GE (AF) Adampur
GE (AF) Adampur
REPAIR TO INTERNAL WIRING IN VAYU VIHAR AF AF STN ADAMPUR
2026_MES_755740_1
GE(AF)/ADM/T-92 OF 2025-26
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Under GE (AF) Adampur
As per tender
8 documents required · 8 mandatory
₹500
GE (AF) Adampur
₹40,000
Yes
18 Mar 2026
10 Mar 2026
2 Apr 2026
10 Mar 2026
31 Mar 2026
25 Mar 2026
Taking down copper/aluminium point wiring (light, fan , socket or power) complete including fixtures and fittings such as switches, ceiling rose, pendant ,regulators,sockets,light fittings etc.removing materials to store for keeping in safe custody or for taking credit (credit for items shall be made as per conditions separatly) and making good disturbed surfaces of wall, floor etc. complete all as specified and as directed.
M&L for pointing wiring with 1.5 sqmm (nominal area) PVC insulated FRLS H, unsheathed, multistrand, 1100 volts grade copper conductor cable single core. drawn through existing non metallic concealed PVC conduit medium grade of suitable dia as per SSR specification and its accessories including one run of 1.5 sqmm PVC insulated copper conductor cable green in colour for continuous earthing including MS terminal box flushed to wall with 3mm thick laminated hylem sheet top cover for fixing of switch/socket etc complete all as specified and directed. Note:- surface conduit shall be laid in ceiling portion only.
One light/ceiling fan/exhaust fan /call bell point controlled by one switch.
One 3 pin 5 amps socket point on independent board
One 3 pin 5 amps socket point on same board
One light point controlled by 2 Nos two way switches
One socket outlet three pin, 6/16 Amp, independent, with 2.5 Sq. mm (nominal area) cable & 2.5 Sq. mm (nominal area) cable as earth continuity conductor, in and including rigid non metallic PVC medium duty concealed conduit complete all as specified and directed. .
M&L for pointing wiring with 1.5 sqmm (nominal area) PVC insulated FRLS H, unsheathed, multistrand, 1100 volts grade copper conductor cable single core. drawn through in and including non metallic concealed PVC conduit medium grade of suitable dia as per SSR specification and its accessories including one run of 1.5 sqmm PVC insulated copper conductor cable green in colour for continuous earthing including MS terminal box flushed to wall with 3mm thick laminated hylem sheet top cover for fixing of switch/socket etc all as specified. Note:- surface conduit shall be laid in celing portion only.
One light/fan call bell point controlled by one switch
One 3 pin 5 amps socket point on independent board
One 3 pin 5 amps socket point on same board
One light point controlled by 2 Nos two way switches
One socket outlet, 6/16 Amp, independent, with 2.5 Sq. mm (nominal area) cable & 2.5 Sq. mm (nominal area) cable as earth continuity conductor, in and including rigid non metallic PVC medium duty concealed conduit complete all as specified and directed. .
S&F, Switch piano flush button single pole one way, 6 Amp complete all as specified.
S&F, Switch piano flush button single pole two way, 6 Amp complete all as specified.
S&F, Switch piano, bell/buzzer push, flush button single pole one way, 6 Amp complete all as specified.
S&F, Switch piano flush button single pole one way, 16 Amp complete all as specified.
S&F, Socket outlet multipurpose having provision for 2&3 pin, 6 Amp, flush type, complete all as specified.
S&F, Socket outlet multipurpose having provision for two-in-one 3 pin 6 Amp & 3 pin 16 Amp, flush type complete, all as specified.
S&F, Ceiling rose, surface bakelite, 65 x 50mm, three terminals complete, all as specified.
S&F, Lamp (angle) holder, insulated body, cord grip pattern, complete, all as specified.
S&F, Electric buzzer AC 230 volt, single pole, Ding Dong type complete, all as specified.
S&F, Fan regulator (electronic) suitable for 48”/56” sweep fan, step socket type, single phase, complete all as specified.
S & F in repair LED light fitting 1x10W bulkhead luminaires including LED light connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed
Supply and fixing in repair LED lights fitting 1x 20W, 220V, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose to fitting complete all as specified.
Supply and fixing in repair of LED mirror light fitting with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder including connecting up with flexible copper conductor cable of suitable size complete all as specified and directed.
S&F for Submain wiring alongwith PCV insulated unsheathed multi stranded copper conductor cable of size 2x6.00 sqmm+1x6.00 sqmm earth wire FRLS in and including non metallic concealed/on surface PVC conduit medium grade suitable dia as per SSR specification including taking down old complete all as specified and directed.
S&F for Submain wiring alongwith PCV insulated unsheathed multi stranded copper conductor cable of size 2x4.00 sqmm+1x4.00 sqmm earth wire FRLS in and including non metallic concealed/on surface PVC conduit medium grade suitable dia as per SSR specification including taking down old complete all as specified and directed.
Supply and fixing in replacement rigid non-metallic PVC conduit of size 20mm dia medium grade suitable for electrical wiring complete all as specified and directed.
S&F in replacement (Load line) sheet metal enclosure (DB) double door triple pole and neutral 4 way, 415 volt with 200 Amps rated bus bar in and including MCCB 4 pole 63 Amps, 16 KA, 415 Volts complete all as specified and directed.
S&F in replacement sheet metal enclosure (DB) double door single pole and neutral 12 way,240 volt with 200 Apms rated bus bar complete all as specified and directed.
S&F in replacement sheet metal enclosure (DB) double door single pole and neutral 8 way,240 volt with 200 Apms rated bus bar complete all as specified and directed.
S&F in replacement Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 Amp, 240 volt, breaking capacity not less than 10 kA, complete all as specified and directed.
S&F, in replacement MCB suitable for 240 volt AC supply, SP with over load and short circuit protection and rupturing capacity not less than 10 kA, 'C' curve type of rating 6 to 32 Amp, complete all as specified and directed. .
S&F, in replacement MCB suitable for 240 volt AC supply, SPN with over load and short circuit protection and rupturing capacity not less than 10 kA, 'C' curve type of rating 32 Amp, complete all as specified and directed.
S&F in replacement ceiling fan complete with blades, down rods, electronic regulator and accessories 230V, 1200mm sweep, minimum air delivery 210 CFM with service value 6.00 BEE five star rated with brushless direct current motor (BLDC) complete all as specified and directed.
M&L for Earthing complete with galvanized steel earth plate electrode 60 cm x 60cm x 6mm thick buried dircetly in ground (Earth pit not less than 2.25 m below normal ground level) with top edge of the palte not less than 1.5m below ground level connected to galvanized iron or steel pipe 15mm medium garde all as shown in electrical plate No.3 of SSR {Part I connecting to earthing test point (earth test point to be provided at 5 mtr distance from earth pit) and testing on completion including necessary excavation and earth work by using galvanised earth lead wire 4.0mm dia as earthing lead. The rate alos include charcol dust ans salt in alternator layers 20mm dia medium GI watering pipe, funnel , wire mesh, concrete 1:3:6 type C-1 for pit and RCC pit cover PCC pit shall be provided 50 cm away from earth pit and not on the earth pit itself. The extra cost of the watering pipe, bends, elbows shall be included in the unit rate. Note: RCC pit cover shall be precast of RCC 1:2:4 type B-1 80mm thcik reinforced with XPM weighing not less than 4 kg/Sqm including dismantling old complete all as specified and directed.
M&L for collection of items like ceiling fans, exhaust fans, wall mounted fans, cabin/table fans, flame proof ceiling fans from EM store yard for repair, transporting to workshop, opening and reassembling after including necessary cleaning greasing oiling etc, testing and depositing back to EM store yard of GE (AF) Adampur including necessary loading unloading and transporting etc. complete all as specified and directed. NOTE: Supply only spares & rewinding of fan(s) shall be measured & paid for separately under respective items of BoQ.
M&L for Rewinding Ceiling fan 1200 mm sweep with super enameled copper winding wire of size, gauge & weight as per original specifications providing insulating material and varnishing with synthetic varnish, replacement of bush, bearings condenser, U clamp with real including transporting, collection and handed over to E/M store after repair complete to the entire satisfaction of Engineer-in-charge including taking out old burnt winding wire after opening the same.
M&L for Rewinding Ceiling fan 1400 mm sweep with super enameled copper winding wire of size, gauge & weight as per original specifications providing insulating material and varnishing with synthetic varnish, replacement of bush, bearings condenser, U clamp with real including transporting, collection and handed over to E/M store after repair complete to the entire satisfaction of Engineer-in-charge including taking out old burnt winding wire after opening the same.
M&L for Rewinding Exhaust fan 300 mm sweep with super enameled copper winding wire of size, gauge & weight as per original specifications providing insulating material and varnishing with synthetic varnish, replacement of bush, bearings condenser, U clamp with real including transporting, collection and handed over to E/M store after repair complete to the entire satisfaction of Engineer-in-charge including taking out old burnt winding wire after opening the same.
M&L for Rewinding Exhaust fan 380 mm sweep with super enameled copper winding wire of size, gauge & weight as per original specifications providing insulating material and varnishing with synthetic varnish, replacement of bush, bearings condenser, U clamp with real including transporting, collection and handed over to E/M store after repair complete to the entire satisfaction of Engineer-in-charge including taking out old burnt winding wire after opening the same.
M&L for Rewinding Wall mouted fan 400/650 mm sweep with super enameled copper winding wire of size, gauge & weight as per original specifications providing insulating material and varnishing with synthetic varnish, replacement of bush, bearings condenser, U clamp with real including transporting, collection and handed over to E/M store after repair complete to the entire satisfaction of Engineer-in-charge including taking out old burnt winding wire after opening the same.
Supply & fixing in replacement 2.5 MFD fan capacitor complete all as specified and directed
Supply & fixing in replacement 3.15 MFD fan capacitor complete all as specified and directed
Supply and fixing in replacement Fan canopy suitable for 1200/1400mm sweep ceiling fan complete all as specified and directed.
Supply and fixing in replacement Fan hanging clamp complete rubber reel nut bolt washer all complete all as specified and directed.
Notes: Amount of credit for retrieved materials is mentioned in tender documents in pdf form which will be deducted while acceptance of tender offline.
stage.html
html • 0.02 MB
cancelled_1.pdf
pdf • 0.18 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.41 MB
ten.pdf
Tender Documents • 0.61 MB
BOQ_846499.xls
BOQ • 0.86 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .