Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.2 LAccepted-AOC 19 62 1ST FLOOR WEST MOTI BAGH SARAI ROHILLA NEW DELHI 110035 | NEW DELHI | NEW DELHI | DELHI | 110035 | L1 | Accepted-AOC DUE TO L1 | |
| 2 | L2₹30.8 L+₹2.9 L (10.3%)Rejected-AOC RZ A2 2 CHANAKYA PLACE PART I OPP C 1A BLOCK JANAK PURI NEW DELHI 110059 | NEW DELHI | WEST DELHI | DELHI | 110059 | L2 | Rejected-AOC HIGHER RATE | |
| 3 | L3₹36.3 L+₹8.4 L (30.0%)Rejected-AOC | L3 | Rejected-AOC HIGHER RATE |
Tender Value
Refer Docs
EMD Value
₹90,000
Closing Date
13 May 2023, 6:00 pmClosed
GE NEW DELHI
GE NEW DELHI
CA NO GE/ND-10/2023-24 REPAIR/ MAINTENANCE OF COOLING APPLIANCES, WINDOW SPLIT CASSETTE TOWER TYPE AND PACKAGE TYPE ACs, DEEP FREEZERS, RO AND WATER COOLER IN NAVY AREA UNDER GE NEW DELHI
2023_MES_589620_1
GE/ND-10/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE NEW DELHI
REFER TENDER DOCUMENTS
7 documents required · 7 mandatory
₹500
GE NEW DELHI
₹90,000
Yes
15 Jan 2024
15 Apr 2023
15 May 2023
15 Apr 2023
13 May 2023
29 Apr 2023
Amount
Labour for checking and attending complaints of ACs, water coolers, deep freezer, RO, Desert cooler,Refrigerators etc. of any capacity, including rectification of minor defects and making the equipment functional complete all as specified and directed. (Note : 1) Any parts required for replacement shall be measured and paid separately under respective items 2) The contractor should detail minimum one AC Mechanic & one helper to attend complaints in Navy Areas 3) The complaint should be attended within 2 hours. 4) If the complaint will not attended/not completed within 2 hrs, recovery will be done as follows:- a) For 2-4 hrs @ Rs.100/- b) For 4-12 @ Rs.200/- c) For more than 12 hrs @ Rs.500/- per 12 hrs
Servicing of Window type AC 1.5/2 Ton capacity of any make / model quarterly by taking out the AC, Cleaning of evaporating coil, condensing coil with water & brush to remove dust including cleaning of filter, greasing, oiling of fan motor and checking of electric circuit for smooth functioning of AC. Note: Unserviceable spares parts required to be replaced shall be measured and paid separately under respective items.
All as per item No 2.00 here-in-before but Split type AC of any type and 1.5/2 Ton capacity.
Servicing of three phase cassette type AC 4.0 Ton capacity of any make/model quarterly with indoor and outdoor unit by taking out the AC, cleaning of evaporating coil, condensing coil with water & brush to remove dust including cleaning of filter, greasing, oiling of fan motor and checking of electric circuit for smooth functioning of AC complete all as specified and as directed. Note: Unserviceable spares parts required to be replaced shall be measured and paid separately under respective items.
Supply only starting capacitor 80-100 Mfd suitable for AC 1.5 Ton complete all as specified and as directed. Make : Usha/Epcos/Havells/Tesla
Supply only starting capacitor 100-120 Mfd suitable for AC upto 2.0 Ton complete all as specified and as directed. Make : Arcos/Epcos//Tesla
Supply only Running capacitor 36 mfd 230 volt suitable for AC 1.5 Ton complete all as specified and as directed. Make : Arcos/Epcos//Tesla
Supply only running capacitor combination 50 mfd + 6 mfd 230 Volt for AC upto 2.0 Ton complete all as specified and as directed. Make : Arcos/Epcos//Tesla
Supply only Running capacitor 6 mfd 230 volt complete all as specified and as directed. Make : Arcos/Epcos//Tesla
Supply only Running capacitor 4 mfd 230 volt complete all as specified and as directed. Make : Arcos/Epcos//Tesla
Supply & charging gas refrigerant R-22/R 410 A/ R-32 or as existing to window type AC up to 2 Ton capacity and testing complete all as specified & directed by Engineer-in-charge. Make- Mafron/Refron/Refromax
All as per item No. 11.00 here-in-before but for Split AC of any type and 1.5/2 Ton capacity.
Supply & charging the gas refrigerant R-22/R 410 A or as existing to cassette type Split AC 4.0 Ton capacity and testing complete all as specified & directed. Make- Mafron/Refron/Refromax
Supply & fix in replacement starting relay suitable for 1.5/2 Ton capacity AC complete all as specified and as directed.
Supply & fix in replacement over load protector suitable for 1.5 Ton capacity AC complete all as specified and as directed.
Supply & fix in replacement of old unserviceable contactor 32 Amps or as requires size suitable for 4.0 Ton capacity AC complete all as specified and as directed.
Supply & fix in replacement of unserviceable over load relay suitable for 4.0 Ton capacity AC complete all as specified and as directed.
Material and labour for taking down of defective /unserviceable reciprocating compressor of split type AC capacity 1.5 TR and replacing the same with new compressor reciprocating type capacity 1.5 TR, refixing including brazing work etc, pressure testing & establishing vacuum for dehydration complete all as specified and directed by Engr-in-Charge. Make : Kirloskar/Carrier/Tecumseh/Copeland/ existing make
Material and labour for taking down of defective /unserviceable rotary compressor of split type AC capacity 1.5 TR and replacing the same with new compressor rotary type capacity 1.5 TR, refixing including brazing work etc, pressure testing & establishing vacuum for dehydration complete all as specified and directed by Engr-in-Charge. Make : Kirloskar/Carrier/Tecumseh/existing make
Material and labour for taking down of defective /unserviceable rotary compressor of window AC capacity upto 2.0 TR and replacing the same with new compressor rotary type capacity upto 2.0 TR, refixing including brazing work etc, pressure testing & establishing vacuum for dehydration complete all as specified and directed by Engr-in-Charge. Make: Kirloskar/Carrier/Copeland/existing make ACs complete all as specified.
Supply and fixing in replacement after taking down defective /unserviceable scroll compressor of capacity 4.0 TR , refixing new compressor of 4.0 Ton including brazing work etc, pressure testing & establishing vacuum for dehydration complete all as specified and directed by Engr-in-Charge. Make: Kirloskar/Danfoss/copeland/existing make ACs complete all as specified.
Supply & fix in replacement air filter synthetic/ nylon as per existing size and shape suitable for 1.5/2 Ton capacity window type ACs complete all as specified and as directed.
All as per item No 22.00 here-in-before but for Split type ACs complete all as specified and as directed.
Supply & fix in replacement of air filter synthetic / nylon type as per existing size and shape suitable for 4.0 Ton capacity cassette type split ACs complete all as specified and as directed.
Material and labour for taking down existing unserviceable blower motor (Indoor) capacity 1/4,1/5 HP single/double shaft as per existing and refixing with new blower motor in replacement as per existing model on site suitable for Split type ACs 1.5/2 Ton complete all as specified and directed.Make:-As per existing
Material and labour for taking down existing unserviceable outdoor fan motor and fixing of new fan motor capacity 1/4,1/5 HP single/double shaft as per existing model suitable for Split type ACs 1.5/2 Ton complete all as specified and directed.Make:-As per existing
Material and labour for taking down existing unserviceable outdoor fan motor capacity upto 2 Ton and taking the unserviceable fan motor outdoor type to authorized workshop for rewinding of fan motor suitable for ACs capacity up to 2 Ton capacity with super enameled copper winding wire of same gauge including replacement of insulating material, bushes and shaft all as specified & directed.
Material and labour for taking down existing unserviceable blower motor capacity 4.0 Ton and fixing of new blower motor in replacement single/double shaft as per existing model suitable of any make/type complete as per requirement on site all as specified. Make :As per existing.
Material and labour for taking down existing unserviceable outdoor fan motor capacity upto 4 Ton and taking the unserviceable fan motor outdoor type to authorized workshop for rewinding of fan motor suitable for ACs capacity up to 4 Ton capacity with super enameled copper winding wire of same gauge including replacement of insulating material, bushes and shaft all as specified & directed.
Material and labour for taking down existing unserviceable outdoor fan motor of capacity 4 Ton and and fixing of new fan motor in replacement old unsv fan motor suitable of any make/type complete as per requirement on site all as specified. Make :As per existing.
Supply & fix in replacement PVC insulated flexible copper conductor 3 core 1100V Grade of size 2.5 sqmm complete all as specified and as directed.
All as per item No 31.00 here-in-before but 4 sqmm.
Supply & fix in replacement condensor fan blade suitable for upto 2 Ton capacity window type ACs.
All as per item No 33.00 here-in-before but for Split ACs of 1.5/2.0 Ton capacity
Supply & fix in replacement of condensor fan blade made out of aluminium suitable for upto 4.0 Ton capacity cassette type split ACs complete all as specified & directed.
Supply & fix in replacement of evaporating air blower made out of aluminium suitable for upto 2 Ton capacity for window type AC all as specified and directed
All as per item No 36.00 here-in-before but for air blower of Split ACs of 1.5/2 Ton capacity
Supply & fix in replacement of evaporating air blower made out of aluminium suitable for upto 4.0 Ton capacity cassette type split ACs complete all as specified & directed.
Supply and fix in replacement of synthetic rubber tube insulation of thickness internal diameter (1/4") for refrigerant copper piping of split AC units. Make:- Supreme/Gulf-o-flex/Superlon.
All as per item No 39.00 here-in-before but internal dia (1/2")
All as per item No 39.00 here-in-before but internal dia (3/8")
All as per item No 39.00 here-in-before but internal dia (6/8")
Material and labour for replacement of front grill suitable for window type ACs upto 2 Ton capacity of any Make as per existing size and shape complete all as specified and as directed.
Supply and fix in replacement copper tubing heavy duty inner dia (1/4") for refrigerant for Split type ACs capacity upto 2 Ton. Make-Carrier/ Totalline/Mandev
Supply and fix in replacement copper tubing heavy duty inner dia (1/2") for refrigerant for Split type ACs capacity upto 2 Ton. Make-Carrier/ Totalline/Godrej
Supply and fix in replacement copper tubing heavy duty inner dia (3/8") for refrigerant for Split type ACs capacity upto 4 Ton. Make-Carrier/ Totalline/Godrej
Supply and fix in replacement copper tubing heavy duty inner dia (6/8") for refrigerant for Split type ACs capacity upto 4 Ton. Make-Carrier/ Totalline/Godrej
Material and labour for taking down existing condensing coil by removing it from existing outdoor unit by using LPG blower and fixing of new condensing coil of suitable size/capacity for 1.5/2 Ton split type ACs complete all as specified and as directed by Engr-in-Charge. Note: Work includes brazing work as required for fixing of condensing coil
Material and labour for taking down existing evaporating coil by removing it from existing indoor unit by using LPG blower and fixing of new evaporating coil of suitable size of existing make, capacity for 1.5/2 Ton split type ACs complete all as specified and as directed by Engr-in-Charge. Note: Work includes brazing work as required for fixing of condensing coil.
Material and labour for taking down existing condensing coil by removing it from existing outdoor unit by using LPG blower and fixing of new condensing coil of suitable size/capacity for 1.5/2 Ton window type ACs in replacement as per existing size/shape and as per existing make complete all as specified and as directed by Engr-in-Charge. Note: Work includes brazing work as required for fixing of condensing coil.
Material and labour for taking down existing evaporating coil by removing it from existing unit by using LPG blower and fixing of new evaporating coil of suitable size/capacity for 1.5/2 Ton window type ACs in replacement as per existing size/shape and as per existing make. Complete all as specified and as directed by Engr-in-Charge. Note: Work includes brazing work as required for fixing of condensing coil.
Material and labour for checking the leakage by feeding dry Nitrogen to maintain adequate pressure in the system, plugging the leak and charging by charge refrigerant gas R-12/22/134a or existing type gas for water cooler, Split type/Window type/tower/ductable AC/ Deep Freezer /Refrigerator any size any capacity as on site complete all as specified and directed by Engr-in-Charge.
Supply & fix in replacement brass flare nut/connector heavy duty of size (1/4", 1/2",3/8",6/8) as per existing make complete all as specified and as directed.
Material and labour for Repair of processing control board (Remote control kit) with handset including replacement of current transformer, ICs, diodes, resistances, sensors etc complete for 1.5/2 Ton split type ACs of any make & model complete all as specified and as directed.
supply and fix in replacement of unserviceable PCB alongwith display suitable for Split type/window type AC 1.5/2 TR with new PCB alongwith display unit. Make-Hitachi/Voltas/Carrier/Daikin
Material and labour for replacement of unserviceable PCB along with display suitable for Cassette Type AC 4TR with new PCB along with display unit. Make-Hitachi/Voltas/Carrier/Daikin
Material and labour for opening and taking down existing unserviceable PCB unit and fixing of new PCB unit suitable for Indoor unit of capacity1.5/2 Ton inverter split type AC complete all as specified and directed by Engr-in-Charge.
Material and labour for opening and taking down existing unserviceable PCB and fixing of new PCB suitable for Outdoor unit of 1.5/2 Ton inverter split type AC complete all as specified and directed by Engr-in-Charge.
Material and labour for taking down unserviceable condensor fan motor of outdoor unit inverter type and supply and fix new DC motor of existing capacity suitable for outdoor unit of Inverter type AC of capacity 1.5/2.0 Ton complete all as specified and as directed by engr-in-Charge
Material and labour for taking down existing unserviceable compressor of Inverter type AC 1.5/2 TR and replacement of same by new hermetically sealed rotary compressor of capacity suitable for Inverter type AC 1.5/2 Ton refixing including brazing work etc, pressure testing & establishing vacuum for dehydration complete all as specified and directed by Engr-in-Charge
Supply and fixing in replacement window AC kit 1.5/2.0 TR with sensor complete with condensing coil, remote,compressor,blower and motor suitable to existing model and make AC all as specified and directed. Make:- Carrier, Voltas,LG
Supply and fix in replacement split type AC indoor unit kit 1.5 TR capacity complete with cooling coil, blower with motor, PCB and remote complete with fixing plate suitable to existing model and make AC all as specified and directed. Make- Hitachi/Carrier/Voltas/LG.
Supply and fix in replacement split type AC outdoor kit 1.5 TR complete with condensing coil, condensor fan motor suitable to existing model and make iron grill, suitable for outdoor unit and flair nuts for connection of Copper pipe all as specified and directed. Make- Hitachi/Carrier/voltas/LG
Supply & fix in replacement direction changer louver motor ( swing motor) suitable for split type ACs 1.5/2 capacity as per existing make and model
Supply & fix in replacement cordless Remote for inverter type ACs suitable for 1.5/2 Ton AC as per sample. Make- Hitachi/Voltas/Carrier
Supply & fix in replacement cordless Remote for ACs suitable for 1.5/2 Ton AC as per sample. Make- Hitachi/Voltas/Carrier
Servicing of Ductable type AC 5.5 Ton capacity complete (quarterly) with blower motor dismantling all parts and refixing after cleaning and replacement of defective parts, dismantling the cover of condensing coil carefully and carryout servicing, cleaning the external surface (both side) and fan of the unit out side of the equipment like base plate runner fan blade thoroughly with the help of descaling chemical, brush, water and dry properly including using air blower for cleaning air dust deposited on the equipment and re-fixing the same after repair complete all as specified. Note:- Spare parts shall be measured and paid separately.
Material and labour for taking down existing unserviceable compressor and fixing in replacement new Reciprocating compressor suitable for 5.5 Ton capacity pductable type refixing including brazing work etc, pressure testing & establishing vacuum for dehydration complete all as specified and directed by Engr-in-Charge. Make: Kirloskar/Tecumsheh/Copeland/Danfoss/existing make ACs complete all as specified.
Supply & charging the gas refrigerant R-22/R 410 A or as existing to Ductable type AC's of capacity 11 (2x5.5) Ton capacity including removing of leakage if any and testing complete all as specified & directed.
Supply and fix in replacement of LP cut-out suitable for Ductable type ACs of capacity 11 (2x5.5) Ton complete all as specified.
Supply and fix in replacement of HP cut-out suitable for Ductable type ACs of capacity 11 (2x5.5) Ton complete all as specified.
Supply and fix in replacement of expansion valve suitable for Ductable type ACs of capacity 11 (2x5.5) Ton complete all as specified.
Material and labour for taking down of unserviceable PCB and transporting it to authorized workshop for its repair complete along with necessary accessories like diodes, resistors, capacitors for PCB card suitable for package type AC's of capacity 11 (2x5.5) Ton complete all as specified and as directed by Engr-in-Charge.
Material and labour for opening and taking down existing unserviceable PCB and fixing of new PCB suitable for 11(2X5.5) Ton ductable AC complete all as specified and directed by Engr-in-Charge.
M&L for repair/maint and servicing of micro roster based panel of ductable AC of capacity 11(2X5.5) ton complete including replacement of faulty diode,resistance,solenoid coil complete all as specified and as directed by Engr-In-Charge.
Material and labour for taking down existing unserviceable fan blade and replacement of new condensor fan blade made out of aluminium/plastic suitable for package type AC's of capacity 11 (2x5.5) Ton complete all as specified and as directed by Engr-in-Charge.
Material and labour for taking down existing unserviceable blower and replacement by new evaporating air blower made out of aluminium/plastic suitable for package type AC's of capacity 11 (2x5.5) Ton complete all as specified and as directed by Engr-in-Charge..
Material and labour for taking down unserviceable fan motor and supply and fix in replacement new fan motor single/double shaft as per existing model suitable for package type AC's of capacity 11 (2x5.5) Ton complete all as specified and as directed by Engr-in-Charge.
Supply and fix in replacement air filter synthetic / nylon type as per existing size and shape suitable for package type AC's of capacity 11 (2x5.5) Ton complete all as specified and as directed by Engr-in-Charge.
Servicing of Water cooler of 40,120,150 ltr capacity of any make / model quaterly by cleaning of evaporating coil, condensing coil with water & brush to remove dust including cleaning, greasing, oiling of fan motor and checking of electric circuit for smooth functioning complete all as specified and directed by Engr-in-Charge
Supply & charging the gas refrigerant R-134 or as existing to water coolers up to 150 ltr capacity including removing of leakage if any and testing complete all as specified & directed
Taking down of defective /unserviceable reciprocating compressor of Water Cooler 40-150 L and replacing the same with new compressor reciprocating type capacity upto 60-150 Ltrs, refixing including brazing work etc, pressure testing & establishing vacuum for dehydration complete all as specified and directed by Engr-in-Charge. Make:- Kirloskar/Tecumseh/Copeland/Emersons
Material and labour for taking down existing condensing coil from water cooler any capacity and replacement by new Condensor coil as per existing capacity including brazing and dehydration by creating vacuum for more than 24 Hrs so that no oil/sludge remains in the cooling coil/system. Complete all as specified and as directed by Engr-in-Charge.
Material and labour for taking down fan motor of water cooler capacity upto 150 Litres and replacement of the same by new fan motor as per existing on site upto capacity 150 litres along with fan blade complete all as specified and as directed by Engr-in-Charge.
Servicing of Refrigerators of 195 to 310 ltr capacity single door of any make / model quaterly by cleaning of condensing coil with wire & brush to remove dust including checking of electric circuit for smooth functioning complete all as specified and directed by Engr-in-Charge.
Material and labour for taking down existing unserviceable condensing coil from Refrigerators of any capacity and replacement by new Condensor coil as per existing capacity upto 310 Ltrs including brazing and dehydration by creating vacuum for more than 24 Hrs so that no oil/sludge remains in the cooling coil/system. Complete all as specified and as directed by Engr-in-Charge.
Material and labour for taking down unserviceable fan motor of refrigerators of any capacity upto 310 Litres and replacement of the same by new fan motor as per existing on site upto capacity 310 litres along with fan blade and along with all mountings complete all as specified and as directed by Engr-in-Charge.
Material and labour for Taking down of defective /unserviceable reciprocating compressor of Refrigerator capacity upto 310 Ltrs and replacing the same with new compressor reciprocating type capacity 310 Ltrs, refixing including brazing work etc, pressure testing & establishing vacuum for dehydration complete all as specified and directed by Engr-in-Charge. Make : Kirloskar/LG/Tecumseh
Supply & charging the gas refrigerant R-134a or as existing to Refrigerators up to 310 ltr capacity including removing of leakage if any and testing complete all as specified & directed
Supply & fix in replacement of unserviceable starting relay suitable for 195 to 310 ltr capacity Refrigerator
Supply & fix in replacement of unserviceable over load protector suitable for Refrigerator capacity upto 310 ltrs
Supply & fix in replacement thermostat switch suitable for Refrigerator capacity upto 310 L
Material and labour for Servicing of Deep fridger upto capacity 1300 Ltr 2/3/ 4 door of any make / model quarterly by cleaning of condensing coil with wire & brush to remove dust ,oiling and greasing as required including checking of electric circuit for smooth functioning complete all as specified and directed by Engr-in-Charge
Supply & charging the gas refrigerant R-134a or as existing to Deep Freezers up to 1300 ltr capacity including removing of leakage if any and testing complete all as specified & directed
Material and labour for taking down existing unserviceable condensing coil from Deep freezers of any capacity and replacement by new Condensor coil as per existing capacity upto 1300 Ltrs including brazing and dehydration by creating vacuum for more than 24 Hrs so that no oil/sludge remains in the cooling coil/system. Complete all as specified and as directed by Engr-in-Charge
Material and labour for taking down unserviceable condensor fan motor of deep freezer of capacity 1300 Litres any type and replacement of the same by new fan motor as per existing on site of capacity 1300 litres along with fan blade and along with all mountings complete all as specified and as directed by Engr-in-Charge
Material and labour for taking down unserviceable condensor fan motor of deep freezer of capacity upto 492 Litres and replacement of the same by new fan motor as per existing on site upto capacity 492 litres along with fan blade and along with all mountings complete all as specified and as directed by Engr-in-Charge
Material and labour for Taking down of defective /unserviceable reciprocating compressor of Deep freezers of capacity upto 492 Ltrs and replacing the same with new compressor reciprocating type capacity upto 492 Ltrs, refixing including brazing work etc, pressure testing & establishing vacuum for dehydration complete all as specified and directed by Engr-in-Charge Make : Kirloskar/LG/Tecumseh/Copeland
Material and labour for Taking down of defective /unserviceable reciprocating compressor of Deep freezers of capacity 1300 Ltrs 4 door and replacing the same with new compressor reciprocating type capacity upto 1300 Ltrs, refixing including brazing work etc, pressure testing & establishing vacuum for dehydration complete all as specified and directed by Engr-in-Charge Make : Kirloskar/LG/Tecumseh/Copeland
Supply & fix in replacement of unserviceable starting relay suitable for 165 to 1300 ltr capacity Deep freezer
Supply & fix in replacement of unserviceable over load protector suitable for Deep freezer capacity upto 1300 L
Supply & fix in replacement thermostat switch suitable for Deep Freezer upto 1300 L
Supply and fix in replacement of old U/S single phase voltager stabilizer floor mounting type of capacity 01 KVA,Minimum input voltage 90-130V,minimum output voltage130V, maximum output voltage 290-300 Volts including digital display,digital indicators,over volt protection and overload protection complete all as specified and dorected by Engr- In- Charge.
Supply and fix in replacement of old U/S single phase voltager stabilizer floor mounting type of capacity 02 KVA,Minimum input voltage 90-130V,minimum output voltage130V, maximum output voltage 290-300 Volts including digital display,digital indicators,over volt protection and overload protection complete all as specified and dorected by Engr- In- Charge.
Supply and fix in replacement of old U/S single phase voltager stabilizer floor mounting type of capacity 04 KVA,Minimum input voltage 90-130V,minimum output voltage130V, maximum output voltage 290-300 Volts including digital display,digital indicators,over volt protection and overload protection complete all as specified and dorected by Engr- In- Charge.
Supply & Fix in replacement of plug top 3 pin, 15 Amps, 230 volts, 50 Hz AC complete all as specified.
Supply and fix in replacement Metal Clad Plug & socket enclosure with with MCB SP 20-32 Amps complete all as specified and as directed by Engr-in-Charge.
Supply and fix in replacement of PVC insulated and PVC sheathed, flexible copper conductor cable 3 core, 1100 volts grade, multi stranded type of size 6.0 sqmm complete all as specified.
Material and labour for taking down of desert cooler and Servicing of Desert cooler of any type/ capacity, cleaning of tank including checking of electric circuit for smooth functioning of desert cooler complete all as specified and directed.
Supply and fix in replacement of desert cooler pad for desert cooler (PVC Body type) window complete (in set of three) as per sample suitable for cooler of Size as required at site complete all as specified & directed.
Material & labour taking down of desert cooler fan motor and transporting the unserviceable motor to workshop for rewinding of desert cooler fan motor with supper enameled copper winding wire of same gauge including replacement of insulating material, bushes, bearing and shaft after taking out burnt wire including transportation to civil workshop complete all as specified & directed.
Supply & fix in replacement ON/OFF switch of desert cooler complete all as specified.
Supply & fix in replacement of step type regulator desert cooler regulator complete all as specified.
Supply & fix in replacement of drain pipe PVC flexible, spring type of size 15 mm dia as per site requirement complete all as specified.
Supply & fix in replacement of water lifting pump for desert cooler of any capacity as per sample all as specified and directed by Engr-In-Charge.
Supply and fix in replacement of desert cooler fan motor with supper enameled copper winding wire of same gauge (as per sample) complete all as specified & directed.
M & L for servicing of RO Plant of capacity upto150 LPH quarterly including replacement of minor spares, Pump repair, refixing the plant after repair, testing complete all as specified and directed of entire satisfactory level by Engr-in charge. Note: Spares required shall be measured and paid under relevant items
Supply only Membrane suitable for 50 to 150 LPH RO Plant
Supply only Filter heavy Grade suitable for 50 to 150 LPH RO Plant
Supply only Electrical accessories ,Solenoid valve suitable for 50 to 150 LPH RO Plant
Supply only activated carbon Filter heavy Grade for 50 to 150 LPH RO Plant
Supply & fix in replacement HDPE pipe 3/8"dia suitable for inlet & outlet of RO plant all as specified
S & F in replacement of booster pump for 50 to 150 LPH RO Plant
Material and labour for Shifting to new location, window type ACs 1.5 /2.0 TR capacity including wooden frame,ply of required size and shape,removing of connected accessories all as directed by Engr -in- charge
Material and labour for Shifting of Split type Acs 1.5 /2.0 TR capacity to new location including wooden frame,ply of required size removing of indoor unit, out door unit and connected accessories all as directed by Engr -in- charge
Servicing of Ductable type AC 8.5 Ton capacity complete quarterly with blower motor dismantling all parts and refixing after cleaning and replacement of defective parts, dismantling the cover of condensing coil carefully and carryout servicing, cleaning the external surface (both side) and fan of the unit out side of the equipment like base plate runner fan blade thoroughly with the help of descaling chemical, brush, water and dry properly including using air blower for cleaning air dust deposited on the equipment and re-fixing the same after repair complete all as specified. Note:- Spare parts shall be measured and paid separately.
Supply and fixing in replacement after taking down defective /unserviceable scroll compressor of capacity 8.5 TR ductable AC, refixing new compressor of 8.5 Ton including brazing work etc, pressure testing & establishing vacuum for dehydration of three phase compressor suitable for 8.5 Ton capacity for ductable Type AC complete all as specified and directed by Engr-in-Charge. Make: Kirloskar/Emerson/Hitachi/existing make ACs complete all as specified.
Supply & charging the gas refrigerant R-22/R 410 A or as existing to Ductable type AC's of capacity 8.5 Ton capacity including removing of leakage if any and testing complete all as specified & directed.
Supply and fix in replacement of LP cut-out suitable for ductable type ACs of capacity 8.5 Ton complete all as specified.
Supply and fix in replacement of HP cut-out suitable for Ductable type ACs of capacity 8.5 Ton complete all as specified.
Supply and fix in replacement of expansion valve suitable for Ductable type ACs of capacity 8.5 Ton complete all as specified.
Material and labour for taking down of unserviceable PCB and transporting it to authorized workshop for its repair complete along with necessary accessories like diodes, resistors, capacitors for PCB card suitable for package type AC's of capacity 8.5 Ton complete all as specified and as directed by Engr-in-Charge.
Material and labour for taking down existing unserviceable fan blade and replacement of new fan blade made out of aluminium/plastic suitable for package type AC's of capacity 8.5 Ton complete all as specified and as directed by Engr-in-Charge.
Material and labour for taking down existing unserviceable blower and replacement by new evaporating air blower made out of aluminium/plastic suitable for package type AC's of capacity 8.5 Ton complete all as specified and as directed by Engr-in-Charge..
Material and labour for taking down unserviceable fan motor and supply and fix in replacement new fan motor single/double shaft as per existing model suitable for package type AC's of capacity 8.5 Ton complete all as specified and as directed by Engr-in-Charge.
Supply and fix in replacement air filter synthetic / nylon type as per existing size and shape suitable for package type AC's of capacity 8.52 Ton complete all as specified and as directed by Engr-in-Charge..
Material and labour for GI Duct fabricated from 24 Gauge GI Sheet with acousticlining with connected accessories i.e-nut,bolts,fastener,flat iron strip,clamps etc complete all as specified and directed.
Material and labour for Thermal insulation of ducts comprise of prepration of surfaces and fixing of new cross linked closed cell polythene,plane,fire retardant insulation of 9 mm thick nitrile insulation with aluminium foil of the duct,fire retardant self extinguishing on dripping,good ozone resistance,including fixing the insulation to the duct surface with help of adhesive paste and closing the gap with self adhesive tapre of 3mm thick complete all as specified and directed.
Servicing of towe type AC 4.0 Ton capacity quarterly complete with blower motor dismantling all parts and refixing after cleaning and replacement of defective parts, dismantling the cover of condensing coil carefully and carryout servicing, cleaning the external surface (both side) and fan of the unit out side of the equipment like base plate runner fan blade thoroughly with the help of descaling chemical, brush, water and dry properly including using air blower for cleaning air dust deposited on the equipment and re-fixing the same after repair complete all as specified. Note:- Spare parts shall be measured and paid separately.
Supply and fixing in replacement defective /unserviceable scroll compressor of capacity 4.0 TR tower AC , refixing new compressor of 4.0 Ton including brazing work etc, pressure testing & establishing vacuum for dehydration complete all as specified and directed by Engr-in-Charge. Make: Kirloskar/Emerson/Hitachi/existing make ACs complete all as specified.
Supply & charging the gas refrigerant R-22/R 410 A or as existing to Tower AC's of capacity 4.0 Ton capacity including removing of leakage if any and testing complete all as specified & directed.
Supply and fix in replacement of LP cut-out suitable for tower type ACs of capacity 4.0 Ton complete all as specified.
Supply and fix in replacement of HP cut-out suitable for Tower type ACs of capacity 4.0 Ton complete all as specified.
Supply and fix in replacement of expansion valve suitable for Tower type ACs of capacity 4.0 Ton complete all as specified.
Material and labour for taking down of unserviceable PCB and transporting it to authorized workshop for its repair complete along with necessary accessories like diodes, resistors, capacitors for PCB card suitable for tower type AC's of capacity 4.0 Ton complete all as specified and as directed by Engr-in-Charge.
Material and labour for opening and taking down existing unserviceable PCB and fixing of new PCB suitable for 4.0 Ton tower AC complete all as specified and directed by Engr-in-Charge.
Material and labour for taking down existing unserviceable fan blade and replacement of new fan blade made out of aluminium/plastic suitable for Tower type AC's of capacity 4.0 Ton complete all as specified and as directed by Engr-in-Charge.
Material and labour for taking down existing unserviceable blower and replacement by new evaporating air blower made out of aluminium/plastic suitable for Tower type AC's of capacity 4.0 Ton complete all as specified and as directed by Engr-in-Charge..
Material and labour for taking down unserviceable fan motor and supply and fix in replacement new fan motor single/double shaft as per existing model suitable for Tower type AC's of capacity 4.0 Ton complete all as specified and as directed by Engr-in-Charge.
Supply and fix in replacement air filter synthetic / nylon type as per existing size and shape suitable for package type AC's of capacity 4.0 Ton complete all as specified and as directed by Engr-in-Charge..
M&L for comprehensive maintenance of Servo Voltage Stabilizer/ Servo Voltage Regulator, 150 KVA, comprising of following jobs complete all as specified and as directed:- (a) Taking out of electric connection of defective voltage stabilizer and transport it to workshop for repair, opening up and taking out coil, core and core assembly for repair including cleaning/washing of tanks and removing the dust from all parts including cores, tanks, cooling tubes, removal of damaged parts making connection and assembling complete in all respects after repair of coils IC's, Regulators, Condensers, Triac, Transistors etc. respective cards nuts and bolts, refilling of transformer oil, transport to site including installation,connecting the electric connection and testing on full load. (b) Preventive maintenance on quarterly basis and upkeep of Report. (c) Contractor shall be attending complaints round the clock i.e. 24 hrs. If contractor is not able to rectify the complaint within 8 hours panelty shall be charged as given below:- (i) upto 1st day- 500 (ii) Subsequency for every days - Rs 1200/day. Note:- (i) The rates quoted by the contractor shall deemed to be inclusive of T&P and minor sundries items etc as required. (ii) Major Spares Part shall be measured and paid for separately under respective item of this Schedule. The parts which are not These shall be identical to those specified by the original manufacturer. (iii) Any items not covered under as supply & Fix/M&L shall be deemed to be included in this section for the smooth functioning of voltage stabliser and the contractor may quote the rate accordingly. Contractor is expected to inspect the stabliser before quoting the rate. (iii) The job shall also includes shifting through crane with necessary accessories, transportation from site to work shop and vice- versa.
M&L for repair and rewinding dimmer suitable for 150 KVA voltage stabilizer including taking out old winding complete all as specified and as directed.
M&L for repair and rewinding buck/boost loading transformer complete suitable for 150 KVA voltage stabilizer including taking out old winding complete all as specified and as directed.
S&F in repair cut off circuit with contactor suitable for 150 KVA voltage stabilizer complete all as specified and as directed.
S&F in replacement control wiring of Servo Voltage Stabilizer/ Servo Voltage Regulator, 150 KVA complete all as specified and as directed.
M&L for comprehensive maintenance of Servo Voltage Stabilizer/ Servo Voltage Regulator, 50 KVA, comprising of following jobs complete all as specified and as directed:- (a) Taking out of electric connection of defective voltage stabilizer and transport it to workshop for repair, opening up and taking out coil, core and core assembly for repair including cleaning/washing of tanks and removing the dust from all parts including cores, tanks, cooling tubes, removal of damaged parts making connection and assembling complete in all respects after repair of coils IC's, Regulators, Condensers, Triac, Transistors etc. respective cards nuts and bolts, refilling of transformer oil, transport to site including installation,connecting the electric connection and testing on full load. (b) Preventive maintenance of on quarterly basis and upkeep of Report. (c) Contractor shall be attending complaints round the clock i.e. 24 hrs. If contractor is not able to rectify the complaint within 8 hours panelty shall be charged as given below:- (i) upto 1st day- 500 (ii) Subsequency for every days - Rs 1200/day. Note:- (i) The rates quoted by the contractor shall deemed to be inclusive of T&P and minor sundries items etc as required. (ii) Major Spares Part shall be measured and paid for separately under respective item of this Schedule. The parts which are not These shall be identical to those specified by the original manufacturer. (iii) Any items not covered under as supply & Fix/M&L shall be deemed to be included in this section for the smooth functioning of voltage stabliser and the contractor may quote the rate accordingly. Contractor is expected to inspect the stabliser before quoting the rate. (iii) The job shall also includes shifting through crane with necessary accessories, transportation from site to work shop and vice- versa.
M&L for repair and rewinding dimmer suitable for 50 KVA voltage stabilizer including taking out old winding complete all as specified and as directed.
M&L for repair and rewinding buck/boost loading transformer complete suitable for 50 KVA voltage stabilizer including taking out old winding complete all as specified and as directed.
S&F in repair cut off circuit with contactor suitable for 50 KVA voltage stabilizer complete all as specified and as directed.
S&F in replacement Power wiring and copper thimble of Servo Voltage Stabilizer/ Servo Voltage Regulator, 50 KVA complete all as specified and as directed.
S&F in replacement Input/output connection suitable for 50 KVA voltage stabilizer/ Servo Voltage Regulator, 50 KVA complete all as specified and as directed.
M&L for comprehensive maintenance of Servo Voltage Stabilizer/ Servo Voltage Regulator, 10/20 KVA, comprising of following jobs complete all as specified and as directed:- (a) Taking out of electric connection of defective voltage stabilizer and transport it to workshop for repair, opening up and taking out coil, core and core assembly for repair including cleaning/washing of tanks and removing the dust from all parts including cores, tanks, cooling tubes, removal of damaged parts making connection and assembling complete in all respects after repair of coils IC's, Regulators, Condensers, Triac, Transistors etc. respective cards nuts and bolts, refilling of transformer oil, transport to site including installation,connecting the electric connection and testing on full load. (b) Preventive maintenance of on quarterly basis and upkeep of Report. (c) Contractor shall be attending complaints round the clock i.e. 24 hrs. If contractor is not able to rectify the complaint within 8 hours panelty shall be charged as given below:- (i) upto 1st day- 500 (ii) Subsequency for every days - Rs 1200/day. Note:- (i) The rates quoted by the contractor shall deemed to be inclusive of T&P and minor sundries items etc as required. (ii) Major Spares Part shall be measured and paid for separately under respective item of this Schedule. The parts which are not These shall be identical to those specified by the original manufacturer. (iii) Any items not covered under as supply & Fix/M&L shall be deemed to be included in this section for the smooth functioning of voltage stabliser and the contractor may quote the rate accordingly. Contractor is expected to inspect the stabliser before quoting the rate. (iii) The job shall also includes shifting through crane with necessary accessories, transportation from site to work shop and vice- versa.
M&L for repair and rewinding dimmer suitable for 10/20 KVA voltage stabilizer including taking out old winding complete all as specified and as directed.
M&L for repair and rewinding buck/boost loading transformer complete suitable for 10/20 KVA voltage stabilizer including taking out old winding complete all as specified and as directed.
S&F in repair cut off circuit with contactor suitable for 10/20 KVA voltage stabilizer complete all as specified and as directed.
S&F in replacement control wiring of Servo Voltage Stabilizer/ Servo Voltage Regulator, 10/20 KVA complete all as specified and as directed.
S&F in replacement Power wiring and copper thimble of Servo Voltage Stabilizer/ Servo Voltage Regulator, 10/20 KVA complete all as specified and as directed.
S&F in replacement electronic control card, suitable for 10 KVA to 150 KVA Servo Voltage Stabilizer/ Servo Voltage Regulator complete all as specified and as directed.
S&F in replacement Amp meter (Digital), suitable for 10 KVA to 150 KVA Servo Voltage Stabilizer/ Servo Voltage Regulator complete all as specified and as directed.
S&F in replacement Volt meter (Digital), suitable for 10 KVA to 150 KVA Servo Voltage Stabilizer/ Servo Voltage Regulator complete all as specified and as directed.
S&F in replacement Synchronus motor 10kg torque, suitable for 10 KVA to 150 KVA Servo Voltage Stabilizer/ Servo Voltage Regulator complete all as specified and as directed.
S&F in replacement RC network, suitable for 10 KVA to 150 KVA Servo Voltage Stabilizer/ Servo Voltage Regulator complete all as specified and as directed.
S&F in replacement DPDT switch, suitable for 10 KVA to 150 KVA Servo Voltage Stabilizer/ Servo Voltage Regulator complete all as specified and as directed.
S&F in replacement sensing transformer, (16V/1Amp, 12V/1 Amp), suitable for 10 KVA to 150 KVA Servo Voltage Stabilizer/ Servo Voltage Regulator complete all as specified and as directed.
S&F in replacement 12 pin connector (PCB), suitable for 10 KVA to 150 KVA Servo Voltage Stabilizer/ Servo Voltage Regulator complete all as specified and as directed.
S&F in replacement micro switch, 5 Amp, suitable for 10 KVA to 150 KVA Servo Voltage Stabilizer/ Servo Voltage Regulator complete all as specified and as directed.
S&F in replacement liver Nylon/Metal, suitable for 10 KVA to 150 KVA Servo Voltage Stabilizer/ Servo Voltage Regulator complete all as specified and as directed.
S&F in replacement gear assembly suitable size, suitable for 10 KVA to 150 KVA Servo Voltage Stabilizer/ Servo Voltage Regulator complete all as specified and as directed.
S&F in replacement potentiometer, suitable for 10 KVA to 150 KVA Servo Voltage Stabilizer/ Servo Voltage Regulator complete all as specified and as directed.
S&F in replacement push button switch for and high voltage, suitable for 10 KVA to 150 KVA Servo Voltage Stabilizer/ Servo Voltage Regulator complete all as specified and as directed.
M&L for painting of Servo Voltage Stabilizer any capacity, including cleaning the body surface of panel by rubbing with emery Paper to remove oil stains, dust etc and applying two coat of synthetic enamel paint by spray paint complete all as specified and as directed.
Dehydration/ filtration of voltage stabilizer oil for voltage stabilizer of various capacities installed at different locations in base hospital by disconnecting plants electrically for recirculation existing voltage stabilizer oil with trolley mounted filtration plant till achieving dielectric strength 10 KV to 150 KV complete all as specified and as directed. Notes- (i) Oil shall be tested after filtration and test result shall be recorded before & after filtration of oil. No payment shall be made till testing report submitted by contractor. (ii) Contractor shall make his own arrangement for oil filtration plant including transportation complete without any extra cost to Deptt. (iii) Stabilizer oil required for topping up shall measured and paid separately under respective item of this Schedule.
Supply & topping up oil for voltage stabilizer, up to required level, dielectric strength 50 KV & above all as per IS specification complete all as specified and as directed.
Attending complaints for checking and replacing the existing defective electrical items for continuous electric supply including carrying out minor repair as required to make the item functional and replacing fuse, small pieces of copper wire, copper cable as of suitable size at site, insulation tape roll etc., Attending minor repair(s) such as testing, connections, fittings, nut, bolts screws etc to ceiling fan, exhaust fan etc, emergent complaints i.e. no light, earth leakage, short circuit, neutral break in mains/sub mains/ internal circuits of existing electrical system of main building/block and making continuous electric supply including carrying out minor repairs etc. required to make the system in order/functional with insulation tape roll, copper thimbles, glands, earthing wire as required at site complete all as specified and directed by Engineer-in-Charge. Notes :- This item is applicable only where no store is required. 1. The site for attending complaints is DAD Complex Pachwati. Contractor shall provide minimum one tradesmen (electrician) for site to attend the complaint in all working days between 0830Hrs to 1700Hrs including holiday and sunday. 2. Contractor shall ensure the security passes for his staff, to be obtained from concern authority for attending complaints. 3. The contractor will ensure that the team of electricians with necessary tools bag shall always remain present at complaint cell to attend the complaints. 4. A recovery of Rs. 100/- for not attending the complaint upto 24 hours and after 24 hours Rs. 200/- per 24 hours shall be recovered from the contractor due. 5. All the complaint slip, register,necessary tools & other connected document will be provided by the contractor without any extra cost. 6.The above tradesmen shall not be utilize for the complaints where material is required and these complaint shall be measured and paid seperately as S&F here-in-after.
S&F in replacement of switch piano flush type 6 Amp, SP, one way 230 volts AC all as specified.Make:-philips/schneider/anchor
S&F in replacement of switch piano flush type 6 Amp SP two way 230 volts AC all as specified.Make:-philips/schneider/anchor
S&F in replacement of bell push switch piano flush type 6 Amps, SP, 230 Volts AC all as specified. Make:-philips/schneider/anchor
S&F in replacement of switch piano flush type 16 Amp, SP, one way 230 volts AC all as specified.Make:-philips/schneider/anchor
S&F in replacement of piano flush type socket out let 5 pin 6 Amp, 230 volts AC all as specified.Make:-philips/schneider/anchor
S&F in replacement of piano flush type socket out let 6 pin 16 Amp, 230 volts AC all as specified.Make:-philips/schneider/anchor
S&F in replacement of piano type electronic fan regulator suitable for 1200/1400 mm ceiling fan all as specified.Make:-philips/schneider/anchor
S&F in replacement of call bell suitable for 230 volts AC all as specified.
S&F in replacement of ceiling rose 3 terminal / PVC / Polycarbonate, insulated body all as specified.
S&F in replacement of decorative lamninated sheer 3 mm thick of size 9"x13" including necessary cutting of sheet for fixing switch/socket complete as specified and directed
S&F in replacement of decorative lamninated sheet 3 mm thick of size 9"x11" including necessary cutting of sheet for fixing switch/socket(As per enclosed diagram) complete as specified and directed
S&F in replacement of decorative lamninated sheet 3 mm thick of size 8"x5" including necessary cutting of sheet for fixing switch/socket (As per enclosed diagram)complete as specified and directed
S&F in replacement of decorative lamninated sheet 3 mm thick of size 5"x5" including necessary cutting of sheet for fixing switch/socket(As per enclosed diagram) complete as specified and directed
S&F in replacement of single core,FRLS cable, PVC insulated, unsheathed, multi stranded copper conductor cable of size 1.5 Sqmm all as specified.
S&F in replacement of single core,FRLS cable, PVC insulated, unsheathed, multi stranded copper conductor cable of size 2.5 Sqmm all as specified.Make:RR/POLYCAB/HAVELLS
Supply only in replacement for MCB SP 06 to 32 Amps 240 Volts, 10 KA, `C' curve, all as per site requirement and as directed by Engr-in-Charge.
Supply only in replacement for MCB SPN 32 Amps, 240 Volts, 10 KA, `C' curve, all as per site requirement and as directed by Engr-in-Charge.
Supply only in replacement MCB TPN/ Isolator 4P ,63 Amps 415 volts, 'C' Series 10 KA as per site requirement and as directed of approved
S&F in replacement of MCCB TP 125 Amp, 415 Volts,36kA thermal type complete all as specified.MAKE:-As per existing
S&F in replacement of MCCB TP 160 Amp, 415 Volts ,36kA adjustable type complete all as specified.MAKE:-As per existing
S&F in replacement of MCCB TP 250 Amp,415 Volts, 36kA thermal type complete all as specified.MAKE:-As per existing
S&F in replacement of metal clad plug top 20 Amp, 230 volts AC all as specified.MAKE:-As per existing
S&F in replacement of metal clad socket outlet 20 Amps, 230 volts AC all as specified.MAKE:-As per existing
S&F in replacement of LED Batten fitting 10 watt - 2FT White, indoor decorative aluminium extruded complete all as specified and directed of Make : Havells or equivalent Model in Crompton/Philips.
S&F in replacement of LED Batten fitting 20 watt LED White, indoor decorative aluminum extruded complete all as specified and directed. of Make : Havells or equivalent Model in Crompton/Philips/Bajaj.
Supply only in replacement Decorative wall light made up of high grade engineering plastic material suitable for 9 W LED lamp B22 base complete all as specified and directed.Cat LHFHCHE1TL1W020 of Havells or equivlent make in Crompton/Phillips.
S&F in replacement of LED Building security light fitting 25W energy saving and environmental friendly made up of pressure diecast aluminium housing with high power LEDs as lighting source and lens embedded PC cover having TOP Opening seperate driver compartment with IP66 protection as directed. of Make:-Havells or equivqlent model in Crompton/Phillips).
S&F in replacement of B-22 holder suitable Led bulb 9 watts all as specified.
S&F in replacement of fan capacitor 2.5 Mfd all as specified.
S&F in replacement of fan capacitor 3.15 Mfd all as specified.
Taking down of old unserviceable ceiling fan/exhaust fan dismantling of blades, transportation to work shop and carrying out rewinding, transportation to site, reinstallation and testing Complete all as specified and directed by Engineer-in-charge. Note : Rewinding will be measured and paid separately under this Schedule.
M&L for Rewinding of ceiling fan 1200 mm sweep by dismantling of fan motor cutting and removing of burnt windings, cleaning, winding with supper enameled copper wire of superior quality, same gauge of wire, same Nos of turns, provn of insulation paper applying of varnish drying of varnish and assembling of fan including replacement gun metal bush where ever required Complete all as specified and directed by Engineer-in-charge. Note : The lathe machine work if necessary to making uppper/lower sheet of fan will be measured under this item only.
All as per ser item No 33 but 1400 mm sweep
All as per ser item No 33 but exhaust fan 230/300 mm sweep
All as per ser item No 33 but exhaust fan 450/600 mm sweep
S&F in replacement of ceiling fan Ball bearing of suitable size & model (as per sample). Make:- NBC/ SKF
S&F in replacement of 'U' clamps with rubber reel, bolts, nuts, washers and safety pin ceiling fan of any size/ make
S&F in replacement of Down rod of 1' height fabricated out of MS pipe 12mm dia heavy duty duly painted with one coat of white paint complete.
S&F in replacement of Canopy of Celing fans of 1200/1400mm swipe size heavy duty duly painted with one coat of white paint complete.
S&F in replacement of blade (set of three) of Celing fans of 1200/1400mm swipe size heavy duty duly painted with one coat of white paint complete.(As per sample)
S&F in replacement of blade (set of three) of exhaust fans metal body of 300 mm swipe size heavy duty duly painted with one coat of paint of suitable colour complete.(As per sample)
S&F in replacement of metal frame of exhaust fans metal body of 300 mm swipe size heavy duty duly painted with one coat of paint of suitable colour complete.(As per sample)
S&F in replacement of motor (copper winding) of exhaust fans metal body of 300 mm swipe size heavy duty duly painted with one coat of paint of suitable colour complete.(As per sample)
M&L for spray painting two coat (white colour) with synthetic enamel paint to Ceiling fans/Exahust fan of any capacity to reach upto satisfied finish of painting after cleaning and preparation of surface complete all as specified and directed by Engineer-in-charge.
M&L for spray painting two coat (white colour) with synthetic enamel paint to Geysers 25/50 Liters capacity to reach upto satisfied finish of painting after cleaning and preparation of surface complete all as specified and directed by Engineer-in-charge.
S&F in replacement of heating element of 1.5 KW (triangular/circular) as required at site including rubber washers (ISI marked) etc complete all as specified and directed (As per sample).
S&F in replacement of heating element of 2.0 KW (triangular/circular) as required at site including rubber washers (ISI marked) etc complete all as specified and directed Make Venus or As per sample.
S&F in replacement of storage tank made out of stainless steel sheet of appropriate thickness ) for 25 litre capacity geysers with collar complete duly tested at required pressure complete all as specified and directed.
S&F in replacement of insulating material (Glass wool) for 25 litre capacity Geysers all as directed by Engineer -in - charge.
S&F in replacement of base plate assembly 20 SWG heavy duty suitable for 25 litre capacity stainless steel tank geyser with inlet, outlet and thermostat pipe with drain plug and screw for fixing the element including clamps for holding the element with nuts, bolts and safety valves suitable for all type of geysers installed at site (As per sample).
S&F in replacement of chromium plated connection pipe 600mm long with two brass adopters washers and connecting up complete all as specified and directed.
S&F in replacement of PVC connection pipe 450mm long with two brass adopters washers and connecting up complete ISI mark all as specified and directed by Engr-in Charge
S&F in replacement of safety nut for high pressure release (As per sample).
S&F in replacement of non return valves 15mm dia and connecting up complete (ISI marked).as per sample
S&F in replacement of top cover for geysers of 25 ltrs capacity any make as required at site duly painted with two coats of Synthetic enamel spray paint (first quality) all as directed.
S&F in replacement of bottom cover for geysers of 25 ltr any make required at site duly painted with synthetic enamel spray paint (first quality) with inspection plate in two pieces all as specified and directed.
S&F in replacement of outer cover for geyser made out of MS sheet suitable for 25 ltrs capacity geyser vertical/horigontal type all as specified and directed.
S&F in replacement of thermostat (ISI Marked) for 25 Liters capacity Geyser.Make : Daspass/Theeta/TTE
S&F in replacement of indicator lamp (Red & Green) 230 volts suitable for Geyser (as per sample)
S&F in replacement of of mild steel hole fastner 10mm dia, 100mm long including nut and washer.
S&F in replacement of 15 mm gun metal valve..
Taking down carefully old point wiring (Light / Fan/ Socket/ Bell Point ) with aluminium/ copper conductor cable complete including fittings such as ceiling rose, holders, regulators, bell, switch and socket and making good the disturbed surface of wall/ floor complete all as specified.
M&L for point wiring with PVC insulated unsheathed multi stranded, single core, FRLS type, copper conductor cable of size 1.5 sqmm 1100 Volts including one run of PVC insulated unsheathed multi stranded, single core, FRLS type, copper conductor cable of size 1.5 sqmm as earth continuity conductor connected to common earth dolly, in and including PVC concealed rigid non-metallic conduit medium grade and its accessories including provn of new galvanised sunken box including decorative sheets for housing the piano type switches, sockets & fan regulators for the following:- Note :- In existing conduit wiring (new conduit will be added where there is a burnt/blokage/damage to the existing conduit including bends/elbows/tees/Junction boxes).
(a) One light/fan point controlled by one No, one way switch.
(b ) 6 Amp socket outlet point controlled by one No, one way switch on same board
(c ) 6 Amp socket outlet point controlled by one No, one way switch on independent board
M&L for point wiring with PVC insulated unsheathed multi stranded, single core, FRLS type, copper conductor cable of size 2.5 sqmm 1100 Volts including one run of PVC insulated unsheathed multi stranded, single core, FRLS type, copper conductor cable of size 2.5 sqmm as earth continuity conductor connected to common earth dolly, in and including PVC concealed rigid non-metallic conduit medium grade and its accessories including provn of new galvanised sunken box including decorative sheets for housing the piano type switces and sockets on independent board. Note :- In existing conduit wiring (new conduit will be added where there is a burnt/blokage/damage to the existing conduit including bends/elbows/tees/Junction boxes). Note for item No 64 & 65:- (i) Cutting chases for concealed conduit and making good in cement mortar is deemed included in unit rate. (ii) No cutting shall be done in the roof for laying PVC conduit for ceiling point wiring. In this specified portion wire shall run through the existing conduit or surface new conduit shall be provided as required. (iii) In case the wiring is encountered with any beam/column, then the wiring will run on surface to avoid any damage to the RCC portion.
S&F in replacement of PVC Casing Caping of size 1" complete all as specified & directed.
S&F in replacement of PVC conduit 20mm dia, rigid, complete all as specified & directed.
S&F in replacement of flexible PVC pipe of 20mm dia complete all as specified & directed.
S&F in replacement of LED Glass Bulb 10 Watt B-22 Cap, AC 230V, 50 Hz, suitable for Batten Holder/Bulk head/wall light fittings complete all as specified and directed by Engineer -in-Charge.Make: havells/philips/crompton.
S&F in replacement of single core, FRLS cable, PVC insulated, unsheathed, multi stranded copper conductor cable of size 4 Sqmm complete all as specified and as directed.Make:Polycab/Havells/RR.
S&F in replacement of submain wiring with PVC insulated unsheathed copper conductor cable, multi stranded, single core, FRLS type, 1100 volts grade 2 x 6 sqmm complete drawn in existing conduit along with 1x 6 sqmm PVC insulated unsheathed copper conductor cable, multi stranded, single core, FRLS type for continuous earth wire and connected to common earth dolly complete all as specified.Make:-RR/Havells/Polycab
S&F in replacement of submain wiring with PVC insulated unsheathed copper conductor cable, multi stranded, single core, FRLS type, 1100 volts grade 2 x 10 sqmm complete drawn in existing conduit along with 1x 10 sqmm PVC insulated unsheathed copper conductor cable, multi stranded, single core, FRLS type for continuous earth wire and connected to common earth dolly complete all as specified.Make:-RR/Havells/Polycab
S&F in replacement of factory made concealed sheet steel distribution boards, double door, SPN, 4 way, 230 volts AC, IP 43 with suitable busbar, neutral link, earth link suitable for MCB, DP/SPN as incomer & MCB SP as outgoing all as specified.Make:-Havells/indoasian/legrand
S&F in replacement of factory made concealed sheet steel distribution boards, double door, SPN, 8 way, 230 volts AC, IP 43 with suitable busbar, neutral link, earth link suitable for MCB, DP/SPN as incomer & MCB SP as outgoing all as specified.Make:-Havells/indoasian/legrand
S&F in replacement of factory made concealed sheet steel distribution boards, double door, SPN, 12 way, 230 volts AC, IP 43 with suitable busbar, neutral link, earth link suitable for MCB, DP/SPN as incomer & MCB SP as outgoing all as specified.Make:-Havells/indoasian/legrand
S&F in replacement of factory made load line DB's double door made out of CRCA mild steel sheet with insulating materials like polyester epoxy coated surface mounting 4 way TPN 415 Volts, IP 43 with suitable busbar, neutral link & earth link suitable for MCCB TP as incomer & MCB SP/TP as out going complete all as specified.Make:-Havells/indoasian/legrand
S&F in replacement of factory made load line DB's double door made out of CRCA mild steel sheet with insulating materials like polyester epoxy coated surface mounting 8 way TPN 415 Volts, IP 43 with suitable busbar, neutral link & earth link suitable for MCCB TP as incomer & MCB SP/TP as out going complete all as specified.Make:-Havells/indoasian/legrand
Supply only in replacement Rugby Bulk head 9 watt in die cast aluminium housing & frosted glass complete all as specified and directed by Engineer-In-Charge Cat LHKL01160099 of Havells or equivlent model in Crompton/Bajaj/Phillips).
S&F in replacement of Exhaust fan Louvers 300 mm Size of iron upto forth floor including taking out old louvers complete all as specified. Note:-Staircase arrangement for fixing louvers will be made by contractor.
Preventive maintenace of ceiling fan/exhaust fan/cabin fan/wall mounted fan of any make & any size including checking of fan clamp, nuts, bolts & washer and carry out the oiling/greesing all as specified and directed by Engr-in-charge. (Note: Spare parts shall be measured & paid separately).
Preventive maintenace of 25 Ltrs geysers of any make including checking of its fastner/ nuts, bolts & washer and carry out checking/testing of cut out, thermostate, element, assembly all as specified and directed by Engr-in-charge. (Note: Spare parts shall be measured & paid separately).
Preventive maintenance chcking of elect DBs (SPN/TPN/Load line DBs ) switch board such as checking the looses conncetion in MCBs , cutting the burnt cables and reconnecting to MCBs/DBs spare required shall be maintained and paid under relevent items
M&L for Earthing complete with galvanized steel earth plate 600x600x6mm thick, buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate n.less than 1.5 m below normal ground level, connected to galvanized iron wire 4 mm as earthing lead by means of bolts, nuts, check nuts & washers of galvanized iron or steel besides building at all joints as shown in drgs and including excavation and earth work, GI pipe light grade 25mm bore of protection of GI wire from earth electrode, supply and laying charcoal dust, common salt, PCC (1:2:4) type B-1 Chamber and MS angle iron frame 40x40x3mm and RCC cover 40 mm thick (1:2:4) type B-1using 20 mm graded stone aggregate Reinforced with 6 mm dia round bars @ 75 mm C/C both ways with MS handle 12 mm dia , PGI funnel and wire mesh , 20 mm dia GI Pipe light grade for watering complete all as shown in drg and connected to earth test point including testing as directed by Engr-in-Charge.
S&F in replacement of two core flexible cable, PVC insulated, unsheathed, multi stranded copper conductor cable of size 1 Sqmm complete all as specified and as directed.
S&F in replacement of aesthetically designed ceiling/surface mounting circular shaped decorative green perform sleek LED downlighter of 09 W fixture with opal diffuser to give glare free light including suitable LED lamp complete all as specified and as directed.
RUCHIKA ENGG.WORKS
ASHUTOSH BUILDERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .