Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.3 LAccepted-AOC | L1 | Accepted-AOC ACCEPTED BEING L1 | |
| 2 | L2₹23.5 L+₹1.6 L (7.34%)Rejected-Finance | L2 | Rejected-Finance REJECTED BEING L2 | |
| 3 | L3₹23.9 L+₹2.1 L (9.40%)Rejected-Finance | L3 | Rejected-Finance REJECTED BEING L3 | |
| 4 | L4₹25.8 L+₹3.9 L (18.0%)Rejected-Finance | L4 | Rejected-Finance REJECTED BEING L4 |
Tender Value
₹24.5 L
EMD Value
₹49,000
Closing Date
15 Mar 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Col Vaibhav Fazudar, CWE
HQ 134 WORKS ENGRS PIN-914134 C/O 56 APO
REPAIR AND MAINT OF HT POWER, DISTRIBUTION, POTENTIAL AND CURRENT TRANSFORMERS INCLUDING SERVICING AND CALIBRATION OF BREAKERS, AB SWITCHES, FUSE ARRANGEMENTS CONTROL CABLES AND ALLIED WORKS AT MANASBAL UNDER GE 970 EWS
2021_MES_415797_1
134 WE-70/2020-21
Open Tender
Civil Works
Item Rate
270 days
SRINAGAR
PLEASE SEE TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE 970 EWS
₹49,000
Yes
12 Apr 2021
25 Jan 2021
17 Mar 2021
25 Jan 2021
15 Mar 2021
1 Mar 2021
60 days
Amount
Excavating in trenches not exceeding 1.5 meter wide and not exceeding 1.5 meter in depth for foundation for erection of poles, stays, laying cables, stays etc and getting out in hard / dense soil all as specified and directed.
Excavating in trenches not exceeding 1.5 meter wide and exceeding 1.5 meter and not exceeding 3meter in depth for foundation for erection of poles, stays, laying cables, stays etc and getting out in hard / dense soil all as specified and directed.
Returning filling in excavated earth work including spreading, levelling, watering and well ramming in layers n.exc 25cm thick in any strata
Removing excavated soil to a distance n.exc 50m, depositing where directed at a level n.exc 1.5M above the starting point
Supply/ Lay dry river sand /m -sand in trenches for cable protection all as directed. Note : Punned thickness only will be measured & Paid
M & L Sub Class 'B' brick covering protection to the eletric cable laid dry flat transversally along the length of cable on sand cushioning with width equal to length of brick complete all as specified
S & F in trenches/on wall in repairs GI tubing light grade for road crossing and cable protection of the following sizes as in repairs :-
80 mm dia
100 mm dia
Plain cement concrete (1:4:8) type D-2 (using 40mm graded crushed stone aggregates) as in foundation of pole etc all specified and directed.
PCC 1:3:6 type C-2 using 40mm graded stone aggregate as in foundation filling and mass concrete for stay and pole complete all as specified and directed.
M & L for PCC 1:2:4 type B-1 using 20 mm graded stone aggregate including use and waste of form work for coping of pole and stay foundation complete all as specified and directed by Engr-in-charge.
Dismantling old and unserviceable pre stressed concrete /Steel poles any type including breaking cement concrete complete, Material and erection of steel tubular swaged pole with cast iron base plate finial tapper plug, bolts nuts and screws and specified type 410-SP-55 ( 11mtr long) in truly vertical position 1.5 m length of pole above ground level shall be painted with two coats of synthetic enamel paint in strips of 30 cm width, black and yellow alternatively and painting with two coats of aluminum paint over a coat of red oxide primer on rest part of pole and its connected parts complete all as specified and directed by engir-in charge. (note- Excavation and PCC shall be measured and paid seperately )
S&F (In repair) Aluminium conductor steel reinforced any size in over head lines on HT poles including stretching the aluminium conductor and binding with binding wires of aluminium or aluminium tapes etc. jumpers and connections, complete all as specified and directed by Engr-in-Charge.
S&F (in repair) Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed by Engr-in-Charge.
Dismantling old unserviceable stay assy complete, material and labour for new stay assembly complete with 20 mm dia stay rod with accessories shown in electric plate No 01 incl stay clamp, (loop insulator, stay wire, excavation and concrete measured seperately) complete all as directed.
S & F in repairs Disc type porcelain vitreous, brown or white insulator suitable for 33 KV HT working Pressure of size 145 mm height, 255 mm dia , including. one galvanised mild steel spindle, two galvanised iron washer and one GI nut complete all as directed.
S & F in repairs Pin type porcelain vitreous,brown of white insulator suitable for 33 KV HT of working pressure of size 150mm height, 150mm dia, including one galvanised mild steel spindle, two galvanished iron washer and one GI nut complete all as directed.
S & F in repairs cable jointing kit for 11KV grade cable for Outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 120 to 185 sqmm. (Make : 3M/Birla/Denson)
S & F in repairs cable jointing kit for 11KV grade cable for Indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 120 to 185 sqmm. (Make : 3M/Birla/Denson)
S & F in repairs cable jointing kit for 11KV grade cable for Straight through joint heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 120 to 185 sqmm. (Make : 3M/Birla/Denson)
M & L for painting of HT/LT panel of any description with one coat of synthetic enamel paint of standard colour code over the existing painted surfaces after preparing the old painted surfaces by using spray gun all as directed.
XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power UG cables (heavy duty) with aluminium conductor HT cable, 11000 volts, grade cross sectional area 120 sqmm 3 Core including taking down old unserviceable ACSR conductor, complete all as specified and directed by Engr-in-Charge.
XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power UG cables (heavy duty) with aluminium conductor HT cable, 11000 volts, grade cross sectional area 95 sqmm 3 Core including taking down old unserviceable ACSR conductor, complete all as specified and directed by Engr-in-Charge.
S & F in repairs post insulator suitable for 33 KV HT working pressure in GOD / DO arrangements of any description all as directed.
Repairing / Servicing the Air break isolating switch HT 33 KV 200/400 Amps by replacing the defective major spares including provn of minor bolts nuts etc all as specified. Note :- UNSV spare will be measured & paid seperately.
Supply only 33 KV Airbreak switch spares all as directed.
Supply only male contact/moving Contact Blade
Supply only female contact/Fix Contact Jaw
Supply only rotating contactor pipe 200A/400 A
Supply only MS jumper carrier
Supply only Back Connector plate
Re- Stringing only existing HT 11/33 KV / LT OH line / Jumpers including dismantling of existing old binding wire for tightneing complete. Note: (a) Restringing of each wire shall be measured as in RM. (b) Supply only binding wire shall be measured and paid separately.
M & L for PVC insulated armoured heavy duty single strand solid copper conductor electric cable with 1100 V grade with cross section area 12 Core 2.5 Sqmm all as direcetd.
S & F in repairs drop out (DO) fuse unit expulsion type outdoor three pole 200 Amp suitable for HT 33 KV, comprising of insulators, steel base mounting frame , GI nut bolts etc with 30A , HT barrel type fuse complete
S & F in repairs incl testing, and commissioning of gang operated type air break isolating switch horizontal / vertical type type mounting complete, double break and operation rod of suitable length 400 A capacity and suitable for 33 KV HT supply, complete all as specified and directed.
S & F in repairs lighting arrestor Zinc oxide gap less type , station class suitable for 33 KV / 10 KA complete with all fittings all as specified and directed .(Make : M/s Crompton Greaves / M/s Lamco / M/s Elpro / M/s Oblum)
S & F in repairs single post insulator, 33 KV with mounting spindle etc. complete.
S & F in repairs Pin insulator, 33 KV with mounting spindle etc. complete.
S & F in repairs disc insulator, 33 KV with hardware fittings etc. complete.
S & F in repairs incl testing of metering & protection current transformer Oil filled out door type of 33 KV capacity ratio 100-50/5 or 200-100/5 class=5P, 10/1 15 VA including dismantling old existing CT all as directed. Note : Calibration & testing records should be properly maintained.
Dismantling old and burnt out PT unit 33000/110/220 volts oil filled out door type taking out contact with lead and bushing from the bus bar and replacing by new one of same model suitable for 33 KV PT unit incl testing on completion all as directed.
Trimming of tree branches touching to the LT/ HT over head line or near to the HT /LT over head line as per the direction of AGE E/M/JE incharge complete including removing the tree branches. Notes:- (i) Written shut down shall be obtained from concerned JE/AGE (E/M) before cutting of tree branches touching to the LT/HT over head lines or near to the LT/ HT over head lines. (ii) Span from one pole to next pole will be considered as a one Job. (iii) Any damage cause due to contractor men will be rectified without any extra payment. (iv) T & P such as ladder, rope, cutter, Axes and other related tools shall be provided by the contractor.
S & F in repairs insulating rubber mat ISI marked of size 1 m x 2 m x19mm suitable for 11 KV at 33 KV MRS Old Air Field
M & L for PVC sleeves suitable for LT / HT ACSR conductor / jumper in any type in R Y B Colours superior quality inserted over the existing ACSR all as directed.
S & F in repairs bolted type LM 6 alloy aluminium rigid stud type terminal connector of type universal connector suitable for 33/11 KV type ACSR conductor / busbar all as directetd.
S & F in repairs bolted type LM 6 alloy aluminium rigid pad type terminal connector for pad to conductor suitable for 33/11 KV type ACSR conductor all as directetd.
S & F in repairs bolted type LM 6 alloy aluminium rigid parallel connector conductor to conductor suitable for 33/11 KV type ACSR conductor all as directetd.
Disconnecting 11KV/433 Volts distribution transformer of capacity 100 KVA to 500 KVA by removing overhead connection/underground cables and earth strips etc. Installation of transformer after repairs, making all connections, testing and recommissioning to full satisfaction of Engr-in-charge. Taking out the transformer from any substation using suitable capacity crane or by any other method irrespective of type of approach available, loading in vehicle, transportation to workshop for repairs and unloading carefully. Reloading the transformer after repairs, transportation to site and unloading including placing at given position, complete all as required at site or as directed by Engr-in-Charge. Note : All the T&P required for disconnection, connection, loading and unloading including necessary petty items like bolts, nuts etc will be arranged by the contractor and rates for the same deem to be included in the rates quoted.
Repair to transformer step down 11KV/0.433 KV indoor/outdoor type of cap 100 KVA to 250 KVA, after dismantling the transformer carefully, opening the top cover of transformer for inspection /repair, draining out the transformer oil from the housing complete, taking out the core and winding assembly by disconnecting the internal connections, removing the carbon/sludge deposit in transformer housing core, renewal/replacement of unserviceable rubber bushes and washers , replacement of tap changer winding and thimbles, replacement of silica gel, replacement of top cover gasket set including pasting with pasting material, replacement of worn out nut and bolts, replacement of unserviceable LT & HT bushes, cutting the burnt out winding and re-winding the same with suitable size of super enamelled copper wire as per existing guage, insulating the winding connection by using fire proof sleeve and fire proof tape, varnishing the coil, keeping the coils in electric oven chamber for 24 hrs to remove the moisture, painting of complete transformer body from outside and inside by spray gun, marking of MES/SM Number etc, replacement of conservator tank glass, re-installing the core and winding inside properly, making the all connection with suitable copper lugs, refilling of dehydrated transformer oil, reinstalling the top cover after cleaning and painting of housing, conservator tank, expulsion vent etc, meggering the LT and HT side of the transformer and testing complete all as specified and directed by Engr-in-Charge. Note :- (i) Winding wire including labour for making of coils and supply of new spare for replacement of UNSV spare will be measured & paid separately. (ii) Painting of transformer shall be measured and paid separtaely. (iii) Dehydration transformer oil will be measured and paid separately.
Repair to transformer step down 11KV/0.433 KV indoor/outdoor type of cap 300 KVA to 500 KVA, after dismantling the transformer carefully, opening the top cover of transformer for inspection /repair, draining out the transformer oil from the housing complete, taking out the core and winding assembly by disconnecting the internal connections, removing the carbon/sludge deposit in transformer housing core, renewal/replacement of unserviceable rubber bushes and washers , replacement of tap changer winding and thimbles, replacement of silica gel, replacement of top cover gasket set including pasting with pasting material, replacement of worn out nut and bolts, replacement of unserviceable LT & HT bushes, cutting the burnt out winding and re-winding the same with suitable size of super enamelled copper wire as per existing guage, insulating the winding connection by using fire proof sleeve and fire proof tape, varnishing the coil, keeping the coils in electric oven chamber for 24 hrs to remove the moisture, painting of complete transformer body from outside and inside by spray gun, marking of MES/SM Number etc, replacement of conservator tank glass, re-installing the core and winding inside properly, making the all connection with suitable copper lugs, refilling of dehydrated transformer oil, reinstalling the top cover after cleaning and painting of housing, conservator tank, expulsion vent etc, meggering the LT and HT side of the transformer and testing complete all as specified and directed by Engr-in-Charge. Note :- (i) Winding wire including labour for making of coils and supply of new spare for replacement of UNSV spare will be measured & paid separately. (ii) Painting of transformer shall be measured and paid separtaely. (iii) Dehydration transformer oil will be measured and paid separately.
Disconnecting 33KVA/11KVA transformer of capacity 1000 KVA by removing HT overhead connection/underground cables and earth strips etc. Installation of transformer after repairs, making all connections, testing and recommissioning to full satisfaction of Engr-in-charge. Taking out the transformer from any substation using suitable capacity crane or by any other method irrespective of type of approach available, loading in vehicle, transportation to workshop for repairs and unloading carefully. Reloading the transformer after repairs, transportation to site and unloading including placing at given position, complete all as required at site or as directed by Engr-in-Charge. Note : All the T&P required for disconnection, connection, loading and unloading including necessary petty items like bolts, nuts etc will be arranged by the contractor and rates for the same deem to be included in the rates quoted.
Repair to power transformer 33/11 KV outdoor type of cap 1000 KVA, after dismantling the transformer carefully, opening the top cover of transformer for inspection /repair, draining out the transformer oil from the housing complete, taking out the core and winding assembly by disconnecting the internal connections, removing the carbon/sludge deposit in transformer housing core, renewal/replacement of unserviceable rubber bushes and washers , replacement of tap changer winding and thimbles, replacement of silica gel, replacement of top cover gasket set including pasting with pasting material, replacement of worn out nut and bolts, replacement of unserviceable LT & HT bushes, cutting the burnt out winding and re-winding the same with suitable size of super enamelled copper wire as per existing guage, insulating the winding connection by using fire proof sleeve and fire proof tape, varnishing the coil, keeping the coils in electric oven chamber for 24 hrs to remove the moisture, painting of complete transformer body from outside and inside by spray gun, marking of MES/SM Number etc, replacement of conservator tank glass, re-installing the core and winding inside properly, making the all connection with suitable copper lugs, refilling of dehydrated transformer oil, reinstalling the top cover after cleaning and painting of housing, conservator tank, expulsion vent etc, meggering the LT and HT side of the transformer and testing complete all as specified and directed by Engr-in-Charge. Note :-(i) Winding wire including labour for making of coils and supply of new spare for replacement of UNSV spare will be measured & paid separately. (ii) Painting of transformer shall be measured and paid separtaely. (iii) Dehydration transformer oil will be measured and paid separately.
Supply and filling of fresh transformer power oil of BDV not less than 50 KV for topping up of reduced level due to evorapation/ leakage/ loss due to dehydration in HT 33 KV transformer/HT 11 KV AVR /Distribution transformer 100 to 600 KVA complete including removing of old unserviceable transformer oil, complete all as specified and directed by the Engr-in-Charge. Make: Powerlink/poweroil/Savita/Midel
M & L for conducting oil filtration by stream line / Vacuum type filter machine to remove the moisture/carbon particles to improve required BDV of oil 50 to 60 KV for 1 min for power transformer & as BDV of oil 40 to 50 KV for 1 min for distribution transformer incl routine testing after filtration for any capacity of transformers/AVR/CT/PT units all as directed. (Note : The contractor shall change the filter assy before starting the filtration of transformer / AVR in presence of Engr In charge) Note : Necessary documents should be submitted by the contractor to Engr In Chrge.
Supply only for replacement of brass terminal rod with nuts,bolts washers & bushings suitable for HT side of the transformer of any make and capacity from 100 KVA to 300 KVA.
All as specified as per item No 49 above but LT side.
Supply only for replacement of brass terminal rod with nuts,bolts washers & bushings suitable for HT side of the transformer of any make and capacity from 315 KVA to 500 KVA.
All as specified as per item No 51 above but LT side.
Supply only silica gel breather clear view type including first fill of good quality silica gel of capacity suitable for 100 KVA to 300 KVA transformer.
Supply only silica gel breather clear view type including first fill of good quality silica gel of capacity suitable for 315 KVA to 500 KVA transformer.
Painting the outer surface of the transformer with two coats of anti corossive heat resistance emulsion paint after preparing the surface dust and oil free and cleaning the bushes, name plate including writing the MES/SM No with white enameled paint all as directed for capacity of transformer 100 KVA to 500 KVA (indoor/outdoor type), complete all as specified and directed by the Engr-in-Charge.
All as specified as per item No 55 here in before but for capacity of transformer 1000 KVA (Indoor/outdoor type).
Supply for replacing silica gel breather clear view type including first fill of good quality silica gel of capacity suitable for 1000 KVA transformer / AVR units.
M&L for Earthing complete with GI earth plate 60x60cmx6mm thick electrode and 32x6mm GI strip as earthing lead burried directly in ground (Earth pit not less then 2.25 metres deep below ground level) with top edge of the plate not less then 1.5 metre below normal ground level, conneceted to GI strip 32x6mm as earth lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No.5 and incl earth work, PCC pit and RCC cover, watering pipe 20mm dia light grade, funnel, wire mesh, charcoal dust, 40mm dia light grade protection pipe and salt etc and connected to earthing test point all as specified or directed and testing complete all as specified.
Supply only for replacement off load tap changer for distribution transformer of any make and capacity from 100-500 KVA
M&L for super enamelled copper conductor wire of suitable gauge and size as per requirement for rewinding the HT/LT transformer / HT AVR of any capacity / any make complete all as directed.
Supply only for replacement of brass terminal rod with nuts,bolts washers & bushings suitable for 33KV side of power transformer of any make and capacity from 1000KVA complete.
Supply only for replacement of brass terminal rod with nuts,bolts washers & bushings suitable for 11KV side of power transformer of any make and capacity from 1000KVA complete.
Supply only for replacement of bush type insulator white/brown/green working pressure 33000Volts HT side all as specified and directed by Engr-in-charge.
Supply only for replacement of bush type insulator white/brown/green working pressure 433 Volts LT side all as specified and directed by Engr-in-charge.
Supply only for replacement of temperature gauge suitable size for power transformer/AVR of any capacity all as specified and directed by Engr-in-charge. Make-: AE or Equivalent.
Material and labour for servicing 33/11KV VCBs installed at various locations including calibration by dismantling, cleaning, greasing the complete VCB with attached relays, bus bar etc, insulation testing, setting the contractor gap by measuring as required, reassembling the VCB and reinstalling back to its original position checking repairing the current, circuit panel wiring, relay testing (i.e. Primary and Secondary injection test)/setting of relay rating in 06 months intervals of all CT's and submitting the test report to Engr in Charge including provision of new spares as required complete including operational testing and commissioning all as directed. Note: New spares, if required for repair/service of VCBs will be measured and paid separately.
M & L for carrying out primary & secondary injection test of 33 KV or 11 KV indoor /outdoor type current transformer (Set of three) of VCB's by using standard injection test method and checking the electrical circuits for fault condition, all relay testing and proper functioning incl submitting the test report all as directed by Engr in charge. (Note : PIT/SIT for VCB will be carried out in 6 months intervals and each primary & secondary injection test will be measured and paid)
Supply only the following spares for outdoor VCB 33 KV 800 A 750 MVA fault level 36V-26/2000 & VCB 11 KV 400 A 25 KA 250MVA as approved by GE
Closing coil 24/30V DC
Tripping coil 24/30V DC
Antipumping device 24/30V DC
33 KV porcelain bushing for VCB Top
33 KV porcelain bushing for VCB bottom
Earth Fault and over current relay of L & T Model No MC31A 24-110V
Digital type power factor indicator meter
Digital type Voltmeter / Ammeter 96 x 96 mm size
LED type indicator lamp assembly
Spout incoming side
Spout outgoing side
Epoxy insulators bushings for incoming / out going cables / bus bar suppors as per existng size of VCBs
Gear system assy complete with handle for charging / discharging of VCBs
Spring charging motor for VCBs
Over current protection relay of ERL Model No 8431H32403 18-135V DC
xvi) Metering and protection current transformer epoxy/resin filled of 11 KV grade of ratio 100-50/5 class = 5P, 10/1 25 VA draw out type with necessary mounting and connected items.
M/S ZAHOOR ENTERPRISES
M/S YATTOO CONTRACTORS
M/S Noor Mohammad Shalla
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .