| 1 | L1₹36.8 LAccepted-AOC 01 VILLAGE BABOORI BARARI MATHURA UTTAR PRADESH 281005 | MATHURA | UTTAR PRADESH | 281005 | ₹36.8 L | L1 | Accepted-AOC Accepted |
| 2 | L2₹42 L+₹5.2 L (14.1%)Rejected-Finance | ₹42 L+₹5.2 L (14.1%) | L2 | Rejected-Finance Rejected |
Tender Value
₹31 L
EMD Value
₹62,000
Closing Date
13 Dec 2021, 11:00 amClosed
Executive Engineer-V, Sew. Divi, Infra-II, GMDA
Plot No. 3, Sec-44, GMDA Office, Gurugram
Revised DNIT of supply, installation and commissioning of Parshall Flume FRP material, open channel flow meter with transmitter for data connectivity to GMDA, HSPCB, CPCB server with existing online monitoring analyzer at Outlet, Byepass channel.
2021_HRY_196884_1
EE-V/GMDA/Job No.19/21.
Open Tender
Civil Works
Works
90 days
Gurugram
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
₹62,000
Yes
4 Mar 2022
22 Nov 2021
13 Dec 2021
22 Nov 2021
13 Dec 2021
22 Nov 2021
Amount
1/N.S. Item i) Supply, installation, commissioning of Parshall flume confirming to IS 14371: 1996 & amendment (if any) for accurate measurement of water flowing through open channels with prefabricated fiberglass lining, moulded engraved gauge marking in m3/hr or lit/sec and also in centimeter including discharge table, capacity marking, flow direction, hold fasts and sand treatment on backside of the flume including all required civil works, transportation & handling charges etc. during the installation & commissioning complete in all respect. Material: Fiberglass reinforced plastic (FRP). i) Parshall Flume 1’6” for 50 MLD STP Behrampur, 68 & 50 MLD STP at Dhanwapur:- Dimensions: Throat Width: 457 mm Max Width: 1026 mm Height: 914 mm Length: 2945 mm Max discharge: 2496 m3/hr (Outlet channel of 50 MLD STP Behrampur, 68 & 50 MLD STP at Dhanwapur = 3 No.) (Bypass channel of 50 MLD STP Behrampur = 1 No.)
ii) Parshall Flume 3’ for 100 MLD STP at Dhanwapur:- Dimensions: Throat Width: 915 mm Max Width: 1572 mm Height: 914 mm Length: 3170 mm Max discharge: 5125 m3/hr (Outlet channel of 100 MLD STP at Dhanwapur = 1 No.) (Bypass channel of 100 MLD STP Dhanwapur = 1 No.)
iii) Parshall Flume 4’ for 120 MLD plant Behrampur. Dimensions: Throat Width: 1220 mm Max Width: 1937 mm Height: 914 mm Length: 3320 mm Max discharge: 6917 m3/hr (Outlet channel of 120 MLD STP at Behrampur = 1 No.) (Bypass channel of 120 MLD STP Behrampur = 1 No.)
2/N.S. Item Supplying and installing of Ultrasonic level/Open Channel flow meter/transmitter for high functionality on standard product as open channel flow meter complete with instrument fittings & mounting accessories etc. & One Channel data logger with upgradation in existing OMLS data logger with data connectivity to GMDA, HSPCB & CPCB Server complete in all respect to the entire satisfaction of Engineer-in-charge with the following specifications:- Sr. No. Description Specification 1 Type Suitable for water applications 2 Measuring principle Ultrasonic type, 2 wire system 3 Temperature compensation Built -in to compensate over temperature range 4 Measurement Continuous level measurement from 0 to 100% of the range 5 Output 4 – 20 Ma isolated with HART 7 6 Power Supply Nominal 24 V DC 7 Preamplifier Included 8 Measurement Range 0 to 4 Mtr 9 Mounting connection 2” NPT [(Taper), ANSI / ASME B1.20.1] 10 Full Insulation Provided 11 Accuracy +/-0.5% of FS 12 Operating temperature Up to 600 C 13 Material (transducer) ETFE (Ethylene Tetrafluoroethylene) Make: - Siemens, ABB, Forbes Marshall.
UNIQUE TECHNOLOGIES
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .