Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.0 LAccepted-AOC 82 10 POST OFFICE ROAD MANDI HP | KANGRA | HIMACHAL PRADESH | 175013 | L1 | Accepted-AOC L1 | |
| 2 | L2₹2.0 L+₹330.40 (0.17%)Rejected-Finance CHOBATA STREET MANDI DISTT MANDI HP | MANDI | HIMACHAL PRADESH | 175001 | L2 | Rejected-Finance L2 | |
| 3 | L3₹2.0 L+₹1,321.60 (0.67%)Rejected-Finance PLOT NO 16 INDUSTRIAL AREA PHASE I MANDI H P 175001 | MANDI | HIMACHAL PRADESH | 175001 | L3 | Rejected-Finance L3 | |
| 4 | L4₹2.3 L+₹32,709.60 (16.6%)Rejected-Finance 18 6 LOWER SAMKHETAR MANDI 175001 H P | MANDI | MANDI | HIMACHAL PRADESH | 175001 | L4 | Rejected-Finance L4 | |
| 5 | L5₹2.5 L+₹55,837.60 (28.4%)Rejected-Finance | L5 | Rejected-Finance L5 |
Tender Value
₹2 L
Closing Date
29 Aug 2024, 12:15 pmClosed
CE OP Hamirpur
O/o CE OP Hamirpur
The scope of work covers the supply of following LT Distribution Panel Box for 63kVA
2024_HPSEB_92145_1
NIQ2
Limited
Electrical Work/ Equipment
Item Rate
45 days
Area under CE OP Hamirpur
Please refer Tender documents.
3 documents required · 3 mandatory
₹0
Exempted
6 Sept 2024
22 Aug 2024
29 Aug 2024
22 Aug 2024
29 Aug 2024
23 Aug 2024
Amount
LT Distribution Panel Box suitable for 63 KVA Transformer/ Sub Station of size 900x800x200 mm +/- 5% made of steel sheet of 1.63 mm thickness having double door locking arrangement duly Powder coated painted complete with MCCB 100 Amps 3 Poles having following specifications (1) Minimum frame size 100 Amp (2) Type; fixed trip free (3) breaking capacity-Icu & Ics at 415, 50 Hz (KA) : Not less than 35 KA (4) Thermal release range : 100 Amp (5) Mechanical life (Operation) 25000 Nos. (6) Electrical life (Operation) 7000 No’s (7) Rated insulation voltage (V) : 690 V (8) Tripping Thermal Release Setting : Thermal O/L fixed setting (9) Tripping Magnetic release setting :Magnetic-S/C Fixed setting (12 in) (10) (Operation) voltage: 415V, AC (11) Calibration temperature : 50 Degree C (12) High voltage withstand voltage: 3KV for 1minute (13) Confirming to IS: 1993/60947-2,1989 (14) Make L&T/Havel/Schneider/ABB 15) ICS: 100% ICU Rectangular type Aluminium alloy bus bar of 100 Amps Having Length 600 mm for phase, 450 mm long for neutral outgoing feeders 2No. outgoing feeders shall be made in the panel U type rewire able Kit Kat fuses of 200 Amp shall be provided in all three phases The panel should be fully wired with insulated copper wire shall have adequate clearance as per specifications.
Ashoka Electronics and Electrical industries
Powerlines
BHARATBHUSHANSHARMA
raghav and company
EVEREST ENGINEERS INTERNATIONAL
stage.html
html • 0.05 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_136033.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .