Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.4 LAccepted-AOC SHIV BARI ROAD NEAR KASUMAL HOTEL BIKANER 334003 RAJASTHAN | BIKANER | BIKANER | RAJASTHAN | 334003 | L1 | Accepted-AOC L1 | |
| 2 | L2₹11.5 L+₹64,520 (5.93%)Rejected-Finance WARD NO 02 LAKHUWALI PO TEH PILIBANGA DISTT HANUMANGARH RAJ PIN 335803 | HANUMANGARH | RAJASTHAN | 335803 | L2 | Rejected-Finance Other than lowest bidder | |
| 3 | L3₹11.6 L+₹72,450 (6.66%)Rejected-Finance | L3 | Rejected-Finance Other than lowest bidder | |
| 4 | L4₹11.9 L+₹1.1 L (9.66%)Rejected-Finance | L4 | Rejected-Finance Other than lowest bidder | |
| 5 | L5₹13.9 L+₹3.0 L (27.8%)Rejected-Finance | L5 | Rejected-Finance Other than lowest bidder |
Tender Value
₹15 L
EMD Value
₹30,000
Closing Date
16 Jun 2020, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE (N) Bikaner
GE (N) Bikaner Mil Stn Bikaner
Repair and Maintenance of external electric works and LT UG cables at North Camp, East Camp and Desert battle School at AGE MFFR under GE (N) Bikaner
2020_MES_345608_1
GE (N) BKN-Token/18/2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
330 days
GE (N) Bikaner
Class E category b (i)
8 documents required · 8 mandatory
₹500
GE (N) Bikaner
₹30,000
Yes
2 Mar 2021
18 May 2020
18 Jun 2020
18 May 2020
16 Jun 2020
2 Jun 2020
60 days
Amount
Excavation in trenches in soft/loose soil not exceeding 1.5m wide and not exceeding 1.5 metre in depth for route of cable and getting out complete all as specified and as directed by the Engineer-in-Charge.
All as per Srl item No. 01 here in before but exc 1.5m and not exceeding 3.0 in depth complete all as specified and as directed by the Engineer-in-Charge.
Returning, filling in soft/loose soil including spreading, levelling, watering and well ramming, in layers not exc 25 cm complete all as specified and as directed by the Engineer-in-Charge.
Removing of surplus soil to a distance not exc. 50 metre and depositing where directed at a level not exc.1.5 metre above the starting point complete all as specified and as directed by the Engineer-in-Charge.
Local tibba dry sand cushioning and cover (8 cm thick layer of sand before laying of cable and 15 cm thick layer of sand after laying of cable) for protection of cable, material and labour complete all as specified and as directed by the Engineer-in-Charge.(Punned thickness will be measured and paid).
Protection to cable with one layer of bricks laid flat butting to each other in such a way that the length of the bricks is at right angle to the central axis of the cable using old size sub-class ‘B’ burnt-clay bricks having compressing strength not less than 75 kg/Square cm complete all as specified and as directed by the Engineer-in-Charge.
Plain cement concrete 1:4:8 type D-2 using 40mm graded stone aggregate in foundations of poles above ground level including finishing to exposed concrete surfaces even and fair and provision of form work for rough finished surface complete all as specified and as directed by Engineer-in-charge.
Plain cement concrete 1:3:6 type C-2 using 40mm graded stone aggregate in foundations for stays and coping complete all as specified and as directed by Engineer-in-charge.
Dismantling and taking down old damaged/broken pre-stressed concrete/steel LT electric poles of any type inclding breaking down existing pcc foundation and removing from site complete all as specified and as directed by the Engineer-in-Charge.
Taking out old US/faulty PVC armoured/un-armoured LT under ground cable of size 10 Sqmm to 120 sqmm 2/3 1/2 4 core complete all as specified and as directed by the Engineer-in-Charge.(Note:- Excavation and earthwork will be measured and paid separatly).
Cross linked poly-ethylene (XLPE) insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables ( heavy duty) with aluminium conductor, 1100 volts LT grade of cross-sectional area 06 Sqmm 2 core laid in trenches/through pipe in road crossings/paths/ drains/ducts/ floors/along poles/walls/ceilings/equipments etc supplied and fixed including commissioning and testing complete all as specified and as directed by the Engineer-in-Charge. Note : (i) Necessary excavation and earth work, brick protection, sand cushioning and cover and GI pipe shall be measured and paid for separately. (ii) Road/boring roads manualy cutting/floor cutting/cutting holes etc in wall required for laying fising of cable etc shall be made good as per existing site condition. Nothing extra shall be admissible on this account and quoted rate for this item shall be deemed to include for the same.
Ditto All as per srl item No. 11 here in above but aluminium conductor 100 Volts LT of size 10 Sqmm 2 core
Ditto All as per srl item No. 11 here in above but aluminium conductor 1100 Volts LT of size 16 Sqmm 2 core
Ditto All as per srl item No. 11 here in above but aluminium conductor 1100 Volts LT of size 25 Sqmm 4 core
Ditto All as per srl item No. 11 here in above but aluminium conductor 1100 Volts LT of size 35 Sqmm 3.5 core
Ditto All as per srl item No. 11 here in above but aluminium conductor 1100 Volts LT of size 50 Sqmm 3.5 core
Ditto All as per srl item No. 11 here in above but aluminium conductor 1100 Volts LT of size 70 Sqmm 3.5 core
Ditto All as per srl item No. 11 here in above but aluminium conductor 1100 Volts LT of size 95 Sqmm 3.5 core
Ditto All as per srl item No. 13 here in above but aluminium conductor 1100 Volts LT of size 120 Sqmm 3.5 core
Ditto All as per Srl item No 13 here in above but of size 185 Sqmm 3.5 core
Boring of holes under road, pavement, hard standing by manually without damaging of road, material & labour including pipe 80/100 mm dia suitable complete all as specified and as directed by the Engineer-in-Charge. Note; lenth of pipe to be measured and paid seperately under relavant item
Supply and fixing in replacement New generation energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover having TOP Opening seperate driver compartment with IP66 protection and impact resistance of IK07.Device.including suitable GI bracket 1.5 meter with 40x5 mm clamp and nut bolt complete. Make:- Havells :- Cat pt No ENDURAPEARLNEOSL45WLED757PASYTOPC or equivalent in Phillips/ CG.
Supply and fixing in replacement for two core PVC insulated weather proof cable with aluminum conductor size 6 Sqmm (nominal area), & drawing into hollow street light pole from fitting to juntion box or fitting to over head line complete all as specified and as directed by the Engineer-in-Charge.
Pre-stressed concrete poles 9 meter long, 102mm x 172 mm at top and 102 mm x 279 mm at bottom, class 10, complying with requirements of IS-1678, including painting with two coats of synthetic enamel paint (in alternate black & white/yellow strips of 30 cm height) upto 1.5 meter height from top of PCC coping and also including numbering to poles with synthetic enamel paint on black base of size 15 cm x 10 cm and numbering in 8 cm height of number with white paint incl required iron channels/clamps/GI pipe for the protection of flexible cable connecter box with bus bars, bolts & nuts complete all as specified and as directed by the Engineer-in-Charge.
Supply and fixing juction box IP 66 made out of thermoplastic material of size 200mmx160mmx98 mm with provn of three phase cable connector incomming and outgoing with MCB SP 'C' curve 6 Amps and single phase connection for street light fitting IP 65 protection totally enclosed weather and dust proof internally embedded gasket with cable entry gland along with GI clamp nut bolt and washer foxed on poles including 3 phase busbar with neutral in juction box complete all as specified.
S&F in replacement GI pipe light grade 100 mm bore (ISI marked) laid in trenches/ road crossings/ fixed to poles/Ceiling/along walls/path/drain/floors with and including all necessary clamps, nuts, bolts washers etc all fittings as required complete all as specified and as directed by the Engineer-in-Charge. (Note: - excavation, earth work and same work shall be measured and pain for separately.)
Ditto All as per srl item No 25 here in above but dia of pipe 80 mm.
Ditto All as per srl item No 25 here in above but dia of pipe 50 mm.
Ditto All as per srl item No 25 here in above but dia of pipe 40 mm.
Earthing complete with galvanised steel earth plate electrode 60cm x 60cm x 6 mm thick, buried directly in ground (earth pit not less than 2.25 metre depth below normal ground level) with top edge of plate at a depth not less than 1.5 mtr below ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides, connected to galvanized earth wire 04 mm dia with and including bolts, nuts, check nuts and washers of galvanised iron or steel and riveted to earth plate and one end and connecting to main switch board or metallic bodies of HT/LT equipments etc at the other end, GI wire encased in and including 15 mm bore GI light grade pipe with all fittings, from top of electrode to body of equipment fixed with and including flatiron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI light grade and including funnel, wire mesh, copper lugs etc from bottom of earth pit to top of electrode complete with earth pit in PCC 1:3:6 type C-2 using 40 mm graded crushed stone aggregate and CI cover complete all specified and shown in electrical plate No 03 of SSR Pt-I connecting earth electrode to test point with and including earthing lead including neessary excavation and earthwork in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance n.exc 50m, material and labour complete all as specified and as directed by Engineer-in-Charge. (Notes 1. The rate quoted shall be deemed to include for all the above provisions. 2. PCC chamber shall be constructed at least 1.5 m away from the earth electrode and pipe for watering shall be provided in slanting maner) .
Cable jointing kit for LT 1100 V cable for straight through end termination (Epoxy), cold applied insulation & sealing system type joint kit complete with jointing material and accessories suitable for 25 Sqmm to 50 Sqmm 3.5/4 core XLPE armoured aluminium conductor cable including testing after jointing, fixing in replacement complete all as specified as directed by Engineer-in-charge.make: m seal/dension.
Ditto all as per srl item No. 31 here in above but 70 to 95 Sqmm
Ditto all as per srl item No. 31 here in above but 120 to 150 Sqmm
S&F MCB DB 2 Way 240 Volts with MCB SPN 32 Amps 10 KA repturing capacity with mounting clamps nuts/bolts/washers for street light control complete all as specified and directed by E-in-C
Disconnection electric incoming cable connection and taking down old unserviceable change over switch of any size and description including complete all as directed by Engr-in-charge.
S&F inreplcement of change over switch 200 Amps, four pole, 415 Volt, cubical type and including making fixing arrangement in existing LT control panel and with proper connection of as per existing system all as directed by the Engineer-in-Charge Make- Havells/HPL/C&S
S&F in replacement of U/S Feeder pillar box outdoor cubical type factory made vermin protected dust proof with canopy, water proof made out of MS sheet 1.6 mm thick and 50 cm x50 cm x1.6mm thick angle iron base frame having insulated bus bar aluminum 200 Amps cap 3 phase with neutral bus bar including fixing in PCC bed block complete all as reqd at site of all four camps and DBS as directed by Engineer in Charge.
Aluminium conductor, steel reinforced (ACSR) of any size/make including stringing for overhead line on HT poles including aluminum binding wire 14 SWG, jumpers, line tapes, conducting jelly etc including taking down old conductor complete all as specified and as directed by Engineer-in-Charge. (Notes : (i) The ACSR conductors shall be conforming to IS-398 and as specified in SSR Part-I. (ii) The unit rate quoted shall also be deemed to include for supply & fixing of aluminium binding wire, aluminium tapes etc which shall not be included in the weight of conductors.(iii) Weight of conductors shall be determined by measuring true horizontal distance between centers of two adjacent poles and compounding the weight of conductors of that size and length and 3% extra added for sag, jointing, jumpers etc.(iv) Weight of the conductors shall be calculated from the nominal weights given in tables in the relevant IS.)
Re-stringing of existing over head line ACSR conductor/GI wire ( 03 Nos) of any size/type including repair of conductor broken due to wind storm/expansion, contraction etc, on existing HT steel and/or PCC pole including replacement of aluminium binding wire of suitable size carefully without damaging of insulator etc complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement disc type insulator, porcelain, vitreous, white brown or green, 145mm high, and 225 mm dia ball and socket type single disc assembly for tension with tension clamps for conductors, working pressure 11000 volts grade complete. Make :- Rastriya/Jaipuria
Supply and fixing in replacement pin type porcelain , vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150 mm height and 150 mm dia suitable for working pressure 11000 Volts grade complete. Make Rastriya/Jaipuria
M & L for repairing of broken ACSR vessal/ squarel /ferrot/ mink conductor after proper shutdown of electric supply and jumpring / cut points changing the damaged/burned conductor, cable endes, change over MCCBs condutor broken due to wind/storm and binding with the aluminium wire etc and changing the damaged pin/disc insulators and replace the broken conductor, repairing the faults in the 11/0.44 KV outdoor/ indoor electric panels at sub stations complete all as specified and directed by engineer-in-charge.( Note :- cost of fues wire minor spares, aluminium binding wire shall be deemed included in the above quoted item.,(ii) Cost of items i.e pin insulator,disc insulator etc. shall be measured and paid seprately under respective items.(iii) contrator will receive complaints from complaints cell(JE E/M)and rectify on the same day and duly signed by the users and deposited the same.(iv) one breakdown/complaint attended shall be measure as each job.
Repair the following work for ( North camp, East camp & DBS) to existing Feeder pillar box outdoor cubical type factory made vermin protected dust proof, water proof made out of MS sheet 1.6 mm thick and 50 cm x50 cm x6mm thick angle iron base frame having insulated bus bar aluminum 200 Amps cap 3 phase with neutral bus bar including fixing in PCC bed block complete all as reqd at site and as directed by Engineer in Charge with following: -(a) welding of broken/cracked joints of the feeder pillar box
(b) Replacing to locking arrangement of the feeder pillar box as per sample existing.
(c ) Painting feeder pillar box of size (50 cm x 50 cm x 20 cm) with one coat of synthatic enamel paint (inner & outer) surface after applying one coat of red oxide as a primer complete all as specified
(d) Replacing of aluminium bus bar of size (400x25x8) mm (RYB with neutral 200 amps suitabale capacity as per existing complete all as specified
Cable indoor / outdoor end terminals jointing kit for LV/LT 1100 V cable heat shrinkable type joint kit complete with jointing material and accessories, thimbles etc suitable for 25 Sqmm to 50 Sqmm 3.5 core XLPE armoured aluminium conductor cable including testing after jointing, fixing in replacement complete all as specified as directed by Engineer-in-Charge.
Ditto All as per Srl item No . 44 here in above but 70 Sqmm to 120 sqmm 3.5 Core
Ditto All as per Srl item No . 44 here in above but 150 Sqmm to 185 sqmm 3.5 Core
S&F in replcement of MCCB 3 pole 100 Amp, fixed type 25 KA, 415 Volt including making fixing arrangement in existing LT control panel and with proper connection of as per existing system all as directed by the Engineer-in-Charge.
Gill Construction Co
RATHORE ENTERPRISES
AJAY ELECTRIC COMPANY
ALPHA ENGINEERING COMPANY
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .