Special repairs to Bldg No T165 LT OH line to UG cable and certain minor works at 02 to 13 Mile under GE Gangtok
2020_MES_380714_2
8902
Open Tender
Miscellaneous Works
Item Rate
Gangtok
As per tender documents
8 documents required · 8 mandatory
₹500
GE Gangtok
₹61,500
Yes
3 Nov 2020
23 Oct 2020
2 Nov 2020
23 Oct 2020
31 Oct 2020
23 Oct 2020
Amount
SCHEDULE 'A' PART-I (B/R WORKS)
Dismantling old PGI/CGI/ sheeting any guage, thickness including Nainital.Sikkim or similar pattern roof/facia including ridge etc and keeping serviceable sheets in safe custody for re-use complete all as directed.
Dismantling of wall and ceiling board (fibre pulp, insulation etc) /AC sheets and plywood any thickness and cover fillets and removal of dismantled materials/ruibbish from site complete all as specified and directed.
Dismantling of timber in scantling 40 sqcm and over in section in any position in unframed work all as specified.
Dismantling structural steel work including doors, gates but excluding framed truss etc complete all as specified and as directed.
Taking down chowkats or frames with shutters (without taking off shutters from the frame) each area n. exc 1.5 sqm but n.exc 4.0 sqm all as specified and as directed.
Taking down chowkats or frames with shutters (without taking off shutters from the frame) each area n. exc 1.5 sqm all as specified and as directed.
Dismantling floor, hearth or wall tiling including cement mortar bedding (but not backing), removing serviceable tiles to store and rubbish off the premises complete all as specified & as directed.
Taking down cement plaster of any description on brick or stone walls, including racking out joints, hacking for key, scrubbing down with water etc complete all as specified and directed by the Engr-in-Charge.
Demolition to cement concrete of any description and in any position not otherwise specifically provided for (unreinforced) complete all as specified and directly.
Demolition of brickwork or stone/boulder masonary built in cement mortar including all quoins, archers, pillars, precast PCC bond stones including seperating serviceable stones/bouldrs & setting aside for reuse in the work and removal of unserviceable materials from site complete all as specified and directed.
Supply and fix 0.50mm thick pre-painted galvalume aluminium zinc coating GI based corrugated steel sheets of any colour having tensile strength of 550 Mpa as in roof covering fixed with self tapping screws as in roof complete all as specified and directed by the Engr-in-Charge.
Supply and fix 0.50mm thick pre-painted galvalume aluminium zinc coating GI based plain steel sheets of any colour having tensile strength of 550 Mpa as in roof covering fixed with self tapping screws as in roof complete all as specified and directed
All as per itemNo 13 here-in-before but except sheeting
Material and labour for applying one coat of anti-corrosive coptic green paint on old treated roof/wall surfaces of CGI/PGI sheeting of any description and any in position over 10cm width or girth including necessary preparation of surfaces complete all as specified and as directed.
Material and labour 6 mm thick plywood, 5 ply, grade BWR type BB fixed with nails to timber frame work in Wall/Ceiling complete all as specified and as directed.
Material and labour for 2nd class hard wood fillets, square,rectangular and triangular in section, wrought, secured with nails, sectional area exc 3 sqcm but n.exc 6 Sqcm in section complete all as specified and as directed
Material and labour for 2nd class hardwood scantling fixed clean sawn including treating with raw linseed oil complete all as specified and as directed.
All as per item No 18 here-in- above except timber.
Supply and fix framed work as in doors or gates of angle or other section with gusset plates, rails, braces, etc complete, drilled for fixing of steel sheeting or other covering.Doors, etc to be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fittings (exclusive of steel sheeting or other covering, running rails and guides) and hanging, also fastening and fixing conforming to Fe 410-W (Gde-E- 250) complete all as specified and directed by the Engr-in-Charge.
S&F mild steel bands, straps,supports or stays for rainwater, ventilating pipes incl bolts, hooks for large gates, pintle hinges, large hasp and staples, chains, hand made sliding bolts,clamps,hold fast, and wall tie, hook for hanging fans, plain angle cleats for securing purlins trusses or rafters, knee piece inserts,two way and three way straps, plate washers and all similar small articles conforming to FE-290 Gde and E-165 all as directed and specified by Engr-in-Charge.
M&L for preparation of new steel surface of any description not otherwise described over 10 cm width or girth and applying two coats of synthetic enamel paint over a coat of red oxide complete all as specified and as directed.
Materials & labour for preparation of old steel of iron surfaces of any description n.exc.10cm width or girth and applying two coats of synthetic enamel paint over a coat of red oxide complete all as specified and directed by the Engr-in-Charge.
S&F 2nd class hard wood Plain, solid, straight chowkats and frames, wrought, framed rebated on the solid, rounded or chamfered, put together with glue pinned at joints,all as specified.
Supply & fix 25mm thick Flush shutters, solid core construction with block board core and plywood face panels, commercial type on both sides and fitted to chowkats. NOTE : All builder's hardware shall be measured and paid separately.
S&F 100mm long butt hinges, medium weight, cold rolled, mild steel complete all as specified.
S&F 250 mm long aluminium anodised sliding door bolt with hasp, staple (bolt type) and fixing clips of sheet, cast or extruded section and fixing bolts and sliding bolts of extruded sections or cast aluminium complete all as specified and as directed.
S&F 150 mm long aluminium anodised handles,cast type, complete all as specified and directed.
Supply and fix 200 mm long aluminium anodised barrel tower bolt of extruded section complete all as specified and directed by the Engr-in-Charge.
Material & labour for preparation of old painted surfaces of wood & wood based materials over 10 cm width or girth and applying one coat of synthetic enamel paint complete all as directed by the Engr-in-Charge.
Material and labour for preparation of new or previously untreated wooden surfaces of any description over 10 cm width or girth and applying two coats of synthetic enamel paint over one coat of pink primer complete all as specified and as directed.
S&F in repaired aluminium powder coated fancy curtain rails plain or colour 25 mm dia as approved with teak wood fininshing brackets and knobs complete all as specified.
M & L for 0.56mm thick plain Aluminium sheeting Alloy 31000 H4 in stepped flashing (measured as the minimum rectangle from which the pieces can be cut) complete all as specified and as directed.
S&F powder coated aluminium two track sliding window of heavy duty Jindal sections frame and shutter of appropriate sizes fixed with rubber gasket, handle, locking arrangements and fittings complete all as shown of drawings & as specified & as directed. (Make : Jindal or equivalent approved)
S&F aluminium powder coated door side hung type heavy duty Jindal sections frame & shutters of appropriate sizes including jointing cleats, glazing clips, aluminium snap bidding, rubber neoprene gasket packing handles, tower bolts and all other fittings as required etc complete all as shown on drawings & as specified and directed. (Make: Jindal or equivalent approved)
S&F 5.5mm thick tinted float glass fixed to two track Aluminium sliding windows / and side hung doors complete all as shown on drawings, specified & directed.
Material and labour for 12mm dia mild steel screw bolts (machine made) with hexagonal or square heads at one end and screwed the other, each screwed end to be fitted with washers and one hexagonal or square nut, exc 15cm and n exc 22.5 cm long comlete all as specified and as directed.
S&F 3mm thick, sheet glass,ordinary quality and glazing with oil putty in square n.exc 0.5 sqm in each pane complete all as specified and as directed.
Material and labour for non skid Ceramic coloured tiles of approved make and colour shade 7 to 8mm thick (Square/ rectangular) confroming to IS- 13712 grade II (a) of first quality area of each tile exc 0.18 Sqm but not exc. 0.38 Sqm, in floors etc set and jointed in neat cement slurry and pointed in white or coloured cement over and including 15mm thick screed bed or bedding layer in CM 1:6 complete all as specified and directed by the Engr-in-Charge.
M&L for lacquer coated coloured chequered cement concrete tiles 20cm x 20cm x 25mm / 30cm x 30cm x 25mm thick set, jointed and pointed in neat cement slurry in floors with grey cement and pigments over and incl 15mm thick screed bed or bedding layer of CM 1:6 complete all as specified and as directed.
Taking down rainwater pipes (any size or pattern), including all fittings, heads, shoes,bends, swan-necks, etc, including cleaning or refixing or removal to store (measured overall as fixed along the centre line over fittings and accessories) complete all as specified and as directed.
S&F PVC (SWR) half round 150mm bore with rounded edges incl all accessories like bend T etc for eaves gutter complete all as specified and directed. (Make:PRINCE or equivalent approved)
Supply & fix in repairs 150 mm bore PVC (SWR) pipes single socketed, in any length with rubber ring joints fixed to wall with necessary clamps, bolts etc complete all as specified and as directed. Make:- PRINCE or equivalent approved.
Supply & fix in repairs 150 mm bore PVC (SWR) bends any radius complete all as specified and directed by the Engr-in-Charge. Make:- PRINCE or equivalent approved.
Supply & fix in repairs 110 mm bore PVC (SWR) pipes single socketed, in any length with rubber ring joints fixed to wall with necessary clamps, bolts etc complete all as specified and as directed. Make:- PRINCE or equivalent approved.
Supply & fix in repair 110 mm bore PVC (SWR) bends any radius complete all as specified and directed by the Engr-in-Charge. Make:- PRINCE or equivalent approved.
M&L for 20 mm thick rendering plaster on fair faces of stone masonary surfaces or other than fair face of brick work in CM 1:6 complete all as specified and as directed.
M&L preparation of newly plastered surfaces of walls and applying two coats of cement based paint over a coat of alkali resistance primer on new surfaces of walls all as specified and directed.
M & L walling of RR stone masonary uncoursed, well bonded, bedded and solidly hearted built in CM 1:6 incl brought upto course at interval of every 60 cm complete all as specified and as directed.
Materials and labour for PCC (1:3:6) type C -2 using 40mm graded stone aggregate as in surface channels and drains & including necessary formwork complete all as specified and as directed.
Extra for forming fair finished drain or channel 30cm inner girth in cement concrete using extra cement including form, moulds, mitrred/stopped ends complete all as specified and as directed.
Materials and labour for 75mm thick PCC 1:3:6 type C2 (using 40mm graded stone aggregate) as in sub-base of floor over and including 50 micron polythene film laid complete all as specified and as directed by the Engr-in-Charge.
M&L for 75mm thick PCC (1:3:6), type C-2 (using 40 mm graded stone aggregate ) as in plinth protection; path / hardstanding etc laid in bays / panels not exc.2.00 Sqm each including construction joints at suitable interval and each corner and filled with bituminous mastic filling (1 part bitumen & 3 part sand) and finished the surface even and smooth without using extra cement complete all as specified and as directed.
SCHEDULE 'A' PART-II (E/M WORKS)
Dismantling of old ACSR conductor from the disturbed span including line spacer and unserviceable material removing from site of work complete all as specified and as directed.
Dismantling of old unserviceable/defective (pin type, Shackle type)insulators of any size/type and removing materials from site of work complete all as specified and as directed.
Dismantling of old cross-arms of mild steel channel or angle sections,etc,including mild steel bolts,nuts, washers, etc and removing from site of work complete all as specified and as directed.
Supply, laying, jointing and testing in trenches or passing through pipe, 1100 Volts grade XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured LT electric power under ground cable conforming to IS:7098 (Pt-I)-1988, heavy duty with aluminium conductor of cross sectional area 120 Sqmm 3.5 core with necessary fixing arrangements such as lungs, glands and terminal etc complete all as specified and as directed.
Supply, laying, jointing and testing in trenches or passing through pipe, 1100 Volts grade XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured LT electric power under ground cable conforming to IS:7098 (Pt-I)-1988, heavy duty with aluminium conductor of cross sectional area 10 Sqmm 4 core with necessary fixing arrangements such as lungs, glands and terminal etc complete all as specified and as directed.
Excavation in trenches n.exc 1.5 mtr wide and n.exc 1.5 mtr in depth for laying of cable and getting out in hard /dense soil complete all as directed.
Returning filling in soil including spreading, levelling, watering and well ramming in layers not exceding 25cm complete all as specified and as directed.
Removal of surplus excavated (soil) to a distance not exceeding 50 mtr and depositing where at a level not exceeding 1.50m above the starting point complete all as specified and as directed.
Supply and laying dry coarse sand as in cushioning of under ground electric cable in trenches, laid to a uniform thickness of 23 cm (15 cm under the cable & 8 cm over the cable) and gently punned down to 18 cm thickness complete all as specified and as directed by the Engr-in-Charge. Note :- Consolidated punned thickness shall be measured and paid.
M&L for protection to cable with one layer of new bricks laid flat butting to each other in such a way that the length of the bricks is at right angle to the central axis of the cable using old size sub-class ''B'' bricks complete all as specified and as directed.
Supply and laying 50 mm bore GI pipe light grade including fittings fixed to pole/laying under road crossing with clamps complete all as specified and as directed.
Supply and fix in repair, Cable junction box made of polycarbonate, ''halogen free and weather proof', for outdoor installation (with metric knockouts for cable entry) IP-66 protection including short cable eantry gland tread type with lock nut, four way bakelite terminal with brass studs and nuts, GI flat strip clamps of size 25mm X 3mm with bolts, nuts and washers for fixing with MCB one 06 Amps inside the junction box complete all as specified & as directed. (Make: HANSEL Cat No. KF 1616G or equivalent approved).
Materials & Labour for point wiring (surface type) with 4 Sqmm (nominal cross sectional area) PVC insulated(FRLS) unsheathed single core multi stranded copper conductor cable of working voltage 1100 volts grade conforming to IS-694 Part I & II of 2000 drawn in and including min 25 mm size heavy grade non metallic casing caping (Double lock) with all casing caping fittings & accessories with PVC poycarbonate rectangular box of suitable size fixed with brass screws & cup washers including 4 Sqmm (nominal cross sectional area) PVC insulated (FRLS) unsheathed single core multistranded copper conductor cable as earth continuity conductor connected to main switch 'DB's or common earth dolly for SSC 15A independent complete all as specified and as directed. Note: Red coloured cable shall be used for live connection, black coloured cable shall be used for neutral connection and green coloured cable shall be used for earthing. Separate cable for earthing and neutral to be used for each individual circuit from the distribution board.
Supply and fix switch socket combination, 2 in 1, 6 pin,5/6 Amps and 15/16 Amps, multipurpose, flush, non shutter, non inter locking type, 230 volt flush type, white/ivory finish with two fixing hole complete all as directed. Make : Anchor Cat No 38808/50665 or equivalent approved.
Supply, installation, testing and commissioning of deep freezer single phase 240 volts, 50 Hz of 200 ltrs capacity having top complete all as specified & directed by Engr-in-Charge. Make: Godrej Cat No-DpFrzRZGCHW210R6SHC or equivalent approved.
Supply anf fix Voltage stablizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 280 V with output voltage stablized at 230 V with accuracy of + 2.5% and of capacity 1KVA. Make: V-guard Cat-VC 150 or equivalent approved.
Supply, installation,testing and commissioning of double door hard top deep freezer single phase 240 volts, 50 Hz of capacity more than 401 Litre capacity having double door with inbuilt stabilizer complete all as specified & directed by Engineer-in-Charge. Make: Blue star cat No-CHFDD400MGPW or equivalent approved.
Supply and fix refrigerator, electric driven (single phase), capacity 190 Litres with inbuilt stabilizer complete all as specified & directed by Engineer-in-Charge. Make: LG Cat No- GL-B201ASPY or equivalent approved.
Supply, installation, testing and commissioning of deep freezer single phase 240 volts, 50 Hz of capacity more than 320 Litre capacity and upto 400 Litre capacity having double door complete all as specified & directed by Engineer-in-Charge. Make: Voltas 405L glass top double door Horizontal Deep Freezer (Classic white) or equivalent of Godrej/Bluestar/LG.
Supply and fix refrigerator, electric driven (single phase),capacity 195 Litres complete all as specified & directed by Engineer-in-Charge. Make: LG Cat No -GL-0201APZ2 or equivalent of Godrej/Bluestar/Voltas.
Supply and fix Voltage stablizer for automatic operation, single phase natrurally air cooled indore type & designed for input variation between 170 V to 250 V with output voltage stablized at 230 V with accuracy of + 2.5% and of capacity 1 KVA. Make: V-guard VG100 or equivalent of LG/Microtek.
Supply and fix Voltage stablizer for automatic operation, single phase natrurally air cooled indooe type & designed for input variation between 170 V to 250 V with output voltage stablized at 230 V with accuracy of +- 2.5% and of capacity 2 KVA. Make: V-guard- VND500 or equivalent of LG/microtek.
Taing down carefully old aluminium/copper point wiring for one light, socket or power etc incl all fittings such as switched sockets, holders, light fittings, fan regulators etc and keeping aside complete all as specified and as directed.
Dismantling of main switch board of sheet metal wooden etc including main switch, MCB DB, change over with MCB/MCCBs etc complete for replaceent or reuse complete all as specified and as directed.
Dismantling of unserviceable light fittings of any description and keeping aside for replacement or reuse complete all as specified and as directed.
M&L for point wiring with 1.5 Sqmm (nominal cross-sectional area) PVC (FRLS) insulated unsheathed single core copper cable working voltage 1100 volts grade conforming to IS-694 with multistranded copper conductor in including PVC heavy grade rigid non metallic 25 mm PVC casing caping (double lock) including PVC polycarbonate/PVC/rectangular block/box of suitable size fixed by means of brass machine screw and cap washer including size 1.5 sqmm (nominal cross sectional area PVC (FRLS) insulated unsheathed single core multistranded copper conductor cable as earth continuity conductor connected to main switches/DBs or common earth dolly complete all as specified and directed for one light point controlles by one switch.Make of cable-Havells/Finolex/plaza, Make of casing caping-Prestoplast/Plaza/Modi Note: Red coloured cable shall be used for live connection, black coloured cable shall be used for neutral connection and green coloured cable shall be used for earthing. Separate cable for earthing and neutral to be used for each individual circuit from the distribution board.
(a) All as per item No. 80 above but one light point/fan point controlled by one switch
(b) All as per item No. 80 above but one 5 pin 5 Amps switch socket point controlled by one switch with 1.5 Sqmm copper cable independent board.
All as item sl.No.80 above but with 2.5 sqmm FRLS copper conductor with FRLS 2.5 Sqmm earth stranded wire for 16 Amps power point in independent board.
Supply and fixing of Decorative LED tube light fittings 4 long 20/18 Watt with fixture electronic driver complete with connection. Make : Havells cat No REGALBATTEN8UPTO1X22WSSBSWH and Tube light Cat No TITANIANEO1213T8SSTL18WLED865SPC or equivalent in CG/Bajaj.
S&F in repairs lamp holder angular/straight insulated body, with back plate suitable for batten fittings, white/ivory finish complete all as directed. Make : Anchor Product Code No 39527 or equivalent of approved make
Supply and fixing of water proof 10 Watt LED bulk head. Make:Crompton Cat No-LBHP-10-CDL OR equivalent make Havells/C&S/Philips.
S&F in repairs switch piano, flush type, 6 amps, 230 volts, single pole, one way (ISI marked) complete all as directed by Engineer-in-charge Make : Anchor Product Code No 50053 or equivalent of approved make
S&F in repairs switch socket combination, 2 and 3 pin, 5/6 amps, multipurpose, flush, non shutter, non inter locking type, 230 volt flush type, white/ivory finish with two fixing hole including suitable gang box complete all as directed including taking down old one. Make : Anchor Product Code No 4056/50483 or equivalent of approved make
S&F in repairs ceiling rose, PVC/polycarbonate insulated body, 3 terminal and 240 volts, ISI marked complete all as specified and directed Make : Anchor Product Code No 39040 or equivalent of approved make
S&F ceiling rose surface Bakelite three terminals including dismantling old one. Make:- Legrand/Anchor/Crabtree.
M&L in repairs of SPN 8 way, double door DB with MCB SPN as incomer and SP MCB as outgoing with IP 43 and IK 09 protection complete with fixing in wall and amking good disturbed surfaces and connection. Note: - MCB are not included in the item rate and considered separately. Make:- Legrand, model-EKINOXE Cat No-607711 or equivalent approved.
S&F in repairs MCB single pole 6 to 32 Amps, 240 Volts, 10 KA rapturing capacity, 'C' Curve complete all as directed by Engineer-in-charge. (Make : L&T cat No BB10060C to BB10320C or equivalent/approved)
S&F in repairs MCB, Triple pole & neutral, 63 amps, 240 volts, ‘C’ curve, 10KA complete all as specified and as directed (Make : L&T cat No BB40630C or equivalent/approved)
M & L for providing earthing with GI earth plate electrode 600 x 600 x 6mm buried directly in ground (earth pit not less than 2.25m deep below ground level ) with top edge of the earth plate not less than 1.5m below ground level connected to galvanised earth lead width 4.0mm dia by means of nuts, bolt,washers etc of copper/brass connected to earth test point complete all as specified in electrical plate No-3 of SSR 2009 part 1, including necessary excavation and earth work in any strata of soil, GI water pipe light grade with 20mm dia funnel & wire mesh PCC (1:3:6) type C1 pit with CI cover and frame etc all as specified and directed by Engineer-in-Charge. Note:- All the joints shall be made with welding to get proper conductivity.
Supply, laying, jointing and testing in trenches or passing through pipe, 1100 Volts grade XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured LT electric power under ground cable conforming to IS:7098 (Pt-I)-1988, heavy duty with aluminium conductor of cross sewctional are 35 Sqmm 3.5 core with necessary fixing arrangements such as lungs, glands and termnal etc complete all as specified and as directed.
DHARMINDER SINGH
KAMLESH ENTERPRISE
M/S ANIL KUMAR THAKUR
M/S S. S CHETTRI AND SONS
KARMA SHERPA
MAHENDRA KHAWAS
BIJAY MITTAL
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .