Planning, Design, Engineering, Construction, Fabrication, Supply, Erection, Trial Run and Commissioning of 2 X 5 MVA, 33/6.6 kV Substation on Turnkey Basis at Rampur Batura OCP, Sohagpur Area, SECL
2023_SECL_278545_1
SECL/BSP/CMC/e-T/TK/SGP /2023-24/584 Dtd 05.05.23
Turnkey
Electrical and Maintenance Works
Item Rate
2190 days
Sohagpur Area
As per NIT
7 documents required · 7 mandatory
₹14.7 L
Office of GM(CMC), SECL
19 Dec 2023
6 May 2023
21 Jun 2023
6 May 2023
19 Jun 2023
18 May 2023
6 May 2023 - 12 Jun 2023
15 May 2023
Amount
DESIGN AND ENGINEERING COST (for 2 X 5 MVA, 33/6.6 kV S/S)
Design and Engg on PLANT & MACHINERY ( P&M - Electrical) to be supplied by bidder inlcusive of Overhead constuction cost, Contigencices, but excluding GST
Design and Engg on Civil & Structural work
CIVIL CONSTRUCTION AND STRUCTURAL WORKS for 2 X 5 MVA, 33/6.6 kV S/S on Turnkey Basis at Jhiria West OCP inclusive of Insurance,Contingencie but excluding GST
Sub-station Building
Outdoor steel structures
Foundation of outdoor structures including Transformer foundation
Cable Trench
Barbed wire fencing
Boundary wall
Surface dressing
Stone laying
Anti weed treatment
Bore well with submersible pump
Path way
Security Room
RCC sump and Pump House
Shed for DG & oil filter unit
Drain along boundary wall
Parking Shed
Oil Overflow Chamber
Oil Drain Pipe
Survey & Soil testing
SUPPLY OF PLANT & MACHINERY inclusive of Overhead Construction cost, Insurance, Contingencies , but excluding GST for substation ( 2 X 5 MVA, 33/6.6 kV Substation )
Isolators, 33 kV (nominal),3 poles, pole mounted, 1250A,25kA, arrangement for interlocking with 33 kV Vacuum Circuit breaker (Min 4 Sets)
Isolators, 33 kV (nominal), 3 poles, pole mounted, 1250A,25kA, arrangement for interlocking with 33 kV Vacuum Circuit breaker with Earthing switch (Min 2 Sets)
Isolators, 33 kV (nominal), 3 poles, pole mounted, 630A,25kA, arrangement for interlocking with 33 kV Vacuum Circuit breaker (Min 2 Sets)
Isolators, 33 kV (nominal), 3 poles, pole mounted, 630A,25kA, arrangement for interlocking with 33 kV Vacuum Circuit breaker with Earthing switch (Min 2 Sets)
Isolators, 33 kV (nominal), 3 poles, pole mounted, 630A,25kA, with D.O. Fuses. (Min 4 Sets)
Lightning Arrestors, station class, 30 kV,10 kA, suitable for 33kV, solidly earthed (each set consists of 3 nos.) with counters/surge monitors (Min 6 Sets)
Single phase current transformer ,outdoor type with required CT ratio for 33 kV system for metering and protection (1 set consists of 3 units for 3 phase supply) (Min 5 Sets)
Potential transformer ,outdoor type 33kV, 100 VA each 33/√ 3 kV/ 110/ √ 3 V for metering and protection each for three phase system (Min 2 Sets)
Vacuum Circuit Breaker, 33kV,630 A/1250A, outdoor type, 25 kA with remote control panel having IDMTL relay for O/L and E/F protection, ammeter, energymeter (Min 4 Nos)
Power Transformer outdoor type plinth mounted 33/6.6kV, 5 MVA, ONAN cooled, DY-11 conforming to IS:2026 (current) having OFF-LOAD tap changer on HV side and LV neutral effectively earthed through required value of Resistance ( Restricted Neutral System) with all accessories including 33 kV remote control panel for on load tap changer as per IS:3639 (Current) with the rating as given below Rated kVA: 5000 Rated Voltage(primary):33000V Rated Voltage(secondary):6600V Connection and vector group:Dy11 (Min 02 Nos)
Neutral Grounding Resistors with Protection (Min 2 Nos)
Lightning Arrestors, station class, 6 kV,5 kA, suitable for 6.6kV, solidly earthed (each set consists of 3 nos.) with counters/surge monitors (Min 2 Nos)
Isolators, 6.6 kV (nominal), 3 poles, pole mounted, 630A, arrangement for interlocking with 6.6 kV Vacuum Circuit breaker with Earthing switch (Min 2 Nos)
6.6 kV switch-board, indoor type, 19 panel, with vacuum circuit brakers 75 MVA symmetrical breaking capacity. The function of each panel is as given below: All panels will conform to IS:3427 (Current) and relevant parts to IS:2516 ( current). These will be provided with cable entry boxes. The incoming panels will be provided with restricted earth fault protection. All panels will be provided with IDMTL relays for over current and earth fault protection. The incoming and outgoing panels shall be provided with Trivector meters. (Min 1 Set)
Station Transformer,outdoor type rated as follows: Rated kVA: 160 Rated Voltage(primary):33000 V Rated Voltage(secondary):433 V , Cu wound , Plinth mounted (Min 1 Nos)
Lighting Transformer,outdoor type rated as follows Rated kVA: 100 Rated Voltage(primary):33000 V Rated Voltage(secondary):230V(L-L) , plinth mounted (Min 1 Nos)
415V switch board, indoor type with 4 nos MCCB having O/L, S/C and E/L protection, 25 MVA symmetrical breaking capacity (All out going panels will be provided with ammeter, and incoming panel with ammeter and voltmeter). The function of panels will be as follows : - 1 no, MCCB, 800A, CTR of 300/5 A, as controller for incoming feeder. - 3 nos, MCCBs, 400A, CTR of 100/5 A, as controller for outgoing feeders. (Min 1 Nos)
230 V (L-L) Main Lighting Distribution boards with the following : --1no. MCCB, 3 pole,400 amps for control of incoming feeder. --3 nos.,MCBs, 2 pole,63 amps for control of out going feeders. --3 nos.,MCBs, 2 pole, 32 amps for control of out going feeders. (Min 1 Nos)
Capacitor bank, 6.6 kV indoor type 1000 kVAR including APFC. (Min 2 Sets)
Battery (110 V) lead Acid type, 200 AH and battery charging (with one stand bye battery charging unit) equipment, control panels, wooden racks etc.
Earthing system (Safe Earth Electrode type) including earth pits, required galvanised strips/flats for inter connection etc.
Lightning protection system consisting of spikes, earth pits, galvanised strips/flats, shield conductors etc.
Luminaries
Decorative, 1x12/15/18W and 2x15/18 W LED (Suitable rating) light fittings
Suitable rating LED Bulbs for indoor lighting
Tubular steel poles,11m height along with 90 W LED lamps with fittings
Lighting masts, 16m height (Min) along with required nos. of 200 W LED lamps with fittings.
90 W LED fitted on substation building (Min 4 Nos)
Emergency lighting system suitable for operation on 110 V DC supply in substation building.
Accessories such as sub distribution board, junction boxes, individual control cables, PVC conduits/ casings, back up fuses, switches, sockets, ceiling roses, single core PVC cable with copper conductors, flexible wire etc.
Cable and accessories
HT power cable, 6600 V grade, XLPE, FRLS, Copper conductor
LT Power cable, 1100V grade, PVCSWA, 10 sq. mm.(minimum),3/4 core copper stranded conductors
Outdoor Lighting cable, 1100V, PVCSWA , 2 cores, 10 sq mm (minimum) stranded Al conductors
Outdoor Control cables, 1100V grade, PVCSWA, not less than 2.5 sq mm , copper conductors of with required number of cores
Wires for internal wiring of 1.5 sq mm and 6 sq mm size, PVC insulated copper conductor cable of 1100 V grade.
Cables for internal control wiring of illumination, ceiling fans, power sockets etc. 2.5 sq mm size, PVC insulated copper conductor of 1100 V grade
Cable trays, cable racks, binding materials, cable glands/lugs, cable jointing kit, bolts, nuts, washers, termination kit etc.
Overhead conductors,Insulators,Towers, poles, insulators, string bus, ACSR conductors, steel hardware etc for 33 kV sides in the out door yard. 2 pole structure fitted with gang operated AB switch, lightning arrester etc for out going feeders
Fire Fighting System
Fire fighting equipment consisting of fire hydrants hose cabinets, hose reels, valves, pipes, fire detection alarming system, high velocity water spraying system for transformers,diesel pump, electric pump with electricals and cables, jockey pump etc
Supply of portable fire extinguisher system
Sand buckets with stand
Miscellaneous items
Room air conditioners, min. 1.5 t capacity ( 5 star rating ) including servo stabilizer
Supply of 63 kVA Diesel Generator set (silent type) with 3 ph, 50 Hz ,415 V output supply with cable, change over switch and earthing etc (Min 1 Nos)
Exhaust fans, 600 mm sweep.
Ceiling fan ,1200 mm sweep along with electronic regulator (5 star rating)
Water cooler with water purifier (Min 1 Nos)
Vacuum Cleaner Set (Min 1 Nos)
Erection and commissioning of Plant and Machinary for substation to be suplied by bidder as above inclusive of Overhead Construction cost, Insurance, Contingencies , but excluding GST
Training of O&M staff
Store cost for maintenance of P&M during Defect Liability Period (DLP) of five years.
Cost of Maintenace during during Defect Liability Period (DLP) of five years.
Total impact of GST for the purpose of CTC
ADEPT POWER PRIVATE LIMITED
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
BOQ_288381.xls
BOQ Document • 0.29 MB
120389708.pdf
Tender Document • 0.76 MB
120389709.pdf
Tender Document • 1.27 MB
120389711.html
Tender Document • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .