, 415 volts, 04 pole, 160 Amps, 16 KA, adjustable type , including spreader terminals, phase barriers, complete all as specified and directed by Engr-in-Charge.
S&F, in replacement, MCCB, 415 volts, 04 pole, 200 Amps, 25 KA, adjustable type including spreader terminals, phase barriers, complete all as specified and directed by Engr-in-Charge.
S&F, in replacement, MCCB, 415 volts, 04 pole, 250 Amps, 25KA adjustable type including spreader terminals, phase barriers, complete all as specified and directed by Engr-in-Charge.
S&F, in replacement, MCCB, 415 volts, 04 pole, 400 Amps,36 KA adjustable type including spreader terminals, phase barriers, complete all as specified and directed by Engr-in-Charge.
S&F, in replacement, MCCB, 415 volts, 04 pole, 630 Amps, 50 KA adjustable type including spreader terminals, phase barriers, complete all as specified and directed by Engr-in-Charge.
Taking out old UNSV LT panel board / Junction box of any size complete all as specified and directed by Engr-in-Charge.
Supply, installation, testing and commissioning, in replacement, of Feeder Pillar box , cubical type, factory made, outdoor type, dust and vermin proof, fabricated out of mild steel sheet not less than 3.15 mm thick, and mild steel angle iron frame complete with openable shutters in front and rear having proper locking arrangement including 04 Nos legs made out of angle iron of suitable size and height of each leg shall be grouted in PCC. Feeder Pillar box shall be spray painted internally and externally with two coats of synthetic enamel paint over a priming coat of red oxide primer and connecting all incomming and outgoing cables with suitable size of Aluminium lugs complete all as specified and as directed by Engineer-in-Charge and comprising of following accessories/fittings :- (a) MCCB 4 pole, 400 Amps, 415 Volt, AC ,36 KA = 01 Nos (I/C) (b) MCCB 4 pole, 200 Amps, 415 Volt, AC ,16 KA = 02 Nos (O/G) (c) MCCB 4 pole, 160 Amps, 415 Volt, AC, 16 KA = 02 Nos (O/G) (d) MCB SPN 63 Amps, 230 Volts = 10 Nos (O/G) (e) Multifunction meter MFM 4400 LED meter Cl 0.5S with RS485 (f) Phase indicating lamp = 03 Nos (R, Y, B) (g) Copper bus bar of capacity 600 amps four strip with colour coding should be shrinkable sleeves 4 Nos fixed on insulators-01 Set of four Note : Unit rate quoted by the contractor here-in-before also includes for installation of panel on suitable PCC foundation and PCC plat form incl necessary earth and PCC work all as per manufacturer instructions and as directed by the Engr-in-Charge.
Supply, installation, testing and commissioning, in replacement, of Feeder Pillar box , cubical type, factory made, outdoor type, dust and vermin proof, fabricated out of mild steel sheet not less than 3.15 mm thick, and mild steel angle iron frame complete with openable shutters in front and rear having proper locking arrangement including 04 Nos legs made out of angle iron of suitable size and height of each leg shall be grouted in PCC. Feeder Pillar box shall be spray painted internally and externally with two coats of synthetic enamel paint over a priming coat of red oxide primer and connecting all incomming and outgoing cables with suitable size of Aluminium lugs complete all as specified and as directed by Engineer-in-Charge and comprising of following accessories/fittings :- (a) MCCB 4 pole, 250 Amps, 415 Volt, AC ,25 KA = 01 Nos (I/C) (b) MCCB 4 pole, 160 Amps, 415 Volt, AC ,16 KA = 02 Nos (O/G) (c) MCCB 4 pole, 100 Amps, 415 Volt, AC ,16 KA = 02 Nos (O/G) (d) MCB SPN 63 Amps, 230 Volts, AC = 11 Nos (O/G) (e) Multifunction meter MFM 4400 LED meter Cl 0.5S with RS485 (f) Phase indicating lamp = 03 Nos (R, Y, B) (g) Copper bus bar of capacity 400 amps four strip with colour coding should be shrinkable sleeves 4 Nos fixed on insulators-01 Set of four Note : Unit rate quoted by the contractor here-in-before also includes for installation of panel on suitable PCC foundation and PCC plat form incl necessary earth and PCC work all as per manufacturer instructions and as directed by the Engr-in-Charge.
Supply, installation, testing and commissioning, in replacement, of Feeder Pillar box , cubical type, factory made, outdoor type, dust and vermin proof, fabricated out of mild steel sheet not less than 3.15 mm thick, and mild steel angle iron frame complete with openable shutters in front and rear having proper locking arrangement including 04 Nos legs made out of angle iron of suitable size and height of each leg shall be grouted in PCC. Feeder Pillar box shall be spray painted internally and externally with two coats of synthetic enamel paint over a priming coat of red oxide primer and connecting all incomming and outgoing cables with suitable size of Aluminium lugs complete all as specified and as directed by Engineer-in-Charge and comprising of following accessories/fittings :- (a) MCCB 4 pole, 250 Amps, 415 Volt, AC ,25 KA = 01 Nos (I/C) (b) MCCB 4 pole, 100 Amps, 415 Volt, AC ,16 KA = 03 Nos (O/G) (c) MCB SPN, 63 Amps, 230 Volt, AC, = 04 Nos (O/G) (d) Multifunction meter MFM 4400 LED meter Cl 0.5S with RS485 (e) Phase indicating lamp = 03 Nos (R, Y, B) (f) Copper bus bar of capacity 400 amps four strip with colour coding should be shrinkable sleeves 4 Nos fixed on insulators-01 Set of four Note : Unit rate quoted by the contractor here-in-before also includes for installation of panel on suitable PCC foundation and PCC plat form incl necessary earth and PCC work all as per manufacturer instructions and as directed by the Engr-in-Charge.
Supply, installation, testing and commissioning, in replacement, of Feeder Pillar box , cubical type, factory made, outdoor type, dust and vermin proof, fabricated out of mild steel sheet not less than 3.15 mm thick, and mild steel angle iron frame complete with openable shutters in front and rear having proper locking arrangement including 04 Nos legs made out of angle iron of suitable size and height of each leg shall be grouted in PCC. Feeder Pillar box shall be spray painted internally and externally with two coats of synthetic enamel paint over a priming coat of red oxide primer and connecting all incomming and outgoing cables with suitable size of Aluminium lugs complete all as specified and as directed by Engineer-in-Charge and comprising of following accessories/fittings :- (a) MCCB 4 pole, 250 Amps, 415 Volt, AC ,35 KA = 01 Nos (I/C) (b) MCCB 4 pole, 100 Amps, 415 Volt, AC ,35 KA = 02 Nos (O/G) (c) On load change over switch (side handled) 4 pole, 100 Amps, 415 Volt = 01 Nos Make : Havells (d) MCB SPN 63 Amps, 230 Voltst, AC = 2 Nos (O/G) (e) Multifunction meter MFM 4400 LED meter Cl 0.5S with RS485 (f) Phase indicating lamp = 03 Nos (R, Y, B) (g) Copper bus bar of capacity 400 amps four strip with colour coding should be shrinkable sleeves 4 Nos fixed on insulators-01 Set of four Note : Unit rate quoted by the contractor here-in-before also includes for installation of panel on suitable PCC foundation and PCC plat form incl necessary earth and PCC work all as per manufacturer instructions and as directed by the Engr-in-Charge.
Supply, installation, testing and commissioning, in replacement, of Feeder Pillar box , cubical type, factory made, outdoor type, dust and vermin proof, fabricated out of mild steel sheet not less than 3.15 mm thick, and mild steel angle iron frame complete with openable shutters in front and rear having proper locking arrangement including 04 Nos legs made out of angle iron of suitable size and height of each leg shall be grouted in PCC. Feeder Pillar box shall be spray painted internally and externally with two coats of synthetic enamel paint over a priming coat of red oxide primer and connecting all incomming and outgoing cables with suitable size of Aluminium lugs complete all as specified and as directed by Engineer-in-Charge and comprising of following accessories/fittings :- (a) MCCB 4 pole, 250 Amps, 415 Volt, AC ,50 KA = 01 Nos (I/C) (b) MCCB 4 pole, 100 Amps, 415 Volt, AC, 25 KA= 02 Nos (O/G) (c) MCCB 4 pole, 63 Amps, 415 Volt, AC, 25 KA= 01 Nos (O/G) (d) MCB SPN 63 Amps, 230 Volts, AC = 04 Nos (O/G) (e) Multifunction meter MFM 4400 LED meter Cl 0.5S with RS485 (f) Phase indicating lamp = 03 Nos (R, Y, B) (g) Copper bus bar of capacity 400 amps four strip with colour coding should be shrinkable sleeves 4 Nos fixed on insulators-01 Set of four Note : Unit rate quoted by the contractor here-in-before also includes for installation of panel on suitable PCC foundation and PCC plat form incl necessary earth and PCC work all as per manufacturer instructions and as directed by the Engr-in-Charge.
Supply, installation, testing and commissioning, in replacement, of Feeder Pillar box , cubical type, factory made, outdoor type, dust and vermin proof, fabricated out of mild steel sheet not less than 3.15 mm thick, and mild steel angle iron frame complete with openable shutters in front and rear having proper locking arrangement including 04 Nos legs made out of angle iron of suitable size and height of each leg shall be grouted in PCC. Feeder Pillar box shall be spray painted internally and externally with two coats of synthetic enamel paint over a priming coat of red oxide primer and connecting all incomming and outgoing cables with suitable size of Aluminium lugs complete all as specified and as directed by Engineer-in-Charge and comprising of following accessories/fittings :- (a) MCCB 4 pole, 250 Amps, 415 Volt, AC ,50 KA = 01 Nos (I/C) (b) MCCB 4 pole, 100 Amps, 415 Volt, AC, 25 KA= 02 Nos (O/G) (c) MCCB 4 pole, 63 Amps, 415 Volt, AC, 25 KA= 04 Nos (O/G) (d) MCB SPN 63 Amps, 230 Volts, AC = 04 Nos (O/G) (e) Multifunction meter MFM 4400 LED meter Cl 0.5S with RS485 Make : L&T (f) Phase indicating lamp = 03 Nos (R, Y, B) (g) Copper bus bar of capacity 400 amps four strip with colour coding should be shrinkable sleeves 4 Nos fixed on insulators-01 Set of four Note : Unit rate quoted by the contractor here-in-before also includes for installation of panel on suitable PCC foundation and PCC plat form incl necessary earth and PCC work all as per manufacturer instructions and as directed by the Engr-in-Charge.
Supply, installation, testing and commissioning, in replacement, of Feeder Pillar box , cubical type, factory made, outdoor type, dust and vermin proof, fabricated out of mild steel sheet not less than 3.15 mm thick, and mild steel angle iron frame complete with openable shutters in front and rear having proper locking arrangement including 04 Nos legs made out of angle iron of suitable size and height of each leg shall be grouted in PCC. Feeder Pillar box shall be spray painted internally and externally with two coats of synthetic enamel paint over a priming coat of red oxide primer and connecting all incomming and outgoing cables with suitable size of Aluminium lugs complete all as specified and as directed by Engineer-in-Charge and comprising of following accessories/fittings :- (a) MCCB 4 pole, 250 Amps, 415 Volt, AC ,50 KA = 01 Nos (I/C) (b) MCCB 4 pole, 100 Amps, 415 Volt, AC, 25 KA= 01 Nos (O/G) (c) MCCB 4 pole, 63 Amps, 415 Volt, AC, 25 KA= 03 Nos (O/G) (d) MCB SPN 63 Amps, 230 Volts, AC = 04 Nos (O/G) (e) Multifunction meter MFM 4400 LED meter Cl 0.5S with RS485 Make : L&T (f) Phase indicating lamp = 03 Nos (R, Y, B) (g) Copper bus bar of capacity 400 amps four strip with colour coding should be shrinkable sleeves 4 Nos fixed on insulators-01 Set of four Note : Unit rate quoted by the contractor here-in-before also includes for installation of panel on suitable PCC foundation and PCC plat form incl necessary earth and PCC work all as per manufacturer instructions and as directed by the Engr-in-Charge.
Supply, installation, testing and commissioning, in replacement, Junction box , cubical type, factory made, outdoor type of Size 45cm(l)x30cm(w)x60cm(h) , dust and vermin proof, fabricated out of mild steel sheet not less than 3.15 mm thick, complete with openable shutters in front and rear having proper locking arrangement including including 04 Nos legs made out of angle iron of suitable size and height of each leg shall be grouted in PCC and copper bus bar of size 400 Amps capacity , Three phase and neutral bus bar , making hot and cold drilling holes to aluminium bus bar . Junction box shall be spray painted internally and externally with two coats of synthetic enamel paint over a priming coat of red oxide primer and connecting all incomming and outgoing cables with suitable size of Aluminium lugs complete all as specified and as directed by Engineer-in-Charge.
Supply, installation, testing and commissioning, in replacement, Junction box , cubical type, factory made, outdoor type of Size 45cm(l)x30cm(w)x60cm(h) , dust and vermin proof, fabricated out of mild steel sheet not less than 3.15 mm thick, complete with openable shutters in front and rear having proper locking arrangement including including 04 Nos legs made out of angle iron of suitable size and height of each leg shall be grouted in PCC and Copper bus bar of size 600 Amps capacity , Three phase and neutral bus bar , making hot and cold drilling holes to aluminium bus bar . Junction box shall be spray painted internally and externally with two coats of synthetic enamel paint over a priming coat of red oxide primer and connecting all incomming and outgoing cables with suitable size of Aluminium lugs complete all as specified and as directed by Engineer-in-Charge and comprising of following accessories/fittings :- (a) MCCB 4 pole, 160 Amps,240/415 Volt, 50Hz, 10 KA= 01 Nos (I/C). (b) MCB SPN 63 Amps, 240 Volts - 04 Nos (O/G) Note : Unit rate quoted by the contractor here-in-before also includes for fixing and connecting of MCBs and installation of panel on suitable PCC foundation and PCC plat form incl necessary earth and PCC work all as per manufacturer instructions and as directed by the Engr-in-Charge.
Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6.3 mm thick buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 metres below normal ground level, connecting to the Galvanised earth lead GI Strip 32 mm by means of bolts, nuts , check nuts and washers of galvanized iron and steel earth wire protected by provision of GI light grade pipe 40 mm bore including provision of concrete pit made from PCC ( 1:2:4) type B-1 (using 20 mm graded stone aggregate) with 40mm thick cover of RCC 1:2:4 reinforced with XPM (Weight not less than 4 Kg/Sqm) and frame of angle iron 40 x 40 x 6 mm and handle of 6 mm dia MS bar made to shape, GI light grade 20 mm bore pipe for watering perforated at bottom, 1.50 metre long placed on top edge of earth plate, common salt & charcoal filling, with fixing arrangement , funnel, wire mesh and earth work in hard/dense soil , returning filling in and removal of surplus soil to a distance not exceeding 50 metres, all as per electrical plate No 5 of SSR 2009 Part-I and connecting to Poles all as specified or indicated including testing on complete all as specified and as directed by Engineer-in-Charge.
Excavation in trenches in hard / dense soil not exceeding 1.5 mtr in depth and not exceeding 1.5 mtr wide and getting out including trimming of sides, for laying of cables & foundation of poles, stay assembly, complete all as specified and directed by Engr-in-Charge.
Returning filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm thick, complete all as specified and directed by Engr-in-Charge.
Removing excavated material to a distance not exc 50m and depositing where directed at a level not exc 1.5m above the starting point, complete all as specified and directed by Engr-in-Charge.
Taking out old unserviceable/serviceable un-reinforced concrete PCC cable covers from excavated trench all as directed by the Engineer-in-Charge. Note:- Serviceable un-reinforced concrete PCC cable cover kept in safe custody for reuse at site and unserviceable un-reinforced concrete PCC cable cover through in low lying area.
Laying only old reinforced PCC cable cover of any size as retrieved from serial item No- 24 above, complete all as directed by Engineer-in-Charge.
M&L for factory made un-reinforced pre cast concrete cable protection cover LV class type - I with size 250mm x 150mm x 40mm laid across the cable (i.e. width of cover along the length of cable) for UG cable protection on the top of the sand cushioning, complete all as specified and directed by Engr-in-Charge.
M&L for sand cushioning with layer of sand 8cm thick before laying of cable and 10cm after laying of cable in trenches complete all as directed and sand cover to UG cable, complete all as specified and directed by Engr-in-Charge. Note:- Punned thickness only to be measured as per SSR.
Supply, laying, testing and commissioning in repairs of LT UG cable XLPE insulated PVC sheathed galvanized steel strip armoured electric power cable with stranded aluminium conductor 1100 volts grade 10 sq mm 2 core confirming to IS:7098 (Part-I), suitable for earthed system, laid in duct/trench/along pole/wall etc including nuts, bolts, washers, saddles & screws etc and making connection, complete all as directed. Note : 1. The cost of Al thimbles/lugs and cable gland etc is included in quoted rate and no extra payment will be made for it. 2. Excavation, earth work, sand cushioning and brick protection will be measured and paid separately under respective items.
S&F of galvanized iron pipe of 50 mm nominal dia light grade fixed to poles with clamps nuts, bolts and washers or laid under road crossing or fixed to wall including painting with two coats of aluminium paint over a coat of red oxide paint, complete all as specified and directed. Note : The cost of MS clamp, nut, bolt, washer and GI fittings etc shall be inclusive in the item rate.
Dismantling and taking down unserviceable / defective street light fitting / Flood light fitting of any wattage alongwith mounting bracket, flat iron clamp, nuts bolts etc from overhead LT poles complete all as directed.
S&F of LED street light luminaire of 40 Watt capacity, made of single piece pressure die-cast aluminium housing with high power LED with lens for proper light distribution luminiaries, IP 66, with toughned glass cover and incl control gear etc, with and incl making all electric connection, complete all as specified and directed by Engineer in charge.
S&F of LED street light luminaire of 60 Watt capacity, made of single piece pressure die-cast aluminium housing with high power LED with lens for proper light distribution luminiaries, IP 66, with toughned glass cover and incl control gear etc, with and incl making all electric connection, complete all as specified and directed by Engineer in charge.
S&F of LED street light luminaire of 90 Watt capacity, made of single piece pressure die-cast aluminium housing with high power LED with lens for proper light distribution luminiaries, IP 66, with toughned glass cover and incl control gear etc, with and incl making all electric connection, complete all as specified and directed by Engineer in charge.
S&F of LED street light luminaire of 120 Watt capacity, made of single piece pressure die-cast aluminium housing with high power LED with lens for proper light distribution luminiaries, IP 66, with toughned glass cover and incl control gear etc, with and incl making all electric connection, complete all as specified and directed by Engineer in charge.
S&F of LED flood light luminaire of 100 Watt capacity, made of single piece pressure die-cast aluminium housing with high power LED with lens for proper light distribution luminiaries, IP 66, with toughned glass cover and incl control gear etc, with and incl making all electric connection, complete all as specified and directed by Engineer in charge.
S&F of LED flood light luminaire of 200 Watt capacity, made of single piece pressure die-cast aluminium housing with high power LED with lens for proper light distribution luminiaries, IP 66, with toughned glass cover and incl control gear etc, with and incl making all electric connection, complete all as specified and directed by Engineer in charge.
S&F LED step light 9 W with die cast aluminium housing with warm white COB LED reflector and IP65 protection and incl making all electric connection, complete all as specified and directed by Engineer in charge.
S&F LED post tops 45 W with die cast aluminium housing and polycarbonate opal diffuser and IP protection and incl making all electric connection, complete all as specified and directed by Engineer in charge.
S&F in replacement of street light fitting bracket, 1.5 mtr long made out of galvanized iron pipe of 40 mm dia size light grade complete with and incl 02 nos MS clamp made of MS flate iron of 50 x 6 mm size with nut, bolts, washer etc with and incl two coats of aluminum paint over a coat of red oxide primer, complete all as directed.
Supply, fixing and testing of Automatic Street Light Control Switch with panel complete with :- (a) Infrared senser based 01 nature switch for automatic switching of street lights. Nature switch operation should based on natural light lux level required illuminance level for switching "ON" is less or equal to 30 lux and for switching "OFF" is 10 lux. The sensor should also have part night operation facility of minimum 04 hrs to maximum 12 hrs - 01 Nos. Make of Sensor- Kakatiya Energy system/Bajaj/Healer (b) Power Contactor single phase, 230 Volts, 40 Amps capacity cnforming to IEC-60947-4-1 03 Nos. Make- BCH/L&T/Schneider Kakatiya Engergy systme/Bajaj/Heater (c) The sensor along with suitable Power Contactor and Incoming/outgoing MCBs shuold be enclosed in a pole/ wall mounted rust proof, electric shock proof, termite proof and FR grade thermoplastic polycorbonate enclosure ( with hinged lid) conforming to IP-66 production class-II of suitable size to accommodate all panels accessories- 01 Job. Make- Hensel/Syntex/equivalent. (d) MCB TPN 40 Amps, B- curve, conforming to IEC-60898/IS-8828-02 Nos. (e) All Control cables wirring inside the panel should be of copper conductor, multistranded, PCV insulated, FRLS, 1100 Volts grade of size 10 sqmm, single core followed by colour coding and lugs/thimbles. (f) All equipments should be mounted on suitable size insulator. Note : Rate should be incl taking down Existting street Control switch.
M&L for preparation old (exposed) painted surfaces of existing LT steel tubular street Light pole, struts including cross arms, clamps etc complete and applying two coats of aluminium paint over a coat of red oxide primer over the ground and making 30cm wide strip with black and yellow paint including numbering of HT/LT poles at a height of 1.5 mtr above ground level as per existing having 15mm width and 50mm bold letter complete all as specified and directed including Marking Red Stipn painting on HT Poles etc.
M&L for two run of 2.5 sqmm Aliminium conductor twin core cable for connection of the street light with junction box / Over head LT line complete all as specified and as directed by Engineer-in-Charge.
M&L, in replacement, junction box outdoor type of size 14cmX19cm made out of MS sheet of thickness not less than 1.6 mm having hinged front opening door with two nos aluminium strip bus bar of capacity 63 amps fitted on resin based insulator and One no. MCB SPN 32 Amps rating and suitable size of clamps for mounting the junction box on Garden light post and painted with two coats of synthetic enamel aluminium paint over a coat of red oxide primer complete all as specified and as directed.
FORTUNE STAR
M/S BHAT ENGINEERS
Ms Salaria Builders
M/S ASHISH AND CO
M/S BETONG CONSTRUCTION CO
M/S TRADE LINK
EESSI
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .