Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹3.1 CrAccepted-AOC BEHIND ANAJ MANDI SHASTRI NAGAR GALI NO 4 BHIWANI 127021 | BHIWANI | BHIWANI | HARYANA | 127021 | ₹3.1 Cr | 1 | Accepted-AOC Lowest |
| 2 | 2₹3.4 L−₹3.1 Cr (98.9%)Rejected-AOC H NO 1100 SECTOR 3 124001 | ROHTAK | HARYANA | 124001 | ₹3.4 L−₹3.1 Cr (98.9%) | 2 | Rejected-AOC Higher |
Tender Value
₹3.4 Cr
EMD Value
₹6.8 L
Closing Date
27 Jun 2024, 12:00 pmClosed
SHASHIKANT
Charkhi Dadri PHED
DETAILED PROJECT REPORT FOR AUGMENTATION OF WATER SUPPLY SCHEME
2024_HRY_380817_1
202477463146 0F8F 4A89 991B 55A0D69590F1555PUH
Open Tender
Civil Works
Works
540 days
BOND KALAN
2 documents required · 2 mandatory
₹15,000
Yes
₹6.8 L
Yes
4 Dec 2024
20 Jun 2024
27 Jun 2024
20 Jun 2024
27 Jun 2024
20 Jun 2024
Amount
NS Item
COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3 core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2 Outer Sheathed, /1100 V grade as per IS 7098 (Part 1) 1988 with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-in-charge complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables / CAPP / Gloster / Universal / Fort Gloster Industries Ltd./ Asian Cables Corporation Ltd. 120mm2 3core
Providing and fixing of CI sluice valves conform to IS 14846 / DIN 3352, with length over flanges as per PD or ALT 1 of IS 14846 corresponding to BS EN – 558 / ISO 5752 Basic Series 3 and 15 respectively including labour, material, joints. Make: IVC / VAG / Kirloskar complete in all respect as per specifications mentioned in DNIT(700 mm i/d)
Providing and fixing of CI sluice valves conform to IS 14846 / DIN 3352, with length over flanges as per PD or ALT 1 of IS 14846 corresponding to BS EN – 558 / ISO 5752 Basic Series 3 and 15 respectively including labour, material, joints. Make: IVC / VAG / Kirloskar complete in all respect as per specifications mentioned in DNIT(800 mm i/d)
Providing and fixing of CI sluice valves conform to IS 14846 / DIN 3352, with length over flanges as per PD or ALT 1 of IS 14846 corresponding to BS EN – 558 / ISO 5752 Basic Series 3 and 15 respectively including labour, material, joints. Make: IVC / VAG / Kirloskar complete in all respect as per specifications mentioned in DNIT(750 mm i/d)
Boring /excavation including pit making at entry and exit point to the precise dimensions for the Launch of the specialized Auger boring machine in normal soil condition but not in Rock/Bolders/ any underground utility like foundation, water supply line coming in alignment or other underground obstructions complete in all respect including caution sign boards, signals, watching fencing, site clearance etc. Including provision for probe radar survey to check any underground obstruction before finalizing the alignment. For 900 mm i/d MS casing pipe.
Providing and insertion of 900 mm i/d M.S. carrier pipe 10 mm thick (Fe-330 grade) fabricated as per IS: 3589 of 1991 from steel plates conforming to IS 2062 including cutting, beveling, grinding and radio graphically welding of pipes as per IS-1182 and also coating of inner and outer surface of casing pipe with high built epoxy paint as per R.D.S.O. specification No. MandC/PCN.III/88 to a dry film thickness of 250 micron for protection against corrosion including cost and cartage of material to site of work complete in all respect as per srecification given in DNIT. 900 mm i/d MS casing pipe
Providing and insertion of 700 mm i/d M.S. carrier pipe 10 mm thick (Fe-330 grade) fabricated as per IS: 3589 of 1991 from steel plates conforming to IS 2062 including cutting, beveling, grinding and radio graphically welding of pipes as per IS-1182 and also coating of inner and outer surface of casing pipe with high built epoxy paint as per R.D.S.O. specification No. MandC/PCN.III/88 to a dry film thickness of 250 micron for protection against corrosion including cost and cartage of material to site of work complete in all respect as per srecification given in DNIT. Providing concrete block 1:1-1/2:3 on both ends to plug the space between casing and carrier pipe including all material and labour complete in all respect to the entire satisfaction of Engineer in charge. 700 mm i/d MS carrier pipe.
Providing and fixing of CI sluice valves conform to IS 14846 / DIN 3352, with length over flanges as per PD or ALT 1 of IS 14846 corresponding to BS EN – 558 / ISO 5752 Basic Series 3 and 15 respectively including labour, material, joints. Make: IVC / VAG / Kirloskar complete in all respect as per specifications mentioned in DNIT(700 mm i/d). Including suitable size sluice valve Hodi complete in all respect.
`RAW WATER PUMP: Supplying, erection, testing and commissioning of Horizontal motor pumping set for Raw water having head as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked ` 11000 LPM x 45.00 m x 200.00 BHP...
PANEL BOARDS FOR MOTORS: Supply, erection, testing and commissioning of wall mounted electrical LT Panel board, fabricated from 16 SWG CRCA sheet duly stouten with suitable angle iron frame work and completely powder coated of suitable size deep having following items for 1 Pumping set a) Main switch suitable ampere 1 No. (L and T Siemens, ABB) b) CT 100/5 = 1 Nos. (AE/ KAPPA/ LandT) c) Digital Multi function meter = 1 No. d) SPP = 1 No. of approved make e) Motor starter, star delta 1 No (LandT Siemens, ABB) f) VSS 1 No. and ASS 1 Nos. of approved make. g) Capacitor KVAR as per site requirement = 1 No. h) Indicating Lamp = One Set i). Change over switch of suitable Amp = 1 No. (Each) 11000 LPM x 45 Mtr. Head.
LT CABLE ALLUMINIUM: Supply, erection, testing and commissioning of IS marked 3.5 core Cables, Solid Aluminum conductor up to 10sqmm and balance stranded conductor, XLPE Insulated, cores laid up, PVC Inner sheathed, Armored (Aluminum wire for single core up to 70sqmm and balance Aluminum strip, Galvanized wire for cables up to2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip) extruded PVC type ST2 Outer sheathed, 650/1100V grade as per IS7098 (Part-1) 1988 with up to date amendments along with all accessories complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables / CAPP / Gloster / Universal / Fort Gloster Industries Ltd./ Asian Cables Corporation Ltd. 240 Sqmm. (for both working and stand-by transformer)
HT. ALLUMINIUM CABLE: Supply erection testing of standard make XLPE 3 core HT / 11 KV grade ISI marked Stranded compact circular aluminium conductor, conductor screen with extruded semi conducting compound, XLPE insulated, insulation screening with extruded semi conducting compound in combination with copper tape, cores laid up, innersheath of PVC, galvanised steel flat strip armoured, and overall PVC sheathed cable conforming to is 7098 (part-2) 2011 with up to date amendments for making following connection a) from G.O switch to metering equipment . b) from metering equipment to transformer complete in all respect. Make: Indian Cables Ltd./ Polycab / RR Cables / CAPP / Finolex / Havells / Gloster / Universal / Fort Gloster Industries Ltd./ Indian Cable Co. / Asian Cables Corporation Ltd. 150 Sqmm x 3 core size for both working and standby transformer
Flow meter Provision for providing and fixing flow meter with electronic display on delivery pipe inside pump chamber complete in all respects. 250 mm
Supplying, fixing, jonting, testing and commissioning Of CI sluice valves resilient Sheet P.N. 1.6 including cost of jointing material complete in all respect. (IVC / VAG make, Kirloskar) 1000 mm i/d.
Providing and fixing of CI sluice valves conform to IS 14846 / DIN 3352, with length over flanges as per PD or ALT 1 of IS 14846 corresponding to BS EN – 558 / ISO 5752 Basic Series 3 and 15 respectively including labour, material, joints. Make: IVC / VAG / Kirloskar complete in all respect as per specifications mentioned in DNIT (1000 mm i/d)
Operation and Maintenance for complete scope of work mentioned in DNIT (Disinfection material will be supplied by PHED) as per schedule-IV for a period of 5 year after 12 month`s during defect liability period and 3 Months trial run period will be charged to the A/Mtc. estimate complete in all respect as per approved NIT. (i) Operation and Maintenance Defect liability period (Operation only) after 3 Months trial run period.
(ii) Operation and Maintenance during 1st year after defect liability period.
(iii) Operation and Maintenance during 2nd year.
(iv) Operation and Maintenance during 3rd year.
(v) Operation and Maintenance during 4th year.
(vi) Operation and Maintenance during 5th year.
Bidder Name
Amount
Kulbir Singh Contractor (GSTN-06ATZPS6352H1ZW) BID ID -1097424
Sunil Kumar Contractor (GSTN-06ANBPK3767E1Z5) BID ID -1098715
Kulbir Singh Contractor (BID ID -1097424)
Sunil Kumar Contractor (BID ID -1098715)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .