Tender Value
₹23.5 L
EMD Value
₹47,000
Closing Date
21 May 2026, 6:55 pmClosed
Executive Engineer
shalimar
Upgradation of Power Supply System for Biofertilizer Unit Under Alternate System of Agriculture for Sustainability (HADP) at FoA Wadura, SKUAST-K.
2026_SKUST_309974_1
E-NIT-12 of 2026-27
Open Tender
Electrical Works
Percentage
30 days
FoA Wadura, SKUAST-K
Please refer Tender documents.
5 documents required · 5 mandatory
₹750
Assistant comptroller
₹47,000
23 Jun 2026
14 May 2026
22 May 2026
14 May 2026
21 May 2026
14 May 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | SITC of 250 KVA Transformer,11/0.433kV, 3-phase Distbution Transformers with Bimetallic Terminal Connectors Energy Level-2, (Cu wound for 250kVA or higher KVA ratings), and with L.V Cable Box having detachable Cu. Gland plate with LV Bimetallic terminal connecton suitable for vertical take off of cable. without OCTC (Off Ckt Tap Changer) including Type Test Certificates for last 5 years, BEE Star approved energy efficiency rating complete as required make L&T, ABB,TATA Powers,Alba | 1 | No | 9,45,000 | ₹9,45,000 |
| 2 | SITC of buck & boost automatic Servo stabilizer of following specification: capacity:
1. Capacity: 200 KVA
2. Input voltage: 208- 460 V PP 120V -220V NP
3. Output: 415 Volts +/- 1 % PP
4. Winding Material : 99.9 % Pure copper wound strip with fibre glass of the guage suitable for 200 KVA capacity
5. Un- balanced type input
6. Dimmers with heat Sink based technology
7. Cooling : Oil Fresh IS 335
8. Micro Controller LCD True RMS with RS 485 Interface
9. Protections are:overload, High Voltage, Under Voltage, Delay line, thermal protection & surge protection, Single Phase Preventer Neutral failure, through micro controller & L&T Make Connector
10. Display Parameters KW, Current Power factor, Input voltage, Output voltage, Frequency, Trouble Shooting in digital form.
11. Auto & Manual Selector switch with up/down switch in case card gets fault.
12. Heavy duty copper bus bar wiring input and output.
13. Servo stabilizer tank shall be design in MS sheet Heavy gauge as suitablle recommended by IS Standard
14. Wheels for locomotion.
15. Radiators for natural cooling
16. cooling of oil / Oil Level inlet, lifting huks etc,wheels
17. Earth terminal
18. Efficiency more than 98%
19. Design as per IS 2026
20. Multi-function meters L&T Make
21. Warranty 1 year.
make Alba, Chinar | 1 | No | 6,05,000 | ₹6,05,000 |
| 3 | Chemical earthing GI 3 Mtr Long 65-80MM with pit and drilling etc , earthing compound included . Pit Cover . Complete job in all respects for Transformer, servo stabilizer, panel & cable | 5 | Job | 8,000 | ₹40,000 |
| 4 | Providing and fixing 25 mm X 5 mm G.I. strip onsurface or in recess for connections etc. as required. | 48.5 | Mtr | 287 | ₹13,919.5 |
| 5 | P/f of 3 ½ core armoured cable Al XLPE 240 Sq MM Grandly / Havells/ Polycab`/Alba and its earthing | 135 | Mtr | 3,850 | ₹5,19,750 |
| 6Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. | |||||
| 6.01 | 120 mm dia (OD-120 mm & ID-103 mm nominal) | 135 | Mtr | 417 | ₹56,295 |
| 7 | Supply,Installation,Testing and Commissioning ing, of Cubical Type Main LT Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC including Incomers,Out Goings,Bus Bars,Interlocking etc. as required as per the Following Description.(IP:66) Size 1220x900x600mm
Incomer/Outgoing
Thermal Magnetic Based MCCB 225 Amps FP Icu=Ics=100% with Breaking Capacity 36 KA (02 Nos) for 2 independent circuits of 2 different loads.
Indicating Lamps RYB (2 Set)
Voltmeter-0-500 Volts(2 Nos)
Ammeter(0-150 A)(2 Nos)
Selector Switch (2 Nos)
Current Transformer 100/5 A 10 VA Burden, Class-1(2 sets)
Aluminium Busbar 600 Amps FP E-91 E Grade Electrolytic Aluminium) (2 Nos)
Indicating Lamps ON OFF TRIP
Load Bearing Members to be made out of 2.0 mm CRCA Sheet.
iron stand
Partitions to be made out of 1.6 mm CRCA Sheet
Gland Plates to be 3.0 mm Thick. | 1 | No | 70,000 | ₹70,000 |
| 8 | Fabrication of shelter with GI roofing and GI galvanized chain link fencing , support
structure and entry door etc . Complete job in all respects . Size of platform 10x8x10 ft height with foundation work etc as needed above ground 24 Inches. With 2 number of flood lights of each 25 watts at two opposite sides . | 1 | Job | 1,00,000 | ₹1,00,000 |
| 15The Buy back of 100 KVA Transformer (Valued at Rs.1,00,00/-) and 70 KVA Servo Stabilizer with all accessories (Valued at Rs. 1,50,000/-) currently located at the FoA Wadura Campus shall be deducted from the allotted amount at the specified minimum rates. | |||||
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
finance_1003116.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.15 MB
BOQ_1003116.xls
BOQ • 6.18 MB
Addendum.pdf
PDF • 0.66 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .