| Sl No | Description | Qty | Unit | M/s Sagar Construction L3 | MONA GENERATOR SEVICES PVT. LTD. L4 | Roy and Sons Infrastructures L1 | HUMERS INFRATECH L2 |
|---|---|---|---|---|---|---|---|
| 1.00 | Supply, install, testing and commisioning of DISTRIBUTION transformer mounted on massonry platform size as recommended by OEM stepdown , 11KV/0.415KV, Three Phase complying with IS:1180(part-1 2014), level-2 with latest ammendments, outdoor type, copper wound suitable for 50 Hz system of capacity 500 KVA , oil immersed naturally cooled delta connected on HT side and Star connected on LT side ,Vector Group Dyn11, provided with OFF load tap changer to vary secondary voltage from -7.5% to + 7.5% in steP of 2.5 %. . The transformers should be supplied with first filling of oil confirming to IS 335 .The transformer should have BOTH SIDE cable end box with neutral brought out complete all as directed by Engineer - in -Charge. | 1 | Each | 17,61,858 ₹17,61,858 | 18,35,050 ₹18,35,050 | 10,99,000 ₹10,99,000 Lowest | 15,50,000 ₹15,50,000 |
| 1.01(a) Lifting lugs for transformer and tank. | |||||||
| 1.02(b) Earthing terminal rating and diagram plate. | |||||||
| 1.03(c ) Air release valve with explosion vent. | |||||||
| 1.04(d) Oil filling inlet pipe with plug. | |||||||
| 1.05(e) Drain outlet pipe with brass gate valve. | |||||||
| 1.06(f) Conservator tank with oil level indicator | |||||||
| 1.07(g) Silica jel breather | |||||||
| 1.08(h) First fill of oil upto level including conservator tank with fresh new oil conforming to IS335. | |||||||
| 1.09(i) Type of connection Delta/Star | |||||||
Tender Value
₹42.8 L
EMD Value
₹86,000
Closing Date
30 Oct 2025, 6:00 pmClosed
SHRI ANIL KUMAR, IDSE, SE, CWE
HQ CWE JHANSI
PROVN OF NEW TRANSFORMERS AGAINST BER UNDER GE GWALIOR
2025_MES_734075_1
CWE/JHA/GWL/TOKEN/48 OF 2025-26
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GWALIOR
AS PER NIT AND TENDER DOCUMENTS
9 documents required · 9 mandatory
₹500
GE GWALIOR
₹86,000
Yes
8 Dec 2025
7 Oct 2025
1 Nov 2025
7 Oct 2025
30 Oct 2025
22 Oct 2025
Amount
Supply, install, testing and commisioning of DISTRIBUTION transformer mounted on massonry platform size as recommended by OEM stepdown , 11KV/0.415KV, Three Phase complying with IS:1180(part-1 2014), level-2 with latest ammendments, outdoor type, copper wound suitable for 50 Hz system of capacity 500 KVA , oil immersed naturally cooled delta connected on HT side and Star connected on LT side ,Vector Group Dyn11, provided with OFF load tap changer to vary secondary voltage from -7.5% to + 7.5% in steP of 2.5 %. . The transformers should be supplied with first filling of oil confirming to IS 335 .The transformer should have BOTH SIDE cable end box with neutral brought out complete all as directed by Engineer - in -Charge.
(a) Lifting lugs for transformer and tank.
(b) Earthing terminal rating and diagram plate.
(c ) Air release valve with explosion vent.
(d) Oil filling inlet pipe with plug.
(e) Drain outlet pipe with brass gate valve.
(f) Conservator tank with oil level indicator
(g) Silica jel breather
(h) First fill of oil upto level including conservator tank with fresh new oil conforming to IS335.
(i) Type of connection Delta/Star
(j) Type of cooling: Oil and Natural Air.
(k) Vector group:DYN 11.
(l) Temperature rise over an ambient of 50 °C maximum.
(m) Cable end box on both side for HT/LT cables of suitable size alongwith cable gland.
(n) Provision of thermometer with pocket.
(o) Provision of oil and winding temperature gauge.
(p) Rating and terminal marking plate.
Supply, install, testing and commisioning of DISTRIBUTION transformer mounted on massonry platform size as recommended by OEM stepdown, 11KV/0.415KV, Three Phase complying with IS:1180(part-1 2014), level-2 with latest ammendments, outdoor type, copper wound suitable for 50 Hz system of capacity 160 KVA, oil immersed naturally cooled delta connected on HT side and Star connected on LT side ,Vector Group Dyn11, provided with OFF load tap changer to vary secondary voltage from -7.5% to + 7.5% in steP of 2.5 %. . The transformers should be supplied with first filling of oil confirming to IS 335 .The transformer should have BOTH SIDE cable end box with neutral brought out complete all as directed by Engineer - in -Charge.
(a) Lifting lugs for transformer and tank.
(b) Earthing terminal rating and diagram plate.
(c ) Air release valve with explosion vent.
(d) Oil filling inlet pipe with plug.
(e) Drain outlet pipe with brass gate valve.
(f) Conservator tank with oil level indicator
(g) Silica jel breather
(h) First fill of oil upto level including conservator tank with fresh new oil conforming to IS335.
(i) Type of connection Delta/Star
(j) Type of cooling: Oil and Natural Air.
(k) Vector group:DYN 11.
(l) Temperature rise over an ambient of 50 °C maximum.
(m) Cable end box on both side for HT/LT cables of suitable size alongwith cable gland.
(n) Provision of thermometer with pocket.
(o) Provision of oil and winding temperature gauge.
(p) Rating and terminal marking plate.
Supply, install, testing and commisioning of DISTRIBUTION transformer mounted on existing 2 Pole structure stepdown, 11KV/0.415KV, Three Phase complying with IS:1180(part-1 2014), level-2 with latest ammendments, outdoor type, copper wound suitable for 50 Hz system of capacity 100 KVA, oil immersed naturally cooled delta connected on HT side and Star connected on LT side ,Vector Group Dyn11, provided with OFF load tap changer to vary secondary voltage from -7.5% to + 7.5% in steP of 2.5 %. . The transformers should be supplied with first filling of oil confirming to IS 335 .The transformer should have BOTH SIDE cable end box with neutral brought out complete all as directed by Engineer - in -Charge.
(a) Lifting lugs for transformer and tank.
(b) Earthing terminal rating and diagram plate.
(c ) Air release valve with explosion vent.
(d) Oil filling inlet pipe with plug.
(e) Drain outlet pipe with brass gate valve.
(f) Conservator tank with oil level indicator
(g) Silica jel breather
(h) First fill of oil upto level including conservator tank with fresh new oil conforming to IS335.
(i) Type of connection Delta/Star
(j) Type of cooling: Oil and Natural Air.
(k) Vector group:DYN 11.
(l) Temperature rise over an ambient of 50 °C maximum.
(m) Cable end box on both side for HT/LT cables of suitable size alongwith cable gland.
(n) Provision of thermometer with pocket.
(o) Provision of oil and winding temperature gauge.
(p) Rating and terminal marking plate.
Supply, install, testing and commisioning of DISTRIBUTION transformer mounted on existing 2 Pole structure stepdown, 11KV/0.415KV, Three Phase complying with IS:1180(part-1 2014), level-2 with latest ammendments, outdoor type, copper wound suitable for 50 Hz system of capacity 63 KVA, oil immersed naturally cooled delta connected on HT side and Star connected on LT side ,Vector Group Dyn11, provided with OFF load tap changer to vary secondary voltage from -7.5% to + 7.5% in steP of 2.5 %. . The transformers should be supplied with first filling of oil confirming to IS 335 .The transformer should have BOTH SIDE cable end box with neutral brought out complete all as directed by Engineer - in -Charge.
(a) Lifting lugs for transformer and tank.
(b) Earthing terminal rating and diagram plate.
(c ) Air release valve with explosion vent.
(d) Oil filling inlet pipe with plug.
(e) Drain outlet pipe with brass gate valve.
(f) Conservator tank with oil level indicator
(g) Silica jel breather
(h) First fill of oil upto level including conservator tank with fresh new oil conforming to IS335.
(i) Type of connection Delta/Star
(j) Type of cooling: Oil and Natural Air.
(k) Vector group:DYN 11.
(l) Temperature rise over an ambient of 50 °C maximum.
(m) Cable end box on both side for HT/LT cables of suitable size alongwith cable gland.
(n) Provision of thermometer with pocket.
(o) Provision of oil and winding temperature gauge.
(p) Rating and terminal marking plate.
HUMERS INFRATECH (BID ID -3467763)
M/s Sagar Construction (BID ID -3463687)
MONA GENERATOR SEVICES PVT. LTD. (BID ID -3468378)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.31 MB
Tenderdocuments48.pdf
Tender Documents • 1.35 MB
BOQ_821948.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .