Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Infra Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹1.2 Cr
EMD Value
₹1.2 L
Closing Date
19 Aug 2024, 5:30 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Facilities Management Division, Bangalore
HINDUSTAN AERONAUTICS LIMITED Facilities Management Division, Bangalore
Providing External power supply and Establishment of Substation for LCA Mk II hangar in ARDC Division Bengaluru as Phase II works
8820
FM/NE-P/Advt./07/24-25 Dt:10.07.24
Works
Electrical Planning and Contract Section-E and M Dept-FMD-Bangalore
₹2,360
₹1.2 L
19 Aug 2024
26 Jul 2024
26 Jul 2024
19 Aug 2024
HINDUSTAN AERONAUTICS LIMITED FACILITIES MANAGEMENT DIVISION
NAME OF THE WORK: " Providing External power supply and Establishment of Substation for LCA Mk-II hangar in ARDC Division, Bengaluru as Phase-II works." Cont.No: HAL/FMD/EC-2932/24-25
Name of the Contractor :
BILL OF QUANTITIES WITH SPECIFICATIONS
The tenderers are requested to read the following before quoting:
1 This BOQ specification has to be read in conjunction with technical specifications and tender drawings. Any ambiguty in these have to be brought to the knowledge of contract section before submission of tender to avoid further claims/dispute.
2 The VCB alongwith entire HT panel board shall be fabricated and factory tested by OEM as indicated in the approved list. VCB HT panel supplied through the OEM's approved agencies(Channel partners) are not acceptable.
3 Supply, erection, testing and commissioning of 11KV VCB Panels boards at LCA MK2 substation-3nos with communication facility using MODBUS TC. The HT panels as shown in the tender drawing.
4 Supply, erection, testing and commissioning of Energy efficient 1000 KVA transformer as shown in tender drawing.
5 Design, fabrication, supply, installation, testing and commissioning of the Indoor type Modular construction TTA (Totally Type tested Assemblies) Switch Board as specified in BOQ.
6 Design, fabrication, supply, installation using suitable MS channel frame work for base, testing & commissioning of floor mounting type 300 KVAR Automatic Power Factor Correction Panel .
7 Supply, erection, testing and commissioning of factory build IP-65/IP-66 rated with canopy for outdoor 1600A Bus trunking system as specified in BOQ.
8 Supply & laying of HT & LT cables and cable end termination, earthing, earth strip and connected civil works etc., complete.
9 Providing 120AH SMF Battery Back up for the trip circuits of HT Panels and Battery charger at substation.
10 Supply and placing of substation accessories and all other required works as brought out in the BOQ.
11 Tenderer shall visit the site to acquaint himself/ themselves with the site condition as detailed at Sl no:1 of special conditions.
12 It is the responsibility of the contractor to obtain statutory approval from CEA authority for the new substation installation including proposed equipments being installed at substation as per BOQ before commissioning of the substation. Liasoning & obtaining necessary statutory approval from Electrical Inspectorate (Central), including preparing necessary drawings if any , other incidental charges have to be included in the scope of work by of the contractor. The statutory fee paid to the Inspectorate will be reimbursed to the contractor against documentary proof. Tenderers are requested to make a note of this and quote accordingly. No extra claims will be entertained in this regard.
13 Successful agency has to prepare the shop drawings as per actual site conditions and it has to be submitted to HAL for approval before taking up the work as and when called by OIC/EIC.
14 The payment terms shall be governed as per the terms indicated in special conditions of contract.
15 The work has to be carried out in co-ordination with engineer-in-charge with minimum power interruption. The shutdown work has to be carreid out during Holidays/Sundays with proper co-ordination of Engineer-in-charge. In case any preparation works requried, same have to be carried out as directed by Engineer-in-charge without any additional cost during execution of work.
16 Basic Rate to be quoted for each item.Subject work is called on works contract basis and prevailing GST of 18% has been added in the BOQ on overall total. Any revision on this GST rate is to HAL account.
17 Sucessful offer that is L-1 (Lowest offer) will be determined including GST.
18 Amount towards GST will be paid along with RAR payment against invoice.
19 The tenderers are requested to abide by the rules of prevailing GST act.
Sl. No Specification of item Quantity Unit Rate in Figs excluding GST Rate excluding GST in words Amount Excluding GST in Figs (E=C*A)
1 Transformer, step-down, 1000 KVA complete, outdoor, copper wound capacity 1 set 0.00
Supply, erection on the proposed plinth, testing and commissioning of Energy efficient 1000 KVA 11 KV/ 415V, Delta-star, outdoor type distribution transformer suitable for 3 phase 4 wire 50Hz AC supply. The transformer shall be suitable for cable end termination on HV side and outdoor sandwich type bus bar trunking termination on LV side. The transformer shall be copper wound, oil cooled corresponding to vector group DYn-11 with neutral brought out on the LT side and separate neutral terminal brought out on the transformer top cover for earthing purpose, OFF load tap changing arrangements on HV side. The tap changer shall be provided for variation of HV voltage with a tapping of (+) 7.5% and (-) 7.5 % at 11KV side of each 2.5% steps. The impedance of transformer shall be 5%(ISTol).
The transformer shall be suitable for continuous rating for full load. The temperature raise not to exceed 40degrees C in oil and 45degrees C by resistance in winding.The transformer shall conform to IS-1180 with its latest amendment and IS 2026-1977 with its latest amendment as applicable. The transformer shall conform to Energy efficiency level-2 of table no:6 of IS -1180(Part-1)-2014. The maximum total losses at 50% load shall not exceed 2.62 KW and at 100% load it shall not exceed 7.0KW at 75º C as specified for level-2 Energy efficiency as per latest amendment no.04 of IS1180.
Transformer consist of the following:
a) An external hand operated 'OFF' load tap changer with handle having a position indicating plate and locking device.
b) Explosive Vent/Pressure release valve(PRV)
c) Air releasing valve.
d) Double float buccholtz relay with an alarm and trip contacts.
e) De-hydrating breather with silica gel and oil seal etc.
f) Diagram and rating plate.
g) Earthing terminals.
h) Lifting hook
j) Filter valve.
k) Radiator with top and bottom stop valves and drain and air releasing plugs.
l) Conservator tank with Magnetic oil level indicator.
m) Dial type thermometer with MRP resetting devices with alarm and trip contacts.
n) Weatherproof marshalling box with connectors and control wiring cable gland including winding temperature indicator.
o) First fill of mineral oil.
p) Bars stud type neutral brought out through a separate bushing for earthing.
q) Bi-directional wheels with locking facility to arrest movements.
r) 1 No. cable end box on HT side suitable for 1R of 3CX95 Sqmm 11KV XLPE insulated Aluminium armoured cable with Heat shrinkable type indoor cable end joints.
s) 1 No. end box on LT side suitable to connect 1600A, 415V TPN Aluminium overhead sandwich bus trunking to LT Panel.
Note: The supply & interconnections of control cables from transformer to HT panel for the alarm & Trip functions will be measured separately.
2 11KV Indoor Type VCB HT Panels (2 Nos of Incomer & 1 No of Outgoing):
Supply, Installation, testing and commissioning of following 11KV indoor HT VCB Panel boards (Horizontal isolated and Horizontal drawout) of any approved make on existing cable duct using M.S channel frame work. The panels shall be cubicle type 11KV VCB HT panel board rated for 25 KA breaking capacity for 3sec fabricated out of 2mm thick Alu-Zinc/CRCA sheet steel of totally enclosed dust and vermin proof finished with two coats of powder coat painting over a coat of good etched primer(Surface preparation and painting for CRCA sheet steel) and fully segregated compartment ensuring no arc or foreign body can travel from or to cable and bus bar compartment and comprising the following:-manually drawout type VCBs suitable for 3 phase 3 wire 50 cycles earthed system having a rupturing capacity of 475MVA at 11KV with VCB, relays, meters, 800Amps tinned copper busbars and jumpers, busbar interconnection covered with special heat shrink sleeves which shall provide effective insulation between phases or phase to earth, even if bridged by vermin or any other conductive body with all protective relays including internal arc protection equal to STC of the system, ie. 25KA with a duration of 1 second and standard accessories and as per technical specifications enclosed, including necessary control wiring using suitable size copper PVC wires etc.,complete in all respects as directed and as detailed below.
Note:- 1) The rate quoted should include supplying of 2sets-Rack-in Rack-out handle for VCB, (2) 1 set of earthing truck for 800A busbar and feeder cable.(If OEM design for earthing truck for busbar and cable is different, separate trucks to be supplied without any additional cost 3) In case the offered HT Panel boards design is having breaker in the middle portion, 1 set of service trolley to be supplied alongwith HT panel boards without any additional cost 4) The VCB HT Panels should be supplied through OEM only. VCB HT panels from approved channel partners are not acceptable. 5) The control cables between Transformer & HT panel and Battery charger & HT panel will be measured separately. 6) Concrete cutting, reconcreting etc., for laying control cables will be measured separately. However, all civil works for installation of HT panel boards have to be included in cost of IT & C for HT panels itself and no additional measurements will recorded for this.
7)List of components in each HT panel is brought out at Annexure-1 to technical specifications. 8)The indicative drawing of the substation layout along with HT Panel board, Transformer location, cable duct etc., are detailed in the tender drawing. 9) For SCADA connectivity, the control wiring from all relays and meters shall be brought out at single point so that each set of HT panel board can be connected to existing SCADA system through data cable (operation required under SCADA: (1) Operation and control of all breakers (2) Real time reading of all meters), the cost of control cable inside HT Panel and interconnecting the same shall be included in the scope of HT Panel itself, control cable from HT panel to HAL SCADA unit not in the scope of contract. 10)Quoted rate of outgoing shall also include the cost of BUS PT on outgoing feeders including suitable enclosure if required (Refer technical specification of HT Panel Board Annexure-I of Technical Bid) 11)Cost towards MS channels required for erection of HT panel on existing duct to be included in HT panel itself and it will not be measured separately.
a) Supply, fixing, testing & commissioning of 800A, 25KA for 3sec draw out type VCB panel as incoming with line PT 2 sets 0.00
b) Supply, fixing, testing & commissioning of 800A, 25KA for 3sec draw out type VCB panel as outgoing with single bus PT. 1 set 0.00
3 BATTERY CHARGER WITH ACCESSORIES :
a) Supply, installation, testing & commissioning of automatic trickle / boost battery charger (230V Input and 24V Output, 15A rating) battery charger enclosed in a dust and vermin proof enclosure with ventilation louvers fabricated out of 14 gauge sheet steel powder coated including front hinged construction doors complete for charging the 24V 120AH SMF battery bank comprising of following accessories: 1 Set 0.00
i)Boost charge – 15A and trickle charge 2A.
ii)Input transformer copper wound 230V/28V-30V tapping.
iii)Rectifier unit with necessary filters.
iv)Input/output voltmeter and ammeter.
v)Input/output protection with MCBs.
vi)Control fuses, control wiring, connector blocks.
vii)Copper Cable for interconnecting between charger and battery bank. Also, power supply cable from near by 230V single phase supply to battery charger including necessary Pintop.(5 to 10 mtrs distance)
viii)Maintenance accessories like portable voltmeter 0 to 20V range for checking battery voltage including suitable probes, complete as required.
b) Supply, installation, testing & commissioning of battery bank comprising 2Nos of 12 Volts, 120AH lead acid SMF batteries with terminal blocks, interconnection links, other standard accessories including Battery stand etc., Battery terminals should be protected against corrosion by applying required petroleum jelly as per requirement complete in all respects.(Battery warranty should be for minimum 36 months and warranty card along with copy of invoice to be submitted to OIC/EIC along with handing over document.) 1 Set 0.00
Supply and laying in already excavated trench / masonry duct / encasing in pipe/ fixing on wall /cable tray/RCC duct using necessary GI clamps at every 1mtr interval (minimum) testing & commissioning of following 11KV XLPE insulated aluminium(Al) conductor armoured(Arm) HT U.G cable as specified in the technical specifications to the tender document and as directed by Engineer-in-charge. Note:- 1)For cables which are to be laid in existing cable duct/pullout chamber/cable tray: scope should includes removing exiting Precast concerte slab/ Chequerred plate/existing sand and refixing of same after laying of cable including chipping and reconcereting to match with existing fiinish complete in all respect. 2) For the cables which are to be laid in soil, Excavation, Concrete cutting, reconcreting & HDD etc., if any will be measured separately.
a) 3C X 300 Sqmm Al.Arm XLPE HT Cable(earthed) 500 Mtrs 0.00
b) 3C X95 Sqmm Al.Arm XLPE HT Cable(earthed) 30 Mtrs 0.00
5 Control Cables
a) Supply, laying and connecting of 16C X 2.5 Sqmm size copper conductor XLPE/PVC insulated 1100V grade Armoured control cables including glands and end terminations using suitable copper lugs with suitable marking ferrules complete as directed by the EIC. Note:- Excavation, Concrete cutting and reconcreting will be measured separately. (HT panels to Tranformer) 40 Mtrs 0.00
b) Supply, laying and connecting of 4C X 2.5 Sqmm size copper conductor XLPE/PVC insulated 1100V grade Armoured control cables including glands and end terminations using suitable copper lugs with suitable marking ferrules and necessary pin top wherever necessary complete as directed by the EIC. Note:- Excavation, Concrete cutting and reconcreting will be measured separately.(HT panels to Battery) 40 Mtrs 0.00
6 HT Cable End Termination
Supply & providing following size Heat shrinkable type indoor cable end joints using bi-metalic end terminal lugs for the proposed 11KV aluminium conductor armoured XLPE/PVC insulated HT cable using suitable jointing kits of approved make with all required accessories complete in all respects including connecting to the 11KV circuit breakers and transformers.
a) 3C X 300 Sqmm XLPE HT Cable 4 Nos 0.00
b) 3C X 95 Sqmm XLPE HT Cable 2 Nos 0.00
7 Carrying out Mechanized Horizontal directional drilling of soil under the existing road/gate way for laying of 1Run of HDPE pipe including supply and laying 1 run of 110mm dia PE100 PN08 HDPE pipes, any ISI approved make conforming to IS 4984:1995 including suitable jointing using welding as required, providing pull tapes in the laid HDPE pipe, ends brought out, the brought out ends shall be sealed with suitable material to prevent soil and water entry and buried under soil. A cement concrete route marker shall be grouted in the soil above both the end of pipes with mark "End of pipes 1Rx110mm"complete as directed by Engineer in charge. 450 Mtrs 0.00
8 1600A Bus Trunking (Outdoor)
a) Supply, erection, testing and commissioning of factory build IP-65/IP-66 rated with canopy for outdoor 1600A, 3 phase and neutral system with 100% neutral busbar 415V, 50Hz outdoor sandwich insulated Aluminium Bus Trunking fabricated out of Aluminum (High Conductivity) conductors having a rated single phase RMS short time current withstanding capacity as specified in technical specifications, including necessary clearance between Phase to Phase and Phase to Neutral/Earth, necessary creepages busbar insulation with class F grade uniformly applied to withstand the relevant di-electric properties, having good structural strength, Electrical characteristics etc., as per IS/IEC standards, with required bus duct fittings & accessories like horizontal and vertical bends, elbows, offset sections, reducers, busbar section joints, expansion joints, making necessary wall openings, making good the same by sealing the opening, replastering, suitable outdoor compatible wall bracket at the opening to avoid rain water leakage, re-painting of the re-made wall portion to match with existing finish etc., complete as per site requirement including providing internal continuous earthing using Aluminum strips of 50% of phase/neutral cross section area etc., complete and as per good Engineering practice. 1.5mm thick CRCA with powder coating with IK10/1.6mm Electro galvanised/ Hot dipped GI Sheet steel/ 2mm thick Aluminium enclosure powder coated to shade RAL 7032 or as per OEM standard. 15 Mtrs 0.00
The above work shall be done in complete as per site requirement and as directed by OIC/EIC. Note:1)Detailed specification have been brought out in Technical specification for Electrical & mechanical works of Sl no:29. The above specification has to be read in conjection with this BOQ specification. 2) Including Supply and fabrication of MS frame works for supporting. 3) Including Civil foundation work for support. 4) Meausrement will be from flange end to flange end. 5)Bidder have to study tender drawings and workout required accessories for BBT. 6) Tentative LT Panels position at substation shown in the tender drawing. Work has to be executed as per actual site condition.
b) Supply, connecting, testing and commissiong of 1600A rated Bi-metallic copper flexible connector for 3phase and neutral supply(4nos in each set) between transformer LT side bus bar and overhead sandwitch busbar trunking with required harwares including suitable outdoor type adopter box at transformer LT side for interconnection complete in all respect and as directed by OIC/EIC. 1 Set 0.00
c) Supply, connecting, testing and commissiong of 1600A rated Aluminium flexible connector for 3phase and neutral supply(4nos in each set) between TTA LT Panel incomer bus bar and overhead sandwitch busbar trunking with required harwares including suitable Indoor type adopter box at TTA LT panel Incomer side for interconnection complete in all respect and as directed by OIC/EIC. 1 Set 0.00
9 Transformer Plinth
a) Providing 150mm thick 1:4:8 cement concrete bed using 40mm graded aggregate including curing, etc., complete as directed by the Engineer-in-charge.(Required for transformer foundation bed & BBT foundation only) 6 Cu.Mtrs 0.00
b) Construction of size stone masonary with 1:8 cement mortar including curing etc., as directed by Engineer In Charge. 4.5 Cu.Mtrs 0.00
c) Rendering 10mm thick 1:6 cement plaster on fair faces of the above stone masonry including curing as directed by Engineer In Charge. 6 Sq.Mtrs 0.00
d) Providing coping slab over the stone/brick masonry platform 100mm thick 1:2:4 cement concrete using 20mm graded aggregate including curing as directed by Engineer In Charge. 0.5 Cu.Mtrs 0.00
10 Transformer Yard Fencing
a) Supply, fabricating & grouting in the soil 75x75x6mm thick M.S angle iron post of not less than 6.8 Kg/mtr., 3mtrs long (600mm below ground level & 2.4 Mtrs. above ground level) for fixing the GI chain link type fencing panels including excavation and providing 1:4:8 cement concrete foundation of size 200mm x 200mm x 800mm for grouting the post and painting the post with 2 coats of aluminium paint over a coat of aluminium primer complete in all respect and as directed by OIC/EIC. 25 Nos 0.00
b) Supply & fabrication of heavy duty GI chain link type fencing panels of size 2000mm width and 2400mm height and fixing the same to the angle iron post indicated above by employing necessary bolts, nuts etc. The chain link mesh fencing panel shall be fabricated out of 40x40x6mm angle iron frame work all round and covering this panel with chain link mesh fencing made up of 8 SWG galvanised steel wire of not less than 4 Kg/m2 conforming to IS 2721 and cross support of 50X6 mm size MS flat( "X" cross section), including painting the MS frame work of fencing panel with 2 coats of aluminium paint over a coat of aluminium primer, preparation of surface etc., complete in all respect and as directed by OIC/EIC. 75 Sq.Mtrs 0.00
c) Supply, fabrication and fixing 1500mm wide 2400mm height M.S angle iron hinged & lockable gate fabricated out of 50x50x6mm thick angle iron frame work all round and covering this panel with chain link mesh fencing made up of 8 SWG galvanised steel wire of not less than 4 Kg/m2 conforming to IS 2721 and cross support of 50X6 mm size MS flat( "X" cross section), with pad lock arrangement including painting the MS frame work of fencing panel with 2 coats of aluminium paint over a coat of aluminium primer, rate complete in all respects. 1 No 0.00
d) Supply and spreading of 75mm thick brick soling base including necessary ramming, consolidating form work for preparation of surface after levelling the complete yard including 1mtr all around the fencing as per site requirement complete in all respect and as directed by OIC/EIC. 40 Sq.Mtrs 0.00
e) Supply, mixing and placing 1:3:6 cement concrete of 100mm thick using 40mm graded aggregate in suitable piles above brick soling base ( Brick soling will be measured separately) and finishing the top by belting complete in all respect and as directed by OIC/EIC. 5 Cu.Mtrs 0.00
f) Supply and spreading crusher made 40mm aggregate stone jelly to a thickness of 100mm in the yard including levelling as directed. 5 Cu.Mtrs 0.00
g) Supply and fixing on the wall 8 SWG GI wire complete with necessary interconnections using suitable bolts & nuts to effect proper earth continuity as per standard practice. 500 Mtrs 0.00
11 Substation accessories
a) Shock treatment chart (Tri-language) with teak wood frame and glass cover. 2 Nos 0.00
b) 5Kg Dry powder type fire extinguishers fixed with suitable clamps. (To be fixed on wall) 2 Nos 0.00
c) Good quality Rubber gloves for electrical operation tested for 22KV. 1 Set 0.00
d) Danger Boards of vitreous enamelled M.S sheets of 2mm thick for 415V installation. 4 Sets 0.00
e) Danger Boards of vitreous enamelled M.S sheets of 2mm thick for 11KV installation. 4 Sets 0.00
f) Supply and spreading 2.5 mm thick synthetic insulating mat as per IS 15652:2006(class-B)suitable for operation of 11KV equipments. 4 Sq Mtrs 0.00
g) Supply and spreading 2.0mm thick synthetic insulating mat as per IS 15652:2006(class-A)suitable for operation of 1.1KV equipments. 14 Sq Mtrs 0.00
h) Supply and fixing in position 4nos Steel Round bottomed fire buckets filled with sand of 9 Ltrs capacity with floor stand, sand, painting etc., without canopy 1 No 0.00
i) Supply and fixing in position 4nos Steel Round bottomed fire buckets filled with sand of 9 Ltrs capacity with floor stand, sand, painting etc., with canopy 1 No 0.00
j) Supplying of First Aid Chart with Lamination. 1 No 0.00
k) First aid box with standard first aid Kit of Thadani make as per standards. 1 No 0.00
12 LT Panels-TTA
Design, fabrication, supply, installation, testing and commissioning of the following Indoor type Modular construction TTA (Totally Type tested Assemblies) Switch Board as per IEC 61439- Part-I & II for Voltages up to 1100 V, degree of protection shall be IP-42, suitable to be mounted on the floor/cable duct as per site requirement including supply & fixing/grouting M.S channel frame work for erection of panel, with cable entry from bottom/top as per drawing coordination by EIC conforming to technical specification complete.
Note:-1)a) ACB's in the LT panels shall be Manually drawout(MDO)/Electrical drawout(EDO) type as specified. Air Circuit breaker of approved make suitable for 415V 3 Ph & N supply with microprocessor based tripping device comprising of overload, short circuit and instantaneous ground fault protection including suitable range CTs and separate LED indications for overload, short circuit and ground fault along with release and also micro switches for service, isolated and locking positions for the breaker, door interlock, secondary isolating contacts, auxiliary contacts as required including ON/OFF indications, trip push button, trip indication, front operating handle and other connected accessories complete in all respects. b) All ACB's should be rated for minimum 50KA breaking capacity as detailed in BOQ (Icu=Ics=Icw for 1sec)
2)The operating height of the Panel shall not exceed 2.1 mtr. from FFL.
3)Aluminium bus bar size for carriying out specified current shall be as per type test certificate.
4)All MCCBs in the LT panels shall be adjustable with thermal settings(80% to 100%), overload and short circuit releases including door interlocking device, front operating handle complete,ON and OFF indication of LED module etc. complete in all respects.
12.1 LT Panel - 1 1 Set 0.00
i) 1No - 1600A, 415V gr. 50KA, 4P EDO Type ACB
ii) Lot - 1600A TP + 800A N, 415V, short circuit rated 50KA for 1sec, Aluminium bus bars with busbar insulators, heat shrinkable PVC sleeves etc.
iii) 1No- Multi function meter (MFM/MDM)suitable for 3ph, 4 wire, 240V(L-N), 5A, CL-1,RS 485 Port Digital MFM/MDM of power logic PM2230 of Schneider or any equivalent make meeting technical specification of above MFM complete in all respect.
iv) 1Set of - 1600/5A current transformers of class 1 and 15VA burden for metering.
v) 1Set of - 1600/5A or 1A current transformers of class 1 and 15VA burden for APFC realy.
vi) 1No- (0-500V) range 96x96mm flush type voltmeter with RYB selector switch
vii) 1No 13A 415V gr TP 100KA MPCB of for tapping power for metering and control circuit
viii) 1Set - RYB indicating lamps of LED module with 6A SP MCB.
ix) 1Set- 6A, MCB for the protection of measuring instruments.
i) 2 Nos - 800 A 415V gr. MDO,50KA TP+NL ACB
ii) 2 Nos - 400 A 415V gr. 50KA TP+NL MCCB MP BASED
iii) 8 Nos - 250A 415V gr. 50KA TP+NL MCCB TM BASED
iv) 2 Nos - 100A 415V gr. 50KA TP+NL MCCB TM BASED
v) 2 Nos - 63A 415V gr. 50KA TP+NL MCCB TM BASED
13 300 KVAR Automatic power factor correction panels 1 Sets 0.00
Design, fabrication, supply, installation using suitable MS channel frame work for base, testing & commissioning of floor mounting type 300 KVAR Automatic Power Factor Correction Panel using filter units comprising of capacitor bank made up of MPP type capacitors suitable for 525V, 3 Phase system, delta connected with equal capacitance between the phase including necessary interconnections, 7% Aluminium detuned reactor, thyristor switching controller module with required control circuits and accessories, cable entry from bottom with removable gland plates with required knock-outs, fabricated out of CRCA sheet steel folded and braced as necessary to provide a rigid support for all components, totally enclosed, dust and vermin proof and degree of protection shall not be less than IP-52, multi-tier cubicle type formation with front hinged lockable doors for the individual compartments, preparation of surface and treatment by seven tank process, powder coated with approved colour for not less than 50 microns, all doors and covers shall be fully gasketed using good quality EPDM gasket and/or rubber strips and ensure good lockable, durable door opening & closing mechanism, Aluminium bus bars for three phases and neutral, bus bar insulators, heat shrinkable colour coded PVC sleeves etc., with necessary interconnections as specified in Technical specifications for electrical & mechanical works, and comprising of following switchgears and accessories complete in all respects & and as directed by Engineer-in-charge.
Note :- 1)The operating height of the Panel shall not exceed 2.1 mtr. from FFL. 2) The APFC panel shall have provision for Auto/manual operations. 3)Full load testing for APFC panel shall be carried out as part of Pre-dispatch Inspection. Contractor has to arrange the same at panel builder premises or in such a place where load testing facility is available before dispacting of panel to HAL. 4)Design details of filter unit has to be given to OIC/EIC along with GA drawing for verification of capacities of capacitors being used in filter unit. Indicated ratings are minimum requirements.
5)All MCCBs in the LT panels shall be adjustable with thermal settings(80% to 100%), overload and short circuit releases including door interlocking device, front operating handle complete,ON and OFF indication of LED module etc. complete in all respects.
i) 1No - 800A 415V gr. 50KA, TPN ACB, ACB shall be Manually drawout(MDO) type. Air Circuit breaker shall be of approved make suitable for 415V 3 Ph & N supply with microprocessor based tripping device comprising of overload, short circuit and instantaneous ground fault protection including suitable range inbuilt CT's and separate LED indications for overload, short circuit and ground fault along with release and also micro switches for service, isolated and locking positions for the breaker, door interlock, secondary isolating contacts, auxiliary contacts as required including ON/OFF indications, trip push button, trip indication, front operating handle and other connected accessories complete in all respects. ACB should be rated for Icu=Ics=Icw for 50KA 1sec.
ii) 1 Lot-800A TP + 400A neutral Aluminium busbars with busbar insulators, heat shrinkable PVC sleeves etc.complete.
iii) 1 Set-800/5A current transformers of suitable class and VA burden for metering.
iv) 1 set Digital VAF meter
v) 1no 16A 415V gr TP 50KA MPCB of for tapping power for metering and control circuit
vi) 1no suitable rating TP SPD
vii) 1Set RYB indicating lamps of LED module with 6A SP MCB.
viii) 1Set- 6A 415v gr TPN MCB for the protection of measuring instruments.
ix) 1Set - 3 Phase 12 channel Intelligent reactive power management controller (power factor correction relay), programmable for controlling thyristor switching module, suitable capacity SMPS, required control wiring, including necessary interconnections among CTs, thyristor switching modules etc., as per standards.
Note: Necessary control cabling from CT at Transformer LT panels to PF correction relay in APFC panel is included in the scope-(Refer substation drawing).
i) Suitable fans for ventilation
ii) 4Nos. - 50KVAR 415 volts filter unit comprising of not less than 66.2KVAr 525V 50Hz, super heavy duty MPP capacitor bank including 440volts grade 7% detuned aluminium reactor controlled by suitable capacity Thyristor switching module(SCR-SCR Type) for each bank separatley.
iii) 2Nos. - 30KVAR 415 volts filter unit comprising of not less than 40KVAr 525V 50Hz, super heavy duty MPP capacitor bank including 440volts grade 7% detuned aluminium reactor controlled by suitable capacity Thyristor switching module(SCR-SCR Type) for each bank separatley.
iv) 1No. - 20KVAR 415 volts filter unit comprising of not less than 26.5KVAr 525V 50Hz, super heavy duty MPP capacitor bank including 440volts grade 7% detuned aluminium reactor controlled by suitable capacity Thyristor switching module(SCR-SCR Type) for each bank separatley.
v) 1No. - 10KVAR 415 volts filter unit comprising of not less than 13.2KVAr 525V 50Hz, super heavy duty MPP capacitor bank including 440volts grade 7% detuned aluminium reactor controlled by suitable capacity Thyristor switching module(SCR-SCR Type) for each bank separatley.
vi) 2Nos - 5KVAR 415 volts filter unit comprising of not less than 6.6KVAr 525V 50Hz, super heavy duty MPP capacitor bank including 440volts grade 7% detuned aluminium reactor controlled by suitable capacity Thyristor switching module(SCR-SCR Type) for each bank separatley.
Note: The capacities of capacitors specified are net value of the respective bank. Accordingly successful tenderer has to submit the detailed calculation of individual unit along with the GA drawing.
vii) 6Nos of 125A, 36KA 415V Gr.TP TM based MCCB (for 50KVAR & 30 KVAR filter unit)
viii) 1No of 63A, 36KA 415V Gr.TP TM based MCCB (for 20KVAR filter unit)
xi) 3Nos of 32A, 36KA 415V Gr.TP TM based MCCB (for 10KVAR filter unit & 5KVAR filter unit)
a) Supply, providing and Fixing Cast Iron Pipe earth station confirming to IS 3043 complete with 2750mm long, 100 mm Inner Dia(ID),13mm thickness CI Pipe, with 2 part clamp made out of G I flat 50 x 6 mm continously welded around the pipe using cast iron welding electrodes as per drawing. The cost also incudes excavation for earth pit, providing & laying homogenous mixture of charcoal lumps, salt & sand all around the pipe as per specification, supplying and fixing of RCC Collar of size 450 mm dia, 450 mm height and 50 mm thick over Cement concrete base of minimum size 150mm width & 100mm thick all around below collar shall be provided using 1:2:6 CC after necessary excavation, refilling of soil, consolidating, ramming, leveling of soil etc., supplying & fixing the label board(MS Plate of size 300mmx200mmX2mm) welding to the elctrode complete as per specification, std drawing, instructions of EIC. 6 Nos 0.00
b) Supply & providing earth stations using 600x600x3.15mm thick copper plate electrode complete at 2.5 mtr. below the ground level with 20mm dia class B G.I pipe for watering, G.I funnel etc. & Cement concrete base of minimum size 750x750x100mm thick shall be provided using 1:2:6 CC after necessary excavation, refilling of soil, consolidating, ramming, leveling of soil etc. and providing cement concrete chamber of inside dimension 300x300x300mm with a wall thickness of 120mm using 1:2:6 CC above the base concrete including providing 50mm thick RCC cover including required salt & charcoal, 2runs of 50x6 mm(300mm) copper strip from plate electrode upto top of the chamber etc. as per technical specification enclosed with the tender documents & as per IS 3043 complete in all respects[For Transformer neutral earthing]. 2 Nos 0.00
a) Supply, fixing & connecting the 50X6mm(300sqmm) size G.I strip on wall / clamping to the existing duct wall / fixing on steel structures/ laying 2 ft. below the ground level with necessary excavation, concrete cutting & re-concreting, refilling, consolidation & levelling of soil after laying for interconnection between the earth pits and LT panels earthing as directed by Engineer-in-charge. Note:- Excavation, concrete cutting & re-concreting will be measured separately. 200 Mtrs 0.00
b) Supply, fixing & connecting the 40X6mm(240 sqmm) size Copper strip on wall / clamping to the existing duct wall / laying in cable tray/ laying 2 ft. below the ground level with necessary excavation, concrete cutting & re-concreting, refilling, consolidation & levelling of soil after laying for interconnection between the earth pits and transformer neutral as directed by Engineer-in-charge. Note:- Excavation, concrete cutting & re-concreting will be measured separately. 50 Mtrs 0.00
16 Supply and grouting in soil using 1:3:6 cement concrete at an intreval of 50mtrs and at turning points, cement concrete cable route markers (100mm x 100mm at top, 250 X 250mm at bottom and 600mm in height) constructed using 6mm size steel rods and 1:2:4 cement concrete including facework.The ' HT CABLE LCA MK2/HT CABLE LS-7/HT CABLE LS-2' should be engraved on two opposite sides and painted with red enamel paint with yellow as background colour. The marker cable route shall be installed 200mm below ground level and as directed by Engineer in charge. 10 Nos 0.00
Total Amount Excluding GST 0.00
Add 18% GST 0.00
Total Amount Including GST 0.00
Total Amount inclusive of GST In Words
HINDUSTAN AERONAUTICS LIMITED
Facilities Management Division
Pre-Qualification Profile APPLICANT PARTICULARS
Tender Ref No. or Contract No.: HAL/FMD/EC-2932/24-25
Name of Work: Providing External power supply and Establishment of Substation for LCA Mk-II hangar in ARDC Division, Bengaluru as Phase-II works.
Estimated Amount in Rs. 12461000
Tender Notice Date:(DD-MM-YYYY) 07-10-24 Can we give in DD/MM/YYYY
Completion Period (In Months) 6
Sl.No Description Details Enclosed / Not Enclosed Any Other Related Information Remarks Kindly mention at Col I J &K as " Any Other related Information"
1 Name of the Individual / Firm / Company: * (Mandatory) Related Document to be Uploaded to eProcurement Portal
2 Type of ownership / Legal Status [Attach copies of the original document defining the legal status]
3 Year of Establishment of Company/Business
4 Registered Office Address, Telegraphic Address, Telephone No., Website / email id, FAX No.
5 Correspondance Address, Telegraphic Address, Telephone No., Website / email id, FAX No.
7 PF number (If any)
9 GST registration number
11 Particulars of registration with various Government bodies (Attach documentary proof)
a) Registration Number/s
b) Organization / Place of registration
c) Category [Limit for tendering]
12 Contact details
Contact person name Please enter Contact person name
Ph. No. with STD code
FAX No. with STD code 5 6
13 Valid Electrical contractor licence of appropriate voltage issued by any state Govt. under clause 45 of Indian Electricity Rules 1956 or as amended from time to time
14 I.T Returns for past 03 years 999999 5 E 6
Assessment year 2023-24 Enclosed Please Select 'Yes','No' for IT Returns for all the 3 years 2499999 4
Assessment year 2022-23 Enclosed 2500000 3
Assessment year 2021-22 Enclosed 4999999 3
15 Maximum value of works executed during the following 05 years and it should be certified by Chartered Accountant. (In Rs. Lakhs)
2018 - 2019 Please enter maximum values of works (sum of all the works in the respective year) in Rs. Lakhs for all the years Here last 3 years cells to be considered to Check Annual Turn Over for 30 % value of Estimation given above 1 6.00 7.00 0 0
Turn over Criteria is Not met
16 DETAIL OF WORK ON HAND UPTO COMPLETION PERIOD OF SUBJECT WORK (N=completion period=6months=6/12= 0.50 year) [For Bid capacity calculation] NOTE : PROVISION for 10 works are given. If more, a separate similar sheet to be made showing all the works with all details as per this FORMAT and same to Uploaded. However, 10 works details to be provided and balance work value of other works to be added and to be provided in 10th row as OTHER works. 0.83
Sl.No(work No) Name of Organization with address Name of the work on hand Amount of Contract in Rs. in Lakhs {X} Period of CONTRACT in months Date of Commencement of work as Work Order in dd-mm-yyyy Probable date of Completion as Agreed Actual progress achieved till date of Tender Notification (in Rs. in Lakhs) {Y} Balance value of work on hand [Col.(3)-Col.(7), ie X-Y] (B- For Bid Capacity Calculation) Related Document to be Uploaded 0.42 0.00
8 0.00 Max Turn Over 07-08 8500000
9 0.00 Current Level to be brought by adding 10% for every year 10-11 8500000 X 1.1 X 1.1 X 1.1
10 0.00 Turn Over to considered A 11313500
0.00 Balance Work On Hand 207452000
Bid Capacity 0.00 Bid Capacity Criteria is not Met this should be hidden while uploading
17 Action plan / bar chart as to indicate the completion of work, within the scheduled time (contract period)] Related Document to be Uploaded -162198000
18 Bank(s) details: [Copy of the cheque leaf to be uploaded]
a) Bank Account No. Please enter Bank Details Related Document to be Uploaded to eProcurement Portal (Note Canceled cheque leaf to be uploaded)
b) Name of the Bank
c) Type of Account
d) Branch, Place
e) Bank Code No.
19 Bank Statement for past THREE months
20 Latest Over draft Facilities with Bankers
21 Latest Bankers Solvency Certificate from Nationalized/ scheduled Bank issued NOT before 12 months from the final date of submission of Tender. SOLVENCY solvency cal
Name of Bank & Branch Please enter Latest Solvency Details and upload the same Related Document to be Uploaded to eProcurement Portal 07-10-24 1-Jan 0 40000
Date of Issue (dd/mm/yyyy) 07-09-23 200000 40000
Value Rs. 200001 150000
Solvency value is NOT as per NIT
22 Experience of having successfully completed similar works during last 7 years ending last day of month previous to the one in which applications are invited. [ Work completion certificates along with LOA/PO/WO should be uploaded] (i) THREE similar completed works each costing not less than the amount equal to 40% of the estimated amount put to tender. (ii) TWO similar completed works each costing not less than the amount equal to 50% of the estimated amount put to tender. (iii) ONE similar completed work costing not less than the amount equal to 80% of the estimated amount put to tender. 4984400 500001 250000
Completed similar works during last 7 years You are Not Eligible Pls Select Works Completed during last 7 years 1000000 250000
Work No I Type of Work [ Incase of private works the same shall be supported with TDS certificate] Related Document to be Uploaded to eProcurement Portal 1000001 500000
Name of The organisation
Brief Description of Work: 2000000 500000
Completed value of Work in Rs. 2000001 1000000
Date of Commencement of Work [DD/MM/YYYY]: 4000000 1000000
Date of Actual Completion of Work[DD/MM/YYYY]: 4000001 2000000
Work Competion is NOT with in 7 years
Work No II Type of Work [ Incase of private works the same shall be supported with TDS certificate] Related Document to be Uploaded to eProcurement Portal 1000001 500000
Name of The organisation
Brief Description of Work
Completed value of Work in Rs.
Date of Commencement of Work [DD/MM/YYYY]:
Date of Actual Completion of Work[DD/MM/YYYY]:
Work Competion is NOT with in 7 years
Work No III Type of Work [ Incase of private works the same shall be supported with TDS certificate]
Name of The organisation work done
Brief Description of Work
Completed value of Work in Rs. 07-10-24 2555
Date of Commencement of Work [DD/MM/YYYY]:
Date of Actual Completion of Work[DD/MM/YYYY]: 07-12-17
Work Competion is NOT with in 7 years
23 DETAILS OF TECHNICAL PERSONNEL AVAILABLE( if space provided is insufficient separate sheet to be uploaded with the same format as below)
Sl.No Name of members or technical personnel available in the organization Qualification of similar nature number of years of experience Related Document to be Uploaded to eProcurement Portal
24 PLANT, MACHINERY AND EQUIPMENT AVAILABLE [The Plant, Machinery and equipment (either owned or leased) that can be made available for this work must be furnished below].
Sl.No Name of Machinery NO OF EQUIPMENTS Make & capacity, Present location and condition Year of Manufacture Related Document to be Uploaded to eProcurement Portal
25 Works of similar nature successfully completed in addition to Sl. No. (22) of Applicant Particulars (1) during the last 07 years ending last day for previous month.
Sl.No. (work No.) Name of the work / project and location Owner or Name and address of the Client with Contact person & Ph. No. Cost of work (in Lakhs) as completed Date of commencement (copy of work order to be uploaded for each work) Stipulated date of completion Actual date of completion Litigation Arbitration pending / in progress with details (indicating gross amount claimed and awarded by the contractor) Name and address, Telephone of officer to whom reference may be made Remarks #REF!
26 Details of person holding the power of Attorney
Name Please enter Person holding the power of attorney Related Document to be Uploaded to eProcurement Portal
Ph. No. with STD code
FAX No. with STD code/ e-mail ID
27 DECLARATION I
I/We declare and confirm that - 1. All information and attachments submitted along with this offer are true and correct. 2. I/We are aware that any false information provided herein will result in the rejection of my offer . 3. I/We shall not make refund claims of expenditure incurred in processing this offer. 4. I//We are aware that document sought only be uploaded for evaluation of offer. 5. I/We shall not associate nor has been associated in the past, directly or indirectly with consultant or any other entity that would prepare the design, specification and other documents of the project. Please Accept the Declaration I
28 DECLARATION II
I/We declare and undertake that - 1. To provide all facilities to HAL, Bangalore for verification of the information / details furnished by us and also for inspection of our works carried out / in progress if required. 2. The bid does not contain any amendment, modification as change of any type whatsoever in the bid documents and to any amendment issued thereafter. Please Accept the Declaration II
29 Tender Document Cost and EMD details
Description DD No. & Issue Date Bank Name & Address Amount [in Rs.] Enclosed / Not enclosed Related Document to be Uploaded to eProcurement Portal
Tender cost Please enter Tender Document Cost and EMD Details
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
raw.json
RAW_JSON
Technical_Bid_2932.pdf
TENDER_DOCUMENT • 1.26 MB
PQ_Freeview.pdf
TENDER_DOCUMENT • 0.21 MB
Price_Bid_Freeview.pdf
TENDER_DOCUMENT • 0.16 MB
CorrigendumNoIEC2932.pdf
TENDER_DOCUMENT • 0.05 MB
Tender_Drawing_No2.pdf
TENDER_DOCUMENT • 0.20 MB
CorrigendumNoII.pdf
TENDER_DOCUMENT • 0.05 MB
Tender_Notice_.pdf
TENDER_DOCUMENT • 0.14 MB
Tender_Drawind_No1.pdf
TENDER_DOCUMENT • 0.08 MB
Amendment_NO1.pdf
TENDER_DOCUMENT • 0.17 MB
Undertaking_Lertter.pdf
TENDER_DOCUMENT • 0.25 MB
ECS_Format.pdf
TENDER_DOCUMENT • 0.01 MB
EC2932_Price_bid.xlsm
TENDER_DOCUMENT • 0.09 MB
EC_2932_Pre_Qualification.xlsm
TENDER_DOCUMENT • 0.04 MB
Check_list.pdf
TENDER_DOCUMENT • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .