Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance 26 740 35 KESARI HOUSE NEAR RICO INDUSTRIAL AREA DEVIPURA SIKAR RAJASTHAN 332 001 | SIKAR | SIKAR | RAJASTHAN | 332001 | Admitted-Finance |
Tender Value
₹45.6 L
EMD Value
₹91,300
Closing Date
12 Dec 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE(I) 873 EWS
Garrison Engineer (Indep) 873 Engineer Works Section PIN 913 873 C/O 56 APO
AUGMENRATION OF 100 KVA TRANSFORMER AT DHARMUND MIL STN, PROVN OF 11KVA VCB PANEL AT CHANDERKOT AND PROVN OF 150 KVA TRANSFPRMER AND 150 KVA SERVO VLTAGE STABILIZER AT MAITRA GRN MIL STN
2023_MES_627636_1
NIT-63 of 2023-2024
Open Tender
Civil Works
Item Rate
180 days
Bhaderwah
As per NIT
7 documents required · 7 mandatory
₹500
GE(I) 873 EWS
₹91,300
Yes
23 Dec 2023
9 Nov 2023
14 Dec 2023
9 Nov 2023
12 Dec 2023
23 Nov 2023
Amount
Supply, installation, testing and commissioning of capacity 100 KVA Transformer, step-down, 11/0.433 KVA complete, outdoor type, copper wound with transformer oil of dieletric strength-45KV including tapping up and down, installing with proper connection of HT/LT side, earthing of capacity 63 KV, Three Phase, Four Wire, 50 Hz, oil immersed naturally cooled, Delta connected on primary (HV) side and star connected (LV) side, having tapping 0%, 2.5%. 5% and 7.5% on HV to be charged by means of hand operated Off Load tap changing gear including first filling of oil and all standard fitting such as breather unit, drain out valve. conservator tank and mounting, complete all as specified in IS-2026 and as directed. Make : Bhel / Alstom / Seimens / ABB / JK Transformer / Bharat Bijlee / Voltamp / Schneider
Supply, installation, testing and commissioning of capacity 150 KVA Transformer, step-down, 11/0.433 KVA complete, outdoor type, copper wound with transformer oil of dieletric strength-45KV including tapping up and down, installing with proper connection of HT/LT side, earthing of capacity 63 KV, Three Phase, Four Wire, 50 Hz, oil immersed naturally cooled, Delta connected on primary (HV) side and star connected (LV) side, having tapping 0%, 2.5%. 5% and 7.5% on HV to be charged by means of hand operated Off Load tap changing gear including first filling of oil and all standard fitting such as breather unit, drain out valve. conservator tank and mounting, complete all as specified in IS-2026 and as directed. Make : Bhel / Alstom / Seimens / ABB / JK Transformer / Bharat Bijlee / Voltamp / Schneider
Steel Tubular swaged poles type 410 SP-55 (11.0 mtr long) conforming to IS : 2713 Part-I to III 1980, complete with 6 mm thick mild steel base plate, finial taper plug, MS bolts, nuts, screws including painting upto 1.5metre above PCC coping in black and white strips 05 Nos of 30cms each starting from the bottom of the pole and two coats epoxy based paint aluminium grade finish to the remaining external surface over one coat of primer complete including taking down old unserviceable Pole all as specified and directed.
Steel Tubular swaged poles type 410 SP-31 (9.0 mtr long) conforming to IS : 2713 Part-I to III 1980, complete with 6 mm thick mild steel base plate, finial taper plug, MS bolts, nuts, screws including painting upto 1.5metre above PCC coping in black and white strips 05 Nos of 30cms each starting from the bottom of the pole and two coats epoxy based paint aluminium grade finish to the remaining external surface over one coat of primer complete including taking down old unserviceable Pole all as specified and directed.
S&F Lightning arrestor expulsion type, consisting of multiple spark gaps in series with one or more non-linear resistor to limit voltage surge on AC power circuit to interrupt power flow current suitable for outdoor installation and exposed direct to sun with ambient temperature between (-)10° C to (+) 50° C suitable for surge discharge capacity 65 KA, 11000 Volts grade conforming to IS-4350 complete with all fittings, complete all as specified and directed.
S&F in replacement of Switch Air break, gang operated (GOD) with 15 Nos insulators, outdoor type, Three Pole mechanically operated, suitable for vertical installation, Single break, provided with locking arrangements consisting of MS channel, HT Post type insulator copper alloy, high Pressure, Assembly operating rod 25 mm dia GI pipe medium grade for operating from 1.2 metre above Ground Level with locking arrangement complete confirming to IS-1018 of 1972 rated voltage 11 KV and for current rating 400 Amps complete all as specified and directed.
S&F in replacement of Switch Air break, gang operated (GOD) with 15 Nos insulators, outdoor type, Three Pole mechanically operated, suitable for vertical installation, Single break, provided with locking arrangements consisting of MS channel, HT Post type insulator copper alloy, high Pressure, Assembly operating rod 25 mm dia GI pipe medium grade for operating from 1.2 metre above Ground Level with locking arrangement complete confirming to IS-1018 of 1972 rated voltage 11 KV and for current rating 200 Amps complete all as specified and directed.
M&L for Pre-painted galvatume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of an colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws complete all as specified and directed.
M&L for Pre-painted galvatume aluminum zinc coating GI based plain steel sheet 0.50mm thick of an colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws complete all as specified and directed.
Supply, installation, testing and commissioning sheet metal enclosure out door type, weather proof for Energy Meter Factory fabricated from 3.15 mm thick CRCA sheet, compartmentalized design, suitable for downloading data from meter to AMRI without opening panel with suitable locking arrangements, of size not less than 0.60 x 0.45 x 0.30 mtr including suitable clump fitted to poles as required at site all as specified and directed.
M&L for Connection cable from CT/PT Unit to trivector meter with PVC insulated unsheathed FRLS cable of size 1.5sqmm x 10 core, complete all as specified and directed.
M&L for earthing complete with GI earth plate electrode of size 600mm x 600mm x 6mm thick buried directly to ground vertically to a depth not less than 2.25 Mtr below the ground level with top edge of earth plate not less than 1.65 Mtr below normal ground level connected to GI strip 32.6 mm size and earthing lead protected with 40 mm bore GI pipe, light grade, filling around with charcoal dust and salt including excavation, returning, filling of earth and disposal of surplus soil to a distance not exceeding 50 mtr and connected to GI strip by means of GI nuts, bolts and washers strip connected to earth plate including chamber PCC 1:3:6 type C-1 using 20mm graded crushed stone aggregate in concrete pit pre-cast RCC 40 mm thick reinforced with 6 mm dia round at 75 mm C/C both way with 12 mm dia mild steel plain bar lifting handle 2 Nos funnel with wire mesh 20 mm dia GI pipe light grade watering pipe and frame work complete all as shown in electrical plate No. 3 of SSR Part-I 2009 including testing on completion complete all as specified and as directed.
M&L for galvanised Iron earthing strip 32 x 6 mm from earth test point to electrical equipment complete all as specified and directed
M&L for earthing complete with galvanized mild steel earth plate electrode size 600mm x 600mm x 6mm thick buried directly in ground (preferably in vertical position) earth pit not less than 2.25 meter below normal ground level with top edge of the earth plate not less 1.5 meter (BGL) connected to galvanized iron earth lead wire 4mm dia by means of bolts, nuts, check nut and washer of galvanized iron including PCC pit in RCC 1:2:4 type B-1, precast RCC cover with suitable handle, excavation and earth work in any type of soil, 20mm bore “medium grade” galvanized iron water tubing fixed with cast iron funnel and wire mesh and 15mm bore “light grade” galvanized iron protection pipe for earth lead wire upto 5m length, charcoal, common salt, complete all as shown in EP No 3 of SSR 2009 Part-I, connected to test point complete, all as specified and testing on completion.
M&L for galvanised Iron earth wire 4 Sqmm from earth test point to electrical equipment including taking down old unserviceable earth wire complete all as specified and directed.
M&L for aluminium conductor steel reinforced (ACSR) including binding to insulator with suitable size of binding wire and size of conductor Weasel (6/1 x 2.59 mm), Squirrel (6/1 x 2.11mm) or Ferret (6/1 x 3.00 mm) all as specified and directed.
S&F disc type insulator, porcelain, vitreous, white, brown or green including one galvanised mild steel spindle, two galvanised 145 mm height 255 mm dia for 11000 Volts grade complete all as specified and directed.
S&F pin type porcelain, vitreous white, brown or green insulator including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, 150mm height, 150mm dia for 11000 volt complete all as specified and directed.
S&F cable Jointing Kit for 11 KV grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95-120 Sqmm including testing and commissioning, complete all as specified and directed.
S&F cable Jointing Kit for 11 KV grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 185 Sqmm including testing and commissioning, complete all as specified and directed.
S&F cable Jointing Kit for 1.1 KV grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 95 Sqmm including testing and commissioning, complete all as specified and directed.
M&L for framed work of hot rolled ateel equal angle of size 65x65x6mm (ref IS:808(PartV1976) as in doors or gates of angle or other section with gusset plates, rails, braces, etc., complete, drilled for fixing of steel sheeting or other covering. Doors, etc. to be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fittings (exclusive of steel sheeting or other covering, running rails and guides) and hanging; also fastening and fixing complete complete all as specified and directed.
M&L for cross arm bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, drilling holes for bolts, in any shape or size as indicated or directed and also inclusive of two coats of aluminium paint over one coat of red oxide primer all as specified and as directed.
Supply, laying, jointing with suitable thimble and cable gland, testing and commissioning or fixing in wall or passing through pipe, 11000 volts grade heavy duty with XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor of cross sectional area of 95 Sqmm 3 Core complete all as specified and directed.
Supply, laying, jointing with suitable thimble and cable gland, testing and commissioning or fixing in wall or passing through pipe, 11000 volts grade heavy duty with XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor of cross sectional area of 120 Sqmm 3 Core complete all as specified and directed.
Supply, laying, jointing with suitable thimble and cable gland, testing and commissioning or fixing in wall or passing through pipe, 11000 volts grade heavy duty with XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor of cross sectional area of 185 Sqmm 3 Core complete all as specified and directed.
Supply, laying, jointing with suitable thimble and cable gland, testing and commissioning or fixing in wall or passing through pipe with XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade ISI marked cross sectional area 95 Sqmm 3.5 core, complete all as specified and directed.
Supply, laying, jointing with suitable thimble and cable gland, testing and commissioning or fixing in wall or passing through pipe with XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade ISI marked cross sectional area 70 Sqmm 3.5 core, complete all as specified and directed.
Supply, laying, jointing with suitable thimble and cable gland, testing and commissioning or fixing in wall or passing through pipe with XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade ISI marked cross sectional area 50 Sqmm 3.5 core, complete all as specified and directed.
Supply, laying, jointing with suitable thimble and cable gland, testing and commissioning or fixing in wall or passing through pipe, 1100 volts grade heavy duty with XLPE insulated armoured heavy duty electric cable with aluminium conductor ISI marked cross sectional area 35 Sqmm 4 core, complete all as specified and directed.
Supply, laying, jointing with suitable thimble and cable gland, testing and commissioning or fixing in wall or passing through pipe with XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade ISI marked cross sectional area 16 Sqmm 2 core, complete all as specified and directed.
1100 volts grade heavy duty cable with PVC insulated aluminiuum stranded conductor served with an inner sheating of PVC tape and overall PVC sheathed in service connection suspended by insulating hangers not more than 1 mtr apart including 4mm suspention wire one twin core 16 sqmm solid conductor all as specified and directed.
Excavating in trenches, not exceeding 1.5metre wide and not exceeding 1.5metre depth for foundation, etc., and getting out in any type of soil, complete all as specified and directed.
Excavating in trenches, not exceeding 1.5metre wide and exceeding 1.5metre depth but not exceeding 3.0metre depth for foundation, etc., and getting out in any type of soil, complete all as specified and directed. Note for item no. 29 & 30 : Due care shall be taken while deciding cable route for excavation. However any damage to Signal, BSNL, MES cable water/sewage pipe or any other service while excavation will be made good by the contractor and cost of the same for jointing material & labour is deemed to be included in the cost of excavation.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick any type of soil, complete all as specified and directed.
Removing excavated soils to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
Sand cushioning to underground cables using new dry river sand laid in trenches 8cm thick below the cable and 15cm thick above the cable after laying and stretching the cable complete, punned to 18cm, complete all as specified and directed Note : Punned thickness of 18cms shall be measured for payment.
Supply and laying brick covering with width equal to length of bricks as mechanical protection to underground cable using old size sub class 'B' bricks, laid flat size 230mm x 115mm x 75 mm with width of brick perpendicular to length of cable, all as specified and directed.
M&L for cement concrete 1:4:8, type D-2 (using 40mm graded crushed stone aggregate) as in foundation filling and mass concrete for pole/stay, complete all as specified and directed.
M&L for cement concrete 1:3:6, type C-2 (using 40mm graded crushed stone aggregate) as in foundation filling and mass concrete, complete all as specified and directed.
M&L for cement concrete type B-1 1:2:4 (using 20mm graded crushed stone aggregate) as in coping of poles, complete all as specified and directed.
M&L for steel pipe galvanised light grade, 100 mm bore laid in trenches or under ground/floor or road of fixed with pole for protection of cable including GI clamps with bolts nuts and washers complete all as specified and directed.
M&L for steel pipe galvanised light grade, 80 mm bore laid in trenches or under ground/floor or road of fixed with pole for protection of cable including GI clamps with bolts nuts and washers complete all as specified and directed.
M&L for steel pipe galvanised light grade, 50 mm bore laid in trenches or under ground/floor or road of fixed with pole for protection of cable including GI clamps with bolts nuts and washers complete all as specified and directed.
Danger notice plate of size 25 x 20 cm, made of 1.6 mm thick mild steel sheet, vitreous enamelled white with letters, figures and conventional skull and bones in signal red colour and fixed with and including mild steel clamps, bolts and nuts of approved size for HT poles, complete all as specified.
Supply, Install Testing & Commissioning of LT panel compartmentalised design, dust and varmin proof of size 1800 mm(Height) x 1200 mm(Length) x600 mm(Width) suitable for 440 Volt 3 phase 4 wire system made out of 1.4mm thick CRCA sheet and built upon regid frame work having front and rear hinged doors with neoprence rubber gasket including danger plate, earthing strip point and, ventilation louvers at the rear side, bottom detachable gland plate complete with suitable size of Zinc/Cromium plated and nuts, bolts ;and washers etc. The pannel shall be powder coated internally & externally and the control circuit diagram shall be with colour code solid conductor copper 1.5 sqmm cable for easy identification including incomming/outgoing cable holes at the bottom, complete after taking down the old unserviceable one. The Panel shall be emmbeded with 75 x 6 mm MS Angle Iron frame and to be grouted with PCC foundation (1:3:6 ) type C2 upto a height of 50 cm from normal ground level complete all as specified, directed and comprising of the following:-
Incoming (a) Bus bar chamber comprising 4 Nos copper strip of size 32 x 6 mm and lenght 600mm each bus bar and having min 10 holes arrangement in each basbar strip. PVC insulated made of copper strip of size suitable for 250A current. PVC sheathed with colour coding. (b) MCCB having current ratings 250 Amps with rupturing cap 36 KA , AC 415 Volts four pole with microprocessor release complete with spreader links. - 01 No (c) Multifunctional digital panel meter with LCD display flush mounting type of size 96X96 mm, accuracy class 1, including suitable CTs with secondary current 5A, with display volt, Amp , Frequency, KWH. - 01 No Outgoing : (a) MCCB 4 Pole, 415 V, Adjustable type, current ratings 160 Amps with breaking capacity 36 KA - 02 Nos. (b) MCCB 4 Pole, 415 V, Adjustable type, current ratings 100 Amps with breaking capacity 36 KA - 02 Nos. All accessories pre-wired with suitable size PVC insulated copper conductor cables for control wiring and PVC insulated copper strips of appropriate size for power circuits as per standard engineering practice and required at site and suitable foundation for panel as per manufacturer recommendation. complete all as specified and directed.
Cable route marker with route indication at every 30mtr lemgth on cast iron disc of 100mm dia and 5mm thick, marked/written for "LT cable 1100 VOLTS" embosed including indication direction fixed/ bolted to 40mmx40mmx6mm thick MS angle iron support of 0.50m long embedded upto 200mm depth in concrete block of size 200mmx200mmx500mm casted in PCC 1:3:6 type C-1 including painting with two coats of synthetic enamel paint over a coat of red oxide primer to exposed steel surfaces, complete all as specified and as directed.
Supply, installation, Commissiong and Testing Automatic Power Factor Correction (APFC) Panel Board, out door type, factory made, cubical kiosk type, weather, dust and vermin proof, CPRI approved with locking arrangement, made out of CRCA sheet of 3.15mm thick with suitable size of channel for base complete with capacitor banks of capacity 50 KVAR reverse power relay 3 phase with tuned reactor for 100 KVA transformer out door type suitable for 1100 Volt 3 phase 50 Hz AC supply floor mounted, connected with suitable size thimbles / lugs, PVC insulated multi-stranded copper wire of suitable size with PVC flexible conduit medium quality as required, comprising of copper bus bar 200Amps capacity fixed on insulators to achieve power factor 0.95 and duly powder coated in siemens grey colour mounted on PCC platform of PCC 1:2:4 type B-1on angle iron frame made of 50 x 50 x 6mm thick angle iron duly marked with incoming and outgoing controls, completed all as specified and as directed comprising of the following :-
Notes for Serial Item No 48 : 1. The drawing for APFC Panel / LT Feeder Pillar Box shall be got approved by the Engineer-in-Charge. 2. The Pre-dispatch inspection of APFC Panel / LT Feeder Pillar Box shall be done by the Rep of the Accepting Officer at factory site. 3. All the existing cables shall be fixed with glands, lugs etc. of the requisite size. Make of Panel : DV Electromatics Private Limited / Simon Fabricators / Electricfield Co / Adhunik Switchgear / Universal Switchgear Make of MCCB & Star Delta Starter : L&T / Legrand / Schneider / Havells Make of Voltmeter / Ammeter / Multifunction Meter : SECURE / L&T (RISHAB) / C&S ELECTRIC / MECO Contactor : SECURE / L&T / ABB / SCHENEIDER / SEIMENS / LEGRAND / AE
M&L for ERW or induction butt welded tubes confirming to IS 1161-1979 grade Yst-240 etc as in posts of nominal bore 80mm and outside dia 88.90 mm medium grade (4.05mm thickness) including special shaped washer etc. complete all as specified and directed.
Bus bar panel size 0.8x0.4x0.4 Mtr, KISOK, outdoor type, CRPI tested, LT 440 Volts, 50 Hz, 3 phase 4 wire supply, comprising of bus bas chamber with 4 Nos aluminium strip bus bars PVC insulated with colour coding af rating 200A, floor mounted factory fabricated weather and vermin proof protection class IP 54 made out of 1.4 thick MS sheet CRCA on angle iron 30x30x4mm frame with front opening doors, locking arrangement powder coated internally and externally, shall have channel base of appropriate size and mounted on PCC foundation of size as required or approved by manufactures in PCC 1:3:6 type C-1, using 20 mm graded crushed stone aggregate including earth work complete all as specified.
Mild steel rolled work as in post, roof trusses (framed), purlins, crane gantries, rails and fastening and heavy bracket framing (beam, tee, angle, square / rectangle sections, channel or flat section) including distance pieces, cleats etc. Fe 410 -W (Gde-E- 250) quality-B complete all as specified and directed.
Rolled mild steel plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk) forming holes, without any attachment Fe 410 -W (Gde-E- 250) quality-A complete all as specified and as directed.
Mild steel bolts purpose made, with hexangonal or square head one end and screwed the other, or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut, exc 30 cm but n.exc 50 cm long dia of n.exc 12, complete all as specified and directed.
Preparation of new steel surfaces and applying two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed.
Mild steel bolts, with hexangonal or square head one end and screwed the other, or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut, exc 30 cm but n.exc 50 cm long dia of n.exc 12, complete all as specified and directed.
Design, Supply, Erection, Testing and Commissioning of 11 KV, 630A, 21kA for 3 sec, SF6 insulated, one side extensible, outdoor duty manual operated 4 way RMU in combination of 2 Nos VCB module as incommer, 2 nos VCB modules as outgoings consisting of copper Busbar in SF6 insulated 304 (NonpFerrite Non- maganetic Grade) stainless steel enclosureof thicness 2.5mm with manometer fixed, with series trip, self-powered microprocesser based numerical ocer current relay (IDMTL+Inst.) in each VCB feeder. Suitable CT for Protection with each VCB feeder. The HVswitchgear and control gear should be confirming to IEC-622771-1, 100, 200. The RMU should be internal arc tested for 21 KA for 1Second with IAC-AFLR classification for gas tank & cable box. The complete RMU front along cable to be covered by an seperate outdoor door to be RMU manufacturer's own make. Each feeder of should have voltage presence indicator. All the type test certificated as per IEC from third party lab to be submitted.
RMU should have following: (a) 1 No microprocesser based self powered numerical relay with over Current/earth fault & short circuit protection with each VCB feder. (b) 3 Nos Protection CT shall be Burden 2.5 V, ratio 200-100/1A, class of Accuracy class 0.5 for metering of each VCB. (c) 3Nos. Metering CT shall be Burden 2.5 V, ratio 100-50/1A, class of Accuracy class 0.5 for metering of each VCB. (d) VCB should confirm operating sequence O-0.3 Sec-CO-3min-CO and 10000 mechanical operation. (e) Mechanical Interlock between two incomers. (f) 3 Nos 1 ph 11KV/110V PT having accuracy class 0.5 & VA burder 50 VA. (g) Multimuction Meter with Accuracey class 0.5 for each VCB feeder (h) 1 No Manometer for each tank (i) Nos Voltage passage indicator for each feeder. (j) Right angle boots for all the feeder Modules. Make of RMU : ABB/SIEMENS/SCHNEIDER INFRA (No system house/Franchise/license partner is approval)
Material and labour for construction of Platform for 04xVCB of size 4.5m x 3.5m with 1.20m (clear height with additional 150 mm thick PCC 1:3:6 type C-2 using 40mm graded crushed stone aggregate as in foundation below ground level), 23cm wide brick masonry in CM 1:6 below & above ground level, hollow space to be filled hard core of size not exceeding 63 mm, deposited spread and levelled in layers not exceeding 15cm thickness, watered and well rammed with 100mm thick cement concreate 1:2:4 type B-2 as in Floor/Top of platform, brick surfaces plastered in CM 1:4 including protection with XPM, gate and chain link fencing rail around the platform with angel iron of 40 x 40 x 6mm frame upto 1.20m clear height supports grouted in PCC 1:2:4 type B-1 using 20 mm graded crushed stone aggregate as in foundation of angle iron including excavation in any type of soil, returning filling in and removal of surplus soil to a distance 50m, complete all as specified and directed.
Material and labour for construction of Platform suitable for 150 KVA transformer of size 6m x 6m with 1.20m (clear height with additional 150 mm thick PCC 1:3:6 type C-2 using 40mm graded crushed stone aggregate as in foundation below ground level), 23cm wide brick masonry in CM 1:6 below & above ground level, hollow space to be filled hard core of size not exceeding 63 mm, deposited spread and levelled in layers not exceeding 15cm thickness, watered and well rammed with 100mm thick cement concreate 1:2:4 type B-2 as in Floor/Top of platform, brick surfaces plastered in CM 1:4 including protection with XPM, gate and chain link fencing rail around the platform with angel iron of 40 x 40 x 6mm frame upto 1.20m clear height supports grouted in PCC 1:2:4 type B-1 using 20 mm graded crushed stone aggregate as in foundation of angle iron including excavation in any type of soil, returning filling in and removal of surplus soil to a distance 50m, complete all as specified and directed.
Excavating in post holes (or similar holes) each n exc 0.5 cu. m, getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm,in soft/loose soil all as specified.
M&L testing & commissioning in replacement of LT panel frame CPRI approved, indoor type, factory made fabricated to CRCA sheet of 3.15mm thickness, double door front/ rear opening and locking arrangement, floor mounted on platform of suitable size, aluminium bus bas chamber (enclosed) with two coat of synthetic enamel paint over a coat of red oxide primer mounted on PCC blocks, fixed with grouted bold, nuts and washer and making complete connection in all respects as directed by Engr-in-Charge comprising of following fitments;- (A) Incoming (i) MCCB 400 Amps, breaking capacity 36 KA, FP, 415 Volts (adjustable thermal and magnetic release) – 01 No (B) Outgoing (i) MCCB 200 Amps, breaking capacity 36 KA, FP 415 Volts (adjustable thermal and magnetic release) – 02 Nos (ii) MCCB 160 Amps, breaking capacity 36 KA, FP 415 Volts (adjustable thermal and magnetic release) – 01 Nos
Make of Panel : DV Electromatics Private Limited / Simon Fabricators / Electricfield Co / Adhunik Switchgear / Universal Switchgear Make of MCCB : L&T / Legrand / Schneider / Havells Make of Voltmeter / Ammeter / Multifunction Meter : SECURE / L&T (RISHAB) / C&S ELECTRIC / MECO
Supply, installation, Commissiong and Testing Automatic Power Factor Correction (APFC) Panel Board, out door type, factory made, cubical kiosk type, weather, dust and vermin proof, CPRI approved with locking arrangement, made out of CRCA sheet of 3.15mm thick with suitable size of channel for base complete with capacitor banks of capacity 100 KVAR reverse power relay 3 phase with tuned reactor for 150 KVA transformer out door type suitable for 1100 Volt 3 phase 50 Hz AC supply floor mounted, connected with suitable size thimbles / lugs, PVC insulated multi-stranded copper wire of suitable size with PVC flexible conduit medium quality as required, comprising of copper bus bar 200Amps capacity fixed on insulators to achieve power factor 0.95 and duly powder coated in siemens grey colour mounted on PCC platform of PCC 1:2:4 type B-1on angle iron frame made of 50 x 50 x 6mm thick angle iron duly marked with incoming and outgoing controls, completed all as specified and as directed comprising of the following :-
Notes for Serial Item No 61 : 1. The drawing for APFC Panel / LT Feeder Pillar Box shall be got approved by the Engineer-in-Charge. 2. The Pre-dispatch inspection of APFC Panel / LT Feeder Pillar Box shall be done by the Rep of the Accepting Officer at factory site. 3. All the existing cables shall be fixed with glands, lugs etc. of the requisite size. Make of Panel : DV Electromatics Private Limited / Simon Fabricators / Electricfield Co / Adhunik Switchgear / Universal Switchgear Make of MCCB & Star Delta Starter : L&T / Legrand / Schneider / Havells Make of Voltmeter / Ammeter / Multifunction Meter : SECURE / L&T (RISHAB) / C&S ELECTRIC / MECO Contactor : SECURE / L&T / ABB / SCHENEIDER / SEIMENS / LEGRAND / AE
Supply and fix Voltage stabilizer for automatic operation, three phase, naturally oil cooled, indoor type & designed for input variation between 300 V to 480 V with output voltage stabilized at 415 with accuracy +2.5% and speed of correction 8 volts per second and of capacity 150 KVA Confirming to BIS9815 :Part :1994) Three Phase, 50 Hz, Copper wound, metallic body with lifting hooks, digital display type, relay free smooth and silent operation including 1st filling of Transformer oil up to level having following specification:- (a) Input voltage 300-480V (b) Output Voltage Stabilized at any designed/desired voltage 415 (+/-)1% (c) No distortion in wave form (d) Respond time not to exceed 20 mili seconds (e) Sensitivity (+/-) 1% (f) Rate of correction 8 Volts/Sec (g) Efficiency more than 96% (h) Type of load 3 phase, unbalanced type (i) Digital display Volt meter and Ammeter (j) Over load and short cicuit protections (k) high & Low voltage cut off (l) By pass arrangement in case of emergency (m) Single Phase sequence change protection.
HUMERS INFRATECH
Bidder Name
darshan kumar gandhi
HUMERS INFRATECH
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .